technical data

air conditioning systems


FTN-EV1B

Wall Mounted Unit

Split
Sky Air
• Indoor Units • R-410A • FTN-EV1B

TABLE OF CONTENTS
FTN-EV1B

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 5


Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring diagram ....................................................... 8

6 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

• Split Sky Air • Indoor Units 1


• Indoor Units • R-410A • FTN-EV1B

1 Features

t i y n k U S B 1 r AVt o 0E i o 1- ld 4N pnT- FSR•I Flat front panel: its stylish appearance blends easily within any • The photocatalytic deodorising air filter: powerfully decomposes
interior décor and is more easy to clean. cigarette and pet odours, removes house dust and pollen and
deactivates bacteria and viruses
• Extremely quiet in operation
• Auto-swing function ensures efficient air and temperature • Washable front panel
distribution. • Daikin remote controls give you easy control at your fingertips.
• Powerful mode can be selected for rapid cooling • The indoor unit also has a start/stop button mounted on the front
1 • Air purification filter: deodorises the air and helps to prevent bacterial
panel
and viral propagation • Up to 5 indoor units can be operated from a single centralised control
• Purpose-designed holder provided for your remote control

optional 5 steps

standard 50 + 60 class

2 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FTN-EV1B

2 Specifications

2-1 FOR INDOOR UNITS ONLY


Nominal Input Cooling kW
FTN50EV1B
0.034
FTN60EV1B
0.040
3
2-2 TECHNICAL SPECIFICATIONS FTN50EV1B FTN60EV1B
Casing Colour White
Dimensions Packing Height mm 366 366 2
Width mm 1147 1147
Depth mm 337 337
Unit Height mm 290 290
Width mm 1050 1050
Depth mm 238 238
Weight Unit kg 12.0 12.0
Packed Unit kg 17.0 17.0
Heat Dimensions Length mm 863 863
Exchanger Nr of Rows 2 2
Fin Pitch mm 1.40 1.40
Nr of Stages 16 16
Tube type Hi-XA (7)
Fin Type ML fin (Multi louver)
Fan Type Cross flow fan
Air Flow Rate Cooling High m³/min 14.7 16.2
Medium m³/min 12.4 13.6
Low m³/min 10.3 11.4
Fan Motor Quantity 1 1
Model ARW30R8P43DA
Number of steps 5 steps, silent and auto
Motor Speed High rpm 1240 1330
(cooling) Medium rpm 1090 1170
Low rpm 930 1010
Fan Motor Output W 43 43
(high)
Cooling Sound Power High dBA 59.0 61.0
Sound High dBA 43.0 45.0
Pressure Low dBA 34.0 36.0
Refrigerant Type R-410A
Piping Liquid (OD) Diameter mm 6.35 6.35
connections (OD)
Gas Diameter mm 12.7 12.7
(OD)
Drain Diameter mm 18 18
(OD)
Heat Insulation Both liquid and gas pipes
Air Filter Removable/washable/Mildew proof
Air direction control Left, right, up and downwards
Temperature control Microcomputer control

• Split Sky Air • Indoor Units 3


• Indoor Units • R-410A • FTN-EV1B

2 Specifications

2-2 TECHNICAL SPECIFICATIONS FTN50EV1B FTN60EV1B


Standard Item Installation manual
Accessories Quantity 1 1
Item Operation manual
Quantity 1 1
Item Infrared remote control
2
Quantity 1 1
Item Indoor unit fixing screws
Quantity 2 2
Item Batteries
Quantity 2 2
Item Titanium apatite photocatalytic air purification filter
Quantity 2 2
Item Remote control holder
Quantity 1 1
Item Mounting plate
Quantity 1 1
Notes Sound values are measured in an anechoic room.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details,
please refer to sound level drawings of this chapter.
The sound power level is an absolute value indicating the power which a sound source generates.

2-3 ELECTRICAL SPECIFICATIONS FTN50EV1B FTN60EV1B


Power Supply Name V1
Phase 1 1
Frequency Hz 50 50
Voltage V 220-240
Current Nominal Cooling A 0.15 0.18
running current
(RLA)
Wiring For Power Quantity 3 3
connections Supply Remark 4 for interunit wiring (included earth wiring)
Voltage range Minimum -10%
Maximum +10%
Power Supply Intake Outdoor unit only

4 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FTN-EV1B

3 Dimensional drawing & centre of gravity


3-1 Dimensional drawing

FTN50-60E Air flow (indoor)


(for performance and
unit (mm) 3
maintenance)
The mark (Y) shows piping direction

performance)
30 Min.
Rear Rear

(space for
Left Right
(space for
maintenance)
50 Min. 50 Min.
3
(space for
maintenance)
(Including Required space
mounting plate)

Operation lamp
Signal receiver Model name plate
Indoor unit ON/OFF switch
Terminal block
Room temp. with earth
thermistor (Inside) terminal (inside)
Gas pipe 12.7Cut (The length of pipe Drain hose for VP13 (connecting part
outside the unit: about 340) I.D.14.0, O.D.18.0)
Timer lamp
(The hose length on the outside of
Front grille fixing screws the unit is approx. 440)
(inside) Liquid pipe J6.4 CuT (the length of pipe outside
Flaps the unit: about 390)

Signal
transmitter Blade angle
Horizontal blade
(Automatic)
Cooling Dry

Fan
Vertical blade(Manual) Wall hole J
Infrared remote control 80 hole
Wall hole for embedded piping
(ARC433A24) J 80 hole
Standard locations of wall holes
3D051704

• Split Sky Air • Indoor Units 5


• Indoor Units • R-410A • FTN-EV1B

3 Dimensional drawing & centre of gravity


3-2 Centre of gravity
FTN50-60E

4D040313S

6 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FTN-EV1B

4 Piping diagram

FTN50-60E
3
Indoor unit

Heat exchanger

Thermistor on heat
exchanger

Cross flow fan


Field piping

Fan motor
Field piping

Refrigerant flow
Cooling
Heating
4D040081L

• Split Sky Air • Indoor Units 7


• Indoor Units • R-410A • FTN-EV1B

5 Wiring diagram
5-1 Wiring diagram

FTN50-60E

g
Field wiring

5 Rectifier

Outdoor

CAUTION
Transmission circuit
Note that operation will restart
automatically if the main power
supply is turned off and then back
on again.

R : Protective earth
FG : Frame ground
FU : Fuse
H1∼H3 : Harness
H1P∼H3P : Pilot lamp
M1F : Fan motor
M1S : Swing motor
PCB1∼PCB4 : Printed circuit board
R1T,R2T : Thermistor
S1∼S38 : Connector
S1W : Operation switch
X1M : Terminal strip

Indoor NOTES
1 Size: length 70 x width 120.
Signal receiver 2 Nameplate material: wood free tack paper
3 Coat the reverse side with pressure sensitive adhesive
Infrared remote 4 Refer to purchasing specification AS303002, unless otherwise specified.
control 5 This drawing was drawn on CAD system.
6 Make a slit on separate liner in vertical direction

3D038532B

8 • Split Sky Air • Indoor Units


• Indoor Units • R-410A • FTN-EV1B

6 Sound data
6-1 Sound pressure spectrum
FTN50E FTN60E 3

6
Octave band sound pressure level

Octave band sound pressure level


dB:(0dB = 0.0002 µ bar)

dB:(0dB = 0.0002 µ bar)


approximate threshold approximate threshold
hearing for continuous hearing for continuous
noise noise

4D051229 4D051232
Octave band center frequency (Hz) Octave band center frequency (Hz)

NOTE NOTE
1 Operation noise differs with operation and 1 Operation noise differs with operation and
ambient conditions. ambient conditions.
Location of microphone Location of microphone

Legend Legend
50Hz 220-240V(H) 50Hz 220-240V(H)
50Hz 220-240V(L) 50Hz 220-240V(L)

• Split Sky Air • Indoor Units 9


Split - Sky Air

The present publication is drawn up by way of ISO14001 assures an effective environmental Daikin units comply with the European
information only and does not constitute an offer management system in order to help protect regulations that guarantee the safety of
binding upon Daikin Europe N.V.. Daikin Europe N.V. human•health•and the environment from the potential the product.
has compiled the content of this publication to the impact of our activities, products and services and to
best of its knowledge. No express or implied warranty assist in maintaining and improving the quality of
is given for the completeness, accuracy, reliability or the•environment.
fitness for particular purpose of its content and the
products and services presented therein. Specifications
are subject to change without prior notice. Daikin
Europe N.V. explicitly rejects any liability for any direct Daikin Europe N.V. is approved by LRQA for its Quality Daikin Europe N.V. is participating in the
or indirect damage, In the broadest sense, arising from Management System in accordance with the ISO9001 EUROVENT Certification Programme.
or related to the use and/or interpretation of this standard. ISO9001 pertains to quality assurance regarding Products are as listed in the EUROVENT
publication. All content is copyrighted by Daikin design, development, manufacturing as well as to services Directory of Certified Products.
Europe N.V.. related to the product.
Prepared in Belgium by Lannoo
EEDE06-1/3 • 05/2006

Zandvoordestraat 300
B-8400 Ostend - Belgium
www.daikineurope.com