Mar 15, 2007


by POWER

O&M

Practical guidelines for determining

electrical area classification

Hazardous areas exist in every power plant. Following proper design rules and
anticipating how the plant will be operated can avoid creating mixtures of gases that
could explode or catch fire.

Quantifying electrical safety risks and reducing them to an acceptable level is a team
effort. The designer must follow applicable codes and standards when engineering the
plant, and operators must run and maintain it within those guidelines. Does your staff
know where the hazardous areas are in your plant? Are hazardous area classifications
made years ago still appropriate under current standards?

Cataloging risks

Hazardous area classification is a rigorous method of determining where an explosive


environment may be present. The codes and standards used in this process provide
guidance for selecting, building, and installing electrical equipment in that area. In
general, hazardous areas (HAs) are defined by:

The type of hazard or hazardous material.


The likelihood of its presence in flammable concentration.
The auto-ignition temperature of the hazardous material.

An explosive atmosphere can be created by a gas or vapor, dust, or even fibers. close x

Methane-based hazards dominate the gas-fired generation sector, whereas


https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 1/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

spontaneous combustion of coal dust plagues plants fired by that fuel. The different
 
zones defined by codes for classifying particular hazardous areas are listed and
Featured Categories

discussed in the online supplement to this article.

The probability that any hazard exists in combustible concentration is determined by


the specifics of the plant or system under consideration. For example, a natural gas vent

line is much more likely to contain such a hazard than a lube oil line—unless, of course,
the oil line’s flanged joint is leaky.

Finally, plant design also must protect against auto-ignition of combustible substances.
A good example of this type of hazard is a flammable gas coming into contact with a hot
surface. Codes define various temperature classes to guide designers as they specify
equipment.

In the field

By design, natural gas-fired power plants are fueled by an extremely combustible


substance. But fuel lines and the turbine deck are hardly the only HAs in the plant. The
prerequisites for developing an area classification for a gas-fired plant are
understanding the characteristics of all of hazardous materials present in it and defining
where those materials exist (or may spread due to a leak). This allows mapping out the
plant’s HAs.

Each HA should be classified according to applicable industry codes and standards. For
example, electrical area classifications explain how to select and install electrical
equipment and wiring—right down to the wiring method—to minimize the likelihood of
ignition of a flammable or explosive mixture.

Disclaimer: The guidelines mentioned in this article describe approaches used by Burns
and Roe Enterprises Inc. The information is provided solely to educate power plant
designers and staff. Burns & Roe is not responsible for classifications prepared by
others using these guidelines.

—Ram K. Saini, PE, is senior principal engineer for Burns and Roe Enterprises Inc. He
can be reached at 201-986-4339 or rsaini@roe.com. Charles Emma, PE, is principal
engineer and can be reached at 856-638-6920 or cemma@roe.com.

The National Electrical Code (NEC), NFPA 70, defines hazardous (classified) areas as
those where fire or explosion hazards may exist due to the presence of flammable
gases, vapors, or liquids, combustible dust, or ignitable fibers. Electrical area
classification (EAC) is the process of determining the existence and extent of hazardous
locations in a facility containing any of those substances. The result of the process is
usually called the EAC of the facility. In the context of electrical equipment, the following
terms—area classification, hazardous locations, hazardous (classified) locations, and close x

classified areas—are all synonymous with EAC. In the following guidelines, the term EAC
https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 2/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification
classified areas are all synonymous with EAC. In the following guidelines, the term EAC
is used to avoid confusion with other nonelectrical classifications.
Featured Categories 

The approach described in this article focuses on a combustion turbine-generator (CTG)
plant, although the same methods are applicable to any type of power plant and its
systems.

Taxonomy and terminology

For a fire or explosion to occur, all three of the following statements must be true:

Flammable or combustible material is present.


The material is mixed with air in the proportions required to produce an ignitable
mixture.
The release of energy is sufficient to ignite the mixture.

The above conditions constitute the well-known “fire triangle” (Figure 1). In the context
of EAC, the source of energy is understood to be the facility’s electrical system.

1.Air, heat, and fuel must be present to start a

fire.
Areas are classified in accordance with the type and properties of the combustible
material and the likelihood that an ignitable mixture will exists. Since 2002, the NEC has
permitted hazardous locations to be categorized using either of two “concepts” or
methods: Class I, II, and III, Division 1 and 2 (NEC Article 500); and Class I, Zone 0, 1, and
2 (NEC Article 505).

The first method has traditionally been used in the U.S. The second method complies
with International Electrotechnical Commission (IEC) standards and has been used in
Europe. The information presented in this article is based on the “Class, Division”
concept.

Hazardous locations are categorized by class, group, and division as follows.


close x

Class (material type)


https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 3/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

Class I: Denotes areas where flammable gas,


Featured vapor, or
Categories liquid is present. 
Class II: Denotes areas where combustible dust is present.

Class III: Denotes areas where ignitable fibers are present. (Class III areas rarely exist in
CTG facilities.)

Group (material properties)

Hazardous chemicals and flammable materials are given group designations based on
their propensity to explode or catch fire. The designations facilitate the approval and
listing of equipment suitable for use in hazardous locations. National Fire Protection
Association (NFPA) Recommended Practices 497 and 499 and other industry sources
also group chemicals in this way. NEC Article 500 segregates chemicals and materials as
follows:

Group A: Acetylene
Group B: Hydrogen
Group C: Cyclopropane, ethyl ether
Group D: Acetone, butane, propane, hexane, natural gas, fuel oil
Group E: Combustible metals
Group F: Carbonaceous materials, including coal dust
Group G: Flour, starch, plastic

Division (the likelihood of hazardous atmosphere)

Division 1: Denotes areas where flammable or combustible concentrations exist under


normal operating conditions or are highly likely to exist under other conditions.

Division 2: Denotes areas where flammable or combustible concentrations exist under


abnormal operating conditions or are not likely to exist under other conditions.

Nonclassified or unclassified: Denotes areas where the presence of hazardous material


is so infrequent that Electrical Area Classification is deemed unnecessary.

Auto-ignition temperature

The auto-ignition temperature (AIT) of the hazardous material in a facility must be


known to complete its EAC. NFPA 497 provides AIT values for various combustible
substances.

A typical area classification for propane gas would be: Class I, Division 2, Group D, 450C
AIT. Here:

Class I indicates the presence of vapor.


Division 2 indicates that the vapor is present only under abnormal conditions. close x

Group D indicates that propane is a member of this group.


https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 4/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification
Group D indicates that propane is a member of this group.
450C is the auto-ignition temperature of propane.
Featured Categories 

Once an area has been classified, the NEC provides very specific and stringent
requirements about the electrical equipment and associated wiring that can be installed
within that area. The requirements are intended to prevent electrical equipment from

being the ignition source for a flammable mixture. Accordingly, the installation itself
must be explosion-proof.

Obviously, a facility’s EAC must be known before any electrical equipment can be
specified, designed, or installed. On many CTG power projects, special-purpose
mechanical equipment with long lead times (motors and instrumentation and control
systems and components, for example) must be specified and ordered early. Failure to
determine the EAC for the facility and such equipment in a timely fashion can result in
unsafe installations, rework, confusion, delays, and cost overruns.

EAC dos and don’ts

An EAC is best performed by a project team whose members are knowledgeable about
classification, applicable codes and standards, electrical equipment and wiring,
chemicals used, fire detection and protection systems, process operations and
conditions, maintenance procedures, HVAC engineering, and plant safety.

Many variables must be included in area classification equations. They include the
properties and behavior of materials, volumes, pressures, temperatures, flows, piping
and equipment construction, weather, building arrangements, adequacy of mechanical
ventilation and gas detection systems, and operator interfaces. Careful evaluation of all
data in accordance with established techniques, along with the application of sound
engineering judgment, should produce a consistent and safe classification.

The NEC calls for each room, section, or area of a facility to be considered individually in
determining its classification. Eschewing this approach in favor of classifying an entire
facility using a broad-brush approach (a process referred to as “blanket classification”)
almost always leads to a more dangerous and ultimately more costly facility. This is
especially true for a power plant, which normally contains several different process,
support, and maintenance areas. A properly conducted EAC, in a well-designed and
constructed facility, might result in a few Division 1 areas and several much larger
Division 2 and nonclassified areas.

Although many other companies and industry organizations have written specific
procedures for Area Classification, the NFPA Recommended Practices for Classification
are most applicable to power plants. NFPA 497 covers Class I areas containing gases,
vapors, and liquids, and NFPA 499 covers Class II areas containing dusts. These practices
assume the ability to identify and locate sources of hazardous material.
close x

https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 5/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

The sources can be necessarily open process points or unintentional leaks in the
Featured Categories 

process. Once sources are located, the practices provide guidance in determining the
degree of the hazard (Division 1 or Division 2) and its extent. They also provide diagrams
for typical situations that give recommended distances from the source for the extent of
a hazardous location. Although the diagrams take into account pressure, volume, flow
rate, ventilation, building construction, and certain process operations, it must be

remembered that they are only typical and require sound engineering for application to
specific situations.

The NFPA way

What follows is a brief, nine-step outline of NFPA practices. The actual practices and
associated references should be consulted when performing any EAC.

To determine an electrical area classification:

1. Assemble pertinent information, including: codes, standards, practices, and reference;


process and operating descriptions; process flow diagrams and material and heat
balance chart; piping and instrumentation diagrams; equipment arrangement drawings
and plot plans; and commissioning, testing, operating, and safety procedures.

2. List all flammable and combustible materials and their pertinent properties, such as
ignition temperatures and flash points.

3. Confirm the need for classification by assessing the likelihood of the presence of
flammable and combustible materials.

4. Locate material release sources, such as open process points, control valves, pump
seals, drains, metering points, sampling points, and vents. See NFPA 497 and 499 for
additional guidance in identifying sources. As a practical matter, areas with large
quantities of process equipment and piping that handle flammable/combustible
materials can, as an area, be considered a release source.

5. Determine an area’s Class and Group from the chemicals present.

6. Determine the degree of hazard (Division 1 or Division 2) by assessing the probability


of presence.

7. Determine the extent (or distance from the source) of hazardous areas by reviewing
the plant’s equipment layout drawings.

8. Consider using recognizable boundaries (walls, floors, ceilings, and column lines) to
delineate Classified Areas. This approach will greatly simplify both design and
installation.

9. Prepare the recommended documentation for the EAC project team to review and
close x

https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 6/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification
approve.
Featured Categories  
Applicable industry codes and standards

The following codes and standards are particularly applicable to Hazardous Classified
Areas in CTG power plants.

a. U.S. standards
National Fire Protection Association

NFPA 30-2003: Flammable and Combustible Liquids Code

NFPA 50A-1999: Standard for Gaseous Hydrogen Systems at Consumer Sites

NFPA 59-2001: Standard for the Production, Storage and Handling of Liquefied Natural
Gas

NFPA 70-2005: National Electrical Code (Chapter 5)

NFPA 497-1997: Classification of Flammable Liquids, Gases, or Vapors and of Hazardous


(Classified) Locations for Electrical Installations in Chemical Process Areas

American National Standards Institute (ANSI)

ANSI K61.1-1999: Safety Requirements for the Storage and Handling of Anhydrous
Ammonia

ANSI C2-2002: National Electrical Safety Code – Section 127

ANSI/ASHRAE 15: Safety Code for Mechanical Refrigeration (for ammonia)

Factory Mutual (FM)

Underwriters Laboratory (UL) standards

Occupational Safety and Health Administration (OSHA) standards

b. European standards

International Electrotechnical Commission (IEC) standards

IEC 79-10 (Part 10): Classification of Hazardous Areas

IEC 79-14 (Part 14): Electrical Installations in Explosive Gas Atmospheres

IEC 79-15 (Part 15): Electrical Apparatus with Type of Protection “n”

c. CTG vendor documentation

Major CTG vendors often supply Area Classification documents pertaining to their close x

systems and equipment.


https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 7/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

d. Other Featured Categories  


Numerous other materials are available for reference through industry sources.

At-risk systems and equipment

The main components and systems in a CTG power plant that are vulnerable to fire or
explosion follow.

Fuel gas systems. These include the gas-receiving station, gas analyzer system, gas
compressor station, main shut-off valve, gas relief points, the filter and scrubber station,
the gas preheater, the gas control valve block, the gas safety relief valve, gas flow
metering, gas distribution piping, and turbine auxiliaries equipment/compartment.

Ignition gas systems. These include propane gas cylinders, piping to ignition burner and
combustor, and gas relief points.

Fuel oil systems. These include fuel oil tanks, the fuel oil unloading and forwarding
pump station, the fuel oil treatment system, fuel oil metering, the fuel oil booster pump
and leakage tank, the fuel oil control valve block, and fuel oil piping to burners. Fuel oil
becomes flammable when heated above its flash point.

Hydrogen gas for generator cooling systems. These include the hydrogen gas cylinder
station, the gas unit, the seal oil unit, the control cubicle, and piping.

Plant battery systems (including battery rooms).

Ammonia systems. These include storage tanks, pumps, and diked areas.

Potential leak sources

Following are some of the most common potential leak sources in fuel gas, propane gas
(ignition), fuel oil, hydrogen gas, and ammonia gas systems. Some are identified by the
CTG vendor.

Fuel gas system

Flange gasket connection points on local piping, tubing, or at equipment.


Flange gaskets or screwed connections in main headers.
Seals (unless seal-less) at pumps and control valves.
Pressure relief devices.
Gas relief points located in the open air above the turbine building roof for
equipment located within the turbine area.

Propane gas (ignition) system close x

Th i iti bi t ith d li
https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/
d l d i th t bi 8/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification
The ignition gas cabinet, with screwed couplings and glands, in the turbine
auxiliary equipment area. Featured Categories  
Gas relief points above the turbine building roof.

Fuel oil system

Fuel oil transfer pipe joints and coupling in the fuel oil�unloading area and
forwarding pump stations.
Fuel oil tank piping, pump blocks, filling and suction valve blocks, vents, indicators,
alarm switches, oil piping (both outdoor and at the combustor), burners, and
heaters.
Open process points, sample points, and sumps.

Hydrogen gas system

H2 gas storage cylinders.


The H2 cooling unit and separator.
The H2-cooled generator.
Battery rooms (hydrogen gas is released from lead acid�flooded cell batteries as
they charge).

Anhydrous ammonia system

Storage tanks, vaporizer, and diked areas.

Bounding hazardous classified locations

Using the references listed above, determine the extent of the Classified Area for each
type of leak source shown in the table.

close x

https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 9/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

Featured Categories  

Hazardous materials

and where they typically exist in a power plant. Source: Burns and Roe Enterprises Inc.
Note 1: Adequately ventilated per NFPA 497 means a ventilation rate that affords either
six air changes per hour, 1 cfm per square foot of floor area, or another similar criterion close x

that prevents accumulated vapor air concentrations from exceeding 25% of the lower
https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 10/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification
that prevents accumulated vapor-air concentrations from exceeding 25% of the lower
flammable limit. Note 2: If vent pipes are being discharged in an otherwise
Featured Categories 

nonhazardous area, they should be discharged outdoors at a minimum distance of 10
feet (for natural gas) and 15 feet (for hydrogen) from any electrical equipment, light
fixture, etc. Note 3: A continuously operated exhaust fan in the battery room is required
to remove any accumulation of hydrogen gas discharged from the batteries. Loss of
electrical power to the fan should be alarmed in the plant control room. Note 4:

Ammonia detectors should be installed around the diked area and connected to the
plant’s distributed control system. A deluge water spray system should be installed for
automatic/manual actuation; its alarm should be sent to the fire alarm panel in the
plant control room.
These guidelines should be used as a minimum requirement for Classification of
Electrical Areas where such materials are located and processes are performed. Sound
engineering judgment should be applied to determine if additional areas, not
mentioned in the table, should be identified. Equipment manufacturers’
recommendations for the Area Classification of specific equipment should be followed,
especially if they are more stringent than the guidelines provided in the table.

When there is more than one leakage source in an area (for example, a manifold serving
several instruments or valves), or if there are several pieces of equipment with potential
leak sources, the area should be boxed out as an overall three-dimensional shape
covering the limits of the extreme leakage points. To avoid undue expense, take
precautions to verify that boxing in overall areas, or extending classified areas to
recognizable boundaries, does not include electrical equipment that would otherwise
not be included in the hazardous area.

Support drawings and documents

Like any engineering study or analysis, EAC must be carefully documented because it
serves as the basis for electrical equipment requirements in classified areas. Such
documentation, along with properly implemented protective measures, reduces the
possibility of an explosion or fire. The documentation also provides the necessary
guidance to engineers working on facility design, as well as to insurance and inspection
personnel. The protective measures ensure the safety of the O&M personnel working in
the facility.

The design engineer should prepare a hazardous location design basis document
defining the plant hazards, the potential leakage sources, and the extent of the
classified areas. The design basis document and the associated plant drawings that
show the extent of the horizontal and vertical boundaries of each classified area should
be discussed with the owner, the construction contractor, and the plant’s operations
staff to ensure their understanding of the affected areas.

Figures 1, 2, and 3 are the plan and elevation drawings used for classifying the close x

hazardous areas around a combustion turbine-generator. Figures 4 and 5 are similar


https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 11/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

drawings for the roof area of a hydrogen-cooled generator and an ammonia vaporizer
skid, respectively. Hazardous area classification drawings should be prepared for each
Featured Categories  
plant and should include similar details for the use of the plant construction contractor
and the operations staff.

Documentation should include:

A listing of all the flammable and combustible materials used in the facility, as well
as their pertinent properties (flash point, ignition temperature, density, etc.) and
how and where the materials are handled.
Brief descriptions of the process and its O&M and cleaning details.
A list (including dates and/or editions) of all the codes, standards, references,
practices, and other data used to prepare the classification.
A discussion of all the assumptions made during the analysis.
A listing of each room or area and its determined area classification, along with the
rationale for making the determination.
A complete set of EAC drawings indicating all of classified area’s process
equipment, normal and leakage sources, and boundaries.

2.The EAC for the

area around a heat-recovery steam generator, fuel gas heat exchanger, and scrubber. close x

Courtesy: Burns & Roe Enterprises Inc.


https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 12/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

Featured Categories  

3.Hazardous area

classification for the area around a combustion turbine-generator, including the


hydrogen manifold and connections. Courtesy: Burns & Roe Enterprises Inc.

4.Hazardous area

close x

https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 13/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification

Featured Categories  
classification for the roof above a hydrogen-cooled generator. Courtesy: Burns & Roe
Enterprises Inc.

5.Hazardous area

classification for the area around the ammonia vaporizer skids and fuel gas valves and
devices at a combined-cycle power plant. Courtesy: Burns & Roe Enterprises Inc.

Designing for hazardous areas

As mentioned earlier, once the EAC for an area has been determined, the NEC provides
stringent requirements for the design and installation of electrical equipment within it.
These rules should be followed very carefully, making exceptions only if absolutely
necessary.

Rather than providing specific design guidelines, the following brief list of NEC rules is
intended only to convey an awareness of the complexity of electrical design in
hazardous areas. Experienced and knowledgeable engineers are needed to apply the
NEC rules to specific situations.

Explosion-proof and dust-ignition proof equipment is required in Division 1 areas


and for certain types of equipment in Division 2 areas.
Equipment approved by Underwriters Laboratories or by another appropriate
agency is preferred in hazardous locations.
It is preferable to locate electrical equipment outside the hazardous area.
General-purpose equipment is permitted for certain applications in Division 2
areas.
Purging and pressurization of enclosures are permitted to prevent the entrance of
flammable and combustible material, provided that specific rules in NFPA 496 are
followed.
Instrumentation enclosures may be the general-purpose type if they are part of
close x

i t i i ll f t d if th i t ll d
https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ NEC A ti l 504 14/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification
intrinsically safe systems and if they are installed per NEC Article 504.
Rigid metal conduit is the allowable
Featuredwiring method
Categories  in Division 1 areas. 
Cable trays and cables, under certain conditions, are permitted in Division 2 areas.
Electrical equipment must have temperature ratings or operating surface
temperatures below the AIT of the hazardous substance present.

Disclaimer: The guidelines discussed in this article describe approaches used by Burns

and Roe Enterprises Inc. The information is provided solely to educate power plant
designers and staff. Burns and Roe is not responsible for classifications prepared by
others using these guidelines.

Print Mode : OFF


—Ram K. Saini, PE, is a senior principal engineer with Burns and Roe Enterprises Inc. He
can be reached at 201-986-4339 or rsaini@roe.com. Chuck Emma, PE, is a principal
engineer at the company; he can be reached at 856-638-6920 or cemma@roe.com.

SHARE this article    

#Hazardous Area Classification


#Electrical Area Classification

MORE O&M NEWS

   WEBINARS

Sponsored By GE Digital

It's Not About Base Load Performance Anymore

Live on July 27, 2022

Learn more SIGN UP

Sponsored By Winsted

From The Lab To The Field: Making The Most Of Your Microgrid

Live on August 10, 2022

close x

L SIGN UP
https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 15/16
7/27/22, 7:35 AM Practical guidelines for determining electrical area classification
Learn more SIGN UP

Featured Categories  
Sponsored By Siemens

"The Use Of Advanced Simulation In The Design Of The Xe-100

Advanced Reactor Power Plant"

Available on demand until June 28, 2023

Learn more SIGN UP

View more

   

close x

https://www.powermag.com/practical-guidelines-for-determining-electrical-area-classification/ 16/16

You might also like