You are on page 1of 7

E702.

Designing Concrete Structures:


Acceptance of Concrete Compressive
Strength Test Results According to
ACI 318-19
ACI E702.3-21

Designing Concrete Structures: Acceptance of


Concrete Compressive Strength Test Results
According to ACI 318-19
Reported by ACI Committee E702

Kimberly Kramer, Chair

John Aidoo Carl Larosche Lawrence Taber


Bryan Castles Lei Lou Jairo Uribe
Om Dixit Katelyn Low Kari Yuers
Claude Goguen William Rushing
Todd Hawkinson Luke Snell*

*Primary author

It is the responsibility of the user of this document to estab- ACI E702.3-21 Designing Concrete Structures: Accep-
lish health and safety practices appropriate to the specific tance of Concrete Compressive Strength Test Results
circumstances involved with its use. ACI does not make According to 318-19.
any representations with regard to health and safety issues
and the use of this document. The user must determine the Copyright © 2021, American Concrete Institute.
applicability of all regulatory limitations before applying All rights reserved including rights of reproduction and
the document and must comply with all applicable laws use in any form or by any means, including the making of
and regulations, including but not limited to, United States copies by any photo process, or by electronic or mechanical
Occupational Safety and Health Administration (OSHA) device, printed, written, or oral, or recording for sound or
health and safety standards. visual reproduction or for use in any knowledge retrieval
system or device, unless permission in writing is obtained
Structural Disclaimer from the copyright proprietors. Printed in the United States
This document is intended as a voluntary field guide for the of America.
Owner, design professional, and concrete repair contractor. The Institute is not responsible for the statements or opin-
It is not intended to relieve the user of this guide of respon- ions in its publications. Institute publications are not able
sibility for a proper condition assessment and structural nor intended to supplant individual training, responsibility
evaluation of existing conditions, and for the specification of or judgment of the user, or the supplier of the information
concrete repair methods, materials, or practices by an expe- provided.
rienced engineer/designer.

1
ACI E702.3 Example Problem Acceptance of Concrete Test Results Luke M. Snell

Example Problem: Acceptance of Concrete Compressive Strength Test


Results According to ACI 318-19, “Building Code Requirements for
Structural Concrete and Commentary.”
Problem Statement
Evaluate if concrete is acceptable based on compressive strength cylinder test results. The project
specification states that the concrete compressive strength is required to be 3500 psi at 28 days.

Given Information
Table 1 provides a set of 15 test results performed on 6 x 12 in. cylinders at 28 days.

Table 1
Test Cylinder 1 (psi) Cylinder 2 (psi)
1 4100 4320
2 4320 4190
3 4310 4310
4 4420 4380
5 4200 4160
6 4250 3810
7 3880 4040
8 3570 3680
9 3570 3210
10 3780 3780
11 3680 2980
12 3300 3740
13 3470 3210
14 2770 2750
15 3200 3480

Assumptions
Reference
Sampling frequency is adequate; the minimum frequency is:
a. Once a day for a given class
b. Once for every 150 yd3
c. Once each 5000 ft2 of surface area for slabs or walls ACI 318, 26.12.2.1(a)
Samples are taken on a random basis—concrete was not to be sampled ACI 318R, 26.12.2.1(a)
due to appearance, convenience, or other biased criteria
Each set of cylinders was cast from a different batch of concrete ACI 318R, 26.12.2.1(a)
No water was added to the concrete after the samples were taken ACI 318R, 26.12.2.1(a)
Certified field-testing technicians performed the tests on the fresh ACI 318, 26.12.1.1(d)
concrete
Certified laboratory technicians performed all required laboratory tests ACI 318, 26.12.1.1(e)

American Concrete Institute – Copyrighted © Material – www.concrete.org 1


ACI E702.3 Example Problem Acceptance of Concrete Test Results
Calculations Reference
Concrete strength is considered satisfactory as long as averages of any three ACI 318,
consecutive compressive strength test results (arithmetic average) remain above fc′ 26.12.3.1(a)(1)(2)
and as long as no individual strength test (ST) falls below fc′ by more than 500 psi
when fc′ is 5000 psi or less, or by more than 0.10fc′ when fc′ is greater than 5000 psi.

Determination of Compressive Strength


Strength test results calculation is the average strength of at least two 6 x 12 in. or
at least three 4 x 8 in. cylinder tests from the same batch tested at 28 days or at test ACI 318,
age designated for determination of fc′. 26.12.1.1(a)

For 6 x 12 in. cylinders:

• Cylinder 1 + Cylinder 2 = Strength test result


2

Note: For 4 x 8 in. cylinders, the equation becomes:

• Cylinder 1 + Cylinder 2 + Cylinder 3 = Strength test result


3

Strength Test Results


• Strength test No. 1: 4100 + 4320 = 4210
2
The strength test results for each of the 15 tests are as shown (Table 2):

Table 2
Test Cylinder 1 Cylinder 2 Strength Test
(psi) (psi) (ST) Result (psi)
1 4100 4320 4210
2 4320 4190 4255
3 4310 4310 4310
4 4420 4380 4400
5 4200 4160 4180
6 4250 3810 4030
7 3880 4040 3960
8 3570 3680 3625
9 3570 3210 3390
10 3780 3780 3780
11 3680 2980 3330
12 3300 3740 3520
13 3470 3210 3340
14 2770 2750 2760
15 3200 3480 3340

American Concrete Institute – Copyrighted © Material – www.concrete.org 2


Arithmetic Average of Strength Test Calculation
ACI 318,
• ST1 + ST2 + ST3 = Arithmetic Average 26.12.3.1(a)(1)
3
Arithmetic Average of Strength Test Results

• Using the first three strength test results:

4210 + 4255 + 4310 = 4258 psi


3
Thus, the arithmetic averages for the tests are shown (Table 3):

Table 3
Test Cylinder 1 Cylinder 2 Strength Test Arithmetic
(psi) (psi) (ST) Results (psi) Average (psi)
1 4100 4320 4210 —
2 4320 4190 4255 —
3 4310 4310 4310 4258
4 4420 4380 4400 4322
5 4200 4160 4180 4297
6 4250 3810 4030 4203
7 3880 4040 3960 4057
8 3570 3680 3625 3872
9 3570 3210 3390 3658
10 3780 3780 3780 3598
11 3680 2980 3330 3500
12 3300 3740 3520 3543
13 3470 3210 3340 3397
14 2770 2750 2760 3207
15 3200 3480 3340 3147

Determination of Value to Verify Strength Test Results are Acceptable


Specified strength is 3500 psi; therefore, to be acceptable, no strength test result
can be below fc′ – 500, or 3500 – 500, which is equal to 3000 psi.

Each strength test (ST) result in Table 2 is to be compared to 3000 psi. ACI 318,
26.12.3.1(a)(2)
Test Results Evaluation
Determine if the arithmetic average of the strength test results fail to meet
satisfactory strength levels.

• Arithmetic averages (Table 3) for Tests 13, 14, and 15 are below fc′.
Strength test results (Table 2) for Test 14 are below 3000 psi (fc′ – 500).

Note: Test 9 has one cylinder test result below 3500 psi (3210 psi). The average
of the two cylinders tested is 3390 psi (the strength test result), which is above

American Concrete Institute – Copyrighted © Material – www.concrete.org 3


3000 psi, so the concrete is acceptable.

Test 11 has a cylinder test result of 2980 psi. The strength test result is 3330 psi, ACI 318,
so the concrete is acceptable. 26.12.3.1(b)

Steps to be taken because the arithmetic averages were low (arithmetic average of
Tests 13, 14, and 15) and because the strength in the Test 14 strength test result
was below fc′ by more than 500 psi:

1. Increase Average of Strength Test Results


Steps to be taken will be dependent on circumstances and could include one or
more of the following:
• Increase in cementitious materials content
• Reduction in, or better control of, water content
• Use of a water-reducing admixture to improve the dispersion of
cementitious materials
• Other changes in mixture proportions
• Reduction in delivery time
• Closer control of air content
• Improvement in the quality of testing, including strict compliance with
ASTM C172, ASTM C31, and ASTM C39.

Note: Changes in operating procedures or small changes in cementitious


materials content or water content should not require a formal resubmission of
mixture proportions; however, changes in sources of cement, aggregates, or
admixtures need to be accompanied by evidence that the average strength level
will be improved.

2. Investigate Low Strength Results in the Area Represented by Test 14 Strength


Test Result
ACI 318,
When the strength test results fall below acceptable levels, steps are to be
26.12.3.1(c)
taken to ensure that the structural adequacy of the structure is maintained.
• Building official should apply judgment as to the significance of the low test
results; however, lower strength may be tolerated under many
circumstances—this is a matter of judgment on the part of the licensed ACI 318R,
design professional and building official. 26.12.6
• If further investigation is deemed necessary, the following methods of
investigation may be used:
a) In-place testing
b) Strength testing of cores, in extreme cases

Note: In-place tests of concrete may be useful in determining whether a portion


of the structure actually contains low-strength concrete. Unless these in-place
tests have been correlated with standard strength test results for the concrete in
the structure, they are of value primarily for comparisons within the same
structure, rather than as quantitative estimates of strength. In-place tests

American Concrete Institute – Copyrighted © Material – www.concrete.org 4


include probe penetration (ASTM C803), rebound hammer (ASTM C803), or
pullout test (ASTM C900).

3. Determine if Concrete is Adequate Using Coring, if Required


When coring is required, three cores are to be taken for each strength test
that falls below fc′ by more than the limit allowed for acceptance (ASTM ACI 318,
C42). 26.12.6.1(a)
• Concrete represented by cores is considered structurally adequate if
the average of the three cores equals or exceeds 85 percent of fc′ with ACI 318,
no single core being less than 75 percent of fc′. 26.12.6.1(e)
• Additional core testing is permitted if the core compressive test results
are considered erratic. ACI 318,
• If additional core tests fail to meet required strength test levels and 26.12.6.1(f)
the structural integrity remains in doubt, the responsible authority is ACI 318,
permitted to order a strength evaluation in accordance with ACI 318 26.12.6.1(g)
Chapter 27 for the questionable portion.

Note: For fc′ of 3500 psi, the average core strength must exceed 85 percent of
3500, or 2975 psi. No single tested core can be below 75 percent of 3500 psi, or
2625 psi.

Conclusions:
1. Steps must be taken to increase the average of the strength results.

2. Concrete in the area represented by strength Test 14 must be investigated and


evaluated.

3. Concrete in all other areas (except concrete in Strength test areas number 14) is
considered to have met code requirements.

Additional Reading

• ACI 214R-11—Guide to Evaluation of Strength Test Results of Concrete


• ACI 228.1R-19—Report on Methods for Estimating In-Place Concrete
Strength
• ACI 228.2R-13—Report on Nondestructive Test Methods for Evaluation of
Concrete in Structures
• ACI 301-16/301M-16—Specifications for Structural Concrete
• ACI 437R-19—Strength Evaluation of Existing Concrete Buildings

American Concrete Institute – Copyrighted © Material – www.concrete.org 5

You might also like