Professional Documents
Culture Documents
Un [V] 22900
Ik LLL [kA] 12.6 * El ingreso y salida de cables sera
P [kW] 2416.7
-QF1
por la parte superior, en bandejas.
Q [kvar] 1292.8
A 1VCF338124R1111
VD4/S 24.06.12 P210
* Considerar espacio de reserva
KECA250B1 (250A)
REF601 CEI 0-16
del 10%.
IB = 69.1 A
Cosphi = 0.88 -B1
Ik max = 11.9 kA U=22889.4 V PGC1 Ï PGC2
3I0 = 0.05 [kA] IB = 69.1 A -QF4 -QF5
E2.2N 2500 Ekip Touch LSI 2500 E2.2N 2500 Ekip Dip LI 2500
Cosphi = 0.88
Ik max = 11.9 kA
kWh kWh
Ik LLL = 11.9 kA
-QF2 -QF3
1VCF338124R1111 1VCF338124R1111 -B2
VD4/S 24.06.12 P210 VD4/S 24.06.12 P210 FU = 0.42
KECA250B1 (80A) KECA250B1 (80A) U=385.2 V
REF601 CEI 0-16 REF601 CEI 0-16 IB = 3953.5 A
B IB = 34.5 A IB = 34.5 A Cosphi = 0.90
Cosphi = 0.88 Cosphi = 0.88 Ik max = 75.8 kA
Ik max = 11.9 kA Ik max = 11.9 kA Ik LLL = 75.8 kA
3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 1.1
-WC1 -WC2
3x(1x50)/16 3x(1x50)/16
IB = 34.5 A IB = 34.5 A -QF6 -QF7 -QF8 -QF9 -QF10
Iz = 334.1 A Iz = 334.1 A T7L 1600 PR231-LS/I 1600A T6L 1000 PR221DS-LS/I 1000A T5L 400 PR221DS-LS/I 400A T5L 400 PR221DS-LS/I 400A T5L 400 PR221DS-LS/I 400A
du = 0.00 du = 0.00
L = 15 m L = 15 m
Ï Ï
-TM1 -TM2
Un2 = 380 V Un2 = 380 V
C Sn = 1600 kVA Sn = 1600 kVA
Sec.: LLLN / TN-S Sec.: LLLN / TN-S
-B2
FU = 0.42
U=385.2 V
1.1 IB = 3953.5 A
Cosphi = 0.90
Ik max = 75.8 kA
Ï Ï Ï Ik LLL = 75.8 kA
-QF11 -QF12 -QF13 -QF14 -QF15 -QF16 -QF17 -QF18
E T6L 1000 PR221DS-LS/I 1000A XT2L 160 Ekip LS/I R63 E2.2S 2500 Ekip Dip LI 2500 T6L 800 PR221DS-LS/I 800A T6L 800 PR221DS-LS/I 800A XT2L 160 Ekip LS/I R63 XT4L 250 Ekip LS/I R250 XT2L 160 Ekip LS/I R160
-QF14
-QF15
T E
S T T E
S T
-QF13
-QF4
-QF5
B -QF9 -QF10
T E
T E
S T
S T
-QF16
2113
-QF8
T E
S T
-QF11
-QF6
-QF7 -QF17
C T E
S T T E
S T
T E
S T
-QF18
-QF12
100
G
Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:
Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 21 21