2.2 HSBT
• Five abnormal starting logics are deployed to recognize the power loss of motor bus. The under-voltage,
under-frequency, change rate of frequency and reverse power caused by power loss is to self-start HSBT.
Even, the in-advertent CB open can be quickly and reliably recognized by 7VU683 and is used to self-start
HSBT.
• FAULT starting condition is classified into type A and B, and can have different switching sequence. This
could be practical in some cases, i.e, type A reflects electric fault while type B reflects non-electric faults.
To avoid the unwanted transfer, measures have to be taken to block HSBT under some operation conditions,
for example,
• CB manual open;
• MCB trip of bus voltage;
• Motor bus fault.
The blocking indications from operator, MCB auxiliary status and bus protective relay should be externally wired
to the binary input 17620 >Block HSBT.
HSBT will automatically be in blocking status and reject any new transfer request after every transfer failure. It
has to be manually reset.
In some cases, it is required to block the device even after the successful transfer and can only conduct the
next transfer request after manual reset. This can be actualized by setting the parameter 8817 Manual Reset
HSBT = YES.
The reset command can be recognized via BI indication 17863 ">Manually reset" or LED reset button on
device panel.
• Line dead voltage threshold: the dead status of line voltage is monitored by this parameter. Typical setting
value ranges from 0.200 U/Un to 0.300 U/Un;
• Line dead current threshold: the live status of line current is monitored by this parameter. Typical setting
value ranges from 0.10 I/In to 0.20 I/In.
Functionality as below can be activated or de-activated under Function:
• VT rated primary voltage of line: directly taken from line VT's plate;
• VT rated secondary voltage of line: directly taken from line VT's plate;
• VT rated primary voltage of busbar: directly taken from bus VT's plate;
• VT rated secondary voltage of busbar: directly taken from bus VT's plate.
Current transformer has to be parameterized as below under CT's:
• CT rated primary current of line: directly taken from line CT's plate;
• CT rated secondary current of line: directly taken from line CT's plate;
• CT rated primary current of busbar: directly taken from bus CT's plate;
• CT rated secondary current of busbar: directly taken from bus CT's plate;
• Earth CT rated primary current of busbar: directly taken from bus CT's plate. It's only required if measured
value instead of computed value of earth current for ground fault protection is adopted;
• Earth CT rated secondary current of busbar: directly taken from bus CT's plate; It's only required if measured
value in-stead of computed value of earth current for ground fault protection is adopted.
The minimum pulse width of OPEN and CLOSE command can be parameterized under CB:
• Minimum TRIP command duration: the factory value 0.2 s should be enough for most cases;
• Minimum CLOSE command duration: the factory value 0.2 s should be enough for most cases.
2.2.1.5 Settings