3516B (DYNAMIC GAS BLENDING)

Transfer switch Status Gas blending control Status


Utility breaker max open time 3 sec status enabled
Utility breaker max close time 30 sec max. 70%
generator to utility transfer mode manual
generator ready to accept load delay time 0 sec Deration information Status
gen. ready to accept load threshold % 90% desired engine speed 1505 rpm
min. unpowered load time 0 sec
gen. to utility transfer failure warn threshold 60 sec Nominal setting Status
utility to gen. transfer failure S/D threshold 90 sec rated voltage 400V
utility to gen. transfer failure warn threshold 60 sec rated frequency 50Hz
gen. to utility fast transfer delay time 10 sec rated real power 1.6MW
gen. to utility transfer delay time 180 sec rated apparent power 2.0MVA
loss of utility event notification delay time 10 sec
gen/utility automatic transfer enable status disabled

Cooling fan status


fan max. aftercooler out air temp. thresh 50C
fan aftercooler out air temp. hysteresis 20C
fan min. aftercooler out air temp. thresh 15C
fan coolant temp. hystersis 16C
fan max. airflow coolant temp. 103C
fan min. airflow coolant temp. 101C

Fuel load status


auto fuel load pump OFF % threshold 5%
auto fuel load pump ON % threshold 5%
fuel transfer feature enable status disabled

Generator breaker control status


generator breaker max. open time 3 sec locked
generator breaker max. closing time 60 sec locked
generator breaker closing pulse rest interval 15 sec locked
generator breaker closing pulse active time 1 sec locked

Automatic start/stop status


digital input ECU fault reset enable status disabled locked
ECU fault reset active time 0.1 sec
remote genset control enable status disabled
engine control data link configuration j1939 locked
emergency stop input active state config. high
engine fuel priming feature enable status disabled locked
engine idle operation enable status enabled locked
engine operation status input config. CAN input locked
engine cooldown speed config. rated speed locked
crank terminate RPM 300 rpm locked
crank alert activation time 0 sec
start AID activation time 0 sec
cooldown duration 3 mint
max. number of crank cycle 4
engine start sequence delay time 0 sec
engine purge cycle time without ignition 0 sec locked
engine purge cycle time with ignition 0.0 sec locked
crank cycle rest interval 10 sec
crank duration 10 sec
Eng. Start fault protection activation delay time 30 sec