Professional Documents
Culture Documents
COMPRESSORS
TYPES OF COMPRESSORS.
Each of the four components of a vapor-compression
system – the compressor, the condenser, the
expansion device, and the evaporator has its own
peculiar behavior. At the same time, each
component is influenced by the conditions imposed
by the other members of the quartet. A change in
condenser-water temperature, for example, may
change the rate of refrigerant in the compressor
pumps, which in turn may require the expansion
valve to readjust and the refrigerant in the
evaporator to change pressure. The compressor is
the first to be analyzed.
1
3/11/2023
TYPES OF COMPRESSORS
The heart of the vapor-compression system is the
compressor. The four most common types of
refrigeration compressors are the reciprocating,
screw, centrifugal, and vane. The reciprocating
compressor consists of a piston moving back and
forth in a cylinder with suction and discharge valves
arranged to allow pumping to take place. The screw,
centrifugal, and vane compressors all use rotating
elements, the screw and vane compressors are
positive-displacement machines, and the centrifugal
compressor operates by virtue of centrifugal force.
RECIPROCATING COMPRESSORS.
The workhorse of the refrigeration industry is the
reciprocating compressor, built in sizes ranging from
fractional-kilowatt to hundreds of kilowatts
refrigeration capacity. Modern compressors are
single-acting and may be single-cylinder or
multicylinder. In multicylinder compressors, the
cylinders are in V, W, radial, or in-line arrangements.
The compressor in Figure 1 has 16 cylinders, 2 in
each of the heads.
During the suction stroke of the piston, low–pressure
refrigerant gas is drawn in through the suction valve,
which may be located in the piston or in the head.
During the discharge stroke the piston compresses
the refrigerant and then pushes it out through the
discharge valve, which is usually located in the
cylinder head.
2
3/11/2023
3
3/11/2023
CONDENSING UNITS.
The compressor and the condenser of a system are
conveniently combined into a condensing unit.
(Figure 3). The motor, compressor, and condenser
may be compactly mounted on the same frame and
located remotely from the expansion valve and
evaporator.
PERFORMANCE.
Two of the most important performance
characteristics of a compressor are its
refrigeration capacity and its power requirement.
These two characteristics of a compressor
operating at constant speed are controlled largely
by the suction and discharge pressures. An
analysis will be made first of an ideal reciprocating
compressor because it affords a clearer
understanding of the effects of these two
pressures.
4
3/11/2023
VOLUMETRIC EFFICIENCY.
Volumetric efficiencies are the bases for predicting
performance of reciprocating compressors. Two
types of volumetric efficiencies will be considered,
actual and clearance. The actual volumetric
efficiency ηva is defined by
volume flow rate entering compressor , m 3 s
ηva = × 100 (1)
displacement rate of compressor , m 3 s
VOLUMETRIC EFFICIENCY.
In the first instance, assume that the suction
pressure is p1. Gas trapped in the clearance volume
must first expand to volume V1 before the pressure
in the cylinder is low enough for the suction valves to
open and draw in more gas. The volume of gas
drawn into the cylinder will be V3 – V1, and the
clearance volumetric efficiency ηvc for this case is
(V3 – V1)(100)/(V3 – Vc).
5
3/11/2023
VOLUMETRIC EFFICIENCY.
Adding Vc – Vc to the numerator of the expression for
hvc gives
V3 − Vc + Vc − V1 V −V
ηvc = × 100 = 100 + c 1 × 100 (3)
V3 − Vc V3 − Vc
and
V1 − Vc Vc V1
ηvc = 100 − ×100 = 100 − − 1 × 100
V3 − Vc V3 − Vc V
c
Therefore,
V1
ηvc = 100 − c − 1
Vc
If an isentropic expansion is assumed between Vc
and V1,
V1 v suc (5)
=
Vc vdis
11
VOLUMETRIC EFFICIENCY.
Values of the specific volumes are available from the
pressure-enthalpy diagram of the refrigerant or from
tables of properties of superheated vapor.
Substituting Equation (5) into Equation (4) gives
v suc
ηvc = 100 − c − 1 (6)
vdis
12
6
3/11/2023
13
14
7
3/11/2023
POWER REQUIREMENT.
The power required by the ideal compressor is the
product of the mass rate of flow and the increase in
enthalpy during the isentropic compression,
P = m∆ hi (8)
where P = power, kW
w = mass rate of flow, kg/s
∆hi = isentropic work of compression, kJ/kg
REFRIGERATING CAPACITY.
The refrigerating capacity q is
q = w (h1 − h4 ) kW (9)
where h1 and h4 are the enthalpies in kilojoules per
kilogram of the refrigerant leaving and entering the
evaporator, respectively. The refrigerating effect; h1
– h4, increases slightly with an increase in suction
pressure, as Figure 7 shows, provided that the
enthalpy entering the expansion valve remains
constant. The increase is due to the slightly higher
enthalpy of saturated vapor at higher evaporating
temperatures.
8
3/11/2023
18
9
3/11/2023
19
10
3/11/2023
11
3/11/2023
COMPRESSION EFFICIENCY.
The compression efficiency ηc in percent is
24
12
3/11/2023
EXAMPLE NO. 1
(a) The clearance volumetric efficiency is The actual volumetric efficiency is, then,
v v
η vc = 100 − c suc − 1 = 100 − c 1 −1 V1 volume flow rate entering compressor , m 3 s
v v ηva = = × 100
dis 2 VD displaceme nt rate of compressor , m 3 s
43.2
η vc = 100 − 4.8 − 1 = 90.1% 27.04 L s
14.13 ηva = × 100 = 77.3%
34.97 L s
(b) The compressor displacement rate is
(c) The compression efficiency is the isentropic
π (0.067)2 3
VD = (6 cyl )(29 r s ) m cyl ⋅ r (0.057) work of compression divided by the actual
4 work of compression. The latter is
VD = 0.03497 m3 s = 34.97 L s
The actual rate of refrigerant flow is actual work of compression = W ′ = 28.9 kW
q = m(h1 − h4 ) kW so that
96.4 kW isentropic work of compression
m= = 0.6260 kg s ηc = ×100
413.1 − 259.1 kJ kg actual work of compressio n
m(h2 − h1 )
The actual volumetric flow rate of the refrigerant ηc = ×100%
W′
measured at the compressor suction is
V1 = (0.6260 kg s )(43.2 L kg ) = 27.04 L s ηc =
(0.6260 kg s )(444.5 − 413.1 kJ kg )
× 100 = 68%
28.9 kW
26
13
3/11/2023
CAPACITY CONTROL.
If a refrigeration system is operating in a steady- Several methods are commonly used to reduce the
state mode and the refrigeration load decreases, the compressor capacity:
inherent response of the system is to decrease the 1. In cycling the compressor stops and starts as
evaporating temperature and pressure. This change needed. The method works well in small
in the evaporator condition results in reduced systems.
compressor capacity, which ultimately matches the 2. Back-pressure regulation throttles the suction
reduced refrigeration load. The reduction in gas between the evaporator and the
evaporator temperature may be undesirable for compressor to keep the evaporator pressure
constant. This method gives good control of
several reasons. the evaporator temperature but is inefficient.
3. Bypassing the discharge gas back to the
In air conditioning, the coil may collect frost and suction line usually affords precise capacity
block the airflow, further reducing the evaporator reduction, but the method is inefficient and
pressure. Stored fresh food and many other the compressor often runs hot. A preferred
products may be damaged by low temperatures. If bypass circuit delivers the discharge gas that
the evaporator chills a liquid, the liquid may freeze is bypassed back to the entrance of the
evaporator.
and burst a tube in the evaporator.
4. Another method is cylinder unloading on a
multicylinder compressor by automatically
holding the suction valve open or diverting the
discharge gas from a cylinder back to the
suction line before compression.
28
14
3/11/2023
29
15
3/11/2023
31
32
16
3/11/2023
33
CAPACITY CONTROL.
Many screw compressors are equipped with a
sliding valve for capacity control. It is in the housing
of the compressor and can be moved axially. As the
valve is opened, it delays the position at which
compression begins. The capacity can be
modulated down to about 10 percent of full
capacity, although there is loss of efficiency in the
capacity reduction.
34
17
3/11/2023
VANE COMPRESSORS.
35
VANE COMPRESSORS.
The two basic types of vane compressors are the
roller or single-vane and the multiple-vane type.
Vane compressors are used mostly in domestic
refrigerators, freezers, and air conditioners,
although they can also be used as booster
compressors in the low-pressure portion of large Figure 18. Roller-type vane compressor.
multistage compression systems.
18
3/11/2023
VANE COMPRESSORS.
The formula for the displacement rate D of the
roller-type compressor is
π
D=
4
( )
A2 − B2 (L)(rotative speed ) m3 s (10)
where A = cylinder diameter, m
B = roller diameter, m
L = cylinder length, m
and the rotative speed is in revolutions per second.
37
VANE COMPRESSORS.
For the two-vane compressor in Figure 20, the
displacement per revolution is proportional to twice
the crosshatched area. For the four-vane
compressor, the displacement per revolution is
proportional to 4 times the crosshatched area. Up
to a certain point, then, the displacement is
greatest on the compressor with the largest
number of vanes.
In the two types of rotary compressors shown here
no suction valves are needed, and since the suction
gas enters the compressor continuously, gas
pulsation is at a minimum.
38
19
3/11/2023
CENTRIFUGAL COMPRESSORS
39
40
20
3/11/2023
OPERATION.
Centrifugal compressors are similar in construction
to centrifugal pumps in that the incoming fluid
enters the eye of the spinning impeller and is
thrown by centrifugal force to the periphery of the
impeller. Thus the blades of the impeller impart a
high velocity to the gas and also build up the
pressure.
41
FLASH-GAS REMOVAL.
A centrifugal compressor with two or more stages
invites the use of flash-gas removal. Flash gas can
be removed by partially expanding the liquid from
the condenser, separating the flash gas, and then
recompressing the gas instead of dropping its
pressure further. Flash-gas removal increases the
efficiency of the cycle and is conveniently achieved
when two or more stages of compression are
available.
42
21
3/11/2023
PERFORMANCE CHARACTERISTICS.
One choice of coordinates for presenting the
characteristics is shown in Figure 22: the
discharge-to-suction-pressure ratio versus the flow
rate. The graph shows the performance for several
different compressor speeds and isoefficiency lines
(lines of constant efficiency). No performance
curves are shown to the left of the surge line.
P = mV2t2 (14)
44
22
3/11/2023
45
EXAMPLE NO. 2
Calculate the speed of the impeller tip in order to Solution:
compress the following refrigerants from saturated (a) In the isentropic compression of refrigerant
vapor at 10 C to pressure corresponding to a 11 from saturated vapor at 10 C to a
condensing temperature of 30 C when the saturated condensing temperature of 30 C
refrigerant is (a) refrigerant 11 and (b) ammonia.
∆hi = 406.7 − 393.9 = 12.8 kJ kg
Given: The tip speed is
Evaporating temperature of 10 C
V2t = 1000(12.8 ) = 113.1 m s
Condensing temperature of 30 C
Required:
Speed of the impeller tip for (a) refrigerant 11 and (b) For ammonia
(b) ammonia.
∆hi = 1560 − 1472 = 88 kJ kg
The tip speed is
V2t = 1000(88 ) = 297 m s
46
23
3/11/2023
47
SURGING.
Figure 22 shows no performance data to the left of
the surge envelope, although the classic
performance of a backward-curved-blade pump, fan,
and compressor would be shown by the dashed line
in Figure 23. As the refrigeration load drops off and
the flow rate decreases from point A, the
performance rides up the pressure-flow
characteristic to point B.
48
24
3/11/2023
CAPACITY CONTROL.
The two most efficient and most widely used
methods of capacity control are (1) adjusting
prerotation vanes at the impeller inlet and (2)
varying the speed. Two methods that are not
efficient and not widely used are varying the
condenser pressure and bypassing the discharge
gas. The latter was mentioned as a means of
preventing surge and is sometimes combined with
prerotation vanes.
49
50
25
3/11/2023
END
51
26