You are on page 1of 2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Un [V] 22900
Ik LLL [kA] 12.6 * El ingreso y salida de cables sera
P [kW] 2416.7
-QF1
por la parte superior, en bandejas.
Q [kvar] 1292.8
A 1VCF338124R1111
VD4/S 24.06.12 P210
* Considerar espacio de reserva
KECA250B1 (250A)
REF601 CEI 0-16
del 10%.
IB = 69.1 A
Cosphi = 0.88 -B1
Ik max = 11.9 kA U=22889.4 V PGC1 Ï PGC2
3I0 = 0.05 [kA] IB = 69.1 A -QF4 -QF5
E2.2N 2500 Ekip Touch LSI 2500 E2.2N 2500 Ekip Dip LI 2500
Cosphi = 0.88
Ik max = 11.9 kA
kWh kWh
Ik LLL = 11.9 kA
-QF2 -QF3
1VCF338124R1111 1VCF338124R1111 -B2
VD4/S 24.06.12 P210 VD4/S 24.06.12 P210 FU = 0.42
KECA250B1 (80A) KECA250B1 (80A) U=385.2 V
REF601 CEI 0-16 REF601 CEI 0-16 IB = 3953.5 A
B IB = 34.5 A IB = 34.5 A Cosphi = 0.90
Cosphi = 0.88 Cosphi = 0.88 Ik max = 75.8 kA
Ik max = 11.9 kA Ik max = 11.9 kA Ik LLL = 75.8 kA
3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 1.1
-WC1 -WC2
3x(1x50)/16 3x(1x50)/16
IB = 34.5 A IB = 34.5 A -QF6 -QF7 -QF8 -QF9 -QF10
Iz = 334.1 A Iz = 334.1 A T7L 1600 PR231-LS/I 1600A T6L 1000 PR221DS-LS/I 1000A T5L 400 PR221DS-LS/I 400A T5L 400 PR221DS-LS/I 400A T5L 400 PR221DS-LS/I 400A
du = 0.00 du = 0.00
L = 15 m L = 15 m

Ï Ï
-TM1 -TM2
Un2 = 380 V Un2 = 380 V
C Sn = 1600 kVA Sn = 1600 kVA
Sec.: LLLN / TN-S Sec.: LLLN / TN-S

-WC5 -WC6 -WC7 -WC8 -WC9


-WC3 -WC4 15x(1x240)+5x(1x120)+5G120 9x(1x240)+3x(1x120)+3G120 6x(1x120)+2x(1x70)+2G70 6x(1x120)+2x(1x70)+2G70 6x(1x120)+2x(1x70)+2G70
24x(1x240)+8x(1x120)+8G120 24x(1x240)+8x(1x120)+8G120 Ib = 1600.0 A Ib = 1000.0 A Ib = 400.0 A Ib = 400.0 A Ib = 400.0 A
Ib = 1976.7 A Ib = 1976.7 A Iz = 2205.4 A Iz = 1323.3 A Iz = 584.2 A Iz = 584.2 A Iz = 584.2 A
Iz = 3528.7 A Iz = 3528.7 A dV = 0.28 % dV = 0.29 % dV = 0.28 % dV = 0.28 % dV = 0.28 %
dV = 0.21 % dV = 0.21 % L = 15 m L = 15 m L = 15 m L = 15 m L = 15 m
-WC10 L = 15 m L = 15 m
3x(1x50)/16
IB = 69.1 A
Iz = 334.1 A -L1 -L2 -L3 -L4 -L5
du = 0.05 Sn = 1053.09 [kVA] Sn = 658.18 [kVA] Sn = 263.27 [kVA] Sn = 263.27 [kVA] Sn = 263.27 [kVA]
D L = 200 m Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90
In = 1600.0 [A] In = 1000.0 [A] In = 400.0 [A] In = 400.0 [A] In = 400.0 [A]
U = 384.2 [V] U = 384.2 [V] U = 384.2 [V] U = 384.2 [V] U = 384.2 [V]
dU = 0.00 % dU = 0.00 % dU = 0.00 % dU = 0.00 % dU = 0.00 %
P = 963.07 [kW] P = 601.95 [kW] P = 240.79 [kW] P = 240.79 [kW] P = 240.79 [kW]
Q = 466.44 [kvar] Q = 291.54 [kvar] Q = 116.62 [kvar] Q = 116.62 [kvar] Q = 116.62 [kvar]

-B2
FU = 0.42
U=385.2 V
1.1 IB = 3953.5 A
Cosphi = 0.90
Ik max = 75.8 kA
Ï Ï Ï Ik LLL = 75.8 kA
-QF11 -QF12 -QF13 -QF14 -QF15 -QF16 -QF17 -QF18
E T6L 1000 PR221DS-LS/I 1000A XT2L 160 Ekip LS/I R63 E2.2S 2500 Ekip Dip LI 2500 T6L 800 PR221DS-LS/I 800A T6L 800 PR221DS-LS/I 800A XT2L 160 Ekip LS/I R63 XT4L 250 Ekip LS/I R250 XT2L 160 Ekip LS/I R160

(!) Important notice about coordination to be verified in Discrimination report


(*) El interruptor automático es selectivo con otro insterruptores.
(**) El interruptor tiene back-up con otros interruptores.
-WC11 -WC13 -WC14 -WC15 -WC17
9x(1x240)+3x(1x120)+3G120 -WC12 24x(1x240)+8x(1x120)+8G120 9x(1x185)+3x(1x95)+3G95 9x(1x185)+3x(1x95)+3G95 -WC16 3x(1x150)+1x(1x95)+1G95 -WC18
Ib = 1000.0 A 4x(1x25)+1G25 Ib = 2500.0 A Ib = 800.0 A Ib = 800.0 A 4x(1x25)+1G25 Ib = 250.0 A 3x(1x70)+1x(1x35)+1G35
F Iz = 1323.3 A Ib = 63.0 A Iz = 3528.7 A Iz = 1114.5 A Iz = 1114.5 A Ib = 40.0 A Iz = 364.6 A Ib = 160.0 A
dV = 0.29 % Iz = 111.7 A dV = 0.27 % dV = 0.27 % dV = 0.27 % Iz = 111.7 A dV = 0.29 % Iz = 220.5 A
L = 15 m dV = 0.33 % L = 15 m L = 15 m L = 15 m dV = 0.20 % L = 15 m dV = 0.34 %
L = 15 m L = 15 m L = 15 m

-L6 -L8 -L9 -L10 -L12


Sn = 658.18 [kVA] -L7 Sn = 1645.45 [kVA] Sn = 526.54 [kVA] Sn = 526.54 [kVA] -L11 Sn = 164.54 [kVA] -L13
Cosphi (nominal) = 0.90 Sn = 41.47 [kVA] Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Sn = 26.33 [kVA] Cosphi (nominal) = 0.90 Sn = 105.31 [kVA]
In = 1000.0 [A] Cosphi (nominal) = 0.90 In = 2500.0 [A] In = 800.0 [A] In = 800.0 [A] Cosphi (nominal) = 0.90 In = 250.0 [A] Cosphi (nominal) = 0.90
U = 384.2 [V] In = 63.0 [A] U = 384.2 [V] U = 384.2 [V] U = 384.2 [V] In = 40.0 [A] U = 384.1 [V] In = 160.0 [A]
dU = 0.00 % U = 384.0 [V] dU = 0.00 % dU = 0.00 % dU = 0.00 % U = 384.5 [V] dU = 0.00 % U = 383.9 [V]
P = 601.95 [kW] dU = 0.00 % P = 1504.69 [kW] P = 481.57 [kW] P = 481.57 [kW] dU = 0.00 % P = 150.50 [kW] dU = 0.00 %
Q = 291.54 [kvar] P = 37.93 [kW] Q = 728.76 [kvar] Q = 233.23 [kvar] Q = 233.23 [kvar] P = 24.08 [kW] Q = 72.89 [kvar] P = 96.32 [kW]
Q = 18.37 [kvar] Q = 11.66 [kvar] Q = 46.65 [kvar]
G
Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:
Rev. n2 Dibujante: David Zacarias Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

8.5 899 899 1099 499 699 8.5

-QF14

-QF15
T E
S T T E
S T

-QF13
-QF4

-QF5
B -QF9 -QF10

T E

T E
S T

S T
-QF16
2113

-QF8

T E
S T
-QF11
-QF6

-QF7 -QF17
C T E
S T T E
S T

T E
S T

-QF18

-QF12
100

(!) Important notice about coordination to be verified in Discrimination report


(*) El interruptor automático es selectivo con otro insterruptores.
1047

(**) El interruptor tiene back-up con otros interruptores.


F

G
Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:
Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 21 21