GAMMA Display Module

Version 04/09 Page 1 of 1


trH=lF*"".-,,,.
1 General
The G4BM480V12ADTL20 is a digital module with a display. The digital module can be programmed via the
keys (Esc / Ent / + / -). The measured values will be indicated on the alphanumerical display.

1.1 Measured value display

Indication measured variable:


P
-;--i s :I 1:0
isl lwi
P ... power
I ... thermistor failure

Please note:
Vvlen the temperature monitoring isn't required the iumper must be set between the terminals T1-T2!

lndication measured variable:

| ... cunent
g ... thermistor failure

Please note:
When the temperature monitoring isn't required the jumper must be set between the terminals T1-T2l

lndication function:

Indication of current function (Func):


- Over Overload monitoring
- Under Underload monitoring
- Window Monitoring the window between MIN and MAX
- 2MlN Minimum monitoring
- 2MAX Maximum monitoring
- MAXMIN Maximum- and minimum monitoring

Version 04/09 Page2 ol2


f,H=lH..=-,,,.
1.2 Parameters
Normally, the display only indicates the programmed parameters. Vvhen the device switches into the
programming mode the letter'P" appears on the last position in the first line.

Parameter Function:

Selected functions (Func):


- Over Overload monitoring
- Under Underload monitoring
- Window Monitoring the window between MIN and MAX
- 2MlN Minimum monitoring
- 2MAX Maximum monitoring
- MAXMIN Maximum- and minimum monitorino

Parameter start-up suppression time:

Indication start-up suppression time (t2): adjustable between 0s to 100s

Parameter current transformer factor:

Indication current transformer factor (Factor): adjustable between I to 100

Parameter measured variable:


R:A: n ..9-,._9.
i'iol i0t0
Indication measuring range (Range): reversible between 2.5kW and 1okw

Parameter threshold A:
T:h: :A: : :P
4;5i0:,:0i iwi
lndication threshold Th A: ad.iustable between 120W to 9960W of measuring range (Range)

Version 04/09 Page 3 of 3


l|H=lF*,".-",,.
Parameter tripping delay for threshold A:

Indication of tripping delay (DeLA) for threshold A: adiustable between 0.1s to 50s

Parameter threshold B:
ThB:P
3i2i0i, ioi iwi
lndication threshold Th B: adjustable between 120W to 9960W of measuring range (Range)

Parameter tripping delay for lhreshold B:

Indication of tripping delay (Del_B) for threshold B. adjustable between 0.1s to 50s

Parameter recognition of disconnected load (l=0):

Activation (on) / Deactivation (off) recognition of disconnected load (l=0)

Parameter recognition of disconnected load (l=0) - arrangement of oulput relays

Indication of relay outputs - normal or inverse if l=0 activated


(Recognition of disconnected load - relay on (1) or otr (0))

Parameter fault latch (Latch):

Fault latch (Latch): on or off

Version 04/09 Page 4 ot 4


llH=lE".,,,".-.,,-
1.3 Menu configuration

MEASUREDVALUE IPARAMETER IPROGRAMMING

t+
l+ l- Esc & Ent l+
l+ l- Ent
->
.- L--
Egc
Esc -
- to cancel the value
Ent - to store the valua

Measured variable
(Active power)

Start-up
sup-pression time t2

+&-
Latch Reset

Version 04/09 Page 5 of5