CT Sizing Calculation for

132 kV Cable Feeder

Page 1 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. 0
PROJECT :
SUBSTATIONS MM SMS AKSM DATE

TITLE : CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV CABLE FEEDER 25/10/11

SUMMARY

Sl.No. Description Page No.


1 Summary Chart 3
2 Single Line Diagram 4
Core - 1

3 CT Sizing Calculation 6
Core - 2

4 CT Sizing Calculation 13
Core - 3

5 CT Sizing Calculation 20
Core - 4

6 CT Sizing Calculation 25

Page 2 of 101
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Current Transformer Parameters for 132kV Cable feeder - BC-2 Substation (Adopted Parameters)

Project : GTC - 371A - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE- X - SUBSTATIONS Dt: 9/11/2011 Rev: A
Itherm-cont
Class of Rated (Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden Rated Short
Core Ratio accuracy Instrument continuous short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - time thermal Remarks
Nos proposed as per IEC security thermal current =
(Ohms) Required Adopted (RMS value) Adopted current (Ith)
60044-1 factor ISF current in 2.5 x Ith (KA)
%)

132kV Cable- Feeder CT

1500 A 5.3 1580 3394 16 mA @ Vk / 2 - - 120% 40kA, 1 sec 100


Cable Line Differential + Backup
1 Distance Protection - Main1(P545) - Core-1 1500-800/1A PX
(87C/21C-1)
800 A 2.8 1810 1810 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

1500 A 5.3 770 1669 16 mA @ Vk / 2 - - 120% 40kA, 1 sec 100


Cable Line Differential + Backup
2 Distance Protection (7SD532) - Core-2 1500-800/1A PX
(87C/21C-2) 800 A 2.8 890 890 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

1500 A 5.3 - - - 28 - 120% 40kA, 1 sec 100


3 BCU+Metering - (C264) Core-3 1500-800/1A 5P20/1.0
800 A 2.8 - - - 15 - 120% 40kA, 1 sec 100

4 Busbar Protection (P743) - (87B/50BF) Core-4 2500/1A PX 2500 A 8.8 191 200 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

Note:

Considering 630 Sq.mm Cu. cable with 1 KM length for 400 A Tap and 1600 Sq.mm Cu. cable with 1 KM length for 800A Tap for calculation of Knee pint voltage has been submitted vide letter PH8 - L&T - 4C - LTR - 09 -
1
0132, Dt: 10/02/2009.

2 The detailed justification for maximum possible Knee Point Voltage has already been submitted vide Letter No: PH8 - L&T - 4C - LTR - 09 - 0132, Dt: 10/02/2009 and the case of Distance Check is not considered here.

3 The final KPV is identical to 132 KV Inter Bus Transformer CT Core - 3 in EDC - 4 (Stage - I) and EDC - 5 respectively.

Page 3 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. MAIN BUS

CT PARAMETER -132kV CABLE FEEDER.(TYP.)

P1 MAIN-1 CABLE DIFF.+


BACK UP DIST. PRTN.
CORE -1 (87C/21C-1)
1500-800/1A
CL:PX
MAIN-2 CABLE DIFF.+
BACK UP DIST. PRTN.
CORE -2 (87C/21C-2)
1500-800/1A
CL:PX

BCU + METERING
CORE -3 [50/51/51N]
1500-800/1A
CL:5P20/1.0

B/B PRTN.- LOW Z.


[87B/50BF]
CORE -4
2500/1A
CL:PX

P2

132/11kV GIS PRIMARY


BARZAN CAMP-2 SUBSTATION
Page 4 of 101
Core – 1
C10CT1 TO C40CT1
(1500 – 800 / 1 A)

Page 5 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 13/02/2011

A. CT Sizing Calculation for 132kV Cable Feeders: C10 TO C40

CT Details:

Core details Device connected & Purpose


Core-1:C10CT1 to C40CT1 P545 - Line Differential with backup distance Protection - Main-I @ 1500A TAP

1.1 Core 1 Sizing (C10CT1 TO C40CT1)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : AREVA

b. Type : P545

c. Rated current IR : 1 A

d. Relay burden SR : 0.04 Ohm (Refer ANNEXURE - R1)

1.1.3 Details of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistnace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.1040 Ohm

1.1.4 Determination of CT parameters

a. Selected CT Ratio : 1500/1

b. Rated primary current (selected tap) Ipn : 1500 A

c. Rated secondary current Isn : 1 A

d. Class : PX

(As per Kahramaa's Protection and


o
e. Max. Sec. Winding Resistance at 75 C Rct : 5.3 Ohm Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35Ω/100A)
2
f. Relay burden Rrelay = [ SR / IR ] SR = Relay rated burden (0.04 VA)
IR = Relay rated current (1A)
= 0.04 / 1 2

Rrelay = 0.04 Ohm

g. Total secondary burden Rsb = Rct+R2lead+Rrelay = 6.4440 Ohm

1.1.5 Fault Current Particulars


Maximum primary fundmental frequency fault current for internal
a. Ikmax : 40000 A
close - in faults

b. Maximum value of through fault current Itmax : 37292 A (Annexure - F1)

c. Maximum primary phase fault current at Zone 1 reach point IFz1 : 38618 A (Annexure - F1)

d. X/R ratio Zone-1 reach fault X/R = 12.2 (Annexure - F1)

Page 6 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 13/02/2011

1.1.6 Differential Check

b. Minimum Knee Point Voltage Vk ≥ K * In * Rsb

K is determined as follows: (for two - ended current differential protection)


For Relays set at Is1 = 20%, Is1 = 2In, K1 = 30%, K2 = 150%,

When (If * X/R) ≤ 1000 * In (Refer ANNEXURE - R1)

K ≥ 40 + 0.07 * (If * X/R) (Condition - 1)

& K ≥ 65

When 1000 * In < (If * X/R) < 1600 * In (Condition - 2)

K ≥ 107

where, If = Maximum through fault current reflected on CT secondary side

If = Itmax / Ipn

= 37292 / 1500

= 24.86 A (Reflected on CT Secondary side)

So,

(24.86 X 12.2) ≤ (1000 X 1)

303.292 ≤ 1000 (Condition - 1satisfied)

(1000 X 1) < (24.86 X 12.2) < (1600 X 1)

1000 ≤ 303.292 < 1600

((Condition - 2 is not satisfied))

Therefore,

K ≥ 40 + [0.07 X (24.86 X 12.2)]

= 61.23

Now, = 65 (Minimum value allowed)

Vk ≥ 65 X 1 X 6.44

= 418.9

Vk = 419 V

Knee point voltage With Design margin(20%) (Vk) = 503 V

Case-2 (Distance check - Close in fault)

a. Hence, Dimensioning factor Kmax : 1.4 (Refer Annexure - R1)

b. Maximum secondary phase fault current Ifmax : 40000/1500


: 26.67

c. Minimum Knee Point Voltage Vk_min : Kmax*Ifmax(Close in.fault)*(Rct+R2lead+Rrelay)

= 1.4x26.67x(5.3+1.104+0.04)

= 240.576 V

= 241 V

d. Knee point voltage with design margin of 20% : 1.2*Vk_min

Vk_min = 1.2 x 241

= 289.2 V

Vk_min = 290 V

Page 7 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 13/02/2011

Case-3 (Distane check - Zone-1 reach fault)

a. Hence, Dimensioning factor Krpa : 0.6 (Refer Annexure - R1)

b. Maximum secondary phase fault current at Zone-1 reach point IfZ1 : 38618/1500
: 25.75

c. Minimum Knee Point Voltage Vk_min : Krpa*IfZ1(Zone-1 reach fault)*(1+X/R)*(Rct+R2lead+Rrelay)

= 0.6x25.73x(1+12.2)x(5.3+1.104+0.04)

= 1313.951 V

= 1314 V

d. Knee point voltage with design margin of 20% Vk_min : 1.2*Vk_min

= 1.2 x 1314

= 1576.8 V

Vk_min = 1580 V

Vk Maximum of differential and distance


Final Knee point voltage =
criteria

= 1580 V

1.1.7 CT parameters chosen for Core-1((C10CT1 to C40CT1)

Rated primary current Ipn : 1500 A


Rated secondary current Isn : 1A

Class : PX

Max. resistance of sec.winding at 75oC Rct < 5.3 Ohm

Final knee point voltage Vk > 1580 V

Note:

1) For final CT Summery details refer 800A Tap.

Page 8 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 13/02/2011

A. CT Sizing Calculation for 132kV Cable Feeders: C10 TO C40

CT Details:

Core details Device connected & Purpose


Core-1:C10CT1 to C40CT1 P545 - Line Differential with backup distance Protection - Main-I @ 800A TAP

1.1 Core 1 Sizing (C10CT1 to C40CT1)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : AREVA

b. Type : P545

c. Rated current IR : 1 A

d. Relay burden SR : 0.04 Ohm (Refer ANNEXURE - R1)

1.1.3 Details of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistnace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.1040 Ohm

1.1.4 Determination of CT parameters

a. Selected CT Ratio : 800/1

b. Rated primary current (selected tap) Ipn : 800 A

c. Rated secondary current Isn : 1 A

d. Class : PX

(As per Kahramaa's Protection and Ind.System


e. Max. Sec. Winding Resistance at 75o C Rct : 2.8 Ohm Volume 3 Rev.2sec.3.3.8. 2.1.22.11 -
0.35Ω/100A)
2
f. Relay burden Rrelay = [ SR / IR ] SR = Relay rated burden (0.04 VA)
IR = Relay rated current (1A)
= 0.04 / 1 2

Rrelay = 0.04 Ohm

g. Total secondary burden Rsb = Rct+R2lead+Rrelay = 3.9440 Ohm

1.1.5 Fault Current Particulars


Maximum primary fundmental frequency fault current for
a. Ikmax : 40000 A
internal close - in faults

b. Maximum value of through fault current Itmax : 37292 A (Annexure - F1)

c. Maximum secondary phase fault current at Zone 1 reach point IFz1 : 38618 A (Annexure - F1)

d. X/R ratio for through fault X/R = 12.2 (Annexure - F1)

Page 9 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 13/02/2011

1.1.6 Differential Check

b. Minimum Knee Point Voltage Vk ≥ K * In * Rsb (Refer ANNEXURE - R1)

K is determined as follows: (for two - ended current differential protection)


For Relays set at Is1 = 20%, Is1 = 2In, K1 = 30%, K2 = 150%,

When (If * X/R) ≤ 1000 * In (Refer ANNEXURE - R1)

K ≥ 40 + 0.07 * (If * X/R) (Condition - 1)

& K ≥ 65

When 1000 * In < (If * X/R) < 1600 * In (Condition - 2)

K = 107

where, If = Maximum through fault current reflected on CT secondary side

If = Itmax / Ipn

= 37292 / 800

= 46.62 A (Reflected on CT Secondary side)

So,

(46.62 X 12.197) ≤ (1000 X 1)

568.62414 ≤ 1000 (Condition - 1satisfied)

(1000 X 1) < (46.62 X 12.197) < (1600 X 1)

1000 ≤ 568.62414 < 1600

(Condition - 2 is not satisfied)

Therefore,

K ≥ 40 + [0.07 X (46.62 X 12.197)]

= 79.80 ( K > 65))

Vk ≥ 79.8 X 1 X 3.94

= 314.7289158

Vk = 315 V

Knee point voltage With Design margin(20%) (Vk) = 378 V

Case-2 (Distance check - Close in fault)

a. Hence, Dimensioning factor Kmax : 1.4 (Refer Annexure - R1)

b. Maximum secondary phase fault current Ifmax : 40000/800


: 50.00

c. Minimum Knee Point Voltage Vk_min : Kmax*Ifmax(Close in.fault)*(Rct+R2lead+Rrelay)

= 1.4x50x(2.8+1.104+0.04)

= 276.080 V

= 277 V

d. Knee point voltage with design margin of 20% : 1.2*Vk_min

Vk_min = 1.2 x 277

= 332.4 V

Vk_min = 333 V

Page 10 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 13/02/2011

Case-3 (Distane check - Zone-1 reach fault)

a. Hence, Dimensioning factor Krpa : 0.6 (Refer Annexure - R1)

b. Maximum secondary phase fault current at Zone-1 reach point IfZ1 : 38618/800
: 48.27

c. Minimum Knee Point Voltage Vk_min : Krpa*IfZ1(Close in.fault)*(1+X/R)*(Rct+R2lead+Rrelay)

= 0.6x48.2725x(1+12.197)x(2.8+1.104+0.04)

= 1507.520 V

= 1508 V

d. Knee point voltage with design margin of 20% Vk_min : 1.2*Vk_min

= 1.2 x 1508

= 1809.6 V

Vk_min = 1810 V

Vk Maximum of differential and distance


Final Knee point voltage =
criteria

= 1810 V

1.1.7 CT parameters chosen for Core-1(C10CT1 to C40CT1)

Rated
R t d primary
i currentt Ipn : 800 A 1500 A
Rated secondary current Isn : 1A 1A
Class : PX PX

Max. resistance of sec.winding at 75oC Rct < 2.8 Ohm 5.3 Ohm
Final knee point voltage Vk > 1810 V 1580 V

Page 11 of 101
Core – 2
C10CT2 TO C40CT2
(1500 – 800 / 1 A)

Page 12 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. X


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

A. CT Sizing Calculation for 132kV Cable Feeders: C10 to C40

1 CT Details

Core details Device connected & Purpose


Core-2:C10CT2 to C40CT2 7SD532 - Line Differential Protection with backup distance protection - Main2 @ 1500A TAP

1.1 Core 2 Sizing (C10CT2 TO C40CT2)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : Siemens

b. Type : 7SD532

c. Rated current IR : 1 A

d. Relay burden R relay : [ Sr / Ir2 ] (Refer Annexure - R2)


2
: 0.05 / 1 Sr = Relay rated burden (0.05 VA)
: 0.05 Ohms Ir = Relay rated current (1A)
The burden of 7SD532 a current input channel Rrelay : 0.05 ohm

1.1.3 Detials of Lead from CT to Relay

a. Sizeof the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)

d. Oneway length of the lead L : 100 m

f. Two-way lead resistance R2lead = 2*L*Rcable/1000

= 2*100*5.52/1000
R2lead = 1.1040 Ohm
1.1.4 Determination CT parameters

a. Selected CT Ratio : 1500/1 A

b. Rated primary current (selected tap) Ipn = 1500 A

c. Rated secondary current Isn = 1 A

d. Class = PX
(As per Kahramaa's Protection and Ind.System
e. Max. Sec. Winding Resistance at 75o C Rct = 5.3 Ohm
Volume 3 Rev.2sec.3.3.8. 2.1.22.11 - 0.35Ω/100A)

f. Maximum primary fundamental frequency Ikmax = 40000 A (Ikmax = Isccmax(ext.fault)=Isccmax(closein fault))


fault current for internal close-in faults(A) (Refer Annexure-F1)

g. Maximum primary fundamental frequency Ikmax1 = 38602 A (Refer Annexure-F1 )


fault current for Zone-1 end fault (Iz1 end
fault)

Page 13 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. X


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

Case-1 (Differential check)

a. Transient dimensioning factor Ktd : 1.2 (Refer Annexure-R2)

b. Connected resistive burden to CT Rb ' : R2lead+Rrelay

= 1.1540

Rb ' = 1.1540 Ohm

c. Minimum Knee Point Voltage Vk_min : Ktd*Iscc max(ext.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 1.2 x 40000 x (5.3 + 1.154) x [ 1 / (1.3 x 1500) ]

= 158.87 V

= 159 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

= 191

Ek = 195 V

Case-2 (Distance check - Close in fault)

a. Time constant for close-in fault TCF : 32.71 msec (Refer Annexure - F1 )

b. Hence, Transient dimensioning factor Ktd(a) : 2 (Refer Annexure - R2)

c. Minimum Knee Point Voltage Vk_min : Ktd(a)*Iscc max(Close in.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 2 x 40000 x (5.3 + 1.154) x [ 1 / (1.3 x 1500) ]

= 264.779 V

= 270 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

= 1.2 x 270

= 324.0 V

Ek = 325 V

Page 14 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. X


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

Case-3 (Distane check - Zone-1 end fault)

a. Time constant for Zone-1 end fault Tz11ph : 28.28 msec (Refer Annexure - F1)

b. Transient dimensioning factor Ktd(b) : 5 (Refer Annexure - R2)

c. Minimum Knee Point Voltage Vk_min : Ktd(b)*Iscc max(Z1end.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 5 x 38602 x (5.3 + 1.154) x [ 1 / (1.3 x 1500) ]

= 638.814 V

= 640 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

1.2 x 640

= 768.0 V

Ek = 770 V

Knee point voltage = 770 V (Maximum of differential and distance criteria)

1.1.6 Note:

1 For summary details of CT parameters of core-I refer 800A tap.

Page 15 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

A. CT Sizing Calculation for 132kV Cable Feeders: C10 to C40

1 CT Details

Core details Device connected & Purpose


Core-2:C10CT2 to C40CT2 7SD532 - Line Differential Protection with backup distance protection - Main2 @ 800A TAP

1.1 Core 1 Sizing (C10CT2 TO C40CT2)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : Siemens

b. Type : 7SD532

c. Rated current IR : 1 A

2
d. Relay burden R relay : [ SR / IR ] (Refer Annexure - R2)

: 0.05 / 1 2 SR = Relay rated burden (0.05 VA)

: 0.05 Ohms IR = Relay rated current (1A)

The burden of 7SD532 a current input channel Rrelay : 0.05 ohm

1.1.3 Detials of Lead from CT to Relay

a. Sizeof the calble : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)

d. Oneway length of the lead L : 100 m

f. Two-way lead resistnace R2lead = 2*L*Rcable/1000

(with 20% uprating) = 2*100*5.52/1000


R2lead = 1.1040 Ohm
1.1.4 Determination CT parameters

a. Selected CT Ratio : 800/1 A

b. Rated primary current (selected tap) Ipn = 800 A

c. Rated secondary current Isn = 1 A


d. Class = PX

o (As per Kahramaa's Protection and Ind.System


e. Max. Sec. Winding Resistance at 75 C Rct = 2.8 Ohm
Volume 3 Rev.2sec.3.3.8. 2.1.22.11 - 0.35Ω/100A)

f. Maximum primary fundamental frequency Ikmax = 40000 A (Ikmax = Isccmax(ext.fault)=Isccmax(closein fault))


fault current for internal close-in faults(A) (Refer Annexure-F1)

g. Maximum primary fundamental frequency Ikmax1 = 38602 A (Ikmax = Isccmax(zone1 reach))


fault current for Zone-1 end fault (Iz1 end (Refer Annexure-F1)
fault)

Page 16 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

Case-1 (Differential check)

a. Transient dimensioning factor Ktd : 1.2 (Refer Annexure-R2)

b. Connected resistive burden to CT Rb ' : R2lead+Rrelay

= 1.1540

Rb ' = 1.1540 Ohm

c. Minimum Knee Point Voltage Vk_min : Ktd*Iscc max(ext.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 1.2 x 40000 x (2.8 + 1.154) x [ 1 / (1.3 x 800) ]

= 182.49 V

= 183 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

= 220

Ek = 220 V

Case-2 (Distance check - Close in fault)

a. Time constant for close-in fault TCF : 32.71 msec (Refer Annexure - F1)

b. Hence, Transient dimensioning factor Ktd(a) : 2 (Refer Annexure-R2)

c. Minimum Knee Point Voltage Vk_min : Ktd(a)*Iscc max(Close in.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 2 x 40000 x (2.8 + 1.154) x [ 1 / (1.3 x 800) ]

= 304.154 V

= 310 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

= 1.2 x 310

= 372.0 V

Ek = 380 V

Page 17 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

Case-3 (Distane check - Zone-1 end fault)

a. Time constant for Zone-1 end fault Tz11ph : 28.28 msec (Refer Annexure - F1 )

b. Transient dimensioning factor Ktd(b) : 5 (Refer Annexure-R2)

c. Minimum Knee Point Voltage Vk_min : Ktd(b)*Iscc max(Z1end.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 5 x 38602 x (2.8 + 1.154) x [ 1 / (1.3 x 800) ]

= 733.809 V

= 734 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

1.2 x 734

= 880.8 V

Ek = 890 V

Maximum of differential and distance


Knee point voltage =
criteria
= 890 V

1.1.6 CT parameters chosen for Core-2 (applicable for C10CT2 TO C40CT2)

Rated primary current Ipn : 800 A 1500 A

Rated secondary current Isn : 1A 1A


Class : PX PX
Rated knee point e.m.f (Min Required) Ek > 890 V 770 V

Max. resistance of sec.winding at 75oC Rct < 2.8 Ohm 5.3 Ohm

Page 18 of 101
Core – 3
C10CT3 TO C40CT3
(1500 – 800 / 1 A)

Page 19 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 10/11/2011

A. CT Sizing Calculation for 132kV Cable Feder: C10 TO C40

1 CT Details

Core details Device connected & Purpose


Core-3:C10CT3 TO C40CT3 C264 - Bay control Unit@ 1500A TAP

1.2 Core 3 Sizing

1.2.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.2.2 Device connected to this core

a. Make : AREVA

b. Type : C264

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ S R / I R2 ] (Refer Annexure - R7)


: 0.1 / 1 2 SR = Relay rated burden (0.1 VA)

: 0.1 Ω IR = Relay rated current (1A)


Burden of IED for measurement Rrelay : 0.1 Ω

y
1.2.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.104 Ω

1.2.4 CT parameters

a. Selected CT Ratio : 1500/1

b. Rated primary current (selected tap) Ipn : 1500 A

c. Rated secondary current Isn : 1 A

d. Class : 5P20/1.0
e. Rated Accuracy Limiting Factor ALFr : 20
(As per Kahramaa's Protection and
o
f. Max. Sec. Winding Resistance at 75 C Rct : 5.3 Ω Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35Ω/100A)
g. Ammeter Resistance RA : 1.5 Ω (Since it is 1.5 VA)

1.2.6 VA Burden and Accuracy Class of CT

Sb,cal = (R2lead +Rrelay + RA )x IR^2


= (1.104 + 0.1 + 1.5) X 1^2
= 2.704 VA
Sb,req  Sb,cal
 2.704 VA

= 15.00 (Adopted) (As Kahrama's per protection&indication technical spec.


of sec.3.3.8.Rev.02. 2.1.23.3)

Page 20 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 10/11/2011

1.2.7 Adequacy Checking of 5P20

The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in
its windings at rated burden.

Accuracy Limit at Rated Burden ALFr = 20


Rated Burden of CT VAr = 15.00 VA
Actual Burden VAa = 2.704 VA

ALF Actual (ALFa) = ALFr* (VAr+Rct) / (VAa+Rct)


= 20 X (15 + 5.3) / (2.704 + 5.3)
= 50.7246
ALF Actual (ALFa) = 51 (Refer Note - 3)

For summary Details refer 800 A Tap

Note

1 The Plug setting is considered as 100% In.


2 The highest plug setting is considered 32 times of In.
Since the 'Actual ALF' is greater than required ALF, the relay will pickup
3
positively.

Page 21 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. X


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 10/11/2011

A. CT Sizing Calculation for 132kV Cable Feder: C10 TO C40

1 CT Details

Core details Device connected & Purpose


Core-3:C10CT3 TO C40CT3 C264 - Bay control Unit@ 800A TAP

1.2 Core 3 Sizing

1.2.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.2.2 Device connected to this core

a. Make : AREVA

b. Type : C264

c. Rated current IR : 1 A

2
d. Relay burden Rrelay : [ SR / IR ] (Refer Annexure - R7)
: 0.15 / 1 2 SR = Relay rated burden (0.15 VA)

: 0.15 Ω IR = Relay rated current (1A)


Burden of IED for measurement Rrelay : 0.15 Ω

1.2.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.104 Ω

1.2.4 CT parameters

a. Selected CT Ratio : 800/1

b. Rated primary current (selected tap) Ipn : 800 A

c. Rated secondary current Isn : 1 A

d. Class : 5P20/1.0

e. Rated Accuracy Limiting Factor ALFr : 20


(As per Kahramaa's Protection and
o
f. Max. Sec. Winding Resistance at 75 C Rct : 2.8 Ω Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35Ω/100A)
g. Ammeter Resistance RA : 1.5 Ω (Since it is 1.5 VA)

Page 22 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. X


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 10/11/2011

1.2.5 VA Burden and Accuracy Class of CT

Sb,cal = (R2lead + Rrelay + RA ) x IR^2


= (1.104+0.15 +1.5) X 1^2
= 2.754 VA
Sb,req  Sb,cal
 2.754 VA
VA = 15.00 (Adopted) (As per technical spec. for protection&indication
sec.3.3.8.Rev.02. 2.1.23.3)

1.2.6 Adequacy Checking of 5P20

The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in
its windings at rated burden.

Accuracy Limit at Rated Burden ALFr = 20


Rated Burden of CT VAr = 15.00 VA
Actual Burden VAa = 2.754 VA

ALF Actual (ALFa) = ALFr* (VAr+Rct) / (VAa+Rct)


= 20 X (15 + 2.8) / (2.754 + 2.8)
= 64.0979
ALF Actual (ALFa) = 65 (Refer Note - 3)

1.2.7 Resulting CT Characteristics


Rated Short time Thermal
Rated Secondary Current
Rated Primary Current at

Accuracy Class at rated


Approved Tap (I pn)

Rated Frequency

Current(2.5*Isc)
Rated Dynamic
Rated Burden
burden

current
(I n)

(A) (A) (–) (VA) (Hz) (kA-s) (kA)


800 1 5P20/1.0 15.0 50 40.0 -1 100
1500 1 5P20/1.0 28.0 50 40.0 -1 100

1.2.8 CT Particulars for Core-III ( applicable for C10CT3 TO C40CT3)

Rated primary current Ipn : 800 1500


Rated secondary current Isn : 1A 1A
Accuracy Class : 5P20/1.0 5P20/1.0
Rated Burden VA : 15 28
o
Max. resistance of sec.winding at 75 C Rct < 2.8 Ohm 5.3 Ohm

Note

1 The Plug setting is considered as 100% In.

2 The highest plug setting is considered 32 times of In.

Since the 'Actual ALF' is greater than Required ALF, the relay will pickup
3
positively.

Page 23 of 101
Core – 4
C10CT4 TO C40CT4
(2500 / 1 A)

Page 24 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev.0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

A. CT Sizing Calculation for 132kV Cable Feeders: C10 TO C40

1 CT Details

Core details Device connected & Purpose


Core-4:C10CT4 TO C40CT4 P743 - Busbar Protection @ 2500A TAP

1.4 Core 4 Sizing

1.4.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 KA

1.4.2 Relay connected to this core

a. Make : AREVA

b. Type : P743

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R3)


2 SR = Relay rated burden (0.04 VA)
: 0.04 / 1

: 0.04 Ω IR = Relay rated current (1A)


Relay burden Rrelay : 0.04 Ohm

1.4.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistnace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.1040 Ohm

1.4.4 CT parameters

a. Selected CT Ratio : 2500/1 A

b. Rated primary current Ipn : 2500 A

c. Rated secondary current Isn : 1 A

d. Class : PX

(As per Kahramaa's Protection and Ind.System


e. Max. Sec. Winding Resistance at 75o C Rct : 8.8 Ω
Volume 3 Rev.2sec.3.3.8. 2.1.22.11-0.35Ω/100A)

Page 25 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev.0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011

f. Minimum Knee Point Voltage Vk_min ≥ 0.5 X Ifmax X (Rct + R2lead+Rrelay) Case - I (Refer ANNEXURE - R3)

Where,
Maximum secondary fault current Ifmax = If / Ipn
= 40000 / 2500
= 16 A

Therefore,

Vk_min = 0.5 X 16 X (8.8 + 1.104+0.04)


= 79.55 V

Now, with 20% margin

Vk_min = 1.2 X 79.55

= 95.462 V
= 95 V

g. Maximum Knee Point Voltage Vk_min ≥ Ifmax int X (Rct + R2lead +Rrelay) Case - II (Refer ANNEXURE - R3)

Where,
Maximum secondary contribution from a Ifmax int = If / Ipn
feeder to an internal fault
= 40000 / 2500
= 16 A

Therefore,

Vk_min = 16 X (8.8 + 1.104+0.04)


= 159.10 V

Now, with 20% margin

Vk_min = 1.2 X 159.1

= 190.925 V
= 191 V

Knee point voltage selected = 191 V (Maximum of case - I & case - II)

1.4.5 CT Particulars for Core-4 ( applicable for C10CT4 TO C40CT4)

Rated primary current Ipn : 2500 A


Rated secondary current Isn : 1 A
Class : PX
Rated knee point e.m.f Ek > 191 V
o
Max. resistance of sec.winding at 75 C Rct < 8.8 Ohm

Page 26 of 101
CT Sizing Calculation for
132/11kV Interbus Tx. feeder

Page 27 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE

CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV (32/40 MVA) Inter Bus Transformer - 132
TITLE : 25/10/11
KV side

SUMMARY

Sl.No. Description Page No.


1 Summary Chart 29
2 Single Line Diagram 30
Core - 1

3 CT Sizing Calculation 32
Core - 2

4 CT Sizing Calculation 37
Core - 3

5 CT Sizing Calculation 42
Core - 4

6 CT Sizing Calculation 49

Page 28 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of Current Transformer Parameter for 132kV Interbus Transformer Feeder- BC-2 Substation (Adopted parameters)

Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 9/11/2011 Rev: A

Itherm-cont
Class of Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden (Rated Rated Short
Core Ratio accuracy Instrument short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - continuous time thermal Remarks
Nos proposed as per IEC security current = 2.5
(Ohms) Required Adopted (RMS value) Adopted thermal current (Ith)
60044-1 factor ISF x Ith (KA)
current in %)

C 132kV Transformer Feeder CT

400 A 4 195 240 20 mA @ Vk / 2 - - 120% 40kA, 1 sec 100


132kV Main-1 Transformer differential
1 Core-1 400-200/1A PX
protection (87T-1) - (P643)
200 A 2 120 120 40 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

400 A 4 45 110 20 mA @ Vk / 2 - - 120% 40kA, 1 sec 100


132kV Main-2
Main 2 Transformer differential
2 Core-2 400-200/1A PX
protection - (7UT613)
200 A 2 55 55 40 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

400 A 1.4 - - - 30 - 120% 40kA, 1 sec 100


3 O/C & E/F + BCU + Metering (C264) Core-3 400-200/1A 5P20/1.0
200 A 0.7 - - - 15 - 120% 40kA, 1 sec 100

4 Busbar Protection (87BB/50BF) - (P743) Core-4 2500/1A PX 2500 A 8.8 191 200 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

Page 29 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. MAIN BUS

CT PARAMETER -132/11kV
INTER BUS TRANSFORMER FEEDER.(TYP.)

P1 MAIN-1 TRANSFORMER
CORE -1 DIFF. PRTN.(87T-1)
400-200/1A
CL:PX

MAIN-2 TRANSFORMER
CORE -2 DIFF. PRTN.(87T-2)
400-200/1A
CL:PX

O/C & E/F + BCU +


CORE -3 METERING[50/51/51N]
400-200/1A
CL:5P20/1.0

B/B PRTN.- LOW Z.


CORE -4
2500/1A
[87B/50BF]
CL:PX

M P2

32/40 MVA
132/11kV
%Z=13.6
@ ONAN

TO 11kV INCOMER 132/11kV GIS PRIMARY


BARZAN CAMP-2 SUBSTATION
Page 30 of 101
Core – 1
C11CT1 & C21CT1
(400 – 200 / 1 A)

Page 31 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. A


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS TRANFORMER -
TITLE 11/9/2011
132KV SIDE

CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-1:C11CT1 & C21CT1 P643 - Tx. Differential Protection-Main1 @ 400A TAP

1.1 Core 1 Sizing

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current (HV Side of Trafo.) If : 40 kA

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 400/1

b. Rated primary current (selected tap) Ipn : 400 A

c. Rated secondary current Isn : 1 A

d. Class : PX

o
e. Max. Sec. Winding Resistance at 75 C Rct : 4.0 Ohm (As per switchgear manufacturer feasibility)

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on Secondary side = (MVA Rating X 1000) / (1.732 X Vs X Min. Tap) (Refer Anne. - 7)

= (40 X 1000) / (1.732 X 132 X 0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : AREVA

b. Type : P643

c. Rated current IR : 1 A

d. Relay burden Rrelay = [ SR / IR2 ] SR = Relay rated burden (0.2 VA)


P643 = 0.2 VA IR = Relay rated current (1A)
= 0.2 / 1 2
Relay burden Rrelay : 0.2 Ohm (Refer Annexure - R4)
(P643 and P141 Relays are connected in series)
1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Sizeof the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km

Page 32 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. A


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS TRANFORMER -
TITLE 11/9/2011
132KV SIDE

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 1.0 X 2 X 100 X 5.52/1000

R2lead = 1.1040 ohms

f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure-F6)
g. X/R ratio for 3phase through fault X/R = 37.76

1.1.4.2 Determination minimum knee point voltage

Vk ≥ K X In (Rct + Rrelay + R2lead) (Refer Annexure- R4 )

K is determined as follows:

When In < Isf ≤ 40In, & 5 ≤ X/R < 120 (Refer Annexure- R4 )

K = 30 (Condition - A)

where, Isf = maximum through fault current reflected on CT secondary side

Isf = 1203 / 400

= 3.0075 A

Now
Now, Vk = (30 X 1(4 + 0
0.2
2+1
1.104)
104)

= 159.12

Knee point Voltage = 1.2 X 159.12

= 190.944

= 195 V

1.1.5 CT Particulars for Core-I(400/1A)

Rated primary current Ipn : 400 A


Rated secondary current Isn : 1 A
Class : PX
Rated knee point e.m.f Ek > 195 V
Max. resistance of sec.winding at 75oC Rct < 4 Ohm

NOTE:
1) For overall CT perticulers refer 300 Tap.

Page 33 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. A


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS TRANFORMER -
TITLE 11/9/2011
132KV SIDE

CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-1:C11CT1 & C21CT1 P643 - Tx. Differential Protection-Main1 @ 200A TAP

1.1 Core 1 Sizing

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current (HV Side of Trafo.) If : 40 kA

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 200/1

b. Rated primary current (selected tap) Ipn : 200 A

c. Rated secondary current Isn : 1 A

d. Class : PX

o
e. Max. Sec. Winding Resistance at 75 C Rct : 2.0 Ohm (As per switchgear manufacturer feasibility)

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on Secondary side = (MVA Rating X 1000) / (1.732 X Vs X Min. Tap) (Refer Anne. - 7)

= (40 X 1000) / (1.732 X 132 X 0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : AREVA

b. Type : P643

c. Rated current IR : 1 A

d. Relay burden Rrelay = [ SR / IR2 ] SR = Relay rated burden (0.2 VA)


P643 = 0.2 VA IR = Relay rated current (1A)
= 0.2 / 1 2
Relay burden Rrelay = 0.2 Ohm (Refer Annexure - R4)
(P643 and P141 Relays are connected in series)
1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Sizeof the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km

Page 34 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. A


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS TRANFORMER -
TITLE 11/9/2011
132KV SIDE

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 1.0 X 2 X 100 X 5.52/1000

R2lead = 1.1040 ohms

f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure-F6)
g. X/R ratio for 3phase through fault X/R = 37.76 (Refer Annexure-F6)

1.1.4.2 Determination minimum knee point voltage

Vk ≥ K X In (Rct + Rrelay + R2lead) (Refer Annexure- R4 )

K is determined as follows:

When In < Isf ≤ 40In, & 5 ≤ X/R < 120 (Refer Annexure- R4 )

K = 30 (Condition - A)

where, Isf = maximum through fault current reflected on CT secondary side

Isf = 1203 / 200

= 6.015 A

Now
Now, Vk = (30 X 1(2 + 0
0.2
2+1
1.104)
104)

= 99.12

Knee point Voltage = 1.2 X 99.12

= 118.944

= 120 V

1.1.5 Overall CT Particulars

Rated primary current Ipn : 200 400 A


Rated secondary current Isn : 1 A A
Class : PX PX
Rated knee point e.m.f Ek > 120 195 V
Max. resistance of sec.winding at 75oC Rct < 2.0 4 Ohm

Page 35 of 101
Core – 2
C11CT2 & C21CT2
(400 – 200 / 1 A)

Page 36 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011

C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21

1 CT Details on HV side(132kV) of Transformer

Core details Device connected & Purpose


Core-2:C11 & C21CT2 7UT613 - MAIN-2 Transformer Differential Protection @ 400A TAP

1.1 Core 1 Sizing (C11CT2 & C41CT2)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

System frequency fn : 50 Hz
b.

c. Maximum fault current (HV Side of Trafo.) If : 40 kA

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 400/1

b. Rated primary current (selected tap) Ipn : 400 A

c. Rated secondary current Isn : 1 A

d. Class : PX

e. Max. Sec. Winding Resistance at 75o C Rct : 4 Ohm (As per switchgear manufacturer
feasibility)

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on primary side = (MVA Rating X 1000) / (1.732 X Vs X 0.85) (Refer Anne. - 7)

= (40 X 1000) / (1.732 X 132X0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : SIEMENS

b. Type : 7UT613 - Transformer Differential Protection

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R5 )


7UT613 = 0.05 VA : (0.05) / 1 2 SR = Relay rated burden (0.05 VA)

: 0.05 ohms IR = Relay rated current (1A)


Relay burden Rrelay : 0.05 Ohm

1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Sizeof the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

Page 37 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 2 X 100 X 5.52/1000

R2lead = 1.1040 ohms

Maximum external fault current on CT


f. Iscc(ext.fault) = 1203.00 A (Refer ANNEXURE - F6)
primary side

1.1.4.2 Determination minimum knee point voltage

Vk ≥ Ktd * (Iscc max(ext fault)/1.3 * Ipn)*(Rct+R'b)*Isn

Transient dimensioning factor Ktd = 3 (Refer ANNEXURE - R5)

R'b = R2lead + Rrelay

= 1.104+0.05

= 1.154

Vk = 3X(1203/400X1.3)X(4+1.154)X1)

= 35.77

Knee point Voltage with 20% margin = 1.2 X 499

= 42.92489

= 45 V

1.1.5 Conclusion:

1. Since Transformer differential protection and REF relays are conneted in series, the highest Vk is chosen as the required Knee point voltage satisfying
bothe the protections.

2. For final values, refer the summary given at 200 A TAP

Page 38 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011

C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21.

1 CT Details on HV side(132kV) of Transformer

Core details Device connected & Purpose


Core-2:C11 & C21CT2 7UT613 - MAIN-2 Transformer Differential Protection @ 200A TAP

1.1 Core 1 Sizing (C11CT2 & C41CT2)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

System frequency fn : 50 Hz
b.

c. Maximum fault current (HV Side of Trafo.) If : 40 kA

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 200/1

b. Rated primary current (selected tap) Ipn : 200 A

c. Rated secondary current Isn : 1 A

d. Class : PX

(As per switchgear manufacturer


e. Max. Sec. Winding Resistance at 75o C Rct : 2 Ohm
feasibility)

1.1.2.1
1 1 2 1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on primary side = (MVA Rating X 1000) / (1.732 X Vs X min. Tap.) (Refer Anne. - 7)

= (40 X 1000) / (1.732 X 132X0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : SIEMENS

b. Type : 7UT613 - Transformer Differential Protection

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R5 )


7UT613 = 0.05 VA : (0.05) / 1 2 SR = Relay rated burden (0.05 VA)

: 0.05 ohms IR = Relay rated current (1A)


Relay burden Rrelay : 0.05 Ohm

1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Sizeof the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

Page 39 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 2 X 100 X 5.52/1000

R2lead = 1.1040 ohms

Maximum external fault current on CT


f. Iscc(ext.fault) = 1203.00 A (Refer ANNEXURE - F6)
primary side

1.1.4.2 Determination minimum knee point voltage

Vk ≥ Ktd * (Iscc max(ext fault)/1.3 * Ipn)*(Rct+R'b)*Isn

Transient dimensioning factor Ktd = 3 (Refer ANNEXURE - R5)

R'b = R2lead + Rrelay

= 1.104+0.05

= 1.154

Vk = 3X(1203/200X1.3)X(2+1.154)X1)

= 43.78

Knee point Voltage with 20% margin = 1.2 X 43.77995

= 52.5

= 55 V

1.1.5 CT Particulars for Core-II ( Applicable for C11CT2 & C21CT2)

Rated primary current Ipn : 400 A 200 A

Rated secondary current Isn : 1A 1A

Class : PX PX
Rated Knee point e.m.f based on Main-2 Tfr Diff.
Vk > 45 V 55 V
protection
Max. resistance of sec.winding at 75oC Rct < 4 Ohm 2 Ohm

1.1.5 Conclusion:

1. Since Transformer differential protection and REF relays are conneted in series, the highest Vk is chosen as the required Knee point voltage satisfying
both the protections.

Page 40 of 101
Core – 3
C11CT3 & C21CT3
(400 – 200 / 1 A)

Page 41 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV INTERBUS TFR FEEDER 09/11/2011

C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-3:C11CT3 & C21CT3 O/C & E/F +BCU + Metering - @ 400A TAP

1.2 Core 2 Sizing

1.2.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.2.2 Device connected to this core

a. Make : AREVA

b. Type : P141 + C264

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R6 & R7)


P141 = 0.04A : 0.19 / 1 2 SR = Relay rated burden (0.15 + 0.04 VA)
C264 = 0.15 VA : 0.19 Ω IR = Relay rated current (1A)
Burden of IED for measurement Rrelay : 0.19 Ω

1.2.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.104 Ω

1.2.4 CT parameters

a. Selected CT Ratio : 400/1

b. Rated primary current (selected tap) Ipn : 400 A

c. Rated secondary current Isn : 1 A

d. Class : 5P20/1.0

e. Rated Accuracy Limiting Factor ALFr : 20


(As per Kahramaa's Protection and Ind.System
f. Max. Sec. Winding Resistance at 75o C Rct : 1.4 Ω Volume 3 Rev.2sec.3.3.8. 2.1.22.11 - 0.35Ω 
/100A)
g. Ammeter Resistance RA : 1.5 Ω (Since it is 1.5 VA)

Page 42 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV INTERBUS TFR FEEDER 09/11/2011

1.2.5 Formulae and Requirements:

Non-directional/Directional Time-delayed Overcurrent

Vk  [Ifp/2] × (Rct+R2lead+Rrelay+RA ) (Refer ANNEXURE - R6)

Where,
Ifp  Maximum Prospective Secondary Phase fault current (or) 31 X I> setting (whichever is lowest)

Requirement 1:
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)

(Ipn = Rated CT Primary Current)

= 40000 / 400
= 100 A

Requirement 2:
(I> setting is 1A which is equivalent to 2500 A in CT
31 X I> setting = 31 X 1
primary)
= 31 A

Ifp (chosen) = 31.0 (whichever option is lower)

Therefore,
Vk  31/2 X (1.4 + 1.104 + 0.19 + 1.5 ) (Refer Note - 2)

 65.01 V

 70 V
 1.2 X 70

= 84 V (with 20% margin)

Instantaneous phase over current

Vk  Isp × (Rct+R2lead+Rrelay+RA) (Refer ANNEXURE - R6)

Where,
Isp  Maximum Prospective Secondary Phase fault current

Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)

(Ipn = Rated CT Primary Current)

= 40000 / 400
Isp = 100 A
Isp (chosen) = 32 (Refer Note - 2)
Therefore,
Vk  32 X (1.4 + 1.104 + 0.19 + 1.5 )
 134.21 V
 135 V
 1.2 X 135
= 162 V (with 20% margin)

Knee Point voltage (Considered) = 162 V

Estimation of VA

Vk  (VAr* ALFr / Isn) +(ALFr*Isn*Rct) (Refer ANNEXURE - 2)

162.00  (VA × 20.0/1.0)+( 20.00 x 1.00 x 1.40)

VA = 6.70

VA = 15.00 (Adopted) (As per Kahramaa's Prote. and Ind.System


Volume 3 Rev.2sec.3.3.8. 2.1.23.3)

Page 43 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV INTERBUS TFR FEEDER 09/11/2011

1.2.6 VA Burden and Accuracy Class of CT

Sb,cal = (Rrelay + R2lead + RA ) x IR2


= (0.19 + 1.104 + 1.5 ) X 1^2
= 2.794 VA
Sb,req  Sb,cal
 2.794 VA

1.2.7 Adequacy Checking of 5P20

The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in its
windings at rated burden.

Accuracy Limit at Rated Burden ALFr = 20


Rated Burden of CT VAr = 15.00 VA
Actual Burden VAa = 2.794 VA

ALF Actual (ALFa) = ALFr* (VAr+Rct) / (VAa+Rct)


= 20 X (15 + 1.4) / (2.794 + 1.4)
= 78.207
ALF Actual (ALFa) = 79 (Refer Note - 3)

1.2.8 Resulting CT Characteristics


Rated Short time Thermal
Rated Secondary Current
Rated Primary Current at

Accuracy Class at rated


Approved Tap (I pn)

Rated Frequency

Current(2.5*Isc)
Rated Dynamic
Rated Burden

current
burden
(I n)

(A) (A) (–) (VA) (Hz) (kA-s) (kA)


400 1 5P20/1.0 15.0 50 40 -1 100

1.2.9 CT Particulars for Core-II ( applicable for C11CT3 & C41CT3)

Rated primary current Ipn : 400

Rated secondary current Isn : 1A


Accuracy Class : 5P20/1.0
Rated knee point e.m.f (Required) Vk > 162 V

Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 1.4 Ohm

Note

1 The Plug setting is considered as 100% In.


As per Kahramaa's Protection and Ind.System Volume 3 Rev.2 sec.3.3.8. 2.1.23.09, The highest plug setting is
2
considered as 32 times of In.
Since the required ALF is greater than the overload capacity of the connected devices. Further considering the Hi- set point of
3
relay is 32 X In.The proposed ALF is sufficient to meet the protection.

Page 44 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV INTERBUS TFR FEEDER 09/11/2011

C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-3:C11CT3 & C21CT3 O/C & E/F + BCU + Metering - @ 200A TAP

1.2 Core 2 Sizing

1.2.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.2.2 Device connected to this core

a. Make : AREVA

b. Type : P141 + C264

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R6 & R7)


P1414 = 0.04A : 0.19 / 1 2 SR = Relay rated burden (0.15 + 0.04 VA)
C264 = 0.15 VA : 0.19 Ω IR = Relay rated current (1A)
Burden of IED for measurement Rrelay : 0.19 Ω

1.2.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.104 Ω

1.2.4 CT parameters

a. Selected CT Ratio : 200/1

b. Rated primary current (selected tap) Ipn : 200 A

c. Rated secondary current Isn : 1 A

d. Class : 5P20/1.0

e. Rated Accuracy Limiting Factor ALFr : 20


(As per Kahramaa's Protection and Ind.System
f. Max. Sec. Winding Resistance at 75o C Rct : 0.7 Ω Volume 3 Rev.2sec.3.3.8. 2.1.22.11 - 0.35Ω
/100A)
g. Ammeter Resistance RA : 1.5 Ω (Since it is 1.5 VA)

Page 45 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV INTERBUS TFR FEEDER 09/11/2011

1.2.5 Formulae and Requirements:

Non-directional/Directional Time-delayed Overcurrent

Vk  [Ifp/2] × (Rct+R2lead+Rrelay+RA ) (Refer ANNEXURE - R6)

Where,
Ifp  Maximum Prospective Secondary Phase fault current (or) 32 X I> setting (whichever is lowest)

Requirement 1:
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)

(Ipn = Rated CT Primary Current)

= 40000 / 200
= 200 A

Requirement 2:
(I> setting is 1A which is equivalent to 2500 A in CT
31 X I> setting = 31 X 1
primary)
= 31 A

Ifp (chosen) = 31.0 (whichever option is lower)

Therefore,
Vk  [31/2] X (0.7 + 1.104 + 0.19 + 1.5 ) (Refer Note - 2)

 54.16 V

 55 V
 1.2 X 55

= 66 V (with 20% margin)

Instantaneous phase over current

Vk  Isp × (Rct+R2lead+Rrelay+RA) (Refer ANNEXURE - R5)

Where,
Isp  Maximum Prospective Secondary Phase fault current

Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)

(Ipn = Rated CT Primary Current)

= 40000 / 200
Isp = 200 A
Isp (chosen) = 32 (Refer Note - 2)
Therefore,
Vk  32 X (0.7 + 1.104 + 0.19 + 1.5 )
 111.81 V
 115 V
 1.2 X 115
= 138 V (with 20% margin)

Knee Point voltage (Considered) = 138 V

Estimation of VA

Vk  (VAr* ALFr / Isn) +(ALFr*Isn*Rct) (Refer ANNEXURE - 2)

138.00  (VA × 20.0/1.0)+( 20.00 x 1.00 x 0.70)

VA = 6.20

VA = 15.00 (Adopted) (As per Kahramaa's Prote. and Ind.System


Volume 3 Rev.2sec.3.3.8. 2.1.23.3)

Page 46 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV INTERBUS TFR FEEDER 09/11/2011

1.2.6 VA Burden and Accuracy Class of CT

Sb,cal = (Rrelay + R2lead + RA ) x IR2


= (0.19 + 1.104 + 1.5 ) X 1^2
= 2.794 VA
Sb,req  Sb,cal
 2.794 VA

1.2.7 Adequacy Checking of 5P20

The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in its
windings at rated burden.

Accuracy Limit at Rated Burden ALFr = 20


Rated Burden of CT VAr = 15.00 VA
Actual Burden VAa = 2.794 VA

ALF Actual (ALFa) = ALFr* (VAr+Rct) / (VAa+Rct)


= 20 X (15 + 0.7) / (2.794 + 0.7)
= 89.8683
ALF Actual (ALFa) = 90 (Refer Note - 3)

128
1.2.8 Resulting CT
C CCharacteristics
Rated Short time Thermal
Rated Secondary Current
Rated Primary Current at

Accuracy Class at rated


Approved Tap (I pn)

Rated Frequency

Current(2.5*Isc)
Rated Dynamic
Rated Burden

current
burden
(I n)

(A) (A) (–) (VA) (Hz) (kA-s) (kA)


200 1 5P20/1.0 15.0 50 40.0 -1 100

1.2.9 CT Particulars for Core-II ( applicable for C11CT3 & C21CT3)

Rated primary current Ipn : 200

Rated secondary current Isn : 1A


Accuracy Class : 5P20/1.0
Rated knee point e.m.f (Required) Vk > 138 V

Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 0.7 Ohm

Note

1 The Plug setting is considered as 100% In.


As per Kahramaa's Protection and Ind.System Volume 3 Rev.2 sec.3.3.8. clause:2.1.23.09, The highest plug setting is
2
considered as 32 times of In.
Since the required ALF is greater than the overload capacity of the connected devices. Further considering the Hi- set point of
3
relay is 32 X In.The proposed ALF is sufficient to meet the protection.

Page 47 of 101
Core – 4
C11CT4 & C21CT4
(2500 / 1 A)

Page 48 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. X


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) Inter Bus
TITLE 10/11/2011
Transformer (132 KV Side)

A. CT Sizing Calculation for 132/11kV Inter Bus Transformer (132 KV Side): C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-4:C11CT4 & C21CT4 P743 - Busbar Protection @ 2500A TAP

1.4 Core 4 Sizing (C11CT4 & C41CT4)

1.4.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 KA

1.4.2 Relay connected to this core

a. Make : AREVA

b. Type : P743

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R3)


2
: 0.04 / 1 SR = Relay rated burden (0.04 VA)

: 0.04 Ω IR = Relay rated current (1A)


Relay burden Rrelay : 0.04 Ohm

1.4.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistnace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.1040 Ohm

1.4.4 CT parameters

a. Selected CT Ratio : 2500/1 A

b. Rated primary current Ipn : 2500 A

c. Rated secondary current Isn : 1 A

d. Class : PX
e. o
Max. Sec. Winding Resistance at 75 C Rct : 8.8 Ohm (As per Kahramaa's Protection and
Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35Ω /100A)

Page 49 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. X


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) Inter Bus
TITLE 10/11/2011
Transformer (132 KV Side)

f. Minimum Knee Point Voltage Vk_min ≥ 0.5 X Ifmax X (Rct + R2lead +Rrelay) Case - I (Refer ANNEXURE - R3)

Where,
Maximum secondary fault current Ifmax = If / Ipn

= 40000 /2500
= 16 A

Therefore,

Vk_min = 0.5 X 16 X (8.8 + 1.104+0.04)


= 79.55 V

Now, with 20% margin

Vk_min = 1.2 X 79.55

= 95.462 V

= 95 V

g. Minimum Knee Point Voltage Vk_min ≥ Ifmax int X (Rct + R2lead) Case - II (Refer ANNEXURE - R3)

Where,
Maximum secondary contribution from a Ifmax int
= If / Ipn
feeder to an internal fault
= 40000 / 2500
= 16 A

Therefore,

Vk_min = 16 X (8.8 + 1.104+0.04)


= 159.10 V

Now, with 20% margin

Vk_min = 1.2 X 159.1

= 190.925 V

= 191 V

Knee point voltage selected = 191 V (Maximum of case - I & case - II)

1.4.5 CT Particulars for Core-4 ( applicable for C11CT4 & C21CT4)

Rated primary current Ipn : 2500 A


Rated secondary current Isn : 1 A
Class : PX
Rated knee point e.m.f Ek > 191 V
o
Max. resistance of sec.winding at 75 C Rct < 8.8 Ω

Page 50 of 101
CT Sizing Calculation for
132kV Bus Section

Page 51 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE
TITLE : CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 25/10/11

SUMMARY

Sl.No. Description Page No.


1 Summary Chart 52
2 Single Line Diagram 53
CT - I (Core - 1) & CT - II (Core - 2)

3 CT Sizing Calculation 56
CT - II (Core - 1)

4 CT Sizing Calculation 59

Page 52 of 101
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Current Transformer Parameters for 132kV Bus Section - BC-2 Substation

Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 26/10/2011 Rev: A

Itherm-cont
Class of Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden (Rated Rated Short
Core Ratio accuracy as Instrument short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - continuous time thermal Remarks
Nos proposed per IEC security current = 2.5
(Ohms) Required Adopted (RMS value) Adopted thermal current (Ith)
60044-1 factor ISF x Ith (KA)
current in %)

D 132kV Bus Section CT-I

1 O/C & E/F +BCU - (C264+P141) Core-1 2500/1A 5P20/1.0 2500A 8.8 - - - 30 - 150% 40kA, 1 sec 100

2 Bus bar protection(87B/50BF) - (P743) Core-2 2500/1A PX 2500A 8.8 190 200 30 mA @ Vk / 2 - - 150% 40kA, 1 sec 100

132kV Bus Section CT-II

3 Bus bar protection(87B/50BF) - (P743) Core-1 2500/1A PX 2500A 8.8 190 200 30 mA @ Vk / 2 - - 150% 40kA, 1 sec 100

Page 53 of 101
CT PARAMETER -132kV
BUS SECTION.(TYP.)

132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. MAIN BUS

M M

P2
B/B PRTN. - LOW Z.
CORE -2
2500/1A
[87B/50BF]
CL:PX

O/C & E/F + BCU


CORE -1 [51/51N]
2500/1A
CL:5P20/1.0
P1

P2
B/B PRTN. - LOW Z.
CORE -1
2500/1A [87B/50BF]
CL:PX

P1

132/11kV GIS PRIMARY


BARZAN CAMP-2 SUBSTATION
Page 54 of 101
CT – I (Core – 1)
&
CT – II (Core – 2)
C12CT2, C12CT3
(2500 / 1 A)

Page 55 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 09/11/2011

A. CT Sizing Calculation for 132kV Bus Section : C12

1 CT Details

Core details Device connected & Purpose


Core1 & 2 :C12CT2, C12CT3 P743 - Busbar Protection @ 2500A TAP

1.4 Core 1 & 2 Sizing

1.4.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 KA

1.4.2 Relay connected to this core

a. Make : AREVA

b. Type : P743

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R3)


2
: 0.04 / 1 SR = Relay rated burden (0.04 VA)

: 0.04 Ω IR = Relay rated current (1A)


Relay burden Rrelay : 0.04 Ohm

1.4.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistnace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.1040 Ohm

1.4.4 CT parameters

a. Selected CT Ratio : 2500/1 A

b. Rated primary current Ipn : 2500 A

c. Rated secondary current Isn : 1 A

d. Class : PX
(As per Kahramaa's Protection and Ind.System
e. Max. Sec. Winding Resistance at 75o C Rct : 8.8 Ω
Volume 3 Rev.2sec.3.3.8. 2.1.22.11- 0.35Ω/100A)

Page 56 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 09/11/2011

f. Minimum Knee Point Voltage Vk_min ≥ 0.5 X Ifmax X (Rct + R2lead +Rrelay)Case - I (Refer ANNEXURE - R3)

Where,
Maximum secondary fault current Ifmax = If / Ipn

= 40000 /2500
= 16 A

Therefore,

Vk_min = 0.5 X 16 X (8.8 + 1.104+0.04)


= 79.55 V

Now, with 20% margin

Vk_min = 1.2 X 79.55

= 95.462 V

= 95 V

g. Minimum Knee Point Voltage Vk_min ≥ Ifmax int X (Rct + R2lead +Rrelay) Case - II (Refer ANNEXURE - R3)

Where,
Wh
Maximum secondary contribution from a feeder Ifmax int = If / Ipn
to an internal fault
= 40000/2500
= 16 A

Therefore,

Vk_min = 16 X (8.8 + 1.104)


= 158.46 V

Now, with 20% margin

Vk_min = 1.2 X 158.46

= 190.157 V

= 190 V

Knee point voltage selected = 190 V (Maximum of case - I & case - II)

1.4.5 CT Particulars for Core-1 & 2 ( applicable for Bus Section)

Rated primary current Ipn : 2500 A


Rated secondary current Isn : 1 A
Class : PX
Rated knee point e.m.f Ek > 190 V
o
Max. resistance of sec.winding at 75 C Rct < 8.8 Ω

Page 57 of 101
CT – II (Core – 1)
C12CT1
(2500 / 1 A)

Page 58 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 09/11/2011

A. CT Sizing Calculation for 132kV Bus Section : C12

1 CT Details

Core details Device connected & Purpose


Core-1:C12CT1 O/C & E/F + BCU - @ 2500A TAP

1.2 Core 1 Sizing

1.2.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.2.2 Device connected to this core

a. Make : AREVA

b. Type : C264 + P141

c. Rated current IR : 1 A

2
d. Relay burden Rrelay : [ SR / IR ] (Refer Annexure - R6 & R7)
2
C264 = 0.15 VA : 0.19 / 1 SR = Relay rated burden (0.15 + 0.04 VA)
P141 = 0.04 VA
: 0.19 Ω IR = Relay rated current (1A)
Burden of IED for measurement Rrelay : 0.19 Ω

1.2.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.104 Ω

1.2.4 CT parameters

a. Selected CT Ratio : 2500/1

b. Rated primary current (selected tap) Ipn : 2500 A

c. Rated secondary current Isn : 1 A

d. Class : 5P20/1.0

e. Rated Accuracy Limiting Factor ALFr : 20


(As per Kahramaa's Protection and
f. Max. Sec. Winding Resistance at 75o C Rct : 8.8 Ω Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11- 0.35Ω/100A)
g. Ammeter Resistance RA : 1.5 Ω (Since it is 1.5 VA)

Page 59 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 09/11/2011

1.2.5 Formulae and Requirements:

Non-directional/Directional Time-delayed Overcurrent

Vk  [Ifp/2] × (Rct+R2lead+Rrelay+RA) (Refer ANNEXURE - R6)

Where,
Ifp  Maximum Prospective Secondary Phase fault current (or) 32 X I> setting (whichever is lowest)
Requirement 1:
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
(Ipn = Rated CT Primary Current)

= 40000 / 2500
= 16 A

Requirement 2:
(I> setting is 1A which is equivalent to 2500 A in
32 X I> setting = 32 X 1
CT primary)
= 32 A

Ifp (chosen) = 16.00 (whichever option is lower)

Therefore,
Vk  [16/2] X (8.8 + 1.104 + 0.19 + 1.5) (Refer Note - 1)

 92.75 V

 95.00 V
 1.2 X 95
= 114 V (with 20% margin)

Instantaneous phase over current

Vk  Isp × (Rct+R2lead+Rrelay+RA) (Refer ANNEXURE - R6)

Where,
Isp  Maximum Prospective Secondary Phase fault current
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
(Ipn = Rated CT Primary Current)

= 40000 / 2500
Isp = 16 A
Therefore,
Vk  16 X (8.8 + 1.104 + 0.19 + 1.5)
 185.50 V
 186.00 V
 1.2 X 186
= 223 V (with 20% margin)

Knee Point voltage (Considered) = 223 V

Estimation of VA

Vk  (VAr* ALFr / Isn) +(ALFr*Isn*Rct) (Refer ANNEXURE - 2)

223.20  (VA × 20.0/1.0)+( 20.00 x 1.00 x 8.80)

VA = 2.36

VA = 15.00 (Adopted)

Page 60 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 09/11/2011

1.2.6 VA Burden and Accuracy Class of CT

2
Sb,cal = (Rrelay + R2lead+RA ) x IR
= (0.19 + 1.104 + 1.5) X 1^2
= 2.794 VA
Sb,req  Sb,cal
 2.794 VA

1.2.7 Adequacy Checking of 5P20

The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in
its windings at rated burden.

Accuracy Limit at Rated Burden ALFr = 20


Rated Burden of CT VAr = 15.00 VA
Actual Burden VAa = 2.794 VA

ALF Actual (ALFa) = ALFr* (VAr+Rct) / (VAa+Rct)


= 20 X (15 + 8.8) / (2.794 + 8.8)
= 41.056
ALF Actual (ALFa) = 42 (Refer Note - 2)

1.2.8 Resulting CT Characteristics


Rated Short ttime Thermal
ary Current at

Rated Secondary Current

Accuracy Cllass at rated


d Tap (I pn)

Rated Frrequency

Current((2.5*Isc)
Dynamic
Burden

currrent
den
(I n)

Rated B
burd

Rated D
Approved
Rated Prima

(A) (A) (–) (VA) (Hz) (kA-s) (kA)


2500 1 5P20/1.0 15.0 50 40.0 -1 100

1.2.9 CT Particulars for Core-I (C12CT1)

Rated primary current Ipn : 2500 A

Rated secondary current Isn : 1A


Accuracy Class : 5P20/1.0
Rated knee point e.m.f (Required) Vk > 223 V

Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 8.8 Ω

Note

1 The Plug setting is considered as 100% In.


Since the 'Actual ALF' is greater than 'Required ALF', the relay will pickup
2
positively.

Page 61 of 101
CT Sizing Calculation for
132/11kV Tx. HV Ph. Bushing CT’s

Page 62 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE

CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV (32/40 MVA) Transformer HV Ph. Bushing
TITLE : 25/10/11
CT's

SUMMARY

Sl.No. Description Page No.


1 Summary Chart 64
2 Single Line Diagram 65
Core - 1

3 CT Sizing Calculation 67
Core - 2

4 CT Sizing Calculation 74
Core - 3

5 CT Sizing Calculation 79
Core
C -4

6 CT Sizing Calculation 85

Page 63 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of HV Bushing Current Transformer Parameter for 132kV Interbus Transformer Feeder- BC-2 Substation (Adopted parameters)

Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 10/11/2011 Rev: 0

Itherm-cont
Class of Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden (Rated Rated Short
Core Ratio accuracy Instrument short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - continuous time thermal Remarks
Nos proposed as per IEC security current = 2.5
(Ohms) Required Adopted (RMS value) Adopted thermal current (Ith)
60044-1 factor ISF x Ith (KA)
current in %)

132/11kV Transformer HV Phase Bushing


A
CT

400 A 4 77 190 15 mA @ Vk / 2 - - 120% 40kA, 1 sec 100


132kV HV Restricted Earth fault Relay (87T-
1 Core-1 400-200/1A PX
1) - (P141)
200 A 2 92 95 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

400 A 4 45 120 15 mA @ Vk / 2 - - 120% 40kA 1 sec


40kA, 100
132kV Main-2 Transformer differential
2 Core-2 400-200/1A PX
protection (87T-2) - (7UT613)
200 A 2 55 60 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

400 A 1.4 1200 1200 15 mA @ Vk / 2 - - 120% 40kA, 1 sec 100


132kV Main-2 Cable differential protection
3 Core-3 400-200/1A PX
(87C-2) - (7SD532)
200 A 0.7 415 600 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

400 A 1 2280 2280 15 mA @ Vk / 2 - - 120% 40kA, 1 sec 100


132kV Main-1 Cable differential protection
4 Core-4 400-200/1A PX
(87C-1) - (P545)
200 A 0.5 211 1140 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100

Page 64 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. RESERVE BUS

132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. MAIN BUS

BUSHING CT PARAMETER -132/11kV


INTERBUS TRANSFORMER FEEDER (TYP.)

HV REF Protection

P1
CORE -1
400-200/1A Main-2 Transformer
CL:PX Diff. Protection
CORE -2
400-200/1A
CL:PX
CORE -3
400-200/1A
CL:PX
Tx. HV PH. Main-2 Cable Diff.
BUSHING CT's CORE -4 Protection
400-200/1A
CL:PX P2
CORE -1 CORE-2
750/1A 2500/1A Main-1 Cable Diff.
32/40 MVA Protection
CL:5P20 CL:PX
132/11kV
P1 P2
%Z=13.6
@ ONAN
NER CUBICAL
750A/30Sec.
NOTES:
Protection

Protection
Restricted Earth fault

P2
Standby Earthfault

CORE - 3
Restricted Earth fault
1) As per Kahramaa's protection and indication system sec.3.3.8 750/1A
Protection
Rev.2, 2.1.18.19, Bushing NCT shall be provided as normal CL:5P20/1.0
practice followed by manufacturers.In addition to that, additional ring CORE - 2
type CT(of the similar characteristics) shall be provided on the neutral 750/1A NER Monitoring
of the Transformer. CL:5P20/1.0
CORE - 1 Standby Earthfault
2500/1A Protection
CL:PX P1 132/11kV GIS PRIMARY
11kV INCOMER BARZAN CAMP-2 SUBSTATION
Page 65 of 101
Core – 1
C11CT1 & C21CT1
(400 – 200 / 1 A)

Page 66 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 10/11/2011
TRANSFORMER - HV Ph. Bushing CT's( 132KV side)

C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21

1 CT Details

Core details Device connected & Purpose

Core-1:C11CT1 & C21CT1 P141 - HV Restricted earth fault protection @ 400A TAP

1.1 Core 1 Sizing (C11CT1 & C21CT1)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

Maximum system fault current (HV


c. If : 40 kA
Side of Trafo.)

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 400/1

b. Rated primary current (selected tap) Ipn : 400 A

c. Rated secondary current Isn : 1 A

d. Class : PX
(As per Switchgear manufacturer feasibility)
e. Max. Sec. Winding Resistance at 75o C Rct : 4 Ohm

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on secondary side = (MVA Rating X 1000) / (1.732 X Vs X Min. Tap) (Refer Annexure -7)

= (40 X 1000) / (1.732 X 132 X 0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : AREVA

b. Type : P141

c. Rated current IR : 1 A

Relay burden Rrelay : [ Sr / Ir2 ] (Refer Annexure -R6)


P141 = 0.04 VA : (0.04) / 1 2 Sr = Relay rated burden (0.04 VA)
: 0.04 ohms Ir = Relay rated current (1A)
d. Relay burden Rrelay : 0.04 Ohm

1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

Page 67 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 10/11/2011
TRANSFORMER - HV Ph. Bushing CT's( 132KV side)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 2 X 100 X 5.52/1000

R2lead = 1.104 ohms

f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure - F6)
g. Through falut X/R Ratio X/R = 37.76
1.1.4.2 Determination minimum knee point voltage

High Impidence REF protection

Vk > 4 x Vs (Refer ANNEXURE - R6)

Where X/R < 25,


(Condition - 1)

Vs  [(0.0123 x X/R)+0.68]x If x (Rct+R2lead+Rrelay) (Refer ANNEXURE - R6)

(Condition - 2)
Where X/R > 25,

Vs  Is x Rs

Rs  (If/Is) x (Rct+R2lead+Rrelay)

where,
where
ISn = 1 A
Ipn = 400 A

Maximum Prospective Secondary through Fault current If = Ithr3ph / Ipn (Ithr3ph = Maximum Fault current = 1203 A)

(Ipn = Rated CT Primary Current)


= 1203/200
If = 3.0075 A

Vs = Stabilizing Voltage under maximum through fault current in volts.

Where X/R > 25, (condition - 2 satisfied)

Stabilizing Voltage Vs  (3.0075)x(4+1.104+0.04)


Vs  15.47
Vs  16.00

Stabilizing Voltage Vs  16.00

Therefore,

Knee point voltage Vk  4 x 16


 64

Knee point voltage(Vk) with 20% margin  64x1.2

 77 (With 20% Design margin )

Knee point voltage(Vk)  77

Page 68 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 10/11/2011
TRANSFORMER - HV Ph. Bushing CT's( 132KV side)

1.1.4.3 For sensitivity refer Relay sensitivity calculation sheet.


(The Stabilizing Vlotage (VS) Calculated here will be considered in the sensitivity check)

1.1.5 CT Particulars for Core-2 ( Applicable for C11NCT2 TO C41NCT2)

Rated primary current Ipn : 400 A

Rated secondary current Isn : 1A

Class : PX

Rated Knee point e.m.f (Min. Required) based on REF Vk > 77 V

Max. resistance of sec.winding at 75oC Rct < 4 Ohm

Note:
1 The final Knee Point voltage adopted will be identical to both Phase side (11 KV AIS) and Neutral side CTs.

Page 69 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 10/11/2011
TRANSFORMER - HV Ph. Bushing CT's( 132KV side)

C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21

1 CT Details

Core details Device connected & Purpose

Core-1:C11CT1 & C21CT1 P141 - HV Restricted earth fault protection @ 200A TAP

1.1 Core 1 Sizing (C11CT1 & C21CT1)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

Maximum system fault current (HV


c. If : 40 kA
Side of Trafo.)

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 200/1

b. Rated primary current (selected tap) Ipn : 200 A

c. Rated secondary current Isn : 1 A

d. Class : PX
(As per Switchgear manufacturer feasibility)
e. Max. Sec. Winding Resistance at 75o C Rct : 2 Ω

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on secondary side = (MVA Rating X 1000) / (1.732 X Vs X Min. Tap) (Refer Annexure -7)

= (40 X 1000) / (1.732 X 132 X 0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : AREVA

b. Type : P141

c. Rated current IR : 1 A

Relay burden Rrelay : [ Sr / Ir2 ] (Refer Annexure -R6)


P141 = 0.04 VA : (0.04) / 1 2 Sr = Relay rated burden (0.04 VA)
: 0.04 ohms Ir = Relay rated current (1A)
d. Relay burden Rrelay : 0.04 Ohm

1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

Page 70 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 10/11/2011
TRANSFORMER - HV Ph. Bushing CT's( 132KV side)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 2 X 100 X 5.52/1000

R2lead = 1.104 ohms

f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure - F6)
g. Through falut X/R Ratio X/R = 37.76 (Refer Annexure - F6)
1.1.4.2 Determination minimum knee point voltage

High Impidence REF protection

Vk > 4 x Vs (Refer ANNEXURE - R6)

Where X/R < 25,


(Condition - 1)

Vs  [(0.0123 x X/R)+0.68]x If x (Rct+R2lead+Rrelay) (Refer ANNEXURE - R6)

(Condition - 2)
Where X/R > 25,

Vs  Is x Rs

Rs  (If/Is) x (Rct+R2lead+Rrelay)

where,
where
ISn = 1 A
Ipn = 200 A

Maximum Prospective Secondary through Fault current If = Ithr3ph / Ipn (Ithr3ph = Maximum Fault current = 1203 A)

(Ipn = Rated CT Primary Current)


= 1203/200
If = 6.015 A

Vs = Stabilizing Voltage under maximum through fault current in volts.

Where X/R > 25, (condition - 2 satisfied)

Stabilizing Voltage Vs  (6.015)x(2+1.104+0.04)


Vs  18.91
Vs  19.00

Stabilizing Voltage Vs  19.00

Therefore,

Knee point voltage Vk  4 x 19


 76

Knee point voltage(Vk) with 20% margin  76x1.2

 91 (With 20% Design margin )

Knee point voltage(Vk)  92

Page 71 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 10/11/2011
TRANSFORMER - HV Ph. Bushing CT's( 132KV side)

1.1.4.3 For sensitivity refer Relay sensitivity calculation sheet.


(The Stabilizing Vlotage (VS) Calculated here will be considered in the sensitivity check)

1.1.5 CT Particulars for Core-1 ( Applicable for C11CT1 & C21CT1)

Rated primary current Ipn : 200 A 400 A

Rated secondary current Isn : 1A 1A

Class : PX PX

Rated Knee point e.m.f (Min. Required) based on REF Vk > 92 V 77 V

Max. resistance of sec.winding at 75oC Rct < 2.0Ω 4.0Ω

Page 72 of 101
Core – 2
C11CT2 & C21CT2
(400 – 200 / 1 A)

Page 73 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011

C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21

1 CT Details of Transformer HV side(132kV) Ph. Bushing

Core details Device connected & Purpose


Core-2:C11 & C21CT2 7UT613 - MAIN-2 Transformer Differential Protection @ 400A TAP

1.1 Core 2 Sizing (C11CT2 & C21CT2)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

System frequency fn : 50 Hz
b.

c. Maximum fault current (HV Side of Trafo.) If : 40 kA

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 400/1

b. Rated primary current (selected tap) Ipn : 400 A

c. Rated secondary current Isn : 1 A

d. Class : PX

e. Max. Sec. Winding Resistance at 75o C Rct : 4 Ohm (As per switchgear manufacturer
feasibility)

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on primary side = (MVA Rating X 1000) / (1.732 X Vs X Min. Tap.) (Refer Annexure - 7 )

= (40 X 1000) / (1.732 X 132 X 0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : SIEMENS

b. Type : 7UT613 - Transformer Differential Protection

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R5 )


7UT612 = 0.05 VA : (0.05) / 1 2 SR = Relay rated burden (0.05 VA)

: 0.05 ohms IR = Relay rated current (1A)


Relay burden Rrelay : 0.05 Ohm

1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Sizeof the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

Page 74 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 2 X 100 X 5.52/1000

R2lead = 1.1040 ohms

Maximum external fault current on CT


f. Iscc(ext.fault) = 1203.00 A (Refer ANNEXURE - F6)
primary side

1.1.4.2 Determination minimum knee point voltage

Vk ≥ Ktd * (Iscc max(ext fault)/1.3 * Ipn)*(Rct+R'b)*Isn

Transient dimensioning factor Ktd = 3 (Refer ANNEXURE - R5)

R'b = R2lead + Rrelay

= 1.104+0.02

= 1.154

Vk = 3X(1203/400X1.3)X(4+1.154)X1)

= 35.77

Knee point Voltage with 20% margin = 1.2 X 499

= 42.9

= 45 V

1.1.5 Conclusion:

1. Since Transformer Main-1 and Main-2 differential protection are conneted, the highest Vk is chosen as the required Knee point voltage satisfying both
the protections.

2. For final values, refer the summary given at 200 A TAP

Page 75 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011

C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21

1 CT Details of Transformer HV side(132kV) Ph. Bushing

Core details Device connected & Purpose


Core-2:C11 & C21CT2 7UT613 - MAIN-2 Transformer Differential Protection @ 200A TAP

1.1 Core 2 Sizing (C11CT2 & C21CT2)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

System frequency fn : 50 Hz
b.

c. Maximum fault current (HV Side of Trafo.) If : 40 kA

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 200/1

b. Rated primary current (selected tap) Ipn : 200 A

c. Rated secondary current Isn : 1 A

d. Class : PX

e. Max. Sec. Winding Resistance at 75o C Rct : 2 Ohm (As per switchgear manufacturer
feasibility)

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on primary side = (MVA Rating X 1000) / (1.732 X Vs x Min. Tap) (Refer Annexure - 7 )

= (40 X 1000) / (1.732 X 132X0.85)

= 205.8 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : SIEMENS

b. Type : 7UT613 - Transformer Differential Protection

c. Rated current IR : 1 A

d. Relay burden Rrelay : [ SR / IR2 ] (Refer Annexure - R5 )


7UT613 = 0.05 VA : (0.05) / 1 2 SR = Relay rated burden (0.05 VA)

: 0.05 ohms IR = Relay rated current (1A)


Relay burden Rrelay : 0.05 Ohm

1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Sizeof the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

Page 76 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 2 X 100 X 5.52/1000

R2lead = 1.1040 ohms

Maximum external fault current on CT


f. Iscc(ext.fault) = 1203.00 A (Refer ANNEXURE - F6)
primary side

1.1.4.2 Determination minimum knee point voltage

Vk ≥ Ktd * (Iscc max(ext fault)/1.3 * Ipn)*(Rct+R'b)*Isn

Transient dimensioning factor Ktd = 3 (Refer ANNEXURE - R5)

R'b = R2lead + Rrelay

= 1.104+0.02

= 1.154

Vk = 3X(1203/200X1.3)X(2+1.154)X1)

= 43.78

Knee point Voltage with 20% margin = 1.2 X 43.77995

= 52.5

= 55 V

1.1.5 CT Particulars for Core-II ( Applicable for C11CT2 & C21CT2)

Rated primary current Ipn : 400 A 200 A

Rated secondary current Isn : 1A 1A

Class : PX PX
Rated Knee point e.m.f based on Main-2 Tfr Diff.
Vk > 45 V 55 V
protection

Max. resistance of sec.winding at 75oC Rct < 4 Ohm 2 Ohm

1.1.5 Conclusion:

1. Since Transformer Main-1 and Main-2 differential protection are conneted, the highest Vk is chosen as the required Knee point voltage satisfying both
the protections.

Page 77 of 101
Core – 3
C11CT3 & C21CT3
(400-200 / 1 A)

Page 78 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011

A. CT Sizing Calculation for 132kV Cable Feeders: C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-3:C11CT3 & C21CT3 7SD532 - Line Differential Protection with backup distance protection - Main2 @ 400A TAP

1.1 Core 3 Sizing (C11CT3 & C21CT3)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : Siemens

b. Type : 7SD532

c. Rated current IR : 1 A

2
d. Relay burden R relay : [ SR / IR ] (Refer Annexure - R2)

: 0.05 / 1 2 SR = Relay rated burden (0.05 VA)

: 0.05 Ohms IR = Relay rated current (1A)

The burden of 7SD532 a current input channel Rrelay : 0.05 ohm

1.1.3 Detials of Lead from CT to Relay

a. Sizeof the calble : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)

d. Oneway length of the lead L : 100 m

f. Two-way lead resistnace R2lead = 2*L*Rcable/1000

(with 20% uprating) = 2*100*5.52/1000


R2lead = 1.1040 Ohm
1.1.4 Determination CT parameters

a. Selected CT Ratio : 400/1 A

b. Rated primary current (selected tap) Ipn = 400 A

c. Rated secondary current Isn = 1 A


d. Class = PX

o (As per Kahramaa's Protection and Ind.System


e. Max. Sec. Winding Resistance at 75 C Rct = 1.4 Ohm
Volume 3 Rev.2sec.3.3.8. 2.1.22.11 - 0.35Ω/100A)

f. Maximum primary fundamental frequency Ikmax = 40000 A (Ikmax = Isccmax(ext.fault)=Isccmax(closein fault))


fault current for internal close-in faults(A) (Refer Annexure-F1 [B])

g. Maximum primary fundamental frequency Ikmax1 = 40516 A (Ikmax = Isccmax(zone1 reach))


fault current for Zone-1 end fault (Iz1 end (Refer Annexure-F1 [B])
fault)

Page 79 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011

Case-1 (Differential check)

a. Transient dimensioning factor Ktd : 1.2 (Refer Annexure-R2)

b. Connected resistive burden to CT Rb ' : R2lead+Rrelay

= 1.1540

Rb ' = 1.1540 Ohm

c. Minimum Knee Point Voltage Vk_min : Ktd*Iscc max(ext.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 1.2 x 40000 x (1.4 + 1.154) x [ 1 / (1.3 x 400) ]

= 235.75 V

= 236 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

= 283

Ek = 285 V

Case-2 (Distance check - Close in fault)

a. Time constant for close-in fault TCF : 47.35 msec (Refer Annexure - F1 [B])

b. Hence, Transient dimensioning factor Ktd(a) : 2 (Refer Annexure-R2)

c. Minimum Knee Point Voltage Vk_min : Ktd(a)*Iscc max(Close in.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 2 x 40000 x (1.4 + 1.154) x [ 1 / (1.3 x 400) ]

= 392.923 V

= 400 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

= 1.2 x 400

= 480.0 V

Ek = 480 V

Page 80 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011

Case-3 (Distane check - Zone-1 end fault)

a. Time constant for Zone-1 end fault Tz11ph : 43.24 msec (Refer Annexure - F1 [B])

b. Transient dimensioning factor Ktd(b) : 5 (Refer Annexure-R2)

c. Minimum Knee Point Voltage Vk_min : Ktd(b)*Iscc max(Z1end.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 5 x 40516 x (1.4 + 1.154) x [ 1 / (1.3 x 400) ]

= 994.979 V

= 995 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

1.2 x 995

= 1194.0 V

Ek = 1200 V

Maximum of differential and distance


Knee point voltage =
criteria
= 1200 V

1.1.5 CT parameters chosen for Core-3 (applicable for C11CT3 & C21CT3)

Rated primary current Ipn : 400 A

Rated secondary current Isn : 1A


Class : PX
Rated knee point e.m.f (Min Required) Ek > 1200 V
o
Max. resistance of sec.winding at 75 C Rct < 1.4 Ohm

Page 81 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011

A. CT Sizing Calculation for 132kV Cable Feeders: C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-3:C11CT3 & C21CT3 7SD532 - Line Differential Protection with backup distance protection - Main2 @ 200A TAP

1.1 Core 3 Sizing (C11CT3 & C21CT3)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : Siemens

b. Type : 7SD532

c. Rated current IR : 1 A

2
d. Relay burden R relay : [ SR / IR ] (Refer Annexure - R2)

: 0.05 / 1 2 SR = Relay rated burden (0.05 VA)

: 0.05 Ohms IR = Relay rated current (1A)

The burden of 7SD532 a current input channel Rrelay : 0.05 ohm

1.1.3 Detials of Lead from CT to Relay

a. Sizeof the calble : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)

d. Oneway length of the lead L : 100 m

f. Two-way lead resistnace R2lead = 2*L*Rcable/1000

(with 20% uprating) = 2*100*5.52/1000


R2lead = 1.1040 Ohm
1.1.4 Determination CT parameters

a. Selected CT Ratio : 200/1 A

b. Rated primary current (selected tap) Ipn = 200 A

c. Rated secondary current Isn = 1 A


d. Class = PX

o (As per Kahramaa's Protection and Ind.System


e. Max. Sec. Winding Resistance at 75 C Rct = 0.7 Ohm
Volume 3 Rev.2sec.3.3.8. 2.1.22.11 - 0.35Ω/100A)

f. Maximum primary fundamental frequency Ikmax = 40000 A (Ikmax = Isccmax(ext.fault)=Isccmax(closein fault))


fault current for internal close-in faults(A) (Refer Annexure-F1 [B])

g. Maximum primary fundamental frequency Ikmax1 = 40516 A (Ikmax = Isccmax(zone1 reach))


fault current for Zone-1 end fault (Iz1 end (Refer Annexure-F1 [B])
fault)

Page 82 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date

TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011

Case-1 (Differential check)

a. Transient dimensioning factor Ktd : 1.2 (Refer Annexure-R2)

b. Connected resistive burden to CT Rb ' : R2lead+Rrelay

= 1.1540

Rb ' = 1.1540 Ohm

c. Minimum Knee Point Voltage Vk_min : Ktd*Iscc max(ext.fault)*(Rct+Rb')*Isn/(1.3*Ipn)

= 1.2 x 40000 x (0.7 + 1.154) x [ 1 / (1.3 x 200) ]

= 342.28 V

= 342 V

d. Knee point voltage with design margin of 20% Ek : 1.2*Vk_min

= 411

Ek = 415 V

1.1.5 CT parameters chosen for Core-3 (applicable for C11CT3 & C21CT3)

Rated primary current Ipn : 200 A

Rated secondary current Isn : 1A


Class : PX
Rated knee point e.m.f (Min Required) Ek > 415 V
o
Max. resistance of sec.winding at 75 C Rct < 0.7 Ohm

Page 83 of 101
Core – 4
C11CT4 & C21CT4
(400-200 /1 A)

Page 84 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for Tx. HV Ph. Bushing CT for cable feeder - 132kV Primary at BC-2 Substation 13/02/2011

A. CT Sizing Calculation for Tx. HV Ph. Bushing CT for cable feeder: C11 & C21

CT Details:

Core details Device connected & Purpose


Core-3:C11CT4 & C21CT4 P545 - Line Differential with backup distance protection - Main-I @ 400A TAP

1.1 Core 4 Sizing (C11CT4 & C21CT4)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : AREVA

b. Type : P545

c. Rated current IR : 1 A

d. Relay burden SR : 0.04 Ohm (Refer ANNEXURE - R1)

1.1.3 Details of Lead from CT to Relay

a. Size of the cable : 2.5 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistnace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.1040 Ohm

1.1.4 Determination of CT parameters

a. Selected CT Ratio : 400/1

b. Rated primary current (selected tap) Ipn : 400 A

c. Rated secondary current Isn : 1 A

d. Class : PX

o
e. Max. Sec. Winding Resistance at 75 C Rct : 1.0 Ohm

f. Relay burden Rrelay = [ SR / IR2 ] SR = Relay rated burden (0.04 VA)


IR = Relay rated current (1A)
= 0.04 / 1 2

Rrelay = 0.04 Ohm

g. Total secondary burden Rsb = Rct+R2lead+Rrelay = 2.1440 Ohm

1.1.5 Fault Current Particulars


Maximum primary fundmental frequency fault current for internal
a. Ikmax : 40000 A
close - in faults

b. Maximum value of through fault current Itmax : 39870 A (Annexure - F1B)

c. Maximum phase fault current at Zone 1 reach point Ifz11ph : 40516 A (Annexure - F1B)

d. X/R ratio Zonr-1 reach fault X/R = 13.6 (Annexure - F1B)

Page 85 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for Tx. HV Ph. Bushing CT for cable feeder - 132kV Primary at BC-2 Substation 13/02/2011

1.1.6 Differential Check

b. Minimum Knee Point Voltage Vk ≥ K * Isn * Rsb

K is determined as follows: (for two - ended current differential protection)


For Relays set at Is1 = 20%, Is1 = 2In, K1 = 30%, K2 = 150%,

When (If * X/R) ≤ 1000 * Isn (Refer ANNEXURE - R1)

K ≥ 40 + 0.07 * (If * X/R) (Condition - 1)

& K ≥ 65

When 1000 * Isn < (If * X/R) < 1600 * Isn (Condition - 2)

K ≥ 107

where, If = Maximum through fault current reflected on CT secondary side

If = Itmax

If = Itmax / Ipn

= 39870 / 400

= 99.68 A (Reflected on CT Secondary side)

So,

(99.68 X 13.57) ≤ (1000 X 1)

1352.6576 ≤ 1000 (Condition - 1is not satisfied)

(1000 X 1) < (99.68 X 13.57) < (1600 X 1)

1000 ≤ 1352.6576 < 1600

(Condition - 2 satisfied)

Therefore,

K ≥ 107 (Refer Annexure - R1)

Vk ≥ 107 X 1 X 2.14

= 229.4

Vk = 230 V

Knee point voltage With Design margin(20%) (Vk) = 276 V

Case-2 (Distance check - Close in fault)

a. Hence, Dimensioning factor Kmax : 1.4 (Refer Annexure - R1)

b. Maximum secondary phase fault current Ifmax : 40000/400


: 100.00

c. Minimum Knee Point Voltage Vk_min : Kmax*Ifmax(Close in.fault)*(Rct+R2lead+Rrelay)

= 1.4x100x(1+1.104+0.04)

= 300.160 V

= 301 V

d. Knee point voltage with design margin of 20% : 1.2*Vk_min

Vk_min = 1.2 x 301

= 361.2 V

Vk_min = 370 V

Page 86 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for Tx. HV Ph. Bushing CT for cable feeder - 132kV Primary at BC-2 Substation 13/02/2011

Case-3 (Distane check - Zone-1 reach fault)

a. Hence, Dimensioning factor Krpa = 0.6 (Refer Annexure - R1)

b. Maximum secondary phase fault current at Zone-1 reach point IfZ1 = 40516/400
IfZ1 = 101.29

c. Minimum Knee Point Voltage Vk_min = Krpa*IfZ1(Close in.fault)*(1+X/R)*(Rct+R2lead+Rrelay)

= 0.6x101.29x(1+13.57)x(1+1.104+0.04)

= 1898.463 V

= 1899 V

d. Knee point voltage with design margin of 20% Vk_min : 1.2*Vk_min

= 1.2 x 1899

= 2278.8 V

Vk_min = 2279 V

Vk Maximum of differential and distance


Final Knee point voltage =
criteria

= 2279 V
1.1.7 CT parameters chosen for Core-4

Rated primary current Ipn : 400 A

Rated secondary current Isn : 1A

Class : 1

Max. resistance of sec.winding at 75oC Rct < 1.0 Ohm

Final knee point voltage Vk > 2279 V

Page 87 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for Tx. HV Ph. Bushing CT for cable feeder - 132kV Primary at BC-2 Substation 13/02/2011

A. CT Sizing Calculation for Tx. HV Ph. Bushing CT for cable feeder: C11 & C21

CT Details:

Core details Device connected & Purpose


Core-4:C11CT4 & C21CT4 P545 - Line Differential Protection - Main-I @ 200A TAP

1.1 Core 4 Sizing (C11CT4 & C21CT4)

1.1.1 Basic System Data

a. Nominal system voltage V : 132 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.1.2 Relay details

a. Make : AREVA

b. Type : P545

c. Rated current IR : 1 A

d. Relay burden SR : 0.04 Ohm (Refer ANNEXURE - R1)

1.1.3 Details of Lead from CT to Relay

a. Size of the cable : 2.5 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistnace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.1040 Ohm

1.1.4 Determination of CT parameters

a. Selected CT Ratio : 200/1

b. Rated primary current (selected tap) Ipn : 200 A

c. Rated secondary current Isn : 1 A

d. Class : PX

o
e. Max. Sec. Winding Resistance at 75 C Rct : 0.5 Ohm

f. Relay burden Rrelay = [ SR / IR2 ] SR = Relay rated burden (0.04 VA)


IR = Relay rated current (1A)
= 0.04 / 1 2

Rrelay = 0.04 Ohm

g. Total secondary burden Rsb = Rct+R2lead+Rrelay = 1.6440 Ohm

1.1.5 Fault Current Particulars


Maximum primary fundmental frequency fault current for internal
a. Ikmax : 40000 A
close - in faults

b. Maximum value of through fault current Itmax : 39870 A (Annexure - F1A)

c. Maximum phase fault current at Zone 1 reach point Ifz11ph : 40516 A (Annexure - F1A)

d. X/R ratio Zonr-1 reach fault X/R = 13.6 (Annexure - F1A)

Page 88 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

Prepared Checked Approved Rev.0


PROJECT GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - SUBSTATIONS
MM SMS AKSM Date
TITLE CT Sizing calculation for Tx. HV Ph. Bushing CT for cable feeder - 132kV Primary at BC-2 Substation 13/02/2011

1.1.6 Differential Check

b. Minimum Knee Point Voltage Vk ≥ K * Isn * Rsb

K is determined as follows: (for two - ended current differential protection)


For Relays set at Is1 = 20%, Is1 = 2In, K1 = 30%, K2 = 150%,

When (If * X/R) ≤ 1000 * Isn (Refer ANNEXURE - R1)

K ≥ 40 + 0.07 * (If * X/R) (Condition - 1)

& K ≥ 65

When 1000 * Isn < (If * X/R) < 1600 * Isn (Condition - 2)

K ≥ 107

where, If = Maximum through fault current reflected on CT secondary side

If = Itmax

If = Itmax / Ipn

= 39870 / 200

= 199.35 A (Reflected on CT Secondary side)

So,

(199.35 X 13.6) ≤ (1000 X 1)

2711.16 ≤ 1000 (Condition - 1is not satisfied)

(1000 X 1) < (199.35 X 13.6) < (1600 X 1)

1000 ≤ 2711.16 < 1600

(Condition - 2 is not satisfied)

Therefore,

K ≥ 107

Vk ≥ 107 X 1 X 1.64

= 175.9

Vk = 176 V

Knee point voltage With Design margin(20%) (Vk) = 211 V


1.1.7 CT parameters chosen for Core-4

Rated primary current Ipn : 200 A

Rated secondary current Isn : 1A

Class : 1

Max. resistance of sec.winding at 75oC Rct < 0.5 Ohm

Final knee point voltage Vk > 211 V

Page 89 of 101
CT Sizing Calculation for
132/11kV Tx. – 11kV Neutral
Bushing CT

Page 90 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE
CT Sizing calculation for 132kV Primary Substation at BC-2Substation - 132/11 KV (32/40 MVA) Inter Bus Transformer -
TITLE : 11/11/11
11 KV Side - Neutral

SUMMARY

Sl.No. Description Page No.


1 Summary Chart 92
2 Single Line Diagram 93
Core - 1

CT Sizing Calculation
3
95
Core - 2

4 CT Sizing Calculation 99

Page 91 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of CT Parameter for 11kV Interbus Tx.(11 KV Side) Neutral Side Bushing CT's- BC-2 Substation (Adopted parameters)

Project :GTC - 371A -2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 26/10/2011 Rev: A

Itherm-cont Dynamic
Class of Rated (Rated short
Rct at 75 Minimum (Vk) in Magnetizing Burden Rated Short
Core Ratio accuracy Instrument continuous circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - time thermal Remarks
Nos proposed as per IEC security thermal current =
(Ohms) Required Adopted (RMS value) Adopted current (Ith)
60044-1 factor ISF current in 2.5 x Ith
%) (KA)

A 11kV Inter Bus Transformer Neutral Bushing CT

1 11kV Stand by Earth Fault Protection - P141 Core-1 750/1A 5P20/1.0 750 A 2.63 - - - 15 - 120% 40kA, 1 sec 100

11kV Restricted Earth Fault Protection


2 Core-2 2500/1A PX 2500 A 12 481 481 30 mA @ Vk / 2 - 120% 40kA, 1 sec 100
(87NH) - P141

Page 92 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. RESERVE BUS

132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. MAIN BUS

BUSHING CT PARAMETER -132/11kV


INTERBUS TRANSFORMER FEEDER (TYP.)

HV REF Protection

P1
CORE -1
400-200/1A Main-2 Transformer
CL:PX Diff. Protection
CORE -2
400-200/1A
CL:PX
CORE -3
400-200/1A
CL:PX
Tx. HV PH. Main-2 Cable Diff.
BUSHING CT's CORE -4 Protection
400-200/1A
CL:PX P2
CORE -1 CORE-2
750/1A 2500/1A Main-1 Cable Diff.
32/40 MVA Protection
CL:5P20 CL:PX
132/11kV
P1 P2
%Z=13.6
@ ONAN
NER CUBICAL
750A/30Sec.
NOTES:
Protection

Protection
Restricted Earth fault

P2
Standby Earthfault

CORE - 3
Restricted Earth fault
1) As per Kahramaa's protection and indication system sec.3.3.8 750/1A
Protection
Rev.2, 2.1.18.19, Bushing NCT shall be provided as normal CL:5P20/1.0
practice followed by manufacturers.In addition to that, additional ring CORE - 2
type CT(of the similar characteristics) shall be provided on the neutral 750/1A NER Monitoring
of the Transformer. CL:5P20/1.0
CORE - 1 Standby Earthfault
2500/1A Protection
CL:PX P1 132/11kV GIS PRIMARY
11kV INCOMER BARZAN CAMP-2 SUBSTATION
Page 93 of 101
Core – 1
C11NCT1&C21NCT1
(750 / 1 A)

Page 94 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 27/10/2011
TRANSFORMER - 11KV SIDE NEUTRAL

C. CT Sizing Calculation for 132/11kV Transformer (11 KV Side - Neutral): C11 & C21

1 CT Details

Core details Device connected & Purpose


Core-1: C11NCT1 & C21NCT1 P141 EF PROTECTION - @ 750A TAP

1.2 Core 3 Sizing

1.2.1 Basic System Data

a. Nominal system voltage V : 11 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA

1.2.2 Device connected to this core

a. Make : AREVA

b. Type : P141

c. Rated current IR : 1 A

2
d. Relay burden Rrelay : [ SR / IR ] (Refer Annexure - R6)
: 0.04 / 1 2 SR = Relay rated burden (0.04 VA)

: 0.04 Ω IR = Relay rated current (1A)


Burden of IED for measurement Rrelay : 0.04 Ω

1.2.3 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead : 2*L*Rcable/1000

= 2*100*5.52/1000

R2lead = 1.104 Ω

1.2.4 CT parameters

a. Selected CT Ratio : 750/1

b. Rated primary current (selected tap) Ipn : 750 A

c. Rated secondary current Isn : 1 A

d. Class : 5P20/1.0
e. Rated Accuracy Limiting Factor ALFr : 20
(As per Kahramaa's Protection and
f. Max. Sec. Winding Resistance at 75o C Rct : 2.63 Ω Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35 Ω/100A)

Page 95 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 27/10/2011
TRANSFORMER - 11KV SIDE NEUTRAL

1.2.5 Formulae and Requirements:

Non-directional/Directional Time-delayed Overcurrent

Vk  [Ifp/2] × (Rct+R2lead+Rrelay) (Refer ANNEXURE - R6)

Where,
Ifp  Maximum Prospective Secondary Phase fault current (or) 31 X I> setting (whichever is lowest)
Requirement 1:

Maximum Prospective Secondary Earth Fault current = Ikmax / Ipn (Ikmax = Maximum Earth Fault Current = 750 A)

(Ipn = Rated CT Primary Current)


= 750 / 750 (Refer Note - 1)
Ifp = 1 A

Requirement 2:
(I> setting is 0.8 A which is equivalent to 750 A
31 X I> setting = 31 X 0.8
in CT primary)
= 16 A

Ifp (chosen) = 1 (whichever option is lower)

Therefore,
Vk  [1/2] X (2.63 + 1.104 + 0.04) (Refer Note - 2)

 1.89 V
 2.00 V
 1.2 X 2
= 2 V (with 20% margin)

Instantaneous phase over current :

Vk  Isp × (Rct+R2lead+Rrelay) (Refer ANNEXURE - R6)

Where,
Isp  Maximum Prospective Secondary Phase fault current
(Ikmax = Maximum Earth Fault Current = 750 A)
Maximum Prospective Secondary Earth Fault current = Ikmax / Ipn

(Ipn = Rated CT Primary Current)

= 750 / 750 (Refer Note - 2)


Isp = 1 A
Therefore,
Vk  1 X (2.63 + 1.104 + 0.04) (Refer Note - 3)

 3.77 V

 4.00 V
 1.2 X 4
= 5 V

Estimation of VA

Vk  (VAr* ALFr / Isn) +(ALFr*Isn*Rct) (Refer ANNEXURE - 2)

 (VA × 20.0/1.0)+( 20.00 x 1.00 x 2.63)

VA = -2.39

VA = 15.00 (Adopted)

Page 96 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 27/10/2011
TRANSFORMER - 11KV SIDE NEUTRAL

1.2.6 VA Burden and Accuracy Class of CT

2
Sb,cal = (Rrelay + R2lead ) x IR
= (0.04 + 1.104) X 1^2
= 1.144 VA
Sb,req  Sb,cal
 1.144 VA

1.2.7 Adequacy Checking of 5P20

The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current
flow in its windings at rated burden.

Accuracy Limit at Rated Burden ALFr = 20


Rated Burden of CT VAr = 15.00 VA
Actual Burden VAa = 1.144 VA

ALF Actual (ALFa) = ALFr* (VAr+Rct) / (VAa+Rct)


= 20 X (15 + 2.63) / (1.144 + 2.63)
= 93.4287
ALF Actual (ALFa) = 94

1.2.8 Resulting CT Characteristics


Rated Short time Thermal
Rated Secondary Current
Rated Primary Current at

Accuracy Class at rated


Approved Tap (I pn)

Rated Frequency

Current(2.5*Isc)
Rated Dynamic
Rated Burden
burden

current
(I n)

(A) (A) (–) (VA) (Hz) (kA-s) (kA)


750 1 5P20/1.0 15.0 50 40.0 -3 100

1.2.9 CT Particulars for Core-II( C11NCT2 & C21NCT2)

Rated primary current Ipn : 750

Rated secondary current Isn : 1A


Accuracy Class : 5P20/1.0
Rated knee point e.m.f (Required) Vk > 5V

Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 2.63 Ohm

Note
1 Maximum Earth Fault current when both transformers are in parallel will not exceed 750 A.
2 The Plug setting is considered as 100% In.
Since the 'Actual ALF' is greater than highest value, the relay will pickup
3
positively.

Page 97 of 101
Core – 2
C11NCT2 &C21NCT2
(2500 / 1 A)

Page 98 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 27/10/2011
TRANSFORMER - 11KV SIDE NEUTRAL

C. CT Sizing Calculation for 132/11kV Station Transformer Feeders( 11kV side - Neutral): C11 & C21

1 CT Details on LV side(11kV) of Transformer

Core details Device connected & Purpose

Core-2: C11NCT2 & C21NCT2 P141 - HV Restricted earth fault protection @ 2500A TAP

1.1 Core 1 Sizing (C11NCT1 & C21NCT1)

1.1.1 Basic System Data

a. Nominal system voltage V : 11 kV

b. System frequency fn : 50 Hz

Maximum system fault current (HV


c. If : 40 kA
Side of Trafo.)

1.1.2 CT parameters on HV side

a. Selected CT Ratio : 2500/1

b. Rated primary current (selected tap) Ipn : 2500 A

c. Rated secondary current Isn : 1 A

d. Class : PX

o Rct :
e. Max. Sec. Winding Resistance at 75 C 12 Ohm
((Ass per
pe the
t e sswitchgear
tc gea manufacturer
a u actu e feasibility)
eas b ty)

1.1.2.1 Feeder Rating

Tranformer Details

Rating = 40 MVA

Primary Rating (Vp) = 132 kV

Secondary Rating (Vs) = 11 kV


Maximum Feeder current on secondary side = (MVA Rating X 1000) / (1.732 X Vs X Min. Tap)

= (40 X 1000) / (1.732 X 11 X 0.85)

= 2470.0 A

1.1.3 Differential protection relay, connected to the above cores:

a. Make : AREVA

b. Type : P141

c. Rated current IR : 1 A

Relay burden Rrelay : [ Sr / Ir2 ] (Refer Annexure -R6)


P141 = 0.04 VA : (0.04) / 1 2 Sr = Relay rated burden (0.14 VA)
: 0.04 ohms Ir = Relay rated current (1A)
d. Relay burden Rrelay : 0.04 Ohm

1.1.4 HV side calculations

1.1.4.1 Detials of Lead from CT to Relay

a. Size of the cable : 4 sq.mm

b. material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

Page 99 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 27/10/2011
TRANSFORMER - 11KV SIDE NEUTRAL

d. Oneway length of the lead L : 100 m

e. Two-way lead resistanace R2lead = 2*L*Rcable/1000


= 2 X 100 X 5.52/1000

R2lead = 1.104 ohms

f. Maximum through fault current on primary side Ithr3ph = 14440 A (Refer Annexure - F6)
g. Through falut X/R Ratio X/R = 36.46
1.1.4.2 Determination minimum knee point voltage

High Impidence REF protection

Vk > 4 x Vs (Refer ANNEXURE - R6)

Where X/R < 25,


(Condition - 1)

Vs  [(0.0123 x X/R)+0.68]x If x (Rct+R2lead+Rrelay) (Refer ANNEXURE - R6)

(Condition - 2)
Where X/R > 25,

Vs  Is x Rs

Rs  (If/Is) x (Rct+R2lead+Rrelay)

where,
where
ISn = 1 A
Ipn = 2500 A

Maximum Prospective Secondary through Fault current If = Ithr3ph / Ipn (Ithr3ph = Maximum Fault current = 14440 A)

(Ipn = Rated CT Primary Current)


= 14440/2500
If = 5.776 A

Vs = Stabilizing Voltage under maximum through fault current in volts.

Where X/R > 25, (condition - 2 satisfied)

Stabilizing Voltage Vs  (5.776) x (12+1.104+0.04)


Vs  75.92
Vs  76.00

Stabilizing Voltage Vs  76.00

Therefore,

Knee point voltage Vk  4 x 76


 304

Knee point voltage(Vk) with 20% margin  304x1.2

 365 (With 20% Design margin )

Knee point voltage(Vk)  365

Page 100 of 101


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR TRANSMISSION SYSTEM EXPANSION-PHASE X - Prepared Checked Approved Rev. 0


PROJECT
SUBSTATIONS MM SMS AKSM Date
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV (32/40 MVA) INTERBUS
TITLE 27/10/2011
TRANSFORMER - 11KV SIDE NEUTRAL

1.1.4.3 For sensitivity refer Relay sensitivity calculation sheet.


(The Stabilizing Vlotage (VS) Calculated here will be considered in the sensitivity check)

1.1.5 CT Particulars for Core-2 ( Applicable for C11NCT2 TO C41NCT2)

Rated primary current Ipn : 2500 A

Rated secondary current Isn : 1A

Class : PX

Rated Knee point e.m.f (Min. Required) based on REF Vk > 365 V

Rated Knee point e.m.f (Min. Required) based on Tx.


Vk > 481 V
Main Diff. +REF Protection
Final (Min required) Rated Knee point Voltage Vk > 481 V
Max. resistance of sec.winding at 75oC Rct < 12 Ohm

Note:
1 The final Knee Point voltage adopted will be identical to both Phase side (11 KV AIS) and Neutral side CTs.

Page 101 of 101