You are on page 1of 1

COLD WATER PRESSURE DROP CALCULATION

Number Up Node Down Node WSFU GPM Pipe Dia. in Inside Diameter, in Velocity, fps Length, ft Fittings Qty E. Length Total Length Pressure Drop/100 ft Pressure Drop T. Press. Drop
1 1 2 16 12 0.75 0.803 7.6 76 Gate Valve 1 0.6 90.40 10.46 9.45584 9.45584
Check Valve 1 8.8
Water Meter 1 0.8
Elbow 2 2.1
2 2 3 9 7.5 0.5 0.638 7.5 17.4 Tee Run 1 1.0 23.20 15.77 3.65864 13.11448
Elbow 3 1.6
3 3 4 7 6 0.5 0.638 6.0 5.8 Tee Run 1 1.0 13.60 10.44 1.41984 14.53432
Elbow 4 1.6
Gate Valve 1 0.4
4 4 5 6 5 0.5 0.638 5.0 2.1 Tee Branch 1 3.1 5.20 7.45 0.38740 14.92172
5 5 6 3 3 0.5 0.638 3.0 5.4 Tee Run 1 1.0 17.60 2.89 0.50864 15.64686
Elbow 2 1.6
Elevation 0.5 0.2165
Angle Valve 1 8
Minimum Pressure Required at End = 15 psi
Minimum Pressure Required at Water Main Required at End + Pressure Drop 30.64686 psi