You are on page 1of 1

1 2 3 4 5

B1900665 01/12/21

GAS FURNACE SCHEDULE HEAT PUMP UNIT SCHEDULE


HEAT CAP. COOL CAP.
CFM ELEC. VENT HEAT CAP. ELEC. FAN MOTOR COMPRESSOR
ID SERVES ESP. EAT (BTUH) HP FLA MFGR MODEL COIL REMARKS (MBTUH)
NOM. (V/Ø/HZ) CONN. ID SERVES EAT MCA MOCP MFGR MODEL SEER REMARKS
(MBTUH) (V/Ø/HZ)
INPUT OUTPUT TOTAL SENS. QTY FLA RLA LRA
AHU-1 UNIT 1 17.0 0.5 0.70 30,000 28,800 120/1/60 1 0.95 9.0 AMANA AMEC960302BNA CAPF3636A6D 1,2,3,4 HP-1 UNIT 1 17.0 11.9 18.0 0.70 230/1/60 1 0.95 9.0 47.5 12.2A 20A AMANA ANZ14018A 15.0 1,2,3,4,5,6,7
AHU-2 UNIT 2 20.6 0.5 0.70 30,000 28,800 120/1/60 1 1.1 10.9 AMANA AMEC960302BNA CAPF3636A6D 1,2,3,4 HP-2 UNIT 2 23.0 16.1 23.6 0.70 230/1/60 1 1.0 10.0 62.9 13.5A 20A AMANA ASZC160241A 15.5 1,2,3,4,5,6,7
SCHEDULE NOTES: SCHEDULE NOTES:
1. PROVIDE UNIT WITH CONDENSATE PUMP. BASIS OF DESIGN: LITTLE GIANT VCMA-20US, 120V/1Ø/60HZ, 93 1. TIME DELAY RELAY 6. 7-DAY PROGRAMMABLE THERMOSTAT
W. CONNECT CONDENSATE DRAIN PIPING TO EVAPORATOR COIL DRAIN & FURNACE DRAIN. ROUTE 3/4" 2. THERMOSTATIC EXPANSION VALVE 7. PROVIDE WITH PRE-FABRICATED EQUIPMENT PAD
PUMPED CONDENSATE PIPING OUTSIDE OF BUILDING DOWN TO SPLASHBLOXK ON GRADE. FIELD VERIFY 3. HI/LO PRESSURE SWITCH
D EXACT ROUTING. 4. LOW AMBIENT CONTROL DOWN TO 0°F D Structural Review - Wayne Ferguson - 01-12-2021
2. 2-PIPE DIRECT VENT KIT THRU ROOF. TERMINATE PER MANUFACTURER'S RECOMMENDATIONS. 5. PURON R-410A REFRIGERANT DOEE SE-SW Review - Nykia Barnes - 01-12-2021
3. PROVIDE WITH PLEATED FILTER SECTION, STAINLESS STEEL HEAT EXCHANGER AND ELECTRONICALLY DOEE EV Review - Sheng Huang - 01-12-2021

HP CONTROLLED VARIBALE SPEED FAN MOTOR.


2
EXHAUST FAN SCHEDULE
HP ELEC EFF.
1 ID SERVES CFM S.P. WATTS/HP
(V/Ø/HZ) (CFM/W)
MFGR. MODEL FAN TYPE REMARKS

CEILING
EF-1 TOILET 110 0.70 31W 120/1/60 3.54 AIR KING FRAK100 VENT OUTSIDE THROUGH WEATHER SHIELD.
MOUNT
KITCHEN WALL
EF-2 250 0.70 75W 120/1/60 3.33 AIR KING ECV VENT OUTSIDE THROUGH WEATHER SHIELD.
HOOD MOUNT

NEW 4" RIGID METAL


DRYER DUCT W/ WALL OA INTAKE
CAP EXHAUST AIR EXHAUST AIR EXHAUST AIR
NEW 4" RIGID METAL
DRYER DUCT W/ WALL
CAP

182 cfm 94 cfm 94 cfm 70 cfm 73 cfm


182 cfm
7" 7" 6" 6"

CONSULTANTS
7" 7" STRUCTURAL ENGINEER:

C C

9"

E06
ROOF DECK
4" 5" 69 cfm
43 cfm
6" 64 cfm REGISTRATION
4" 4 cfm
CATARINA FERREIRA, AIA

8" WASHINGTON DC
COMB.
AIR LICENSE NO. ARC 101008

DW
EF 14 " 438 cfm ATTESTATION STATEMENT:
REF.

2 I AM RESPONSIBLE FOR DETERMINING THAT THE ARCHITECTURAL DESIGNS INCLUDED


EF IN THIS APPLICATION ARE IN COMPLIANCE WITH ALL LAWS & REGULATIONS OF THE
DW 2 DISTRICT OF COLUMBIA. I HAVE PERSONALLY PREPARED OR DIRECTLY SUPERVISED
FLUE 4" THE DEVELOPMENT OF THE ARCHITECTURAL DESIGNS INCLUDED IN THIS APPLICATION.

REF.
THRU
ROOF
11 EF PROJECT INFORMATION
1

AHU
649 cfm
166 cfm 2 1734 Mass Ave 2 Family
4" 4 cfm
6" 4" 16 cfm Donal & Taren Langhorne
10" Sup Riser
16 cfm 13 " 1734 Massachusetts Ave SE
4" 4"
10 "
E06
EF
B 8 cfm 1 69 cfm B PROJECT NUMBER
FLUE THRU ROOF 2018-15
DN
4" RIGID METAL ISSUE RECORD
8" 8" DRYER DUCT MARK DATE DESCRIPTION

AHU 10 "
1 09/28/18 BUILDING PERMIT
1 Ret
T EF Riser 11 2 06/03/19 PERMIT REV 1
1 4" Ret Sup Riser Riser 11
PROGRAMMABLE 8" 414 cfm 11 12 "
THERMOSTAT
4" Sup Riser
4" 12 "
12 " 12 "
E06
4" 8 cfm 7" 4" EF
8" 1 4"
16 cfm
8" 2 cfm
36 cfm 2 cfm
4"
5"

7" EF
4" 1
52 cfm
4"
E06
E06

5"
A A
6" DRAWING INFORMATION

67 cfm Drawing Scale: 1/4" = 1'-0"


Drawn By: TB
161 cfm 83 cfm 43 cfm Checked By: CF

HVAC Diagrams

1 1st Floor Plan HVAC


SCALE 1/4" = 1'-0"

1
2 2nd Floor Plan HVAC
SCALE 1/4" = 1'-0"

2 3
3 3rd Floor Plan HVAC
SCALE 1/4" = 1'-0"

4
4 New Roof Plan HVAC
SCALE 1/4" = 1'-0"
0' 2' 4'
5
8' 16' M0100