Setting the Prehopper Indication to Zero

using the Pfister Handheld PHT


this presentation is a standard procedure to set the prehopper indication
to zero without carrying out a complete calibration
the shown steps are examples only and may vary for each individual plant
if the prehopper is empty and the indication
of the prehopper level is not exactly on zero
this procedure may be used to set the indication to zero
without carrying out a complete calibration
the load cells of the prehopper scale (4 pcs) are located here
to set the prehopper indication to zero
the following preconditions are required

> prehopper must be completely empty

> feeder must be completely empty

> blower should be shut off

> equipment is not running

> air pressure in the system must be zero

> equipment is in local mode


Pfister Handheld PHT

PHT = Pfister Handheld Terminal


link the PHT to the CSC controller or to the LCB

PHT connection at the


CSC controller X17
PHT connection at the
LCB

LCB = Local Control Box


Pfister-Terminal
899.430.63.00
when the PHT is connected wait until
Vers. 1.2
Ctrl Y > Connect
Ctrl Y > Connect
is being displayed then press key Ctrl
Y to establish communication
if the PHT is connected to the LCB
HAUPTMENU CPI1 press key arrow down until
3 CPI -> Server
Operational 3 CPI -> Server
is being displayed

then press key Enter


to get into the CSC menu

if the PHT is connected to the CSC


skip this page
CSC MAIN MENU
the PHT now will show
one of the main menu lines
X xxxxxx
if not press Ctrl A to get there
CSC MAIN MENU press key arrow down until
7 Configuration
7 Configuration
is being diplayed

press key Enter


CONFIGURATION
18.10.2005 11:32
the PHT now will show
1 Syst-Parameter 1 Syst-Parameter

press key Enter


SYSTEM SETTINGS
Entry free
the PHT now will show
<. . . . . . . . . . . . . no Entry free

press key Enter


SYSTEM SETTINGS
Entry free
press key arrow down
<. . . . . . . . . . . . . yes to change to yes

press key Enter


CONFIGURATION
18.10.2005 12:45
press key 0
1 Syst-Parameter to go up one directory

1 Syst-Parameter
is being displayed now
CONFIGURATION
press key arrow down until
18.10.2005 12:45 8 Checkweigher
8 Checkweigher
is being displayed

press key Enter


CW MEAS. PARAMET.
press key arrow down until
>> Zero setting
>> Zero setting is being displayed

press key Enter


at this point the pressure in the prehopper must be

ZERO

prehopper and rotor feeder must be empty


this figure indicates
> < + 0,0276 t the actual load of the prehopper
Set to zero
Keys -> Cr,1,C>
the display now will show
> < + 0,0276 t Set to zero
Set to zero
Keys -> Cr,1,C>

setting to zero is only possible


if the 2 chevrons are visible

setting the prehopper to zero is only


possible within a range of -5% to +10%
of the weighing range of the scale
> < + 0,0276 t press keys Enter 1 Enter
Set to zero
Keys -> Cr,1,C> to set the prehopper indication to zero
the prebin indication will now show
> < + 0,0000 t 0,0000 t
Set to zero
Keys -> Cr,1,C>

press key Ctrl A


to leave this menu
ZEROING THE PREHOPPER WEIGHT INDICATION
DONE