EPC FOR RUMAITHA/SHANAYEL FACILITIES - PHASE III

ADCO Contract No. : 15678.01 / EC 10884


ADCO Project No. : P44010

CLEAN AGENT INERGEN (IG-541) GAS EXTINGUISHING


SYSTEM CAUSE & EFFECT DIAGRAMS FOR CLUSTER-P
CODE DESCRIPTION & INSTRUCTIONS SIGN DATE

APPROVED WITHOUT COMMENTS


1
VENDOR TO SUBMIT FOR FINAL
APPROVED WITH COMMENTS
2
VENDOR TO AMEND AND SUBMIT FOR FINAL
APPROVED WITH COMMENTS
3 VENDOR TO AMEND AND
RE-SUBMIT FOR APPROVAL
NOT REVIEWED/CONSIDERED
4 UNACCEPTABLE QUALITY
VENDOR TO RE-SUBMIT FOR APPROVAL

1 03/10/2017 MOSES DIPANKAR LAKSHMI ISSUED FOR FINAL

A 15/05/2016 KIRAN DIPANKAR LAKSHMI ISSUED FOR APPROVAL

REV. DATE ORIGINATOR REVIEWED APPROVED DESCRIPTION

THIS DOCUMENT IS INTENDED FOR USE BY ADCO AND ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.

PO NO.: 02/PEN/82/YAS/PA/122/125-00/15

CONTRACTOR: THE CONSORTIUM OF

VENDOR: TYCO FIRE & SECURITY UAE LLC

ADCO DOC. No. 44.21.42.6601 PAGE 1 of 2

ORIGINATOR No. ADCO Project


Rev. 1 Date : 03.10.2017
TFS-CA160077-CE-01 No. P44010
NOTES:
SWITCH GEAR ROOM ( ETR) INSTRUMENT TECHNICAL ROOM (ITR) INTERFACES
N1: THE PREDISCHARGE ALARM , DISCHARGE ALARM AND THE GAS RELEASE
WILL NOT GET INITIATED IF THE INHIBIT SWITCH OR KEY MAINTENANCE SWITCH
INDICATION / DISPLAY IN GAS RELEASE INERGEN SOLENOID INERGEN SOLENOID HARDWARE MODBUS IS ACTIVATED
HORN/STROBE INDICATION IN 3-WAY LIGHT HORN/STROBE INDICATION IN 3-WAY LIGHT
PANEL RELEASE DIRECTIONALV RELEASE DIRECTIONALV INTERFACE INTERFACE
ALARM STATUS UNIT INDICATOR ALARM STATUS UNIT INDICATOR
 44-21-FCS-5423-03 ACTUATOR ALVE ACTUATOR ALVE TO F&G TO F&G N2: INERGEN SYSTEM AUTOMATICALLY GET ACTIVATED WHEN RELEASE SIGNAL
IS RECEIVED FROM BUILDING F&G PANEL ONLY IF THE AUTO MODE IS SELECTED
IN THE AUTO/ MANUAL SWITCH.

"SUPERVISORY" LED & CUSTOMTEXT

"TROUBLE" LED & CUSTOM TEXT (N


"FIRE" LED & CUSTOM TEXT ( N 12 )
N3: THE GAS RELEASE WILL GET ACTIVATED ONLY AFTER THE TIME DELAY OF

RESERVE SOLENOID VALVE (N4)

RESERVE SOLENOID VALVE (N4)


30 SECONDS.

PRE-DISCHARGE AUDIO VISUAL

PRE-DISCHARGE AUDIO VISUAL

PRE-DISCHARGE AUDIO VISUAL

PRE-DISCHARGE AUDIO VISUAL


44-21-SOV-54-002 SOLENOID DIRECTIONALVALVE

44-21-SOV-54-001 SOLENOID DIRECTIONALVALVE


MAINTENANCE MODE (GREEN)

MAINTENANCE MODE (GREEN)


PANEL "BUZZER" OPERATION

AUTOMATIC MODE (YELLOW)

AUTOMATIC MODE (YELLOW)


44-21-XGAS-54-01 DISCHARGE AUDIBLE ALARM

44-21-XGAS-54-02 DISCHARGE AUDIBLE ALARM


N4: THE ACTIVATION OF MAIN OR RESERVE SOLENOID WILL BE BASED ON THE

MAIN SOLENOID VALVE (N4)

AUTOMATIC MODE (AMBER)

MAIN SOLENOID VALVE (N4)

AUTOMATIC MODE (AMBER)


SELECTION IN MAIN/RESERVE SELECTOR SWITCH. ONLY ONE SOLENOID WILL

RESERVE CYLINDER LED


DESCRIPTION

GAS DISCHARGED (RED)

GAS DISCHARGED (RED)


MANUAL MODE (GREEN)

MANUAL MODE (GREEN)


BE ACTIVATED FOR RELEASE.

MANUAL MODE (BLUE)

MANUAL MODE (BLUE)


EFFECTS

MAIN CYLINDER LED

INHIBIT MODE (RED)

INHIBIT MODE (RED)



N5: WHEN THE ABORT PUSHBUTTON IS PRESSED, THE TIMER WILL RESET AND
AGAIN STARTS FROM ZERO.

COMMON FAULT
N6: ACTIVATION OF MANUAL RELEASE PUSH BUTTON WILL OVERRIDE THE TIMER
& ABORT PUSHBUTTON FUNCTIONALITY.

NOTE N8
ALARM

ALARM

ALARM

ALARM
N7: ABORT PUSHBUTTON IS MOMENTRY PUSH BUTTON TYPE.

(N 12)

12)
N8.THE INERGEN CONTROL PANEL IS INTERFACED TO CPP ICCS VIA MODBUS
COMMUNICATION.

44-21-SOV-54-004

44-21-SOV-54-006

44-21-SOV-54-003

44-21-SOV-54-005
44-21-XFSB-54-01

44-21-XFSB-54-02

44-21-XFSB-54-03

44-21-XFSB-54-04
44-21-XL-54-01-A

44-21-XL-54-02-A
N9: BOTH DEVICE & PANEL FAULT IS INCLUDED IN THE COMMON FAULT.

44-21-XL-54-01

44-21-XL-54-02
N10 : MANUAL RELEASE CAN BE INITIATED BY F&G AT CPP

TAG No.
N11 : INERGEN IS ACTIVATED BY SMOKE DETECTORS IN 200N LOGIC
CAUSE
AREA TITLE TAG. NO SL No DESCRIPTION N12 : TEXT DESCRIPTION WILL BE FOR INDIVIDUAL ALARAM INPUT DEVICES
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 REFERENCE DOCUMENT & DRAWINGS :
SYSTEM AUTO MODE (N2) X X 44.21.47.6679- CLEAN AGENT INERGEN (IG-541) GAS EXTINGUISHING SYSTEM
Release Signal - Switch Gear CONTROL PANEL SCHEMATIC DRAWING FOR CLUSTER-W

( N 10 & N 11)
- 1 Inergen Release Signal from F&G Panel X X X X N3 N3
44.21.43.6631 - CLEAN AGENT INERGEN (IG-541) GAS EXTINGUISHING SYSTEM
SWITCHGEAR ROOM

CONTROL PANEL GENERAL ARRANGEMENT DRAWING FOR CLUSTER-W


Abort Signal - Switch Gear - 2 Gas Release on Hold Signal from F&G Panel X X 44.21.47.6680 - CLEAN AGENT INERGEN (IG-541) GAS EXTINGUISHING SYSTEM
WIRING DRAWING FOR CLUSTER-W

Manual Release Push Button (N6) 44-21-HS-54-01 3 Gas Discharge-Switch Gear X X X X X X X


30.99.89.6604 -PRE-COMMISSIONING & COMMISSIONING PROCEDURE FOR CLEAN
Abort Switch (N5) 44-21-MS-54-01 4 Gas Release on Hold-Switch Gear X X N5 N5 X AGENT INERGEN (IG-541) GAS EXTINGUISHING SYSTEM CONTROL PANEL

SYSTEM MANUAL MODE(N2) X X X X 44.21.42.6608 - F & G CAUSE & EFFECT DIAGRAMS - CLUSTER - (W) SHANAYEL

Release Signal - Switch Gear - 5 Inergen Release Signal from F&G Panel X X 44.99.84.1603- CLEAN AGENT GAS EXTINGUISHING SYSTEM SPECIFICATION

30.99.91.1627- FIRE AND GAS PHILOSOPHY

Manual Release Push Button (N6) 44-21-HS-54-01 6 Gas Discharge-Switch Gear X X X X X X X


INHIBIT MODE (N1) X X X X
SYSTEM AUTO MODE (N2) X X
Release Signal - ITR
( N10 & N 11 )
- 7 Inergen Release Signal from F&G Panel X X X X N3 N3
INSTRUMENT TECHNICAL

Abort Signal - ITR - 8 Gas Release on Hold Signal from F&G Panel X X

Manual Release Push Button (N6) 44-21-HS-54-02 9 Gas Discharge-ITR X X X X X X X 1 3/8/2017 MF DD PLN ISSUED FOR FINAL

FOR REVIEW / COMMNET


ROOM

Abort Switch (N5) 44-21-MS-54-02 10 Gas Release on Hold-ITR X X N5 N5 A 15/05/2016 MA PJ LN

SYSTEM MANUAL MODE (N2) X X X X


Release Signal - ITR - 11 Inergen Release Signal from F&G Panel X X

Manual Release Push Button (N6) 44-21-HS-54-02 12 Gas Discharge-ITR X X X X X X X

INHIBIT MODE (N1) X X X X


Key Maintenance Switch(N1) 65-21-KMS-54-009 13 System Maintenance X X X X X
44-21-SS-54-001
CYLINDER

Main/ Reserve Main (N4) 14 Main Cylinder Activation X


ROOM

Selector Switch Reserve (N4) 15 Reserve Cyliner Activation X


Pressure Switch (Switch Gear) 44-21-PS-54-002 16 Gas Discharged - Switch Gear X X X X X
Pressure Switch (ITR) 44-21-PS-54-001 17 Gas Discharged - ITR X X X X X
CONSULTANT / CONTRACTOR / VENDOR
Common Fault - 18 NOTE-N9 X X X X
COMMON
EVENTS

DOCUMENT No.TFS-CA160077-CE-01
PROJECT : EPC FOR RUMAITHA/SHANAYEL FACILITIES - PHASE III

DOC. TITLE: CLEAN AGENT INERGEN (IG-541) GAS EXTINGUISHING SYSTEM


CAUSE & EFFECT DIAGRAMS FOR CLUSTER-P

ADCO DRG No: 44 21 42 6601 1 01 / 01