You are on page 1of 1

87Overall Differential CT loop Injection and Burden verification

USB#60 IC
CT
CT side terminal Panel side terminal Injrcted Mesured current in Burden
no. Name/location/fu CABLE No. Current the return wire/relay Measured
nction

XCA-1(R Ph) XJ1-17 1 4.1 1.614

6kV BCT- XCA-2(Y Ph) XJ1-18 1 4.06 1.63


1 1,4000/1A(USB#60 00ACA01C018
IC) XCA-3(B Ph) XJ1-19 1 4.02 1.57

XCA-7(N)+E XJ1-20 .. .. ..
Generator CT
CT
CT side terminal Panel side terminal Injrcted Mesured current in Burden
no. Name/location/fu CABLE No. Current the return wire/relay Measured
nction

T2L1-S2 XJ1-17BIS
60BAA10C0100 1 15.03 3.36
(R Ph)
T2L1-S1 XJ1-21

T2L2-S2 XJ1-18BIS
60BAA10C0101
Generator 1 15.1 3.37
(Y Ph)
2 CT,15000/1A,CORE T2L2-S1 XJ1-22
-1,T2
T2L3-S2 XJ1-24
60BAA10C0102 1 15.1 3.37
(B Ph)
T2L3-S1 XJ1-23

EARTH .. .. ..