You are on page 1of 2

Revision

date content
3/22/2021 first
1、Tab NRTD-21, added Cu53 & BA1 type;
2、Tab NTC-21, chang K to K(EU);
3/23/2021 3、Tab NTC-21, chang E to E(EA);
4、Tab NTC-21, chang T to TC-T;
5、Tab NTC-21, added TC-B & K(EU2) type;
NRTD-21
Max. Min.
Name
resistance value(Ω) temperature(℃) resistance value(Ω) temperature(℃)
PT10 *1
Cu50 82.13 150 41.4 -40
Cu53 87.06 150 41.6 -50
BA1 153.29 650 41.42 -25
PT100 313.71 600 18.52 -200

NTC-21
Max. Min.
Name
thermocouple value(mV) temperature(℃) thermocouple value(mV) temperature(℃)
K(EU) 49.926 1230 -2.919 -80
E(EA) 49.917 660 -2.787 -50
TC-T 20.87 400 -2.788 -80
TC-B 13.59 1800 0.291 250
K(EU2) *2
TC-S 18.5 1750 -0.236 -50

The recommended value is in the NetPAC Hardware System Manual and


notes
the maximum range of measurement is in the table.
*1 In order to reduce module types, NRTD-21 does not calibrate pt10.
*2 K(EU2) is an old standard in the 1980s, which has not been used now.