Professional Documents
Culture Documents
4, NOVEMBER 2005
Abstract—This paper addresses the design and implementation Stator current vector.
of a novel control scheme for a doubly fed induction generator Rotor current vector.
(DFIG), of the type employed with wind turbines, to provide sup- Stator power output.
port to power system operation. It is shown that this controller
provides a DFIG-based wind farm with operational and control Generator torque.
compatibility with conventional power stations, the ability to con- Stator resistance.
tribute to voltage support and recovery following network faults, Stator self-inductance.
the ability to provide a power system stabilizer capability that im- Rotor self-inductance.
proves overall system damping, and the capability of contributing Mutual inductance.
short-term frequency support following loss of network genera-
tion. A simple but realistic test network that combines synchronous Transient reactance.
and wind farm generation has been modeled and used to assess Stator impedance.
dynamic performance. Simulation results are presented and dis-
cussed that demonstrate the capabilities and contributions of the I. INTRODUCTION
new DFIG controller to network support.
Index Terms—Doubly fed induction generators (DFIGs), power
system modeling, power system stability. T HE increasingly wide spread use of wind generation on
power networks imposes the requirement that wind farms
should be able to contribute to network support and operation as
do conventional generating stations based on synchronous gen-
NOMENCLATURE erators. Emerging Grid Code proposals for wind farm connec-
Synchronous generator tion will, of necessity, become increasingly demanding of the
Terminal voltage vector. performance of connected wind farms with respect to voltage
Field voltage, dc. control capability, reactive range capability, active frequency
Internally generated voltage vector (voltage behind ability, and fault ride through capability [1], [2]. If wind gen-
transient reactance). eration does not provide appropriate network support, then as
Rotor flux vector. the proportion of conventional and wind generation varies, the
Rotor angle. changes produced in the operational characteristics of the net-
Stator current vector. work will make it increasingly difficult for the network operator
Synchronous reactance. to provide the required level of stability and security.
DFIG For reasons of improved efficiency of energy transfer from
Terminal voltage vector. the wind and reduced mechanical stresses, many large wind
Rotor voltage vector. turbines (installed either offshore or onshore) will operate at
Internally generated voltage vector (voltage behind variable speed using doubly fed induction generators (DFIGs)
transient reactance). [3]–[6]. DFIG controllers to date have concentrated mainly on
Rotor flux vector. the provision of an adjustable operating speed to maximize tur-
Angle between and axis of DFIG. bine power output, the maintenance of the required generator
Angle between and axis of DFIG. terminal voltage or power factor, and the control of the gen-
Stator frequency. erator torque to match that of the wind turbine [7], [8]. Con-
Rotor speed. trol has concentrated on preserving acceptable conditions for
Slip, . the DFIG and little or no attempt has been made to provide
the DFIG with the capability of contributing to network sup-
port and operation. This paper introduces a novel DFIG control
Manuscript received March 14, 2005; revised May 12, 2005. This work was strategy that relies on controlling the magnitude and physical
supported in part by EPSRC through its Supergen programme and in part the position of the DFIG rotor flux vector (which in turn dictates
Centre for Distributed Generation and Sustainable Energy sponsored by the De- the internal voltage vector). It is demonstrated that by adopting
partment of Trade and Industry (DTI), U.K. Paper no. TPWRS-00156-2005.
F. M. Hughes is a consultant (e-mail: mike_hughes@onetel.com). this strategy, controllers can readily be designed that enable
O. Anaya-Lara, N. Jenkins, and G. Strbac are with the Manchester Centre DFIG-based wind farms to not only match the control contri-
for Electrical Energy, University of Manchester, Manchester M60 1QD, U.K. butions of synchronous generators with regard to active voltage
(e-mail: o.anaya-lara@manchester.ac.uk; nick.jenkins@manchester.ac.uk;
g.strbac@manchester.ac.uk). control and the provision of network damping but also improve
Digital Object Identifier 10.1109/TPWRS.2005.857275 on them.
0885-8950/$20.00 © 2005 IEEE
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
HUGHES et al.: CONTROL OF DFIG-BASED WIND GENERATION FOR POWER NETWORK SUPPORT 1959
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
1960 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
HUGHES et al.: CONTROL OF DFIG-BASED WIND GENERATION FOR POWER NETWORK SUPPORT 1961
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
1962 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005
The generic network shown in Fig. 9 was modeled for the In this paper, both Generators 1 and 2 of the local system are
purpose of assessing the capabilities of DFIG-based wind farms synchronous generators. It provides the dynamic performance
with the FMAC scheme with respect to their ability to contribute characteristics of the network when it is comprised solely of
to network support. conventional synchronous plant and thereby presents a base-line
The network comprises a local network of wind farm and against which the performance of a mixed conventional and
conventional thermal generation connected to the main system DFIG-based wind farm system can be judged.
through coupling transformers and transmission lines. Genera- Fig. 10 shows the simulated responses for generators 1 and 2
tors 1 and 2 have similar ratings. A single DFIG generator rep- of terminal voltage magnitudes (E1mag, E2mag), active power
resents the aggregated behavior of the individual generators of outputs (P1e, P2e), and rotor angles (Delt, Delta2) following the
the wind farm. application and clearance of the fault. It can be seen that syn-
The generators and loads of the main system are also aggre- chronism is retained and that whilst voltage is recovered quite
gated and modeled as a single equivalent synchronous generator quickly after fault clearance, the oscillations in power take a
and a single load. This single synchronous generator has a nom- considerable time to be damped out. Also, Generators 1 and 2
inal capacity of five times that of generator 1. are seen to oscillate in synchronism with one another.
In the studies, the turbine power output of Generator 1 is con-
stant. The steam turbine of equivalent Generator 3 has governor B. DFIG Operation—Basic Control Scheme
control so that when loss of a main system generator occurs, In this case, Generator 1 is a synchronous machine and Gener-
the output power of Generator 3, representing the remaining ator 2 is a DFIG-based wind farm controlled by the FMAC basic
four generators, can be increased to match the demanded load. control scheme without auxiliary loops. A super-synchronous
Generator 3 is considered to be a round rotor machine having a operating condition where is considered. Fault study
rotating excitation control system. A simple third-order model responses of both Generators 1 and 2 are presented in Fig. 11.
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
HUGHES et al.: CONTROL OF DFIG-BASED WIND GENERATION FOR POWER NETWORK SUPPORT 1963
Fig. 11. Mixed system operation. Generator 1—synchronous, Generator Fig. 13. Mixed system operation. Generator 1—synchronous, Generator
0
2—DFIG with the FMAC basic control scheme. (slip = 0:2). 2—DFIG with the FMAC basic control scheme. (slip = 0:1).
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
1964 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005
Fig. 15. Performance of DFIG basic control scheme plus Auxiliary Loop 1. Fig. 16. Performance of DFIG basic control scheme plus Auxiliary Loop 2.
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
HUGHES et al.: CONTROL OF DFIG-BASED WIND GENERATION FOR POWER NETWORK SUPPORT 1965
V. CONCLUSIONS
A new controller has been presented that enables a
DFIG-based wind farm to contribute positively to power
network operation. The new (FMAC) controller independently
exercises control over the magnitude and angular position (with
respect to the terminal voltage vector) of the rotor flux vector
and hence the magnitude and angular position of the internally
generated voltage vector. By adopting this strategy, control
loops can readily be designed to facilitate a DFIG with the
capability of not only providing control functions demanded of
synchronous generators in the support of network operation but
also offering improved contributions and performance.
It has been shown that the new FMAC controller is capable
of providing a DFIG-based wind farm with
Fig. 18. Frequency regulation. Generator 2 is the DFIG with the basic control
1) increased ability to comply with new grid code regula-
scheme plus Auxiliary Loops 2 and 3. tions;
2) good voltage control and voltage recovery following
faults;
3) the ability to emulate synchronous generator dynamic
characteristics via use of Auxiliary Loop 1;
4) the ability to provide a PSS facility and contribute to
system damping via the use of Auxiliary Loop 2;
5) the ability to contribute to frequency support following
loss of network generation via use of Auxiliary Loop 3.
Furthermore, studies not reported here have shown that a
DFIG with the basic FMAC control scheme has the capability
of withstanding significantly longer fault clearance times for
three-phase faults than a synchronous generator with conven-
Fig. 19. Turbine and governor model used with main system generator.
tional excitation control.
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.
1966 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005
C. DFIG Parameters (on Base of Machine Rating) [9] O. Anaya-Lara, M. Hughes, and N. Jenkins, “Generic network model
for wind farm control scheme design and performance assessment,” in
Proc. Eur. Wind Energy Conf., London, U.K., 2005.
[10] R. Peña, J. C. Clare, and G. M. Asher, “Doubly fed induction generator
using back-to-back PWM converters and its application to variable speed
wind-energy generation,” Proc. Inst. Elect. Eng., Elect. Power Appl., vol.
143, no. 3, pp. 231–241, May 1996.
[11] J. G. Slootweg, H. Polinder, and W. L. Kling, “Dynamic modeling of a
wind turbine with doubly fed induction generator,” in Proc. IEEE Power
Converter power rating 25% of DFIG Eng. Soc. Summer Meeting, Vancouver, BC, Canada, 2001.
Nominal slip range [12] A. Feijoo, J. Cidras, and C. Carrillo, “A third order model for the
doubly-fed induction machine,” Elect. Power Syst. Res., vol. 56, pp.
121–127, 2000.
D. Control Parameters and Transfer Functions [13] V. Akhmatov, A. H. Nielsen, and H. Knudsen, “Electromechanical in-
teraction and stability of power grids with windmills,” in Proc. IASTED
Voltage loop: ; ; Int. Conf. Power and Energy Systems, Marbella, Spain, 2000.
[14] P. Kundur, Power Systems Stability and Control. New York: McGraw-
Hill, 1994.
[15] P. C. Krause, Analysis of Electric Machinery. New York: McGraw-
Hill, 1986.
[16] W. Leonhard, Control of Electric Drives. New York: Springer-Verlag,
Power loop: ; ; 1996.
Wash-out time constant [17] K. Burges, “Dynamic Modeling of Wind Farms in Transmission Net-
works,” Sustainable Energy Ireland, 2004.
[18] “Excitation system models for power system stability studies,” IEEE
Trans. Power App. Syst., vol. PAS-100, no. 2, pp. 494–509, Feb. 1981.
[19] “PSS/E 30 Online Documentation,” Power Technologies Inc., Aug.
2004.
Olimpo Anaya-Lara (M’98) received the B.Eng. and M.Sc. degrees from In-
stituto Tecnológico de Morelia, Morelia, México, and the Ph.D. degree from
University of Glasgow, Glasgow, U.K., in 1990, 1998, and 2003, respectively.
His industrial experience includes periods with Nissan Mexicana, Toluca,
Mexico, and CSG Consultants, Coatzacoalcos, Mexico. Currently, he is a Re-
REFERENCES search Associate with the Manchester Centre for Electrical Energy based at the
University of Manchester, Manchester, U.K. His research interests include wind
[1] (2004) Appendix 1, Extracts From the Grid Code Connection Condi- generation, power electronics, and stability of mixed-generation power systems.
tions. National Grid Transco. [Online]. Available: http://www.national-
grid.com.
[2] S. M. Bolik, “Grid requirements challenges for wind turbines,” in Proc.
4th Int. Workshop Large-Scale Integration Wind Power Transmission
Networks Offshore Wind Farms, Billund, Denmark, 2003. Nicholas Jenkins (SM’97–F’05) received the B.Sc. degree from Southampton
[3] J. O. Tande, “Grid integration of wind farms,” Wind Energy J., vol. 6, University, Southampton, U.K., the M.Sc. degree from Reading University,
pp. 281–295, 2003. Reading, U.K., and the Ph.D. degree from Imperial College London, London,
[4] S. Müller, M. Deicke, and R. W. De Doncker, “Doubly fed induction U.K., in 1974, 1975, and 1986, respectively.
generator systems for wind turbines,” IEEE Ind. Appl. Mag., vol. 8, no. His industrial experience includes periods with Eastern Electricity, Ipswich,
3, pp. 26–33, May–Jun. 2002. U.K., Ewbank Preece Consulting Engineering, Brighton, U.K., and BP Solar
[5] J. B. Ekanayake, L. Holdsworth, X. Wu, and N. Jenkins, “Dynamic mod- and Wind Energy Group, London. He joined the University of Manchester, Man-
eling of doubly fed induction generator wind turbines,” IEEE Trans. chester, U.K., in 1992 where he is now a Professor and leader of the Electrical
Power Syst., vol. 18, no. 2, pp. 803–809, May 2003. Energy and Power Systems Group. His research interests include renewable en-
[6] J. Usaola and P. Ledesma, “Dynamic incidence of wind turbines in net- ergy, embedded generation, and FACTS.
works with high wind penetration,” in Proc. IEEE Power Engineering
Society Summer Meeting, 2001, pp. 755–760.
[7] F. W. Koch, I. Erlich, F. Shewarega, and U. Bachmann, “Dynamic inter-
action of large offshore wind farms with the electric power system,” in
Proc. Power Tech Conf., vol. 3, Bologna, Italy, 2003, pp. 632–638. Goran Strbac (M’95) is a Professor of electrical power engineering at the Uni-
[8] L. Holdsworth, X. Wu, J. B. Ekanayake, and N. Jenkins, “Comparison of versity of Manchester, Manchester, U.K. His research interests are in the area of
fixed speed and doubly-fed induction wind turbines during power system economics of power systems centered on pricing of network and ancillary ser-
disturbances,” Proc. Inst. Elect. Eng., Gener., Transm., Distrib., vol. 150, vices, regulation, and the economics of dispersed generation. He actively works
no. 3, pp. 343–352, May 2003. with CIGRE Task Forces and IEEE Specialist Working Groups in these areas.
Authorized licensed use limited to: Cardiff University. Downloaded on November 26,2022 at 09:04:13 UTC from IEEE Xplore. Restrictions apply.