HV CABLE SIZING CALCULATION
A B C D E F G H I J K L M N O P Q R S
Sl. Feeder details Full load Starting Cable type No. of Type Total Min. reqd. Current Result Voltage % Voltage %
No. Cable current current (CU/XLPE/ runs of Derating cable Proposed rating of the for proposed drop Volt-drop drop Volt-drop
Load
From To Length in Amps. in Amps. SWA/PVC) installation factor current cable size proposed cable size during during during during
(L) (Iflc) (Ist) TDF rating cable running running starting starting
kVA metres Iflcx6.5 (F/K) (Sq.mm.) (amps.) volts % volts %
1 14SB-3003 VSDS Input 1600 150 279.9 - YES 1 Ground 0.6208 450.9 300 481 SAFE 8.15 0.25 - -
transformer
Notes:
Derating factors :
VSDS Inverter-1/2&3 VSDS Motor 741 415 0.80 0.90 741.00 0.344 2154.07 300 4 590 140 0.190 1.19 5.0 NA NA N.A