LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. 0
PROJECT :
SUBSTATIONS MM SMS AKSM DATE
TITLE : CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV CABLE FEEDER 25/10/11
SUMMARY
3 CT Sizing Calculation 6
Core - 2
4 CT Sizing Calculation 13
Core - 3
5 CT Sizing Calculation 20
Core - 4
6 CT Sizing Calculation 25
Page 2 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of Current Transformer Parameters for 132kV Cable feeder - BC-2 Substation (Adopted Parameters)
Project : GTC - 371A - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE- X - SUBSTATIONS Dt: 9/11/2011 Rev: A
Itherm-cont
Class of Rated (Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden Rated Short
Core Ratio accuracy Instrument continuous short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - time thermal Remarks
Nos proposed as per IEC security thermal current =
(Ohms) Required Adopted (RMS value) Adopted current (Ith)
60044-1 factor ISF current in 2.5 x Ith (KA)
%)
4 Busbar Protection (P743) - (87B/50BF) Core-4 2500/1A PX 2500 A 8.8 191 200 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100
Note:
Considering 630 Sq.mm Cu. cable with 1 KM length for 400 A Tap and 1600 Sq.mm Cu. cable with 1 KM length for 800A Tap for calculation of Knee pint voltage has been submitted vide letter PH8 - L&T - 4C - LTR - 09 -
1
0132, Dt: 10/02/2009.
2 The detailed justification for maximum possible Knee Point Voltage has already been submitted vide Letter No: PH8 - L&T - 4C - LTR - 09 - 0132, Dt: 10/02/2009 and the case of Distance Check is not considered here.
3 The final KPV is identical to 132 KV Inter Bus Transformer CT Core - 3 in EDC - 4 (Stage - I) and EDC - 5 respectively.
Page 3 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. MAIN BUS
BCU + METERING
CORE -3 [50/51/51N]
1500-800/1A
CL:5P20/1.0
P2
Page 5 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
CT Details:
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P545
c. Rated current IR : 1 A
c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
d. Class : PX
c. Maximum primary phase fault current at Zone 1 reach point IFz1 : 38618 A (Annexure - F1)
Page 6 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
& K ≥ 65
K ≥ 107
If = Itmax / Ipn
= 37292 / 1500
So,
Therefore,
= 61.23
Vk ≥ 65 X 1 X 6.44
= 418.9
Vk = 419 V
= 1.4x26.67x(5.3+1.104+0.04)
= 240.576 V
= 241 V
= 289.2 V
Vk_min = 290 V
Page 7 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
b. Maximum secondary phase fault current at Zone-1 reach point IfZ1 : 38618/1500
: 25.75
= 0.6x25.73x(1+12.2)x(5.3+1.104+0.04)
= 1313.951 V
= 1314 V
= 1.2 x 1314
= 1576.8 V
Vk_min = 1580 V
= 1580 V
Class : PX
Note:
Page 8 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
CT Details:
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P545
c. Rated current IR : 1 A
c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
d. Class : PX
c. Maximum secondary phase fault current at Zone 1 reach point IFz1 : 38618 A (Annexure - F1)
Page 9 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
& K ≥ 65
K = 107
If = Itmax / Ipn
= 37292 / 800
So,
Therefore,
Vk ≥ 79.8 X 1 X 3.94
= 314.7289158
Vk = 315 V
= 1.4x50x(2.8+1.104+0.04)
= 276.080 V
= 277 V
= 332.4 V
Vk_min = 333 V
Page 10 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
b. Maximum secondary phase fault current at Zone-1 reach point IfZ1 : 38618/800
: 48.27
= 0.6x48.2725x(1+12.197)x(2.8+1.104+0.04)
= 1507.520 V
= 1508 V
= 1.2 x 1508
= 1809.6 V
Vk_min = 1810 V
= 1810 V
Rated
R t d primary
i currentt Ipn : 800 A 1500 A
Rated secondary current Isn : 1A 1A
Class : PX PX
Max. resistance of sec.winding at 75oC Rct < 2.8 Ohm 5.3 Ohm
Final knee point voltage Vk > 1810 V 1580 V
Page 11 of 101
Core – 2
C10CT2 TO C40CT2
(1500 – 800 / 1 A)
Page 12 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
1 CT Details
b. System frequency fn : 50 Hz
a. Make : Siemens
b. Type : 7SD532
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)
= 2*100*5.52/1000
R2lead = 1.1040 Ohm
1.1.4 Determination CT parameters
d. Class = PX
(As per Kahramaa's Protection and Ind.System
e. Max. Sec. Winding Resistance at 75o C Rct = 5.3 Ohm
Volume 3 Rev.2sec.3.3.8. 2.1.22.11 - 0.35Ω/100A)
Page 13 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
= 1.1540
= 158.87 V
= 159 V
= 191
Ek = 195 V
a. Time constant for close-in fault TCF : 32.71 msec (Refer Annexure - F1 )
= 264.779 V
= 270 V
= 1.2 x 270
= 324.0 V
Ek = 325 V
Page 14 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
a. Time constant for Zone-1 end fault Tz11ph : 28.28 msec (Refer Annexure - F1)
= 638.814 V
= 640 V
1.2 x 640
= 768.0 V
Ek = 770 V
1.1.6 Note:
Page 15 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
1 CT Details
b. System frequency fn : 50 Hz
a. Make : Siemens
b. Type : 7SD532
c. Rated current IR : 1 A
2
d. Relay burden R relay : [ SR / IR ] (Refer Annexure - R2)
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)
Page 16 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
= 1.1540
= 182.49 V
= 183 V
= 220
Ek = 220 V
a. Time constant for close-in fault TCF : 32.71 msec (Refer Annexure - F1)
= 304.154 V
= 310 V
= 1.2 x 310
= 372.0 V
Ek = 380 V
Page 17 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
a. Time constant for Zone-1 end fault Tz11ph : 28.28 msec (Refer Annexure - F1 )
= 733.809 V
= 734 V
1.2 x 734
= 880.8 V
Ek = 890 V
Max. resistance of sec.winding at 75oC Rct < 2.8 Ohm 5.3 Ohm
Page 18 of 101
Core – 3
C10CT3 TO C40CT3
(1500 – 800 / 1 A)
Page 19 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : C264
c. Rated current IR : 1 A
y
1.2.3 Detials of Lead from CT to Relay
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
R2lead = 1.104 Ω
1.2.4 CT parameters
d. Class : 5P20/1.0
e. Rated Accuracy Limiting Factor ALFr : 20
(As per Kahramaa's Protection and
o
f. Max. Sec. Winding Resistance at 75 C Rct : 5.3 Ω Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35Ω/100A)
g. Ammeter Resistance RA : 1.5 Ω (Since it is 1.5 VA)
Page 20 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in
its windings at rated burden.
Note
Page 21 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : C264
c. Rated current IR : 1 A
2
d. Relay burden Rrelay : [ SR / IR ] (Refer Annexure - R7)
: 0.15 / 1 2 SR = Relay rated burden (0.15 VA)
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
R2lead = 1.104 Ω
1.2.4 CT parameters
d. Class : 5P20/1.0
Page 22 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in
its windings at rated burden.
Rated Frequency
Current(2.5*Isc)
Rated Dynamic
Rated Burden
burden
current
(I n)
Note
Since the 'Actual ALF' is greater than Required ALF, the relay will pickup
3
positively.
Page 23 of 101
Core – 4
C10CT4 TO C40CT4
(2500 / 1 A)
Page 24 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P743
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
1.4.4 CT parameters
d. Class : PX
Page 25 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV CABLE FEEDER 09/11/2011
f. Minimum Knee Point Voltage Vk_min ≥ 0.5 X Ifmax X (Rct + R2lead+Rrelay) Case - I (Refer ANNEXURE - R3)
Where,
Maximum secondary fault current Ifmax = If / Ipn
= 40000 / 2500
= 16 A
Therefore,
= 95.462 V
= 95 V
g. Maximum Knee Point Voltage Vk_min ≥ Ifmax int X (Rct + R2lead +Rrelay) Case - II (Refer ANNEXURE - R3)
Where,
Maximum secondary contribution from a Ifmax int = If / Ipn
feeder to an internal fault
= 40000 / 2500
= 16 A
Therefore,
= 190.925 V
= 191 V
Knee point voltage selected = 191 V (Maximum of case - I & case - II)
Page 26 of 101
CT Sizing Calculation for
132/11kV Interbus Tx. feeder
Page 27 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV (32/40 MVA) Inter Bus Transformer - 132
TITLE : 25/10/11
KV side
SUMMARY
3 CT Sizing Calculation 32
Core - 2
4 CT Sizing Calculation 37
Core - 3
5 CT Sizing Calculation 42
Core - 4
6 CT Sizing Calculation 49
Page 28 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of Current Transformer Parameter for 132kV Interbus Transformer Feeder- BC-2 Substation (Adopted parameters)
Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 9/11/2011 Rev: A
Itherm-cont
Class of Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden (Rated Rated Short
Core Ratio accuracy Instrument short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - continuous time thermal Remarks
Nos proposed as per IEC security current = 2.5
(Ohms) Required Adopted (RMS value) Adopted thermal current (Ith)
60044-1 factor ISF x Ith (KA)
current in %)
4 Busbar Protection (87BB/50BF) - (P743) Core-4 2500/1A PX 2500 A 8.8 191 200 30 mA @ Vk / 2 - - 120% 40kA, 1 sec 100
Page 29 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. MAIN BUS
CT PARAMETER -132/11kV
INTER BUS TRANSFORMER FEEDER.(TYP.)
P1 MAIN-1 TRANSFORMER
CORE -1 DIFF. PRTN.(87T-1)
400-200/1A
CL:PX
MAIN-2 TRANSFORMER
CORE -2 DIFF. PRTN.(87T-2)
400-200/1A
CL:PX
M P2
32/40 MVA
132/11kV
%Z=13.6
@ ONAN
Page 31 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21
1 CT Details
b. System frequency fn : 50 Hz
d. Class : PX
o
e. Max. Sec. Winding Resistance at 75 C Rct : 4.0 Ohm (As per switchgear manufacturer feasibility)
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : AREVA
b. Type : P643
c. Rated current IR : 1 A
Page 32 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure-F6)
g. X/R ratio for 3phase through fault X/R = 37.76
K is determined as follows:
When In < Isf ≤ 40In, & 5 ≤ X/R < 120 (Refer Annexure- R4 )
K = 30 (Condition - A)
= 3.0075 A
Now
Now, Vk = (30 X 1(4 + 0
0.2
2+1
1.104)
104)
= 159.12
= 190.944
= 195 V
NOTE:
1) For overall CT perticulers refer 300 Tap.
Page 33 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21
1 CT Details
b. System frequency fn : 50 Hz
d. Class : PX
o
e. Max. Sec. Winding Resistance at 75 C Rct : 2.0 Ohm (As per switchgear manufacturer feasibility)
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : AREVA
b. Type : P643
c. Rated current IR : 1 A
Page 34 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure-F6)
g. X/R ratio for 3phase through fault X/R = 37.76 (Refer Annexure-F6)
K is determined as follows:
When In < Isf ≤ 40In, & 5 ≤ X/R < 120 (Refer Annexure- R4 )
K = 30 (Condition - A)
= 6.015 A
Now
Now, Vk = (30 X 1(2 + 0
0.2
2+1
1.104)
104)
= 99.12
= 118.944
= 120 V
Page 35 of 101
Core – 2
C11CT2 & C21CT2
(400 – 200 / 1 A)
Page 36 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011
C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21
System frequency fn : 50 Hz
b.
d. Class : PX
e. Max. Sec. Winding Resistance at 75o C Rct : 4 Ohm (As per switchgear manufacturer
feasibility)
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : SIEMENS
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
Page 37 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011
= 1.104+0.05
= 1.154
Vk = 3X(1203/400X1.3)X(4+1.154)X1)
= 35.77
= 42.92489
= 45 V
1.1.5 Conclusion:
1. Since Transformer differential protection and REF relays are conneted in series, the highest Vk is chosen as the required Knee point voltage satisfying
bothe the protections.
Page 38 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011
C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21.
System frequency fn : 50 Hz
b.
d. Class : PX
1.1.2.1
1 1 2 1 Feeder Rating
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : SIEMENS
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
Page 39 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132/11kV Interbus Transformer Incomer 10/11/2011
= 1.104+0.05
= 1.154
Vk = 3X(1203/200X1.3)X(2+1.154)X1)
= 43.78
= 52.5
= 55 V
Class : PX PX
Rated Knee point e.m.f based on Main-2 Tfr Diff.
Vk > 45 V 55 V
protection
Max. resistance of sec.winding at 75oC Rct < 4 Ohm 2 Ohm
1.1.5 Conclusion:
1. Since Transformer differential protection and REF relays are conneted in series, the highest Vk is chosen as the required Knee point voltage satisfying
both the protections.
Page 40 of 101
Core – 3
C11CT3 & C21CT3
(400 – 200 / 1 A)
Page 41 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
R2lead = 1.104 Ω
1.2.4 CT parameters
d. Class : 5P20/1.0
Page 42 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Where,
Ifp Maximum Prospective Secondary Phase fault current (or) 31 X I> setting (whichever is lowest)
Requirement 1:
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
= 40000 / 400
= 100 A
Requirement 2:
(I> setting is 1A which is equivalent to 2500 A in CT
31 X I> setting = 31 X 1
primary)
= 31 A
Therefore,
Vk 31/2 X (1.4 + 1.104 + 0.19 + 1.5 ) (Refer Note - 2)
65.01 V
70 V
1.2 X 70
Where,
Isp Maximum Prospective Secondary Phase fault current
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
= 40000 / 400
Isp = 100 A
Isp (chosen) = 32 (Refer Note - 2)
Therefore,
Vk 32 X (1.4 + 1.104 + 0.19 + 1.5 )
134.21 V
135 V
1.2 X 135
= 162 V (with 20% margin)
Estimation of VA
VA = 6.70
Page 43 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in its
windings at rated burden.
Rated Frequency
Current(2.5*Isc)
Rated Dynamic
Rated Burden
current
burden
(I n)
Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 1.4 Ohm
Note
Page 44 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
C. CT Sizing Calculation for 132/11kV Interbus Transformer Feeders( 132KV side): C11 & C21
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
R2lead = 1.104 Ω
1.2.4 CT parameters
d. Class : 5P20/1.0
Page 45 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Where,
Ifp Maximum Prospective Secondary Phase fault current (or) 32 X I> setting (whichever is lowest)
Requirement 1:
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
= 40000 / 200
= 200 A
Requirement 2:
(I> setting is 1A which is equivalent to 2500 A in CT
31 X I> setting = 31 X 1
primary)
= 31 A
Therefore,
Vk [31/2] X (0.7 + 1.104 + 0.19 + 1.5 ) (Refer Note - 2)
54.16 V
55 V
1.2 X 55
Where,
Isp Maximum Prospective Secondary Phase fault current
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
= 40000 / 200
Isp = 200 A
Isp (chosen) = 32 (Refer Note - 2)
Therefore,
Vk 32 X (0.7 + 1.104 + 0.19 + 1.5 )
111.81 V
115 V
1.2 X 115
= 138 V (with 20% margin)
Estimation of VA
VA = 6.20
Page 46 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in its
windings at rated burden.
128
1.2.8 Resulting CT
C CCharacteristics
Rated Short time Thermal
Rated Secondary Current
Rated Primary Current at
Rated Frequency
Current(2.5*Isc)
Rated Dynamic
Rated Burden
current
burden
(I n)
Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 0.7 Ohm
Note
Page 47 of 101
Core – 4
C11CT4 & C21CT4
(2500 / 1 A)
Page 48 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
A. CT Sizing Calculation for 132/11kV Inter Bus Transformer (132 KV Side): C11 & C21
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P743
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
1.4.4 CT parameters
d. Class : PX
e. o
Max. Sec. Winding Resistance at 75 C Rct : 8.8 Ohm (As per Kahramaa's Protection and
Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35Ω /100A)
Page 49 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
f. Minimum Knee Point Voltage Vk_min ≥ 0.5 X Ifmax X (Rct + R2lead +Rrelay) Case - I (Refer ANNEXURE - R3)
Where,
Maximum secondary fault current Ifmax = If / Ipn
= 40000 /2500
= 16 A
Therefore,
= 95.462 V
= 95 V
g. Minimum Knee Point Voltage Vk_min ≥ Ifmax int X (Rct + R2lead) Case - II (Refer ANNEXURE - R3)
Where,
Maximum secondary contribution from a Ifmax int
= If / Ipn
feeder to an internal fault
= 40000 / 2500
= 16 A
Therefore,
= 190.925 V
= 191 V
Knee point voltage selected = 191 V (Maximum of case - I & case - II)
Page 50 of 101
CT Sizing Calculation for
132kV Bus Section
Page 51 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE
TITLE : CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 25/10/11
SUMMARY
3 CT Sizing Calculation 56
CT - II (Core - 1)
4 CT Sizing Calculation 59
Page 52 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of Current Transformer Parameters for 132kV Bus Section - BC-2 Substation
Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 26/10/2011 Rev: A
Itherm-cont
Class of Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden (Rated Rated Short
Core Ratio accuracy as Instrument short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - continuous time thermal Remarks
Nos proposed per IEC security current = 2.5
(Ohms) Required Adopted (RMS value) Adopted thermal current (Ith)
60044-1 factor ISF x Ith (KA)
current in %)
1 O/C & E/F +BCU - (C264+P141) Core-1 2500/1A 5P20/1.0 2500A 8.8 - - - 30 - 150% 40kA, 1 sec 100
2 Bus bar protection(87B/50BF) - (P743) Core-2 2500/1A PX 2500A 8.8 190 200 30 mA @ Vk / 2 - - 150% 40kA, 1 sec 100
3 Bus bar protection(87B/50BF) - (P743) Core-1 2500/1A PX 2500A 8.8 190 200 30 mA @ Vk / 2 - - 150% 40kA, 1 sec 100
Page 53 of 101
CT PARAMETER -132kV
BUS SECTION.(TYP.)
M M
P2
B/B PRTN. - LOW Z.
CORE -2
2500/1A
[87B/50BF]
CL:PX
P2
B/B PRTN. - LOW Z.
CORE -1
2500/1A [87B/50BF]
CL:PX
P1
Page 55 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 09/11/2011
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P743
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
1.4.4 CT parameters
d. Class : PX
(As per Kahramaa's Protection and Ind.System
e. Max. Sec. Winding Resistance at 75o C Rct : 8.8 Ω
Volume 3 Rev.2sec.3.3.8. 2.1.22.11- 0.35Ω/100A)
Page 56 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV Bus Section 09/11/2011
f. Minimum Knee Point Voltage Vk_min ≥ 0.5 X Ifmax X (Rct + R2lead +Rrelay)Case - I (Refer ANNEXURE - R3)
Where,
Maximum secondary fault current Ifmax = If / Ipn
= 40000 /2500
= 16 A
Therefore,
= 95.462 V
= 95 V
g. Minimum Knee Point Voltage Vk_min ≥ Ifmax int X (Rct + R2lead +Rrelay) Case - II (Refer ANNEXURE - R3)
Where,
Wh
Maximum secondary contribution from a feeder Ifmax int = If / Ipn
to an internal fault
= 40000/2500
= 16 A
Therefore,
= 190.157 V
= 190 V
Knee point voltage selected = 190 V (Maximum of case - I & case - II)
Page 57 of 101
CT – II (Core – 1)
C12CT1
(2500 / 1 A)
Page 58 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
c. Rated current IR : 1 A
2
d. Relay burden Rrelay : [ SR / IR ] (Refer Annexure - R6 & R7)
2
C264 = 0.15 VA : 0.19 / 1 SR = Relay rated burden (0.15 + 0.04 VA)
P141 = 0.04 VA
: 0.19 Ω IR = Relay rated current (1A)
Burden of IED for measurement Rrelay : 0.19 Ω
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
R2lead = 1.104 Ω
1.2.4 CT parameters
d. Class : 5P20/1.0
Page 59 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Where,
Ifp Maximum Prospective Secondary Phase fault current (or) 32 X I> setting (whichever is lowest)
Requirement 1:
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
(Ipn = Rated CT Primary Current)
= 40000 / 2500
= 16 A
Requirement 2:
(I> setting is 1A which is equivalent to 2500 A in
32 X I> setting = 32 X 1
CT primary)
= 32 A
Therefore,
Vk [16/2] X (8.8 + 1.104 + 0.19 + 1.5) (Refer Note - 1)
92.75 V
95.00 V
1.2 X 95
= 114 V (with 20% margin)
Where,
Isp Maximum Prospective Secondary Phase fault current
Maximum Prospective Secondary Phase Fault current = Ikmax / Ipn (Ikmax = Maximum Fault Current = 40000 A)
(Ipn = Rated CT Primary Current)
= 40000 / 2500
Isp = 16 A
Therefore,
Vk 16 X (8.8 + 1.104 + 0.19 + 1.5)
185.50 V
186.00 V
1.2 X 186
= 223 V (with 20% margin)
Estimation of VA
VA = 2.36
VA = 15.00 (Adopted)
Page 60 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
2
Sb,cal = (Rrelay + R2lead+RA ) x IR
= (0.19 + 1.104 + 1.5) X 1^2
= 2.794 VA
Sb,req Sb,cal
2.794 VA
The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current flow in
its windings at rated burden.
Rated Frrequency
Current((2.5*Isc)
Dynamic
Burden
currrent
den
(I n)
Rated B
burd
Rated D
Approved
Rated Prima
Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 8.8 Ω
Note
Page 61 of 101
CT Sizing Calculation for
132/11kV Tx. HV Ph. Bushing CT’s
Page 62 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE
CT Sizing calculation for 132kV Primary Substation at BC-2 Substation - 132kV (32/40 MVA) Transformer HV Ph. Bushing
TITLE : 25/10/11
CT's
SUMMARY
3 CT Sizing Calculation 67
Core - 2
4 CT Sizing Calculation 74
Core - 3
5 CT Sizing Calculation 79
Core
C -4
6 CT Sizing Calculation 85
Page 63 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of HV Bushing Current Transformer Parameter for 132kV Interbus Transformer Feeder- BC-2 Substation (Adopted parameters)
Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 10/11/2011 Rev: 0
Itherm-cont
Class of Rated Dynamic
Rct at 75 Minimum (Vk) in Magnetizing Burden (Rated Rated Short
Core Ratio accuracy Instrument short circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - continuous time thermal Remarks
Nos proposed as per IEC security current = 2.5
(Ohms) Required Adopted (RMS value) Adopted thermal current (Ith)
60044-1 factor ISF x Ith (KA)
current in %)
Page 64 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. RESERVE BUS
HV REF Protection
P1
CORE -1
400-200/1A Main-2 Transformer
CL:PX Diff. Protection
CORE -2
400-200/1A
CL:PX
CORE -3
400-200/1A
CL:PX
Tx. HV PH. Main-2 Cable Diff.
BUSHING CT's CORE -4 Protection
400-200/1A
CL:PX P2
CORE -1 CORE-2
750/1A 2500/1A Main-1 Cable Diff.
32/40 MVA Protection
CL:5P20 CL:PX
132/11kV
P1 P2
%Z=13.6
@ ONAN
NER CUBICAL
750A/30Sec.
NOTES:
Protection
Protection
Restricted Earth fault
P2
Standby Earthfault
CORE - 3
Restricted Earth fault
1) As per Kahramaa's protection and indication system sec.3.3.8 750/1A
Protection
Rev.2, 2.1.18.19, Bushing NCT shall be provided as normal CL:5P20/1.0
practice followed by manufacturers.In addition to that, additional ring CORE - 2
type CT(of the similar characteristics) shall be provided on the neutral 750/1A NER Monitoring
of the Transformer. CL:5P20/1.0
CORE - 1 Standby Earthfault
2500/1A Protection
CL:PX P1 132/11kV GIS PRIMARY
11kV INCOMER BARZAN CAMP-2 SUBSTATION
Page 65 of 101
Core – 1
C11CT1 & C21CT1
(400 – 200 / 1 A)
Page 66 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21
1 CT Details
Core-1:C11CT1 & C21CT1 P141 - HV Restricted earth fault protection @ 400A TAP
b. System frequency fn : 50 Hz
d. Class : PX
(As per Switchgear manufacturer feasibility)
e. Max. Sec. Winding Resistance at 75o C Rct : 4 Ohm
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : AREVA
b. Type : P141
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
Page 67 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure - F6)
g. Through falut X/R Ratio X/R = 37.76
1.1.4.2 Determination minimum knee point voltage
(Condition - 2)
Where X/R > 25,
Vs Is x Rs
Rs (If/Is) x (Rct+R2lead+Rrelay)
where,
where
ISn = 1 A
Ipn = 400 A
Maximum Prospective Secondary through Fault current If = Ithr3ph / Ipn (Ithr3ph = Maximum Fault current = 1203 A)
Therefore,
Page 68 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Class : PX
Note:
1 The final Knee Point voltage adopted will be identical to both Phase side (11 KV AIS) and Neutral side CTs.
Page 69 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21
1 CT Details
Core-1:C11CT1 & C21CT1 P141 - HV Restricted earth fault protection @ 200A TAP
b. System frequency fn : 50 Hz
d. Class : PX
(As per Switchgear manufacturer feasibility)
e. Max. Sec. Winding Resistance at 75o C Rct : 2 Ω
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : AREVA
b. Type : P141
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
Page 70 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
f. Maximum through fault current on primary side Ithr3ph = 1203 A (Refer Annexure - F6)
g. Through falut X/R Ratio X/R = 37.76 (Refer Annexure - F6)
1.1.4.2 Determination minimum knee point voltage
(Condition - 2)
Where X/R > 25,
Vs Is x Rs
Rs (If/Is) x (Rct+R2lead+Rrelay)
where,
where
ISn = 1 A
Ipn = 200 A
Maximum Prospective Secondary through Fault current If = Ithr3ph / Ipn (Ithr3ph = Maximum Fault current = 1203 A)
Therefore,
Page 71 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Class : PX PX
Page 72 of 101
Core – 2
C11CT2 & C21CT2
(400 – 200 / 1 A)
Page 73 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011
C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21
System frequency fn : 50 Hz
b.
d. Class : PX
e. Max. Sec. Winding Resistance at 75o C Rct : 4 Ohm (As per switchgear manufacturer
feasibility)
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : SIEMENS
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
Page 74 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011
= 1.104+0.02
= 1.154
Vk = 3X(1203/400X1.3)X(4+1.154)X1)
= 35.77
= 42.9
= 45 V
1.1.5 Conclusion:
1. Since Transformer Main-1 and Main-2 differential protection are conneted, the highest Vk is chosen as the required Knee point voltage satisfying both
the protections.
Page 75 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011
C. CT Sizing Calculation for 132/11kV Transformer HV Ph. Bushing CT's( 132KV side): C11 & C21
System frequency fn : 50 Hz
b.
d. Class : PX
e. Max. Sec. Winding Resistance at 75o C Rct : 2 Ohm (As per switchgear manufacturer
feasibility)
Tranformer Details
Rating = 40 MVA
= 205.8 A
a. Make : SIEMENS
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
Page 76 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132/11kV (32/40 MVA)Transformer HV Ph. Bushing CT's -132kV Primary at BC-2 Substation 10/11/2011
= 1.104+0.02
= 1.154
Vk = 3X(1203/200X1.3)X(2+1.154)X1)
= 43.78
= 52.5
= 55 V
Class : PX PX
Rated Knee point e.m.f based on Main-2 Tfr Diff.
Vk > 45 V 55 V
protection
1.1.5 Conclusion:
1. Since Transformer Main-1 and Main-2 differential protection are conneted, the highest Vk is chosen as the required Knee point voltage satisfying both
the protections.
Page 77 of 101
Core – 3
C11CT3 & C21CT3
(400-200 / 1 A)
Page 78 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011
1 CT Details
b. System frequency fn : 50 Hz
a. Make : Siemens
b. Type : 7SD532
c. Rated current IR : 1 A
2
d. Relay burden R relay : [ SR / IR ] (Refer Annexure - R2)
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)
Page 79 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011
= 1.1540
= 235.75 V
= 236 V
= 283
Ek = 285 V
a. Time constant for close-in fault TCF : 47.35 msec (Refer Annexure - F1 [B])
= 392.923 V
= 400 V
= 1.2 x 400
= 480.0 V
Ek = 480 V
Page 80 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011
a. Time constant for Zone-1 end fault Tz11ph : 43.24 msec (Refer Annexure - F1 [B])
= 994.979 V
= 995 V
1.2 x 995
= 1194.0 V
Ek = 1200 V
1.1.5 CT parameters chosen for Core-3 (applicable for C11CT3 & C21CT3)
Page 81 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011
1 CT Details
b. System frequency fn : 50 Hz
a. Make : Siemens
b. Type : 7SD532
c. Rated current IR : 1 A
2
d. Relay burden R relay : [ SR / IR ] (Refer Annexure - R2)
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer Annexure - C1)
Page 82 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
TITLE CT Sizing calculation for 132kV Primary Substation at BC-2 Substation -132kV HV TFR BUSHING CT's 10/11/2011
= 1.1540
= 342.28 V
= 342 V
= 411
Ek = 415 V
1.1.5 CT parameters chosen for Core-3 (applicable for C11CT3 & C21CT3)
Page 83 of 101
Core – 4
C11CT4 & C21CT4
(400-200 /1 A)
Page 84 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
A. CT Sizing Calculation for Tx. HV Ph. Bushing CT for cable feeder: C11 & C21
CT Details:
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P545
c. Rated current IR : 1 A
c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
d. Class : PX
o
e. Max. Sec. Winding Resistance at 75 C Rct : 1.0 Ohm
c. Maximum phase fault current at Zone 1 reach point Ifz11ph : 40516 A (Annexure - F1B)
Page 85 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
& K ≥ 65
When 1000 * Isn < (If * X/R) < 1600 * Isn (Condition - 2)
K ≥ 107
If = Itmax
If = Itmax / Ipn
= 39870 / 400
So,
(Condition - 2 satisfied)
Therefore,
Vk ≥ 107 X 1 X 2.14
= 229.4
Vk = 230 V
= 1.4x100x(1+1.104+0.04)
= 300.160 V
= 301 V
= 361.2 V
Vk_min = 370 V
Page 86 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
b. Maximum secondary phase fault current at Zone-1 reach point IfZ1 = 40516/400
IfZ1 = 101.29
= 0.6x101.29x(1+13.57)x(1+1.104+0.04)
= 1898.463 V
= 1899 V
= 1.2 x 1899
= 2278.8 V
Vk_min = 2279 V
= 2279 V
1.1.7 CT parameters chosen for Core-4
Class : 1
Page 87 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
A. CT Sizing Calculation for Tx. HV Ph. Bushing CT for cable feeder: C11 & C21
CT Details:
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P545
c. Rated current IR : 1 A
c. Unit resistance of the cable @ 75 deg C Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
d. Class : PX
o
e. Max. Sec. Winding Resistance at 75 C Rct : 0.5 Ohm
c. Maximum phase fault current at Zone 1 reach point Ifz11ph : 40516 A (Annexure - F1A)
Page 88 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
& K ≥ 65
When 1000 * Isn < (If * X/R) < 1600 * Isn (Condition - 2)
K ≥ 107
If = Itmax
If = Itmax / Ipn
= 39870 / 200
So,
Therefore,
K ≥ 107
Vk ≥ 107 X 1 X 1.64
= 175.9
Vk = 176 V
Class : 1
Page 89 of 101
CT Sizing Calculation for
132/11kV Tx. – 11kV Neutral
Bushing CT
Page 90 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE - X - Prepared Checked Approved Rev. A
PROJECT :
SUBSTATIONS MM SMS AKSM DATE
CT Sizing calculation for 132kV Primary Substation at BC-2Substation - 132/11 KV (32/40 MVA) Inter Bus Transformer -
TITLE : 11/11/11
11 KV Side - Neutral
SUMMARY
CT Sizing Calculation
3
95
Core - 2
4 CT Sizing Calculation 99
Page 91 of 101
Larsen & Toubro Limited,
ECC Division - EDRC
Summary of CT Parameter for 11kV Interbus Tx.(11 KV Side) Neutral Side Bushing CT's- BC-2 Substation (Adopted parameters)
Project :GTC - 371A -2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Dt.: 26/10/2011 Rev: A
Itherm-cont Dynamic
Class of Rated (Rated short
Rct at 75 Minimum (Vk) in Magnetizing Burden Rated Short
Core Ratio accuracy Instrument continuous circuit
Sl No Description Tap degree Vk volts - Current ( Ie ) - (VA) - time thermal Remarks
Nos proposed as per IEC security thermal current =
(Ohms) Required Adopted (RMS value) Adopted current (Ith)
60044-1 factor ISF current in 2.5 x Ith
%) (KA)
1 11kV Stand by Earth Fault Protection - P141 Core-1 750/1A 5P20/1.0 750 A 2.63 - - - 15 - 120% 40kA, 1 sec 100
Page 92 of 101
132kV,3150A(@40 C),3 PH,50Hz,40kA for 1Sec. RESERVE BUS
HV REF Protection
P1
CORE -1
400-200/1A Main-2 Transformer
CL:PX Diff. Protection
CORE -2
400-200/1A
CL:PX
CORE -3
400-200/1A
CL:PX
Tx. HV PH. Main-2 Cable Diff.
BUSHING CT's CORE -4 Protection
400-200/1A
CL:PX P2
CORE -1 CORE-2
750/1A 2500/1A Main-1 Cable Diff.
32/40 MVA Protection
CL:5P20 CL:PX
132/11kV
P1 P2
%Z=13.6
@ ONAN
NER CUBICAL
750A/30Sec.
NOTES:
Protection
Protection
Restricted Earth fault
P2
Standby Earthfault
CORE - 3
Restricted Earth fault
1) As per Kahramaa's protection and indication system sec.3.3.8 750/1A
Protection
Rev.2, 2.1.18.19, Bushing NCT shall be provided as normal CL:5P20/1.0
practice followed by manufacturers.In addition to that, additional ring CORE - 2
type CT(of the similar characteristics) shall be provided on the neutral 750/1A NER Monitoring
of the Transformer. CL:5P20/1.0
CORE - 1 Standby Earthfault
2500/1A Protection
CL:PX P1 132/11kV GIS PRIMARY
11kV INCOMER BARZAN CAMP-2 SUBSTATION
Page 93 of 101
Core – 1
C11NCT1&C21NCT1
(750 / 1 A)
Page 94 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
C. CT Sizing Calculation for 132/11kV Transformer (11 KV Side - Neutral): C11 & C21
1 CT Details
b. System frequency fn : 50 Hz
a. Make : AREVA
b. Type : P141
c. Rated current IR : 1 A
2
d. Relay burden Rrelay : [ SR / IR ] (Refer Annexure - R6)
: 0.04 / 1 2 SR = Relay rated burden (0.04 VA)
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
= 2*100*5.52/1000
R2lead = 1.104 Ω
1.2.4 CT parameters
d. Class : 5P20/1.0
e. Rated Accuracy Limiting Factor ALFr : 20
(As per Kahramaa's Protection and
f. Max. Sec. Winding Resistance at 75o C Rct : 2.63 Ω Ind.System Volume 3 Rev.2sec.3.3.8.
2.1.22.11 - 0.35 Ω/100A)
Page 95 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
Where,
Ifp Maximum Prospective Secondary Phase fault current (or) 31 X I> setting (whichever is lowest)
Requirement 1:
Maximum Prospective Secondary Earth Fault current = Ikmax / Ipn (Ikmax = Maximum Earth Fault Current = 750 A)
Requirement 2:
(I> setting is 0.8 A which is equivalent to 750 A
31 X I> setting = 31 X 0.8
in CT primary)
= 16 A
Therefore,
Vk [1/2] X (2.63 + 1.104 + 0.04) (Refer Note - 2)
1.89 V
2.00 V
1.2 X 2
= 2 V (with 20% margin)
Where,
Isp Maximum Prospective Secondary Phase fault current
(Ikmax = Maximum Earth Fault Current = 750 A)
Maximum Prospective Secondary Earth Fault current = Ikmax / Ipn
3.77 V
4.00 V
1.2 X 4
= 5 V
Estimation of VA
VA = -2.39
VA = 15.00 (Adopted)
Page 96 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
2
Sb,cal = (Rrelay + R2lead ) x IR
= (0.04 + 1.104) X 1^2
= 1.144 VA
Sb,req Sb,cal
1.144 VA
The 5P20 class CT shall comply within composite error of ± 5% for 20 times the rated CT current
flow in its windings at rated burden.
Rated Frequency
Current(2.5*Isc)
Rated Dynamic
Rated Burden
burden
current
(I n)
Rated Burden VA : 15
o
Max. resistance of sec.winding at 75 C Rct < 2.63 Ohm
Note
1 Maximum Earth Fault current when both transformers are in parallel will not exceed 750 A.
2 The Plug setting is considered as 100% In.
Since the 'Actual ALF' is greater than highest value, the relay will pickup
3
positively.
Page 97 of 101
Core – 2
C11NCT2 &C21NCT2
(2500 / 1 A)
Page 98 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
C. CT Sizing Calculation for 132/11kV Station Transformer Feeders( 11kV side - Neutral): C11 & C21
Core-2: C11NCT2 & C21NCT2 P141 - HV Restricted earth fault protection @ 2500A TAP
b. System frequency fn : 50 Hz
d. Class : PX
o Rct :
e. Max. Sec. Winding Resistance at 75 C 12 Ohm
((Ass per
pe the
t e sswitchgear
tc gea manufacturer
a u actu e feasibility)
eas b ty)
Tranformer Details
Rating = 40 MVA
= 2470.0 A
a. Make : AREVA
b. Type : P141
c. Rated current IR : 1 A
c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)
Page 99 of 101
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
f. Maximum through fault current on primary side Ithr3ph = 14440 A (Refer Annexure - F6)
g. Through falut X/R Ratio X/R = 36.46
1.1.4.2 Determination minimum knee point voltage
(Condition - 2)
Where X/R > 25,
Vs Is x Rs
Rs (If/Is) x (Rct+R2lead+Rrelay)
where,
where
ISn = 1 A
Ipn = 2500 A
Maximum Prospective Secondary through Fault current If = Ithr3ph / Ipn (Ithr3ph = Maximum Fault current = 14440 A)
Therefore,
Class : PX
Rated Knee point e.m.f (Min. Required) based on REF Vk > 365 V
Note:
1 The final Knee Point voltage adopted will be identical to both Phase side (11 KV AIS) and Neutral side CTs.