Professional Documents
Culture Documents
discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/4078178
CITATIONS READS
3 52
3 authors, including:
L. Prikler
Budapest University of Technology and Economics
18 PUBLICATIONS 127 CITATIONS
SEE PROFILE
All content following this page was uploaded by L. Prikler on 16 October 2014.
Abstract - The paper reports on studies, which supported the Fig. 1 shows the scheme of the overvoltage protection of the
projecting, reconstruction and modification of a 750 kV, 479 Albertirsa substation. Conventional silicon carbide arresters
km long transmission line. The changes were demanded by the with passive gaps served for the limitation of overvoltage
technical development and the alteration of the role of the line protection in both ends of the line. Arresters A2 protected
in the power transmission. Authors analyse various ways for
the shunt reactors, while A1 the transformer. Being the ratio
influencing on the interaction of the reactive power control,
relaying and overvoltage protection. The possibility of the of the protecting level of conventional arresters to the rated
operation with incomplete, asymmetrical shunt reactor and voltage quite large, a high shunt compensation degree was
arrester sets is investigated. The paper describes a simple way required to keep the temporary overvoltages below the
of controlled three-phase and adaptive single-phase reclosure. permitted level.
Uc ~
Cab
L* 2Cab
Ub ~
Cab
~
Ua ~ -Ua/2 A
Co Is K Ls
L** Co
N
Ln
a. b.
C0 – zero sequence capacitance of the line; Ls – resultant inductance of the
reactors
Ln – the inductance of the neutral coil; Is – secondary arc current
Ls L2 **
L* = 3 + s L = Ls+3Ln.
2 2 Ln
Scheme (a) and simplified circuit (b) for understanding the effect of neutral
reactors.
a. 750 kV b. 400 kV
Secondary arcing on 750 kV and 400 kV transmission line Fig. 6.
Fig. 4.
The circuit in Fig. 6 explains the condition of compensation.
Figures 4a, and 4b. illustrate the formation of the secondary If L* controlled by the neutral inductance and 2Cab form a
arc. Fig. 4a was recorded during a staged fault in the 750 kV resonant circuit resonating to the power frequency, no
line. This figure shows the initial interval of the primary arc secondary arc current and recovery voltage occur.
when the flashover is just developing along the insulator
surface and also the secondary one. Thus the arcs in Fig.4a To find the optimal neutral inductance to minimize the
are not synchronous. Figure 4b was recorded during a field secondary current, a detailed study is needed. The optimum
test in a 400 kV double circuit line, when the secondary arc value of Ln depends on the actual compensation degree that
was initiated by a thin wire, without primary arc. has to be adapted to the actual value of the transmitted
power.
The secondary arc is sustained by the capacitive and
inductive coupling with the healthy phases. Its current The inductance of the neutral coils in Albertirsa has been
depends mainly on the phase-to-phase capacitance, thus the selected in the eighties supposing that every shunt reactor
line length. Generally high secondary currents lead to long set on both line ends will have a neutral coil. In the present
duration secondary arcs. situation only in Albertirsa substation are neutral reactors in
operation, so the secondary current is not suppressed
In any case, the extinction of the secondary arc is preceded sufficiently. This imperfection is partly compensated by
and prepared by an intermittent interval, consisting of high operating the line on the lowest permitted voltage level: 700
current impulses followed by temporary dropping the kV rms. In the most dangerous case (a single incomplete
restrikes. So mainly the intermittent arcing process shunt reactor set in Albertirsa and one or two complete sets
determines the duration of the secondary arc. in the Ukrainian substation) the expectable peak value of the
continuous secondary current reaches 68 Amps. According
to the international statistics of self-extinction times [6] this
value corresponds to 1.45 s self extinction duration. The
permitted maximum dead time for the investigated 750 kV
transmission is 1.6 s. One has to consider the high amplitude
of the recovery voltage due to the shunt compensation and
the fact that the dead time has to be longer, than the sum of
time delay of tripping the faulty phase and the self-
extinction time. Thus the reserve time does not seem to be
sufficient.
.
Secondary arcing. To eliminate the danger of inefficient single phase reclosing,
Upper curve: arc voltage in the intermittent interval. a variant of adaptive reclosing has been elaborated and
Lower curve: the fault current and secondary one during single phase
reclosing in the 750 kV line. proposed for the detection of the actual extinction time. The
Fig. 5. detection is based on the transients taking place in the
intermittent interval of secondary arcing. In this period arc
Secondary arc in long EHV transmission line may be of re-ignitions and extinctions follow each other. Every re-
long duration first of all due to its large Cab. Besides, when ignition and extinction initiates subsequent reflections of
shunt reactors are connected to the line, a recovery voltage steep front waves in the tripped phase conductor.
of beating character occurs at the faulty spot following the
secondary current impulse. Its amplitude can exceed the
1.20
*10 6
The device that detects the final extinction of the secondary
0.76 arc may be utilized in the following ways:
• It effectuates reclosing after detecting the final
0.32 extinction. The dead time is not a constant value.
• Average secondary arc duration is taken as constant
-0.12 dead time. If the secondary arc duration exceeds the
adjusted value, the device elongates the dead time by a
-0.56
pre-determined Δt or prevents it.
-1.00
C. Three-phase reclosing
0.110 0.115 0.120 0.125 0.130 0.135 [s ] 0.140
(file veiporto2new.pl4; x -var t) v:CA c: -XX0014 v:A A
Three-phase reclosure of shunt compensated lines produces
Transients in the faulty phase after a re-strike.
Upper curves: voltages in the line ends. the highest switching overvoltages and the heaviest stresses
Lower curve: the current of the re-strike. in arresters, since the trapped charge in the healthy phases of
Fig. 7. a shunt compensated line is of beating character due to the
transients in the line mode and ground one.
The fundamental harmonic of the extinction transient Three-phase reclosing endangers mainly those lines, which
depends on the line length only (see Fig 7), while that of the contain polluted or foggy zones. Contamination usually
breakdown transient is highly influenced by the location of extends to a large area, where the line insulation is reduced
the fault, Consequently, the detection of the final extinction during foggy weather. It is presumable, that an intensive
has been based on sensing the presence of the intermittent partial arc activity is going along the surface of many line
extinction transients by means of special filters on the line insulators, when one of them flashes over stressed by the
ends. As long as the intermittent secondary arc exists, a high operating voltage. As a rule, the heating effect of the
voltage occurs on the outputs of the filters primary arc dries the faulted insulator, but a high reclosing
350
[kV]
overvoltage is able to initiate partial arcs on some other
insulators. These arcs may be much longer, than they could
250
be at the operating voltage. The temporary overvoltage
following the reclosing transient and then the operating
150 voltage may sustain and elongate the long partial arcs till
occurring the full flashover. This hypothesis is supported by
50 [5], which reports on ''records of failures to reclose having
contamination flashovers and also many examples of
-50 successful reclosing followed by a subsequent flashover''.
The same tendencies show the data about the efficiency of
-150 reclosing Hungarian HV and EHV lines for a four-years
0.20 0.25 0.30 0.35 0.40 0.45 [s ] 0.50
period 1984 - 1988.
Detection of the final extinction in a 400 kV line
Summer Winter
Upper curve: the output voltage of the filter
Lower curve: recovery voltage at the fault Voltage unsucc success unsuccess length
successful
Fig. 8. level essful ful ful (km)
750 kV 5 0 1 2 479
Dropping this output voltage near to zero indicates the final
400 kV 48 20 28 9 1530
extinction of the secondary arc (see Fig.8. A device
operating according the described principle has been 220 kV 83 28 23 47 1687
constructed and tested on 750 kV and 400 kV lines. Fig. 9
120 kV 2437 65 501 177 7039
shows a record about its operation when a single-phase- to-
ground fault turned into a two-phase-to-ground fault (750 ∑ 2573 113 553 235 10733
kV transmission line). Table I
VI. CONCLUSIONS
The application of metal oxide arresters of special
characteristics significantly weakens the strong connection
between the degree of shunt compensation, the relay and
overvoltage protection.
The efficiency of single-phase reclosing can be improved by
a simple variant of detecting the secondary arc extinction
time.
Using the effect of four legged shunt reactors on the
capacitive coupling between phase conductors, a cheap
method of controlled three-phase reclosing can be
effectuated for older types of circuit breakers as well.
Controlled disconnecting offers an efficient protection for
shunt reactor insulation.
VII. ACKNOWLEDGEMENT
VIII. REFERENCES