Professional Documents
Culture Documents
20150E00 Equipos Paquete Rotatorios
20150E00 Equipos Paquete Rotatorios
20150E00 Equipos Paquete Rotatorios
20150.ENG.STA.STD
Rev.00 - February 2013
GENERAL NOTE This Re-coding does not affect the document content.
TO THE Documents traceability is guaranteed by the unchanged document
DOCUMENT RE-
number.
CODING
Any cross-reference between documents remains unaffected.
/
La presente ricodifica non ha effetto sul contenuto del documento.
NOTA
GENERALE
La rintracciabilità dei documenti è garantita dal numero di documento
ALLA che resta immodificato.
RICODIFICA I riferimenti incrociati fra i vari documenti rimangono validi.
First issue
Even if this document covers the most feasible applications, it is not excluded the possibility
to apply different solutions as long as it will be guaranteed at least the same functionality,
performances, and reliability.
INDEX
1. GENERAL................................................................................................................................................... 5
1.1 SCOPE .................................................................................................................................................. 5
1.2 REFERENCE CODES.......................................................................................................................... 5
1.3 DEFINITIONS .......................................................................................................................................... 5
2. FUNCTIONAL GENERIC REQUIREMENTS................................................................................... 7
2.1 MEASUREMENT UNITS ........................................................................................................................... 7
2.2 OPERATIVE ENVIRONMENT .................................................................................................................... 7
2.3 BASIC REQUIREMENTS ................................................................................................................... 7
2.3.1 Hazardous Areas........................................................................................................................... 7
2.3.2 Explosive hazard protection methods............................................................................................ 7
2.3.3 Instrument power supply system ................................................................................................... 7
2.3.4 Protection from the environment................................................................................................... 8
2.3.4.1 Mechanical protection ............................................................................................................................... 8
2.3.4.2 Protection from high temperature.............................................................................................................. 8
2.3.4.3 Protection from low temperature............................................................................................................... 8
2.3.4.4 Protection from Transient Static and Radio Frequency Interference ......................................................... 8
2.3.5 Connection sizes and type ............................................................................................................. 9
2.3.5.1 Electrical ................................................................................................................................................... 9
2.3.5.2 Process & utility ........................................................................................................................................ 9
2.3.5.3 Pneumatic................................................................................................................................................ 10
2.3.6 Material....................................................................................................................................... 10
2.3.7 Tagging criteria .......................................................................................................................... 11
2.3.7.1 Applicable Standards............................................................................................................................... 11
2.3.7.2 Tagging criteria deviations and clarifications.......................................................................................... 11
2.3.7.3 Nameplate ............................................................................................................................................... 11
2.3.8 Painting and protective finishing ................................................................................................ 12
2.4 FUNCTIONAL REQUIREMENTS OF INSTRUMENTATION ACTIVITIES ............................................. 13
2.4.1 General ....................................................................................................................................... 13
2.4.2 Temperature Instruments ............................................................................................................ 14
2.4.3 Pressure Instruments................................................................................................................... 15
2.4.4 Level Instruments ........................................................................................................................ 15
2.4.5 Flow Instruments......................................................................................................................... 16
2.4.6 Control valves ............................................................................................................................. 16
2.4.6.1 General .................................................................................................................................................... 17
2.4.6.2 Control valves type selection................................................................................................................... 17
2.4.6.3 Trim selection.......................................................................................................................................... 17
2.4.6.4 Control valves sizing............................................................................................................................... 18
2.4.6.5 Noise ....................................................................................................................................................... 18
2.4.6.6 Flashing and Cavitation........................................................................................................................... 18
2.4.6.7 Control valves actuators .......................................................................................................................... 18
2.4.6.8 Control valves accessories....................................................................................................................... 19
2.4.7 Self contained control valves....................................................................................................... 19
2.4.8 Anti-surge Control valves ........................................................................................................... 20
2.4.9 Choke valves ............................................................................................................................... 21
2.4.10 On-Off valves .............................................................................................................................. 21
2.4.10.1 Generalities ......................................................................................................................................... 21
2.4.10.2 On/off valves design ........................................................................................................................... 21
2.4.10.3 On/off valves actuators ....................................................................................................................... 22
2.4.10.4 On/Off valves accessories................................................................................................................... 22
2.4.11 Analysers..................................................................................................................................... 23
2.4.12 Interconnections.......................................................................................................................... 23
2.4.13 General Criteria for Instruments Location ................................................................................. 24
2.5 OVERALL BLOCK DIAGRAM AND PHILOSOPHY .............................................................................. 24
2.6 FUNCTIONS AND SYSTEM REQUIREMENTS ........................................................................................ 26
2.6.1 Fire&Gas (F&G) detection system and Emergency ShutDown system (ESD) ........................... 26
2.6.2 Inert gas fire suppressant systems............................................................................................... 27
2.6.3 Control functions of the UCP/PLC system.................................................................................. 28
2.6.4 Functions of Local control panel ................................................................................................ 28
Documento riservato di proprietà di Eni S.p.A. - Divisione Exploration & Production.
Esso non sarà mostrato a Terzi né utilizzato per scopi diversi da quelli per i quali è stato inviato.
eni spa 20150.PKG.STA.FUN
Rev. 0 February 2013
exploration & production division
Page. 4 of 54
APPENDIX B .................................................................................................................................................... 53
APPENDIX C.................................................................................................................................................... 54
1. GENERAL
1.1 SCOPE
This document outlines the minimum requirements to be followed for the design,
construction, testing and installation of the instrumentation and automation systems
included in a package supply based on machinery equipment.
The document is applicable to the oil & gas production/treatment plant of eni exploration &
production division.
Any other additional information not covered by this specification will be specified in the
project technical documentation and in the applicable codes, normative references.
About the project documents, see the following (attached to this specification):
The IDS and DDS forms are partially filled in but they can be modified according to
project needs; while the TDS form has to be properly compiled.
Possible limits, exclusions and particular prescriptions shall be indicated in the Technical
Data Sheet.
The technical requirements of this Functional Specification are based upon considerations
of performances and functionality, therefore the instructions contained in this document are
not meant to be discriminatory.
Any alternative suggestion will be considered, provided that the compliance with what
required in this document is satisfied both from functional and performance points of view.
Contractor / Supplier will have to verify the validity and relevant applicability of each rule
checking at least the latest edition available and also the issuance of new pertinent
regulations.
1.3 DEFINITIONS
For the purpose of this specification, the following definitions apply:
COMPANY is the party that initiates the project and ultimately pays for its design and
construction. The COMPANY will generally specify the technical requirements.
The COMPANY may also include an agent or consultant authorized to act for,
and on behalf of, the COMPANY.
PURCHASER is the party that buys the equipment and its auxiliaries for its own use or
as an agent for the owner. The PURCHASER may either be the COMPANY or the
CONTRACTOR.
The term VENDOR shall be considered to be synonymous with the term Manufacturer
or SUPPLIER as defined above.
PACKAGE SUPPLIER shall perform all detailed design, fabrication and supply of all
necessary materials supplied complete, with all instrumentation fully assembled,
piped, wired when required, and tested to ensure safe, reliable maintainable and
effective operation.
For unusual situations of locally increased hazard, the engineering contractor shall upgrade
the selection.
Protection methods Ex’p’ (pressurization), Ex’s’ (special execution), Ex’m’ (encapsulation)
and Ex’n’ (non sparking) shall be subject to written COMPANY approval.
Hazardous area protection preferred methods are Ex’d’ for sparking equipment/connections
and Ex’e’ for no-sparking equipment connections.
The certification shall be provided by the appropriate authority in the manufacturer country
(i.e. CESI for Italy, PTB for Germany, BASEEFA for United Kingdom, LCIE for France,
etc.).
2.3.5.1 Electrical
Connections for inlet and/or outlet cables shall be threaded NPTF or ISO depending
of the instrument. Electrical certification size shall be as per Manufacturer standard.
Usually it is 1/2" NPT-F ANSI B1.20.3 (water proof) UNI 6125 (explosion proof).
STANDARD CONNECTIONS
As per Piping
Restriction orifice
Class
½’’ (# < 600# ) ½” NPT (F) ¼” NPT
Flow DP Cells ½” NPT (F)
¾’’ (# >900#) ¾’’ NPT (F) (F)
6” flanged (4)
Tank Level
#600 min
Pressure Instrument
INSTRUMENTS
Pressure Instrument
1” or 2” flanged 3/4” NPT F 1/2” NPT F
on Vessel
Diaphragm seals on 2” flanged
2” flanged (4) 2” flanged (4)
Pipes or Vessels (4)
1½” flanged
1/2” NPT F
#300 min / SW (2)
INSTRUMENTS
Thermowells on
TEMPERATURE
Thermowells on 2” flanged
1/2” NPT F
Vessel #300 min
Process-connected instruments that are not line-mounted shall have secondary isolating
valve and bleeder or valve manifold at the instrument.
For more details refer to COMPANY standard:
20041.ICO.STA.STD. CONNECTIONS OF INSTRUMENTS TO THE PROCESS
2.3.5.3 Pneumatic
Threaded joints in instrument air service shall be made up using Teflon dispersion
sealant.
Pocketing of piping and tubing shall be avoided.
Instrument connections should usually be ½’’ for air supply and ¼’’ for inlet/outlet
signals, NPTF as per ANSI B 1.20.1.
2.3.6 Material
The selection of material, the pressure and temperature rating of the pressure parts
and the type of connection to the process of on-line or vessel installed equipment
shall comply with the line mechanical specifications and the vessels project data.
These requirements apply to the material of the body, any internal coating, bolts and
nuts of components as valves, volumetric meters and primary elements for the
measurement of rate, level instruments.
• The internals of instruments, in contact with the process fluid, shall be at least in AISI
316 stainless steel. Where the nature of the fluid requires other metallurgy than
stainless steel, it shall be consistent with the piping class materials.
• When required by the line specification, the materials in contact with the process
fluid shall be in compliance with NACE-MR-01.75.
• The materials shall be, in any case, compatible with the process fluid in terms of
chemical corrosion.
• The pressure and differential pressure transmitters housing shall generally be in
painted casted aluminium (or in stainless steel if required).
• The pressure gauge casing shall be of stainless steel AISI 316.
• Measuring elements shall be of AISI 316 unless the process fluid required a more
suitable material.
• The torsion pipe of the displacement level instruments shall be in K-MONEL or
INCONEL, to obtain more flexibility and resistance to corrosion.
• Bulb extension capillaries shall be of AISI 316 stainless steel and shall be protected
with a flexible sheath also of AISI 316.
• Thermowell material shall be AISI 316 as long as the process fluid does not require
more suitable materials. Material according to line specification can be acceptable for
the thermowells to be installed within the package/machinery supply.
• The identification nameplate shall be in AISI 316.
• For primary and secondary connections (either hydraulic or pneumatic), the tubing
material shall be minimum AISI 316 and also the fittings shall be in AISI 316.
• Cable/Tubing trays shall be AISI 316 SS. Hot dipped galvanized carbon steel can be
acceptable for cable/tubing trays to be installed within the package/machinery
supply.
• Screws, bolts and miscellaneous ancillaries shall be 316 SS minimum; other material
could be used if required due to mechanical reason and to avoid/minimize galvanic
corrosion.
Documento riservato di proprietà di Eni S.p.A. - Divisione Exploration & Production.
Esso non sarà mostrato a Terzi né utilizzato per scopi diversi da quelli per i quali è stato inviato.
eni spa 20150.PKG.STA.FUN
Rev. 0 February 2013
exploration & production division
Page. 11 of 54
• Studs will be in ASTM-A 193-B7 galvanized, while Nuts will be in ASTM-A 194-2H
galvanized.
Material for control and safety valves
• Stainless steel or alloys compatible with the process fluid, having mechanical
characteristics suitable for the controlled process, shall be utilized for trim.
• The stems shall be in AISI 316 chromate stainless steel.
• The trim of valves in the drains of high-pressure separators shall be in tungsten
carbide.
• The same material shall be utilized for the bonnet and the body.
• The bonnet of the pneumatic actuators shall be in cast iron, or carbon steel in cold
climates with ambient temperature lower than - 20°C.
• By a stamped AISI 316 SS nameplate attached with AISI 316 SS ring on the
instrument.
• By a traffolyte label bolted on the instrument support with AISI 316L SS bolts.
Tagging shall include complete COMPANY identification tag number the color
defined in table below.
LETTERS LABEL
Process and other Black White
Safety Black Yellow
IS circuit Black Light Blue
Fire & Gas Black Red
Documento riservato di proprietà di Eni S.p.A. - Divisione Exploration & Production.
Esso non sarà mostrato a Terzi né utilizzato per scopi diversi da quelli per i quali è stato inviato.
eni spa 20150.PKG.STA.FUN
Rev. 0 February 2013
exploration & production division
Page. 12 of 54
2.4.1 General
Instrumentation means the overall of component and/or equipment, with relevant hook up
(process – electric/electronic – pneumatic/hydraulic), to be used as monitor, control,
adjustment of the same component/equipment themselves.
The monitoring and supervisory instruments shall provide information for the diagnosis of
the equipped package during operation and for warning of deterioration of its conditions.
The instrumentation system shall protect personnel and plant against injury or loss under all
conditions of operation or malfunction.
The instrumentation control of a package unit will be identified in the relevant P&ID.
The symbols and numbering of instruments shall conform to ISA S 5.1 and according to
project code numbering.
The instrumentation type, electric / electronic or pneumatic, and the signal type to be used
will be defined, generally, inside the project documentation, and will be executed / installed
according to the reference codes.
All provided instruments shall be pre-calibrated, installed, supported, labelled, and
connected to process piping inside the system.
All instrument piping/tubing shall be properly supported and identified, and the pipe routing
shall be laid in such a way as to suffer the minimum of disturbance when any plant item is
removed for maintenance.
Where piping is subjected to vibration, individual pipe shall not touch each other or any
metal part, other than the pipe support and clips.
In case of pneumatic instruments, these instruments shall be suitable to work with
instrument air (or natural gas treated if air instrument is not available).
The instrumentation to be used within the package unit shall be chosen by the PACKAGE
SUPPLIER in relation to the function of the single instrument and to the project
requirements.
Instrumentation design shall be in accordance to the applicable Codes and Standards.
In case that the PACKAGE SUPPLIER intends to use a different standard, or its own
standard, complete legend and index documentation shall be provided in the bid.
Correspondence between PACKAGE SUPPLIER’s standards and Project required
standards will be provided during the project stage.
The EPC/PACKAGE SUPPLIER shall provide all the instruments and relevant process,
pneumatic/ hydraulic (if any), and electrical hook-ups, for the package unit described in this
document.
The measuring range shall be chosen among Manufacturer's standards.
Electronic transmitters shall be smart type suitable for maintenance by dedicate software
for HART application (except for particular applications where fast response time is
requested). Electronic transmitters shall have an output signal 4÷20 mA obtained through a
two-wire system, and shall have also a local output indicator (digital type).
Electronic Transmitter’s Supplier has to provide the software library for the HART protocol /
Maintenance PC in order to allow the remote calibration, maintenance, diagnostic, etc. For
the same purpose, a Hand held field communicator can be also required.
Trip function shall be provided with electronic transmitter. Thresholds set-up on analogue
signals from transmitters shall be used for trip service.
Instrument for trip purpose shall be not used for other functions, such as measurement or
control.
Only in particular applications due to space limitation and after COMPANY approval,
instruments can be used to perform two different functions (trip and measurement).
When only signalling and alarm functions are required, they can be performed using
relevant process switches.
A dedicated and individual process connection shall be foreseen for each an instrument to
be used independently from its application/purpose such as measurement, signalling,
alarm, control, trip.
Only in particular applications due to space limitation and after COMPANY approval,
different instruments can share the same process connection.
All the instruments and materials (i.e.: vibration monitors, pump suction / discharge
pressures and temperature probes for pump bearings and motor winding) required for
pump monitoring and protection shall be installed and shall be in compliance with the
relevant technical specifications.
Filled Bulbs as primary elements shall mainly be used for local controls, for thermostats
and self-regulating valves. The latter shall be used for temperature control if the control
accuracy does not represent particularly important parameters. In case of local controllers,
the measuring system shall be compensated against ambient temperature variations.
Filled temperature gauges for local temperature display shall have a dial with a minimum
outside diameter of 150 mm, and an accuracy of ± 1% full scale Thermometers with a
smaller dial, and lower accuracy could be used for machine auxiliary services and package
supplies.
The range of these instruments shall be chosen in such a way that the temperature
indicated remains between 35% and 75% of the full scale.
The capillary length shall be suitable for the involved application; it can be from 3 to 5 m.
Thermowells (TW) shall be flanged or threaded. Exception is made for the case of special
applications.
Measuring Elements type of pressure instrument will depend on the service and Supplier
chosen. However, they shall be capable of withstanding a pressure 30% higher than the
instrument full scale.
Measuring elements with separating diaphragms shall be used in the presence of viscous
or corrosive fluids in the same way as in the presence of mud.
Measuring elements which are exceptionally subject to a pressure higher than the
maximum allowable pressure shall be fitted with mechanical protection facilities.
In the case of pulsating pressure, suitable damping methods shall be employed (use of
capacitance, glycerine filling of measuring device, dampers, etc.).
Local Pressure Indicators shall generally be of bourdon type, the dial diameter shall be at
least 150 mm. Smaller dials can be used for machine auxiliary services and package
supplies.
The measuring range of direct pressure gauges shall be chosen in such a way that the
normal pressure is between 33% and 66% of the instrument full scale and in compliance
with the Manufacturer's standards.
Direct pressure gauges shall not have a suppressed range.
Pressure electronic Transmitters could be capacitive type, inductive type, vibrating wire
type, strain-gauge type, etc.
The transmitter’ values of zero and range will be locally adjustable.
Pneumatic transmitters shall be force balance type.
Measuring Elements
In order to reduce the number of connections to process equipment stand pipes shall be
used, whenever possible, to install level gauge glasses, level transmitters and level
switches for alarm purpose.
Transmitters
Measuring elements
Fluid flow measurement can be divided into several types; each type requires specific
considerations such as accuracy requirements, use of the flow information to obtain the
required end results. Normally the flow meter is measure flow indirectly by measuring a
related property such as a differential pressure across a flow restriction or a fluid velocity in
a pipe. A number of different fundamental physical principles are used in flow measurement
devices.
The market offers several types of flow meters technologies, and relevant sub types (or
primary elements), such as: DIFFERENTIAL PRESSURE FLOW METER (Orifice plate,
Venturi tube, Pitot tube, Nozzle), VARIABLE AREA FLOWMETER (Rotameter, Movable
vane meter), POSITIVE DISPLACEMENT FLOWMETER (Oscillating vane, Oval gear,
Single / multiple piston), TURBINE FLOWMETER, VORTEX, ELECTROMAGNETIC
FLOWMETER, ULTRASONIC FLOWMETER (Doppler, Transit- Time), MASS
FLOWMETER (Coriolis, Thermal Dispersion).
Transmitters
The transmitter zero and range will be locally adjustable.
Whenever it is necessary to use more d/p cells to cover wide flow rate measuring ranges, it
is suggested to use transmitters designed with more suitable performances such as wide
range, accuracy, remote electrical reconfiguration, etc, according to project needs.
2.4.6.1 General
Control valves will have straight through.
Generally control valves will have flanged end-connections in accordance with a minimum
rating of 300#. Butterfly valves may be wafer or lug type.
Large butterfly valve will be wafer lug type with a minimum rating of 150#.
Control valves shall be according to the piping class specification, mainly for what concern
material, rating, end connections, etc.
Eccentric or rotating plug or butterfly valves shall be usually flange type.
Where flanges are not permitted by piping standard, socket or butt-welded connection will
be used.
Flangeless valves shall not be used in services with design temperatures above 510 °C.
Extended bonnet can be used when the process fluid has high or low temperature.
Valves with bodies having nominal dimensions equal to 1¼", 2½" and 5" shall not be used.
For pipes that are 1" or less in diameter, the minimum valve body size will be 1" with
reduced trim if necessary.
The direction of flow shall be clearly marked on the valve body.
Control valves shall be equipped with stem travel indicator.
2.4.6.2 Control valves type selection
Control valves will be provided with linear or equal percentage plugs, except for on-off
service or small sizes, for which the manufacturer’s standard plug will be used.
In general, reversible globe control valves with top and bottom guides, or heavy-duty-type
plug guiding shall be used.
The use of butterfly types will be selected for large flows with low pressure drops.
Valves with rotating plug shall be used in non-critical services.
For Cv values of approximately7 and lower, non-reversible globe valves shall be used.
Particular applications may require the use of one of the following types of valves:
• Butterfly valves for low pressure drops and where tight shut-off is not required;
• Characterised ball valves (e.g.: V-ball), for fluids containing suspended solids or
fluids likely to polymerise or crystallise;
• Angle valves for choke valves only;
• Diaphragm valves (e.g. Saunders or equivalent) for corrosive and dirty liquids or for
slurry service.
Special type valve (e.g. multi-step type with cage-type plug, etc.) shall be used in the case
of very high pressure drops or high values of fluid velocity, or in order to reduce the velocity
and excessive noise, etc.
Control valves shall never be used as shut-off valves.
The acceptable valve seat leakage is in accordance with ANSI/FCI 70.2 Class IV as
minimum.
Whenever there is the presence of toxic gas or there are severe environmental
implications, also the fugitive emission from valve packing have to be strongly reduced
using specific and proper material, particular design, dedicated devices such as bellows
seal or other equipment achieving low emission levels.
2.4.6.3 Trim selection
In general, the following table should be used to select the valve characteristic:
Service Characteristic
Flow, linear measurement Equal percent
Flow, non linear measurement Linear
Pressure, liquid Linear
Pressure, gas Equal percent
Level Equal percent
Temperature Equal percent
Analyser Linear
See the section 2.4.8 for the characteristic of Anti-surge control valves.
Documento riservato di proprietà di Eni S.p.A. - Divisione Exploration & Production.
Esso non sarà mostrato a Terzi né utilizzato per scopi diversi da quelli per i quali è stato inviato.
eni spa 20150.PKG.STA.FUN
Rev. 0 February 2013
exploration & production division
Page. 18 of 54
Hardened trim, seats and stems shall be required in the following cases.
a. When the process fluid is a liquid containing suspended solids.
b. When cavitation phenomena may occur.
c. When under maximum flow, the pressure drop across the valve is ≥ 10 bar for liquids,
gases and hydrocarbon vapours.
d. All steam services.
Unless otherwise indicated in the project requirements, the minimum speed of plug travel
shall be 3 mm/s for linear motion actuator/valves and 3°/s for rotary motion actuator/valves.
Maximum time for full travel shall be no greater than 30s.
Service conditions, (associated with high pressure drop, high noise, flashing and cavitations
also), define if they are fitted with cage trim, single seated trim with plug or stem guiding, or
double seated trim, which shall be top and bottom guided.
2.4.6.4 Control valves sizing
The control valves sizing shall be calculated on the basis of the process operating
conditions and in compliance with the ISAS75.01.01. The aim of the maximum rangeability
could be reached if the CV is calculated taken into the following considerations:
CV maximum is:
− Calculated using the maximum flow in conjunction with the minimum pressure
drop across the valve.
− -Selected by usually increasing the calculated maximum CV by a 20 to 30% of its
value.
CV minimum is:
− Calculated using the minimum flow in conjunction with the maximum pressure
drop across the valve and the same run conditions.
− Selected by usually decreasing the calculated minimum CV by a 15 to 20% of its
value.
The manufacturers published Cvs shall be used to determine the valve size.
The controllable Cv values shall be within the limits of 10% and 90% of the total valve
opening, normal flow shall coincide with 80% of the total valve opening for the equal
percentage type and with 70% for the linear type.
Butterfly valves shall be sized for a maximum opening angle of 60°. Exception is made for
characterised disc valves, which may be sized for a maximum opening angle 90°.
For liquid sizing in a pumped circuit the pressure drop allocated to the control valve will take
into account flow-rate fluctuations and consequent differences in friction losses as well as
minimum pressure drop requirements for control purposes.
2.4.6.5 Noise
Noise calculation shall be done for each control valve. Control valve design (including body,
trim, diffusers, etc.) shall be suitable to ensure that the noise result calculation is always
less than 85 dB(A) at one meter distance downstream of the valve. COMPANY/EPC shall
be informed of all cases where this condition is not complied with.
In all cases where it is necessary to use special control valves, silencers or other devices,
they shall be subject to the prior approval of the COMPANY/EPC.
2.4.6.6 Flashing and Cavitation
All valves in liquid service shall be checked for cavitation/flashing in the sizing calculations.
Special precaution shall be taken in sizing control valves for cavitation and flashing
services.
Control valves with low pressure recovery shall be selected to minimise cavitation.
2.4.6.7 Control valves actuators
Control valves manufacturer shall be responsible for proper operation and sizing of the
actuator.
If the instrument air is not present in the plant, or the pneumatic/hydraulic actuators are not
desired, the actuators for control valves shall be electrical type. The electrical actuator will
be equipped with position sensing equipment, torque sensing, motor protection, logic
control, and digital communication capacity. The expected performances (such as response
time, speed of operation, resolution, repeatability, and accuracy) of the electrical actuator
have to be similar or better than the pneumatic actuator.
2.4.6.8 Control valves accessories
Positioner or booster relay
Generally all control valves shall be provided with a pneumatic positioner.
Pneumatic Positioner will be 0,2÷1,0 barg. Input, output signal will be in accordance with
the actuator signal range.
When for process reason a need of high flow is required to satisfied stroke velocity, a
booster relay will be added to the Positioner output.
All Positioners and relays shall be equipped with Pressure gauges (double dial: barg and
psig) at Inlet signal, output signal and supply.
This instrument receives a 4 to 20 mA DC input signal, and uses an I/P converter, nozzle-
flapper, and pneumatic relay to convert the input signal to a pneumatic output signal.
Air Filter-Regulators
An air filter-regulator is required for each control valve air user, such as positioner, booster,
etc. They shall be self reducing valve type and of all-metal construction. A 50 mm diameter
output gauge shall be provided, calibrated in barg to set operating pressure and the scale
shall cover instrument air system’s operating range.
Signal transducer
Current to Pneumatic Conversion (I/P) for a control room 4÷20 mA control signal to a 0.2 to
1.0 barg pneumatic signal (with double dial barg/psig) shall normally be loop powered by 2
wires. Converters shall be field adjustable
The transducer receives the direct current input signal and uses a torque motor, nozzle-
flapper, and pneumatic relay to convert the electric signal to a proportional pneumatic
output signal. Nozzle pressure operates the relay and is piped to the torque motor feedback
bellows to provide a comparison between input signal and nozzle pressure. The transducer
can be mounted directly on a control valve.
Hand-wheel
Every control valve shall be provided with a hand-wheel. It shall preferably be side
mounted, suitable gearing shall be provided where necessary to keep turns and torque
applied at hand-wheel to a minimum.
Limit Switches
Control valves shall normally not be fitted with limit switches, however where limit switches
are required to provide status indication of control valves, these shall be provided fully
installed.
Limit switches shall have a Single Pole Double Throw (SPDT) contacts suitable for the
electrical area classification. They shall be mechanical type or magnetic type.
The limit switches shall be enclosed inside a box certified according to the area hazardous
electrical classification.
Control valves for process control applications are sized as specified in the section 2.4.6.4
but, for anti-surge compressor service, the sizing must address the conditions that may be
conducive to surges at different flow requirements and different compressor speeds.
Criteria for anti-surge valve sizing have to be based on the following:
− Provide adequate anti-surge protection for worst possible disturbances
− Provide adequate anti-surge protection in all operating regimes
− Sized to avoid choke zone
− Not be oversized from controllability point of view
Valves on this service have to be able to handle surges in flow above the normal maximum
flow required by the process. This may result in a larger valve than would be required for a
normal process control application.
Then if the rated travel of the valve is not excessive, the higher flow/lift relationship of a
larger valve might offer the added advantage of achieving significant flow changes in a very
short time. The anti-surge valve selection must consider to have speed a response
adequate for anti-surge protection for all disturbances.
Unless different project requirements, the recommended full stroke times are the following:
Closing time needs to be the same order of magnitude to assure the same loop gain in both
directions of the flow.
Then, the actuator’ speed is the dynamic performance requirement that require special
attention in terms of reaction time (or response time) to initiate movement after a demand
signal change, and speed of operation once motion is initiated.
Anti-surge valves can operate anywhere between 0% and 100%.
In order to have an equal loop-gain over the whole operating range a linear valve is
required. This will allow for the fastest tuning leading to smaller surge margins. Also, the
Linear characteristic is more commonly used due its rapid increase in flow at low lift. Equal
percentage characteristic is also used on occasions. Special flow/lift characteristics will be
designed in order to ensure that the anti-surge valve operates effectively as near to the
surge line as possible.
− SDV shall be ball type valve, SIDE ENTRY type up to 6 inch, and TOP ENTRY type
above 6 inches .
− BDV shall be gate type.
− UV shall be ball type valve, SIDE ENTRY type or butterfly type.
For ESDV, SDV, BDV valves, it is requested “Zero” leaks (Rate A) between the plug and
seat, and shall be in conformity with the Seat Leakage class as defined by standards EN
12266-1 (Industrial valves - Testing of valves - Part 1: Pressure tests, test procedures and
acceptance criteria - Mandatory requirements) and EN 12266-2 (Industrial valves - Testing
of valves - Part 2: Tests, test procedures and acceptance criteria – Supplementary
requirements).
On-off Valves shall be fitted with actuators designed (Pneumatic, Hydraulic or Motorized) in
such a way that, in the event of control air failure, they can drive the plant toward safe
conditions even when the envisaged maximum pressure drop, caused by the process
fluids, is applied to the valve ports.
When necessary, the Partial Stroke Test facilities shall be provided. Partial Stroke can be
mechanical type, Pneumatic type, and Electronic type. In any case an intermediate limit
switch shall be provided in addition to the open/closed limit switches usually required.
2.4.10.3 On/off valves actuators
Actuator for ON-OFF valves shall be single effect spring return type. Double effect
actuators shall be avoided unless approved by COMPANY/EPC.
In some specific case the use of electric or hydraulic actuator could be considered.
In order to overcome dirt and rust particles, the actuator spring torque shall be sized for at
least 2.0 times the required ’long stand still’ torque of the valve, at condition of vessel or
equipment design pressure upstream and atmospheric pressure downstream.
Travel speed shall be adjusted by means of restrictions in the two travel directions and set
at 2 second per inch of valve size, unless specified otherwise.
Pneumatic actuators are generally used, except that hydraulic actuators may be used in
high pressure piping service. As per EN 15714 Part 3 (Pneumatic part-turn actuators for
industrial valves - Basic requirements), “The maximum allowable pressure shall be at least
8 bar, unless otherwise specified. The minimum test pressure for pressurised parts shall be
1,43 times the maximum allowable pressure”. Then, the actuator cylinders shall be rated for
the maximum air pressure value (design pressure) that could be around 10÷11 Barg.; while
4 barg is the minimum pressure value to size the pneumatic actuators.
If the instrument air is not present in the plant, or when “manual” valves need to be
frequently operated, the actuators for on-off valves can be electrical type or hydraulic type.
However, the actuator shall be fail safe and compliant to SIL rating class (if available on the
market) when used for safety application.
2.4.10.4 On/Off valves accessories
Limit switches
The open/closed limit switches shall be assembled and mounted on the valve’s actuator by
the manufacturer.
Limit switches shall have a SPDT contacts suitable for the area electrical classification.
They shall be mechanical type or magnetic type.
The adjustment facilities shall be locked (drilling and pinning) after setting
The limit switches shall be enclosed inside a box certified according to the area hazardous
electrical classification.
Air accumulator
Each BDV shall be equipped with an air accumulator, properly sized, in order to supply
pneumatic power in case of failure of the instrument air network.
All components, either pneumatic or hydraulic or electrical, shall be capable of standing the
maximum instrument air pressure (e.g. 12 bara); then, any air pressure reducer shall be
avoided.
Each Local Control Panel for SDV or BDV shall be equipped with 2 solenoid valves
operating in 2oo2 Voting Logic: the valve will be closed, or opened, when both solenoid
valves are de-energized.
Solenoid valves
Solenoid valves shall be design and supplied according to COMPANY standard
08954B.CMP.STA.STD (SOLENOID VALVES).
Solenoid valves shall normally be the direct-acting type and constructed for heavy industrial
use. Pilot-operated valves are not acceptable.
Solenoid valves shall normally be used in pneumatic or hydraulic circuits.
Automatically re-setting solenoid valves shall be used for all applications except where
"manual reset" is requested.
Solenoid valve shall be universal type, 24VDC, low consumption (max.12W), with class ‘F’
insulation type and Ex‘d execution.
Three-port solenoid valves shall be used for single-acting spring-return actuators.
The minimum solenoid valve size used shall have 1/4" NPT connections.
The coil and spring shall be selected to provide ample operational power to position the
valve stem correctly under all conceivable service conditions.
Coils shall be rated for continuous operation and temperature must not rise to more than
70°C (or the coil service rating if lower).
2.4.11 Analysers
General
Whenever possible, analysers shall be chosen in such a way as to ensure continuous
measurement of the analysed parameters.
Measurements shall normally be recorded and indicated by Supervisory computers system.
The guaranteed performance shall be the Manufacturer's.
If required, the sampling and conditioning system shall generally be of stainless steel AISI
316.
Fittings used shall normally be of the compression type.
Analytic Units
Their execution shall be suitable for the area classification in which they shall be installed.
Depending on the type of analysis, on sample characteristics and on ambient conditions,
analytic units could be installed either close to the plant sampling point inside a suitable
shelter
Small quantities of non-polluting gaseous wastes will be directly vented into the
atmosphere.
2.4.12 Interconnections
All instruments shall be terminated to relevant junction boxes located at skid limits; and
wired properly to the relevant cabinets via multi-cables.
Junction boxes and panels shall be designed and constructed in such a way as to
segregate the power from electric components, to avoid electromagnetic disturbances to
the electronic instrument circuits.
All cables shall be suitable for the electrical circuit AD-I, AD-E or AD-PE where required.
For control and instrumentation duty cabling shall be flame retardant, and comply with IEC
60 332-1, category C2. For applications such as ESD/F&G, including Fire and Gas
detection circuits, Fire Fighting system facilities, and beacons flashing lights, the cabling
shall be fire resistant and meet the additional fire performance characteristics defined in
IEC 60331 category CR1-C1.
Electric shielding is required for the cables carrying analogue and digital signals, total shield
for digital signal, and single pair/total shield for analogical signal.
Instrument signal cables shall be twisted pair shielded. All instrument cables shall be
adequately supported and identified.
Where instruments, pipes and cables are in such a position as to possibly sustain
accidental damage during operation or during maintenance, suitable protective shields shall
be provided.
C
O R
OVERALL BLOCK DIAGRAM N O
T O
R M
UCP & PLANT CONTROL / SAFETY SYSTEMS O
L
I
MOTOR CONTROL UNIT CONTROL DCS SYSTEM ESD SYSTEM ESD MARSHALLING N
CENTRE PANEL PANEL CABINET CABINET CABINET S
T
E
R
L
ESD/PSD/ U
E ESD/PSD/
ESD/PSD/
F&G
ESD/PSD/
F&G
C
F&G F&G
M
E
T
N
R
T
I
C E
A Q
L U
I
R
P
O
M
O
E
M
N
T
REDUNDANT SERIAL LINK
R
O
O
M
PACKAGE SKID
Unit Control Panel (UCP) is equipped with its own autonomous control and safety functions,
generally it is PLC based with the latest release of hardware and software industrial type
and each UCP shall be equipped with at least the following main equipment:
• Human Machine Interface (HMI),
• Control machine/package system (PLC with CPUs, I/O cards, communication
cards, Power supply modules, etc.),
• Vibration Monitoring System,
• Anti-surge system (only for gas compressor package)
• Load sharing system (only for gas compressor units within the MCP)
• Variable Frequency Drive (only for multiphase pump)
• ESD / FIRE & GAS system (if required);
• Marshalling cabinets,
• Local Control Panel (to be installed closed to the skid or directly on the skid).
In order to allow a proper and safe data exchange among the involved systems, provided
by the PACKAGE SUPPLIER, and to/from the plant control system, the PLC shall provide a
redundant communication connection with high performances in terms of standard
interface, communication protocol, speed data exchange, reliability, availability, diagnostic,
etc. avoiding any bottle neck.
Interface signals to/from plant’s control system and PLC shall be achieved by a dedicated
dual redundant data link, whereas some critical commands/information signals are present,
they can be connected also hardwired.
In case of complete communication loss or major failure, communication shall automatically
restart after repair. At common restart, all commands issued by plant’s control system to
the UCP are set in accordance with PLC internal values (UCP is the logic master for all
information concerning the package). The failure of the link shall not affect the operation of
the package. The UCP shall be autonomous.
To ensure the detection of the communication failure, a watchdog function, in the form of
periodic incremental counters, shall be available and exchanged between the plant’s
control system and UCP through the digital data link.
Whenever requested, the UCP can be located in a dedicated shelter (joined with other
electric/electronic cabinets related to the same machine) that will be installed closed to the
machinery skid.
2.6.1 Fire&Gas (F&G) detection system and Emergency ShutDown system (ESD)
Unless otherwise specified, the package, when including a process and/or machine control,
shall include its safety systems: process or/and machine safety devices, shut-down control,
fire and gas systems (including F&G for shelter in case of it is requested) when linked to
machine operation safety.
Generally, the safety functions of the UCP/PLC system will be the following:
• To handle the hardwired I/Os of the facilities units.
• To handle the F&G detectors/devices of the machinery area and relevant Fire
Extinguishing system (if any).
• To be interfaced via hardwired with the plant ESD/F&G system (i.e.: remote shut
down of ESD/PSD).
• Monitor of analogue and digital variables relevant to safety of operation of different
equipment/packages.
• Accomplishment of all actions (i.e.: alarm arisen handling, activate the fire-fighting
system, close fire dampers (if any), apply voting logics, etc.) necessary to take the
package’s plant back to safe condition (i.e.: by means of blowdown) when dangerous
abnormalities are detected upon process upset and/or upon the monitoring of the
relevant risk areas for any fire, gas (toxic or flammable) emergency situation.
• To Alert personnel in the plant Control Room (via UCP/PLC) of any fault detected by
self-test facilities.
• Execute the machine trip performing the 1oo2 voting logic in case of machine radial
vibration has been detected from the Vibration Monitoring System cards.
• Execute the machine trip performing the 2oo2 voting logic in case of machine axial
displacement or compressor thrust bearings has been detected from the Vibration
Monitoring System cards.
• Execute the machine trip performing the 2oo2 voting logic in case of high
temperature on compressor thrust bearings has been detected from the Vibration
Monitoring System temperature cards.
• Execute the machine trip performing the 1oo1 voting logic in case of high
temperature on electric motor windings has been detected from the Vibration
Monitoring System temperature cards.
Even if only one system for ESD and F&G functions is implemented, the functionalities
remain quite distinct. See the relevant PLC technical requirements (i.e.: SIL 3 certification,
technology, redundant and segregation criteria, Hardware and Software, etc) highlighted
inside the PLC section 2.10.2. Different SIL rating and/or technology for the UCPs safety
system shall be under project responsibility.
One or more manual emergency shutdown pushbuttons shall be available locally near the
package and wired to the UCP. A manual emergency shutdown pushbutton shall also be
available on the UCP itself.
The F&G detectors point to point type shall be in accordance with location. The Voting logic
shall be based on 2oo3 for confined spaces, air intakes and air locks. The Voting logic shall
be based on 2ooN for wide installation areas.
Each Fire and Gas system will be interfaced with all necessary F&G detectors, distributed
inside the control container and around the skid / shelter.
The Fire and Gas systems shall follow the NFPA 72 standard or the EN 54 standard
according to project requirements.
SIL 2 is the minimum safety integrity level required for all involved UV-IR detectors and
Flammable gas detectors, according to IEC 61508 and IEC 61511.
PACKAGE SUPPLIER shall develop a detailed Cause and Effect Matrix showing all critical
inputs and outputs of the ESD and F&G system and their specific functions, in the context
of the protective philosophy adopted for the whole supply.
The selection of fire and gas detectors for an area shall be considered upon the expected
kind of fire, or gas, to be detected and the environment in which the detectors are located.
The location of the fire detectors shall take into account the following issues:
• Definition of the foreseeable leak source;
• Released gas dispersion/ dilution and influence of the ventilation air flow patterns;
• Shielding by beams, equipment and piping;
• Process system configuration;
• Accessibility for maintenance and testing.
Refer to following COMPANY standards 20193.VAR.SAF.SDS (Selection of sensors and
gas of fire detection criteria) and 27616.FFS.STA.SDS (Criteri di selezione dei rivelatori di
fumo).
Where possible detectors shall be looped on to common circuits based on: Economy of
wiring, Voting requirements, Fire zone limitations, System integrity.
Fire and gas monitoring modules shall be suitable for the field sensors which can be wired
with two or three wires; however the PACKAGE SUPPLIER will provide the proper signal
conditioning / detectors feeding where necessary.
Temperature sensors shall be 3-wire RTD type, Pt 100 to BS 1904 Cl. B in Ex-d housing,
directly connected to monitors; motor windings temperature RTDs will be led to junction
boxes on motor frame.
Each vibration and temperature monitor shall have independent channel; each channel will
be complete of LCD bar-graph type measurement display, “OK” status LED, alarm and
shutdown LEDs, Bypass switch, LED for alarm bypass, LED for line fault (open circuit or
short circuit occurs in a loop), and 4 to 20 mA analogue output; proportional to the
measured value, common shutdown output signal to be addressed to the UCP via
redundant serial connection (see the communication system mentioned in the overall block
diagram) and/or via hardwired connections. The shutdown settings will be individually
adjustable over the 0 to 100 % range. The Time delays for shutdown shall be field
adjustable over a range of 1 to 6 sec, as minimum. Circuit fault shall not initiate any
shutdown function.
SPDT voltage free contacts rated 1 A at 24 Vdc, resistive load, shall be provided on each
monitor; all contacts shall be wired up to the cabinet terminal strips. Relay status shall be
energised in normal process, supply and equipment conditions, output alarm and shutdown
contacts will connected as “open in abnormal condition”, i.e. fail safe concept. No output
shall be automatically reset.
permanent margin of variation in the electric VFD, will be accomplished through specific
actions in the re-circulation loop of the pump.
The control functions assigned to this system include the electrical supply, conditioning and
conversion of the VFD and ancillary equipment (circuit breaker, power transformer,
switchboards, harmonic filters, etc.), the signals and commands handling - to and from field
instrumentation and operator, the stream flow regulation and the skid bypass and isolation.
All these functions constitute the basic process control, which will be implemented by
means of a conventional PLC architecture and standard I/O interfaces.
2.7.1 General
The purpose of this section is to define the inputs to PACKAGE SUPPLIER / EPC related to
the signals to be exchanged between the UCP (or MCP) and the plant ICSS.
Generally, the main information (signals, alarms, measurements) shall be addressed to
plant Control System where they will be available to Operator Work Stations in forms of
graphic pages, alarm pages, events, logging, etc. These data have to be properly selected
in order to provide only the major package information to the plant ICSS, while the UCP
operator station shall be capable to handle the complete machine without any limitation. In
this way we can also reduce the quantity of signals coming from UCP (or MCP) to the plant
control system with several advantages in terms of DCS performances and operating
handling.
For what concern the command functions (from plant DCS to UCP), they will be identified
according to project requirements and reduced as much as possible, without loose safety
and operability.
However, all information/data related to the maintenance and diagnostic shall be available
on a specific and dedicated communication channel with relevant necessary equipment
(i.e.: server, PC, etc.)
Testing
Commis-
Design Supply Installation sioning
& Start
Item TASK DESCRIPTION Up
COMPANY
COMPANY
COMPANY
COMPANY
PACKAGE
PACKAGE
PACKAGE
PACKAGE
EPS / EPC
ICSS
ICSS
ICSS
ICSS
EPC
EPC
EPC
Instruments within the package/machinery
skid
a) Instrumentation inside the machinery skid D A A X X X Y Y
b) Instrument accessories (Tubing and fittings,
Labels on supports, Cables glands, Supports, D A X X X Y Y
1
etc.) inside the machinery skid
c) Instrumentation outside the machinery skid D A A X Y X X Y Y
d) Instrument accessories (Tubing and fittings,
Labels on supports, Cables glands, Supports, D A X Y X X Y Y
Sun shading, etc.) outside machinery skid
Loose instruments
a) Instrumentation outside the machinery skid D A A X X X Y Y
2 b) Instrument accessories (Tubing and fittings,
Labels on supports, Cables glands, Supports, D A X X X Y Y
etc.) outside the machinery skid
Fire and gas detectors/devices
a) Fire and gas detectors/devices where
3 foreseen on the package skid a/o inside the D A A X X Y Y X Y Y
shelter (if any)
b) Fire and gas detectors/devices where
foreseen outside the machinery skid.
A D Y X Y X Y X Y
Junction boxes
a) Junction Boxes (with Terminals, cable
glands, Labels, Supports, etc.) within the D A X X X Y Y
4 package/machinery skid
b) Junction Boxes (with Terminals, cable
glands, Labels, Supports, etc.) outside the A D X X Y X
package/machinery skid
5 Local panel
Documento riservato di proprietà di Eni S.p.A. - Divisione Exploration & Production.
Esso non sarà mostrato a Terzi né utilizzato per scopi diversi da quelli per i quali è stato inviato.
eni spa 20150.PKG.STA.FUN
Rev. 0 February 2013
exploration & production division
Page. 32 of 54
Testing
Commis-
Design Supply Installation sioning
& Start
Item TASK DESCRIPTION Up
COMPANY
COMPANY
COMPANY
COMPANY
PACKAGE
PACKAGE
PACKAGE
PACKAGE
EPS / EPC
ICSS
ICSS
ICSS
ICSS
EPC
EPC
EPC
a) Local panel (with Pushbuttons, Lamps,
Selectors, Terminals, cable glands, Labels,
Supports, etc.) located within package battery
D A A X X X Y Y
limits.
b) Local panel (with any electronics,
Pushbuttons, Lamps, Selectors, Terminals,
cable glands, Labels, Supports, etc.) located
D A A X X X X Y Y
outside package battery limits.
Instrumentation Cables
a) From instrument up to junction boxes at skid
battery limits
D A X X X Y Y
b) From loose instrument up to junction boxes. D A X Y X Y X
b) From junction boxes up to UCP D A A X Y X X Y Y
6
c) From junction boxes up to marshalling
cabinet of plant ESD system
A D X X Y X Y
d) Special cables (if any) D A X X X X X Y Y
e) Between UCP and plant control/safety
systems
A D X X Y X Y
Cable trays
a) From instrument up to junction boxes at skid
battery limits
D A X X X Y Y
7 b) From skid battery limits up to plant ESD
marshalling cabinets
A D X X Y X
c) Cable tray supports (within battery limits) D A X X X Y Y
d) Cable tray fittings (within battery limits) D A X X X Y Y
Unit Control Panel (PLC and other
automation equipment)
a) Hardware D A A X X X Y Y
8
b) Application software (Programming,
Configuration)
D A A X X X Y Y
c) Configuration tools D A A X X X Y Y
Plant control and Safety systems (ICSS)
a) Hardware (based on purchaser documents) A A D X Y X Y Y Y X
9
b) Application software (Programming,
Configuration)
A A D X Y Y X Y Y X
Interface and Interconnecting (ONLY
10
DOCUMENTATION)
a) Input hardware data (layout cabinets, I/O
quantity, power supply consumption, etc.) to D A A
ICSS Supplier
b) Input Software data (I/O's list of serial link
UCP (a/o MCP) - ICSS) to ICSS Supplier
D A A
Testing
Commis-
Design Supply Installation sioning
& Start
Item TASK DESCRIPTION Up
COMPANY
COMPANY
COMPANY
COMPANY
PACKAGE
PACKAGE
PACKAGE
PACKAGE
EPS / EPC
ICSS
ICSS
ICSS
ICSS
EPC
EPC
EPC
e) Interconnecting wiring diagram between
UCP (a/o MCP) and electrical MCC interface D A A
panel
Testing activities
a) Procedure and Test for the HW & SW
between ICSS system and UCP (a/o MCP) R A A D Y Y Y X
during the FAT of plant ICSS
b) Procedure and Test for the HW and SW of
serial link UCP (a/o MCP) - ICSS during the R A A D Y Y Y X
11 FAT of plant ICSS
c) Procedure and Test for the HW and SW of
serial link UCP (a/o MCP) / ICSS during the R A A D Y Y X Y
SAT of plant ICSS
d) Procedure and Test for the HW and SW of
serial link UCP (a/o MCP) - ICSS during the R A A D Y Y X Y
SAT of plant ICSS
3. DOCUMENT REQUIREMENTS
3.1 GENERAL
At least, and unless different agreement (where PACKAGE SUPPLIER standard can be
accepted if match with project requirements), the EPC / PACKAGE SUPPLIER’s document
content shall meet (where applicable), but not necessarily be limited to, the following
requirements:
4. INSPECTION REQUIREMENTS
4.1 GENERAL
No equipment or materials shall be delivered until all applicable tests have been
completed and all defects rectified and re-tested successfully.
Shop testing:
COMPANY reserves the right to witness testing or to request additional testing
according to its requirements. Such witnessing shall include all control valves, relief
valves, composite systems, control systems etc. The PACKAGE SUPPLIER shall
notify PURCHASER of the detailed requirement for the Quality Plan (Test and
Inspection).
PACKAGE SUPPLIER shall submit the procedures for approval at least six weeks prior to
commencement of testing. Test procedure shall define the surveillance level for each test
(100%, 1 lot, spot check, etc) based on the criticality of the equipment to be tested.
The result of each test can be satisfactory, not conform or pending. In case of not
conformity points, recovery actions shall be identified by the PACKAGE SUPPLIER to solve
the problems. In case of pending points, action shall be identified by the PACKAGE
SUPPLIER or by the Purchaser to clarify the matter.
PACKAGE SUPPLIER shall provide skilled manpower, all standard and special tools, test
and calibration equipment necessary for FAT, site installation, SAT, commissioning and to
generally service and maintain the system equipment to its maximum reliability.
PACKAGE SUPPLIER shall furnish complete internal QA/QC checklist and documents
before FAT to ensure internal checks of the following tests are done by PACKAGE
SUPPLIER before client FAT.
PACKAGE SUPPLIER shall perform the following tests during the FAT as a minimum:
Visual/dimensional Check
Power up and initialization
Power failure and recoveries
Redundancy test for backup controllers, power supply, communication systems, I/O
cards and operator consoles
Integrated test of all involved system
Synchronization test of all involved systems via GPS
The test required inside the IDS
Total system reboot
Hardware/software inventory
Diagnostic test
RFI protection
Functional loop checking (100% signals)
Custom application programs and sequences test
Logic test
Graphics & Alarm list Check
Interface test
Any other test(s) as per project requirements.
5. SPARE PARTS
At least, and unless different project requirements, the supply shall include:
the spare parts for Commissioning and Start-up
the spare parts for two years of continuous operation.
PACKAGE SUPPLIER shall submit a list of these spare parts with the bid.
PACKAGE SUPPLIER shall guarantee to support all spare parts supplied for minimum 20
years following the written announcement of product withdrawal.
Consumables
PACKAGE SUPPLIER shall provide consumables such as:
Documento riservato di proprietà di Eni S.p.A. - Divisione Exploration & Production.
Esso non sarà mostrato a Terzi né utilizzato per scopi diversi da quelli per i quali è stato inviato.
eni spa 20150.PKG.STA.FUN
Rev. 0 February 2013
exploration & production division
Page. 51 of 54
Fuses, relays
Dust filter
Terminal blocks
Cable for wiring
Others as per Supplier's recommendations.
The quantities must be estimated by Supplier and based on his experience.
Special Tools
Any special equipment or tool required for the installation, testing, calibration or
maintenance of the System shall be included in the Bid. Such equipment and tools shall be
new, non-defective and supplied with operation and maintenance instructions.
Spare Parts
PACKAGE SUPPLIER shall supply spare parts including as a minimum:
I/O cards: 5% per type
Fuses: 20%
Push buttons, lamps and/or LEDs: 20%
Others: as per Supplier's recommendations.
In addition at least one power supply module per type shall be included and 2% for each
type of auxiliary device supplied, such as isolators, signal duplicators, relays etc.
Rev Validity
Number Status Date Description Prepared Checked Approved
Revision Index
Company logo and business name Project name Company Document ID
Job N.
exploration & production
Facility Sub Facility Name Scale Sheet of Sheets
n.a. of
APPENDIX B
Rev Validity
Number Status Date Description Prepared Checked Approved
Revision Index
Company logo and business name Project name Company Document ID
Job N.
exploration & production
Facility Sub Facility Name Scale Sheet of Sheets
n.a. of
APPENDIX C
Rev Validity
Number Status Date Description Prepared Checked Approved
Revision Index
Company logo and business name Project name Company Document ID
Job N.
exploration & production
Facility Sub Facility Name Scale Sheet of Sheets
n.a. of