You are on page 1of 72

5/3/2022

Contact information
2018 to 2021 Uniform
• G.F.(jed) Scheuermann
Plumbing Code Changes
• E-mail to: jed.scheuermann@iapmo.org
Presented By: Jed Scheuermann
• Cellular: (971) 300-7649

seminars@iapmo.org | www.iapmo.org | www.iapmolearn.org

Copyright © IAPMO 2021 2

1 2

Copyright

• The content provided here is copyrighted material.


Use of any of the material for other than personal
use is strictly prohibited without the written consent
of the International Association of Plumbing and
Mechanical Officials (IAPMO).

Copyright © IAPMO 2021 3 Copyright © IAPMO 2021 4

3 4

Disclaimers Who am I?
Background & Contact information:

Image Disclaimer • Master & Journeyman Plumber:


• The graphics and illustrations used in this course are presented for educational purposes
• Canada (also Gas Fitter & Steamfitter)
only. IAPMO does not endorse or recommend the vendor/product depicted, nor any vendor or
product. IAPMO makes no representations, warranties or guarantees as to, and assumes no • Oregon (Montana reciprocal State)
responsibility for, the product(s) depicted and IAPMO expressly disclaims all liability for • Alabama
damages of any kind arising out of the use or performance of the vendors, products or
services depicted. • Plumbing & Mechanical Inspector
Content Disclaimer • Field Manager & IWSH Director of N. American Projects
• The information herein is provided for educational purposes only and shall not be treated as
an official interpretation of the referenced codes or standards. Always refer to the complete • Humanitarian
code or standard when installing, replacing, or repairing any plumbing or mechanical system.

Copyright © IAPMO 2021 5 Copyright © IAPMO 2021 6

5 6

Copyright©IAPMO 2022

1
5/3/2022

Question:
Who are you?

“The society which scorns excellence in plumbing as a


• (a) plumbing inspector humble activity and tolerates shoddiness in philosophy
because it is an exalted activity will have neither good
• (b) journeyman or Master plumber plumbing nor good philosophy: neither its pipes nor its
theories will hold water.”
• (c) engineer, designer, architect
John William Gardner
• (d) more than one of the above, or none of the above

Copyright © IAPMO 2021 7 Copyright © IAPMO 2021 8

7 8

What to expect? Legend


This class will focus on: Symbols to indicate changes

• 2018 to 2021 UPC changes


• New provisions & chapters
• Montana Amendments
• Opportunities for interaction:

• Q&A
• Scenarios
• Many relevant photographs!

Copyright © IAPMO 2021 9 Copyright © IAPMO 2021 10

9 10

Section Relocation Chapter 1


Indicates what moved & where it is now located… Administration

• Overview: There have been no changes to this chapter from 2018


• Found on pp. xv and xvi edition.
• 101.2 Scope. The provisions of this code shall apply to the erection,
installation, alteration, repair, relocation, replacement, addition to, use, or
• Very helpful quick reference guide maintenance of plumbing systems within this jurisdiction.
• 101.3 Purpose. This code is an ordinance providing minimum
requirements and standards for the protection of the public health, safety,
and welfare.
• “minimum standards”
• Goal? Protect “…public health, safety & welfare…”

Copyright © IAPMO 2021 11 Copyright © IAPMO 2021 12

11 12

Copyright©IAPMO 2022

2
5/3/2022

Montana amendments 24.301.146 (1, 2 & 3)


Additions to & deletions from model code References to other codes

• (1) The following modifications to the IBC are applicable to both the
• All of these may be found at Montana department’s enforcement program and local government building code
Department of Labor & Industry, Business enforcement programs.
Standards Division, web site under
“Current Codes” • (2) Subsection 101.4, Referenced Codes, is modified by adding the
following: “Any reference to a separate specialty code, by title, either in
this subsection or elsewhere in this code, shall be considered deleted
• http://www.mtrules.org/gateway/Subchapt
erhome.asp?scn=24%2E301.3
and replaced with the title of the model code adopted and in effect at the
time as applicable.”
• Class will sequentially incorporate all
• (3) Subsection 101.4.3, Plumbing is modified by:
Montana plumbing amendments • (a) Deleting “International Plumbing Code” and replacing with “Uniform Plumbing
Code.”

Copyright © IAPMO 2021 13 Copyright © IAPMO 2021 14

13 14

24.301.146 (25 & 26) 24.301.154 (3)


Minimum number of Plumbing Fixtures Uniform Plumbing Code INCORPORATION BY REFERENCE OF IRC

• (25) Table 2902.1 MINIMUM NUMBER OF PLUMBING FIXTURES, is • (3) Chapters 11 through 14, inclusive, are deleted in their
modified by deleting and replacing with ARM 24.301.351.
entirety and chapters 16 through 43 are deleted in their
• (26) Subsection 2902.3, Required Public Toilet Facilities, is deleted in its entirety…
entirety and replaced with “Required Public Toilet Facilities shall be
provided in accordance with the Uniform Plumbing Code 2021 Section • These chapters include IRC “plumbing” provisions. It
422.4. takes all plumbing out of the IRC, replacing them with
• This takes these minimum requirements out of the International Building UPC provisions.
Code IBC and replaces them with UPC provisions.

Copyright © IAPMO 2021 15 Copyright © IAPMO 2021 16

15 16

24.301.172 (1) (b) 24.301.173 (1) (b)


INCORPORATION BY REFERENCE OF IMC INCORPORATION BY REFERENCE OF IMC

• (1) (a) Subsection 102.8, Referenced Codes and Standards, is • (1) (a) Subsection 102.8, Referenced Codes and Standards, is
modified by adding the following: “Any reference to a separate modified by adding the following: “Any reference to a separate
specialty building regulation, by title, either in this subsection or specialty building regulation, by title, either in this subsection or
elsewhere in this code, shall be considered deleted and replaced elsewhere in this code, shall be considered deleted and replaced
with the title of the model code adopted by the department and in with the title of the model code adopted by the department and in
effect at the time. effect at the time. For example, all references to the International
• (b) All references to the International Plumbing Code shall be Plumbing Code shall be deleted and replaced with the Uniform
deleted and replaced with the Uniform Plumbing Code. Plumbing Code.
• It takes all plumbing out of the IMC, replacing them with UPC • It takes all plumbing out of the IFGC, replacing them with UPC
provisions. provisions.

Copyright © IAPMO 2021 17 Copyright © IAPMO 2021 18

17 18

Copyright©IAPMO 2022

3
5/3/2022

24.301.301 24.301.301
Incorporation by reference of Uniform Plumbing Code Incorporation by reference of Uniform Plumbing Code

• (1) The department adopts and incorporates by reference the


Uniform Plumbing Code, 2021 edition, unless another edition is • (d) Appendix D, Sizing Stormwater Drainage systems is adopted.
specifically stated, together with the following appendix chapters
and amendments: • (e) Appendix K, Potable Rainwater Catchment Systems is
adopted.
• (a) Appendix A, Recommended Rules for Sizing the Water
Supply System is adopted. • (f) Appendix L, Sustainable Practices is adopted.
• (b) Appendix B. Explanatory Notes on Combination Waste and • (g) Appendix M, Peak Water Demand Calculator is adopted.
Vent systems is adopted. • (h) Appendix N, Impact of Water Temperature on the Potential for
• (c) Appendix C, Alternate Plymbing Systems is adopted. Scalding and Legionella Growth.

Copyright © IAPMO 2021 19 Copyright © IAPMO 2021 20

19 20

REASON: 24.301.301 (1) (a)-(h) 24.301.301 (2)


Montana Amendment

• 24.301.301 (1) (a)-(h) are modified to reflect the 2021 edition and
add additional appendices for alternative methods of compliance. • The purpose of this code is to provide minimum requirements
(d)-(h) are relabeled as (i)-(m). (i) is repealed as it now mirrors and standards for plumbing installations for the protection of the
the text in the UPC 2021. (l) is relabeled as (o). (m) is repealed public health, safety, and welfare. The Uniform Plumbing Code is
as it mirrors the text in the UPC 2021. (n)-(p) are relabeled as a nationally recognized model code setting forth minimum
(p)-(w). (x) new amendment, Plumbers rarely know where crawl standards and requirements for plumbing installations. A copy of
access holes will be located when installing the underground the Uniform Plumbing Code may be obtained from the
piping. (v) is relabeled as (y). (w) is repealed as it now mirrors International Association of Plumbing and Mechanical Officials at
the text in the UPC 2021. (x)-(ah) are relabeled as (z)-(aj). www.iapmo.org

Copyright © IAPMO 2021 21 Copyright © IAPMO 2021 22

21 22

24.301.301 (1) (d) 24.301.301 (1) (e)


Montana amendment Montana amendment

• Subsection 103.3.1, Licensing is amended with the addition of the • (i) No permit is required for any minor replacement or repair
following language: work, the performance of which does not have a significant
• “Provision for licensing shall be determined by the Authority Having potential for creating a condition hazardous to public health and
Jurisdiction. The requirements for who must be licensed to perform safety.
plumbing work is regulated by Title 37, chapter 69, MCA.”
• (ii) No permit is required where the installation is exempt under
• (1) (e) Subsections 104.1, 104.2, 104.3, 104.3.2, 104.4, 104.5, 105.0, provisions of 50-60-503 or 50-60-506, MCA.
105.4, 106.1, 106.3 and 107.0 will be left as is for use by local
governments (i.e., municipalities and counties), but will not be used by • (iii) The requirements for permits do not apply to regularly
the department and the state of Montana. For the purposes of employed maintenance personnel doing maintenance work on
enforcement by the department, these subsections are replaced with the business premises of their employer unless work is subject to
provisions of Title 50, chapter 60, part 5, MCA. the permit provisions of these rules.

Copyright © IAPMO 2021 23 Copyright © IAPMO 2021 24

23 24

Copyright©IAPMO 2022

4
5/3/2022

24.301.301 (1) (e) 24.301.301 (1) (f)


Montana amendment Montana amendment

• Delete Table 104.5 – PLUMBING PERMIT FEES and replace with the
following schedule:
• (i) for each plumbing fixture $10
• (iv) Factory-built buildings covered by an insignia issued by the
department need not have a plumbing permit for the construction • (ii) water service – domestic or commercial 20
of the unit; however, a permit will still be required for on-site • (iii) for each building sewer and each trailer park sewer 20
work, as provided for in these rules. • (iv) storm drains and storm drainage 20
• (v) for each water heater (replacement or new) 25
• (vi) for each industrial water pretreatment interceptor, including its tray
and vent, excepting kitchen type grease interceptors functioning as
fixture traps 30

Copyright © IAPMO 2021 25 Copyright © IAPMO 2021 26

25 26

24.301.301 (1) (f) 24.301.301 (1) (f)


Montana amendment (continued) Montana amendment (continued)

• (vii) for alteration or repair of water piping and/or water treatment • (xi) requested plumbing inspection fee (provided that such service is not
equipment 30 in excess of one hour duration, and then in $35 for each 30 minutes or
• (viii) for repair or alteration of drainage or vent piping 30 fractional part thereof in excess of one hour. Travel and per diem may be
charged as per the state of Montana’s existing rate for these items) 75
• (ix) for each lawn sprinkler system and fire protection system or any one
meter, including backflow protection devices therefore 30 • (xii) reinspection (provided the $30 does not exceed the original permit
fee, in which case the original fee will be charged) 45
• (x) for each hose bibb, vacuum breakers, or backflow protective devices
on tanks, vats, etc., or for installation on unprotected plumbing fixtures,
including necessary water piping 6 each

Copyright © IAPMO 2021 27 Copyright © IAPMO 2021 28

27 28

24.301.301 (1) (f) 24.301.301 (1) (f)


Montana amendment (continued) Montana amendment (continued)

• (xiii) for each medical gas type/piping system as follows:


• (A) oxygen piping 100
• (B) nitrogen piping 100 • (xiv) for each gray water system (commercial or residential) 60
• (C) medical compressed air piping 100
• (D) nitrous oxide piping 100
• (E) carbon dioxide piping 100
• (G) any other medical gas piping not included above in (A) through (F) 100
• (H) if total outlets for all gases/vacuum piping exceed 20 outlets, then there
is an additional fee for each outlet over 20 10

Copyright © IAPMO 2021 29 Copyright © IAPMO 2021 30

29 30

Copyright©IAPMO 2022

5
5/3/2022

Chapter 1 24.301.361
104.0 Permits Montana amendment

• (1) Any person who is required under 50-60-505, MCA to obtain a plumbing
permit, and the work is not covered by a local government inspection
• This section and its sub-sections deal with the matter of program, shall do so prior to installation through the department.
plumbing permits. • (2) The exception to the plumbing permit requirement listed in 50-60-503,
MCA, for plumbing installations on farms having their own individual water
supply or sewage disposal system applies to farm and ranch installations
• Montana added several amendments which will now be used in conjunction with an agricultural or livestock raising operation which
considered… are not connected to either a public water supply or public sewer system.
Any building used as or in conjunction with a hotel, bed and breakfast
establishment, or other place where sleeping accommodations are
furnished to transient guests for a fee is subject to the requirements of ARM
24.301.301.

Copyright © IAPMO 2021 31 Copyright © IAPMO 2021 32

31 32

24.301.361 24.301.361
Montana amendment Montana amendment

• (3) The exception to the plumbing permit requirement listed in 50-60-


506(4), MCA, for the owner of residential property applies to the owner of • (5) The applicant shall complete the plumbing application form and
a single-family dwelling who does the work on the plumbing installation in designate in the spaces provided the items to be covered by the
the dwelling in which they will reside. The “homeowner exemption” plumbing permit.
applies to those dwellings intended for the owner’s personal use and not
for dwellings built on speculation of resale or intended as rental property. • (6) No plumbing permit shall be issued for a building or structure under
the jurisdiction of the department, until the building permit has been
• (4) The exception to permit requirements listed in 50-60-506(5), MCA, for issued for said building or structure.
regularly employed maintenance personnel doing maintenance work on
the business premises applies to personnel on the regular payroll rather • (7) After review and approval of the application, the department shall
than personnel under contract. Maintenance work includes the stopping issue a permit to the applicant.
of leaks in pipes, valves, or fixtures, when such repairs do not involve or
require the replacement or rearrangement of valves, pipes, or fixtures.

Copyright © IAPMO 2021 33 Copyright © IAPMO 2021 34

33 34

Chapter 1 24.301.371
105.0 Inspections and Testing Montana amendment

• (1) When the permit holder is ready for inspection, he shall notify the
department either orally or in writing. The notification shall be given not
• This section and its sub-sections deal with the matter of less than 24 hours before the work is to be inspected. To assist the
plumbing inspections. department with its scheduling of inspections, it is asked that inspection
requests be made as much in advance of the 24-hour minimum notice
time as possible. Cover (rough-in) inspections are made by a state
• Montana added several amendments which will now be plumbing inspector wherever possible. Insulation and wallboard shall not
considered… be applied prior to inspections unless 48 hours, excluding Saturdays,
Sundays and holidays have expired after the plumbing installation is
complete and notice to inspect has been received.

Copyright © IAPMO 2021 35 Copyright © IAPMO 2021 36

35 36

Copyright©IAPMO 2022

6
5/3/2022

24.301.371 24.301.371
Montana amendment Montana amendment

• (2) The permit holder shall be responsible for assuring that the plumbing • (4) If the inspection reveals code violations, the permit holder shall be
work is not covered before the department has granted permission to given an opportunity to make corrections. If after reinspection the
cover said work. The inspection shall be made during daylight hours violation has been corrected, the permit holder shall be issued a
unless it is more convenient to all parties involved to make the inspection certificate of compliance. If such violation is not corrected, the permit
at night. holder or other responsible persons will be charged as per 50-60-110,
• (3) Upon completion of the final inspection and approval of the plumbing MCA.
work, the department shall, if requested, issue the permit holder a • (5) Plumbing inspectors shall not inspect any plumbing work in which
certificate of compliance. they have any financial or personal interest, or which they have installed
or repaired. (This is a new provision!)

Copyright © IAPMO 2021 37 Copyright © IAPMO 2021 38

37 38

Words have meaning… Chapter 2


Define the word “stock”… Definitions

• (a) liquid made by stewing bones & vegetables, as in soup broth • Foundation of UPC! Words have meaning, context & authorial
• (b) to assess, as in take “stock” of a situation intent are important!
• (c) a store of goods
• (d) farm animals, as in livestock • 18 new or modified definitions
• (e) timber frame with holes to hold criminals for public punishment
• (f) support or handle for an implement or gun • One Montana amendment
• (g) shares or financial interest in a company, as in “stock market”
• (h) reputation – his “stock” is rising as he continues to excel at work
• Plus, a selection of critically important terms to understand…

Copyright © IAPMO 2021 39 Copyright © IAPMO 2021 40

39 40

205.0
Category 3 Vacuum System
Ordinary Words
• A Category 3 vacuum distribution system that can be
either a wet system designed to remove liquids, air-gas,
See a dictionary… or solid from the treated area; or a dry system designed
to trap liquids and solids before the service inlet and to
accommodate air-gas only through the service inlet.
[NFPA 99:3.3.21]

Copyright © IAPMO 2021 41 Copyright © IAPMO 2021 42

41 42

Copyright©IAPMO 2022

7
5/3/2022

205.0 205.0
Circuit Vent (new) Commercial Modular System (new)

• The vent that connects to a horizontal drainage branch • A drinking water treatment unit system consisting of
and vents two traps to a maximum of eight traps multiple components attached to a manifold, produced
connected into a battery of fixtures. specifically for food service applications, and not
intended for use in residential applications.

Copyright © IAPMO 2021 43 Copyright © IAPMO 2021 44

43 44

206.0 206.0 Dead Leg


Dead Leg (new) Continued…

• A section of potable water pipe which contains water that • Many installations are dead legs:
has no flow or does not circulate. • Capped ends
• Futures
• New definition, necessary for section 309.6
• What is the issue?
• Legionella
• Relates also to Appendix N, dealing with Legionella
• Water stagnation

Copyright © IAPMO 2021 45 Copyright © IAPMO 2021 46

45 46

207.0 209.0
Expansion Tank (new) General Anesthesia and Levels of Sedation/Analgesia (new)

• A vessel used to • Deep Sedation/Analgesia. A drug-induced depression of


protect potable water consciousness during which patients cannot be easily aroused
systems from but respond purposefully following repeated or painful
stimulation. The ability to independently maintain ventilatory
excessive pressure. function may be impaired. Patients may require assistance in
maintaining a patent airway, and spontaneous ventilation may be
inadequate. Cardiovascular function is usually maintained.
[NFPA 99:3.3.66.2]

Copyright © IAPMO 2021 47 Copyright © IAPMO 2021 48

47 48

Copyright©IAPMO 2022

8
5/3/2022

209.0
General Anesthesia and Levels of Sedation/Analgesia (continued)

• General Anesthesia. A drug-induced loss of consciousness


during which patients are not arousable, even by painful
stimulation. The ability to independently maintain ventilatory
function is often impaired. Patients often require assistance in
maintaining a patent airway, and positive pressure ventilation
may be required because of depressed spontaneous ventilation
or drug-induced depression of neuromuscular function.
Cardiovascular function may be impaired. [NFPA 99:3.3.66.1]

Copyright © IAPMO 2021 49 Copyright © IAPMO 2021 50

49 50

Copyright © IAPMO 2021 51 Copyright © IAPMO 2021 52

51 52

209.0 209.0
General Anesthesia and Levels of Sedation/Analgesia (continued) General Anesthesia and Levels of Sedation/Analgesia (continued)

• Minimal Sedation (Anxiolysis). A drug-induced state during • Moderate Sedation/Analgesia (Conscious Sedation). A drug-
which patients respond normally to verbal commands. Although induced depression of consciousness during which patients
cognitive function and coordination may be impaired, ventilatory respond purposefully to verbal commands, either alone or
and cardiovascular functions are unaffected. [NFPA 99:3.3.66.4] accompanied by light tactile stimulation. No interventions are
required to maintain a patent airway, and spontaneous ventilation
is adequate. Cardiovascular function is usually maintained.
[NFPA 99:3.3.66.3]

Copyright © IAPMO 2021 53 Copyright © IAPMO 2021 54

53 54

Copyright©IAPMO 2022

9
5/3/2022

209.0
Group Wash Fixture (new)

• A lavatory that allows


more than one person
to utilize the fixture at
the same time. The
fixture has one or
more drains and one
or more faucets.

Copyright © IAPMO 2021 55 Copyright © IAPMO 2021 56

55 56

Copyright © IAPMO 2021 57 Copyright © IAPMO 2021 58

57 58

214.0
Low-Pressure Water Dispenser (new)

• A terminal fitting located downstream of a pressure


reducing valve that dispenses drinking hot water above
710C (1600F) or cold water or both at a pressure of
105kPa (15psi) or less.

Copyright © IAPMO 2021 59 Copyright © IAPMO 2021 60

59 60

Copyright©IAPMO 2022

10
5/3/2022

216.0
Nonwater Urinal with Drain Cleansing Action (new)

• A non-water urinal that conveys waste into the drainage


system without the use of water for flushing and
automatically performs a drain-cleansing action after a
pre-determined amount of time.

Copyright © IAPMO 2021 61 Copyright © IAPMO 2021 62

61 62

24.301.301 (1) (l) 218.0


Montana amendment Point-of-Entry, Water Treatment Unit (new)

• (1) (l) 218.0 Definition of Plumbing System is amended to • A device serving the water distribution system of a
read: Includes all potable water and alternate water sources building for the purposes of altering, modifying, adding,
including supply and distribution pipes, all plumbing fixtures and or removing minerals, chemicals, contaminants, and
traps, all drainage and vent pipes, building drains and building
sewers, including their respective joints and connections, suspended solids in water.
devices, receptacles, and appurtenances within the property line
of any premises, and includes water heaters and vents for the
premises.

Copyright © IAPMO 2021 63 Copyright © IAPMO 2021 64

63 64

218.0 218.0
P.o.E. (continued) Point-of Use, Water Treatment Unit (new)

• A device serving a single atmospheric outlet such as a


There are many different faucet for the purposes of altering, modifying, adding, or
models… removing minerals, chemicals, contaminants, and
suspended solids in water.
Maintenance is essential!

Copyright © IAPMO 2021 65 Copyright © IAPMO 2021 66

65 66

Copyright©IAPMO 2022

11
5/3/2022

218.0
Pre-Fabricated Shower Enclosure (new)

• A factory-assembled watertight structure with enclosing


walls, a drain, and a door or access way.

Copyright © IAPMO 2021 67 Copyright © IAPMO 2021 68

67 68

218.0 218.0
Private or Private Use Public Water System (new)

• Applies to plumbing fixtures in residences and • A system for the provision to the public of water for
apartments, to private bathrooms in hotels, hospitals, human consumption through pipes or other constructed
and health-care facilities, and to restrooms in commercial conveyances, if such system has at least fifteen service
establishments where the fixtures are intended for the connections or regularly serves an average of twenty-five
use of a family or an individual. individuals daily for at least 60 days per year.

• New phrase added

Copyright © IAPMO 2021 69 Copyright © IAPMO 2021 70

69 70

224.0 Question
Vent Offset Which of these constitutes a “dead leg”?

• An arrangement of two or more fittings • (A) a 2” long section of 1” Type K copper water tube with a cap
and pipe installed for the purpose of
locating a vertical section of the vent • (B) water pipe provided for future fixtures
pipe in a different but parallel plane
with respect to an adjacent section of
vertical vent pipe. [NFPA 54:3.3.102] • (C) waterline roughed in at a non-water urinal for future retrofit of a
water-supplied urinal

• One word deleted…


• (D) all of the above

Copyright © IAPMO 2021 71 Copyright © IAPMO 2021 72

71 72

Copyright©IAPMO 2022

12
5/3/2022

Chapter 3 301.2
General Regulations Minimum Standards.

• Pipe, pipe fittings, traps, fixtures, material, and devices used in a


• Predominantly minor changes plumbing system shall be listed (third-party certified) by a listing
agency (accredited conformity assessment body) as complying
with the approved applicable recognized standards referenced in
• One new section added this code, and shall be free from defects. Unless otherwise
provided for in this code, materials, fixtures, or devices used or
entering into the construction of plumbing systems, or parts
• No Montana amendments thereof shall be submitted to the Authority Having Jurisdiction
(AHJ) for approval prior to being installed.
• New verbiage added

Copyright © IAPMO 2021 73 Copyright © IAPMO 2021 74

73 74

Creativity abounds…
And it even “works”…

• …but does this conform to


UPC requirements?

Copyright © IAPMO 2021 75 Copyright © IAPMO 2021 76

75 76

301.2.2
Standards.

• … A list of plumbing standards that appear in specific sections of this


code is referenced in Table 1701.1. Standards referenced in Table
1701.1 shall be applied as indicated in the applicable referenced section.
A list of additional approved standards, publications, practices, and
guides that are not referenced in specific sections of this code appear in
Table 1701.2. The documents indicated in Table 1701.2 shall be
permitted in accordance with Section 301.3. An IAPMO Installation
Standard is referenced in Appendix I for the convenience of the users of
this code. It is not considered as part of this code unless formally
adopted as such by the AHJ.
• New word added, sentence deleted

Copyright © IAPMO 2021 77 Copyright © IAPMO 2021 78

77 78

Copyright©IAPMO 2022

13
5/3/2022

Unlisted Urinal 309.6


Creative, but… Dead Legs.

• This installation may fit well in • Dead legs shall have a method of flushing.
a pub, tavern or similar
establishment, however…
• What constitutes this?
• A valve?
• Sediment faucet or boiler drain?
• Removable plug or cap?
• Enforcement to ensure flushing occurs?

Copyright © IAPMO 2021 79 Copyright © IAPMO 2021 80

79 80

Dead Legs Chapter 4


Continued… Plumbing Fixtures and Fixture Fittings

• Ten changes
• When is an eyewash station • Hot water temperature limitations at various fixtures:
used? • Public lavatories
• Gang showers
• Bathtubs & whirlpool bathtubs
• Does this not in effect become
• Bidets
a “dead leg”?
• New devices
• Other minor changes

Copyright © IAPMO 2021 81 Copyright © IAPMO 2021 82

81 82

402.6.3
Securing Floor-Mounted, Back-Outlet Water Closet Bowls.

• Where floor-mounted back-outlet water closets are used,


the soil pipe shall be not less than 3 inches (80mm) in
diameter. Offset, eccentric, or reducing floor closet
flanges shall not be used.

Copyright © IAPMO 2021 83 Copyright © IAPMO 2021 84

83 84

Copyright©IAPMO 2022

14
5/3/2022

Copyright © IAPMO 2021 85 Copyright © IAPMO 2021 86

85 86

What is it?
WC Flange

• This is an “offset”
WC Flange:

• (A) True

• (B) False

Copyright © IAPMO 2021 87 Copyright © IAPMO 2021 88

87 88

407.3 Water temperature at fixtures…


Limitation of Hot Water Temperature for Public Lavatories. How is it verified?

• A calibrated thermometer must be


• Hot water delivered from public-use lavatories shall be limited to used!
a maximum temperature of 1200F (490C). The water heater
thermostat shall not be considered a control for meeting this • Do not rely on guesses by holding
provision. The maximum temperature shall be regulated by one your hand under the tap…
of the following means:
• (1) A limiting device conforming to either ASSE 1070/ASME
A112.1070/CSA B125.70, or • Keep a record findings at time of
installation or inspection.
• (2) A water heater conforming to ASSE 1084.

Copyright © IAPMO 2021 89 Copyright © IAPMO 2021 90

89 90

Copyright©IAPMO 2022

15
5/3/2022

408.1 408.3.1
Application. Gang Showers.

• Manufactured shower receptors and shower bases shall • Where gang showers are supplied with a single
comply with ASME A112.19.1/CSA B45.2, ASME temperature-controlled water supply pipe, it shall be
A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4, controlled by a mixing valve that complies with ASSE
CSA B45.12/IAPMO Z402, or CSA B45.5/IAPMO Z124. 1069.
Prefabricated shower enclosures shall comply with
IAPMO IGC 154.
• Reworded, however essence remains unchanged.

Copyright © IAPMO 2021 91 Copyright © IAPMO 2021 92

91 92

Master mixing valve 408.3.2


Gang shower… Temperature Limiting.

• The maximum water temperature discharging from an individual


• UPC requires ASSE (or equivalent) listing showerhead shall be limited to 1200F (490C) by one of the
following methods:
• (1) A shower or tub/shower combination valve conforming to
• Master controls should NOT be accessible ASSE 1016/ASME A112.1016/CSA B125.16 where either:
to public
• (a) The valve is field-adjusted to the required maximum
temperature, or
• (b) The handle position, stop, or temperature limiting control is
set in accordance with the manufacturer’s instructions to the
required maximum temperature.

Copyright © IAPMO 2021 93 Copyright © IAPMO 2021 94

93 94

408.3.2
Temperature Limiting. (Continued)

• (2) For gang showers supplied by a single water supply pipe, a


mixing valve that conforms to ASSE 1069 that is field-adjusted to
the required maximum temperature.
• (3) A limiting device conforming to either ASSE 1070/ASME
A112.1070/CSA B 125.70 or CSA B125.3.
• (4) A water heater conforming to ASSE 1084.
• (5) A temperature actuated flow reduction device conforming to
ASSE 1062.

Copyright © IAPMO 2021 95 Copyright © IAPMO 2021 96

95 96

Copyright©IAPMO 2022

16
5/3/2022

408.5
Finished Curb or Threshold.

• The immediate adjoining space to showers without


thresholds Where there is a shower without a threshold,
the floor space within the same room shall be considered
a wet location and shall comply with the requirements of
the building, residential, and electrical codes.

Copyright © IAPMO 2021 97 Copyright © IAPMO 2021 98

97 98

Wet location… 409.4


Limitation of Hot Water Temperature in Bathtubs & Whirlpool Bathtubs.

• The maximum hot water temperature discharging from


the bathtub and whirlpool bathtub filler shall be limited to
1200F (490C). The water heater thermostat shall not be
considered a control for meeting this provision. The
maximum temperature shall be regulated by one of the
following means:
• (1) A limiting device conforming to either ASSE
1070/ASME A112.1070/CSA B125.70 or CSA B125.3.
• (2) A water heater conforming to ASSE 1084.
Copyright © IAPMO 2021 99 Copyright © IAPMO 2021 100

99 100

410.3 412.1.2 (new sub-section)


Limitation of Water Temperature in Bidets. Nonwater Urinals with Drain Cleansing Action.

• The maximum hot water temperature discharging from a bidet


shall be limited to 1100F (430C) by a device that complies with • Nonwater urinals with drain cleansing action shall comply
ASSE 1070/ASME A112.1070/CSA B125.70. The water heater
with ASME A112.19.19 and shall be cleaned, maintained
thermostat shall not be considered a control for meeting this
provision. The maximum temperature shall be regulated by one and installed in accordance with the manufacturer’s
of the following means: installation instructions.
• (1) A limiting device conforming to either ASSE 1070/ASME
A112.1070/CSA B125.70 or CSA B125.3.
• (2) A water heater conforming to ASSE 1084.

Copyright © IAPMO 2021 101 Copyright © IAPMO 2021 102

101 102

Copyright©IAPMO 2022

17
5/3/2022

24.301.301 (1) (m) Chapter 5


Montana amendment Water Heaters

• Table 422.1, Minimum Plumbing Facilities, is deleted and • Quite a few changes…
replaced with ARM 24.301.351, Minimum Required
Plumbing Fixtures.
• Focus on “plumbing” changes

• Many have to do with “mechanical” side of water heater


installations
• Since Montana utilizes IMC, we will NOT go into these…

Copyright © IAPMO 2021 103 Copyright © IAPMO 2021 104

103 104

Table 501.1(1) 507.2


Water Heaters Seismic Provisions.

• New category, • In seismic design categories C, D, E, and F, Water


“Electric heaters shall be anchored or strapped to resist horizontal
Instantaneous displacement due to earthquake motion. Strapping shall
• Changes to Gas: be at points within the upper one-third and lower one-
• Added “storage and third of its vertical dimensions. At the lower point, a
instantaneous”
distance of not less than 4 inches (102mm) shall be
• Changes to Electric: maintained from the controls with the strapping.
• Added ”storage”
• Now all water heaters, everywhere…

Copyright © IAPMO 2021 105 Copyright © IAPMO 2021 106

105 106

Seismic strap…

Copyright © IAPMO 2021 107 Copyright © IAPMO 2021 108

107 108

Copyright©IAPMO 2022

18
5/3/2022

24.301.301 (1) (i) 24.301.301 (1) (i)


Montana amendment Continued…

• Subsection 507.13, REPEAL: Gas utilization equipment, or any


equipment that generates a glow, spark, or flame, in residential • ALL water heaters are now FVIR…
garages and in adjacent spaces that open to the garage and are
not part of the living space for a dwelling unit shall be so installed
that all burners, burner-ignition devices, and heating elements • Combustion chamber is sealed
are located not less than 18 inches (450mm) above the floor from garage atmosphere
unless listed as flammable vapor ignition resistant.

• This subsection is deleted!

Copyright © IAPMO 2021 109 Copyright © IAPMO 2021 110

109 110

507.23
Combination of Appliances and Equipment.

• A Any combination of appliances, equipment,


attachments, or devices used together in a any manner
shall be in accordance comply with the standards that
apply to the individual appliance and equipment. [NFPA
54:9.1.21]

Copyright © IAPMO 2021 111 Copyright © IAPMO 2021 112

111 112

507.24 HWT instructions


Installation Instructions. Left with heater

• The installing agency shall comply with conform to the


appliance and equipment manufacturer’s installation • Shall be available
instructions recommendations in completing an to inspector,
installation. The installing agency shall leave the owner and
manufacturer’s installation, operating and maintenance consumer
instructions in a location on the premises where they are
readily available for reference and guidance of the AHJ,
service personnel, and the owner or operator. [NFPA
54:9.1.22]

Copyright © IAPMO 2021 113 Copyright © IAPMO 2021 114

113 114

Copyright©IAPMO 2022

19
5/3/2022

508.2.1.1 508.2.1.1
Guards and Rails. Guards and Rails.

• Guards or rails shall be required where the following • Where guards or rails are installed, they shall be
exist: constructed so as to prevent the passage of a 21inch
• (1) The clearance between the appliance and a roof (533mm) diameter ball, resist the imposed loading
edge or open end of an equipment platform is less than 6 conditions, and shall extend not less than 30 inches
feet (1829mm). (762mm) beyond each side of the equipment or
appliance.
• (2) The open end of the equipment platform is located
more than 30 inches (762mm) above the roof, floor, or • Exception: Guards shall not be required where a
grade below. permanent fall arrest anchorage connector system in
accordance with ASSE Z359.1 is installed.

Copyright © IAPMO 2021 115 Copyright © IAPMO 2021 116

115 116

508.3.1 Roof Access


Access. Consult with AHJ

• Exterior roof
• Buildings more than 15 feet (4572 mm) in access permitted
height shall have an inside means of
access to the roof, unless other means • Security
acceptable to the AHJ are used. [NFPA (unauthorized
54:9.4.3.2] access) is a real
concern…

Copyright © IAPMO 2021 117 Copyright © IAPMO 2021 118

117 118

509.4.1 509.4.1
Plastic Piping. Plastic Piping. (continued)

• Where plastic piping is used to vent an appliance,


the appliance shall be listed for use with such • Piping shall be marked
venting materials and the appliance manufacturer’s for gas appliance
installation instructions shall identify the specific venting use.
plastic piping material. The plastic pipe venting
shall be labeled in accordance with the product
standards specified by the appliance manufacturer
or shall be listed and labeled in accordance with
UL 1738. [NFPA 54:12.5.2]

Copyright © IAPMO 2021 119 Copyright © IAPMO 2021 120

119 120

Copyright©IAPMO 2022

20
5/3/2022

509.4.2 Chapter 6
Plastic Vent Joints. Water Supply and Distribution

• Plastic pipe and fittings used to vent • Several new sections


appliances shall be installed in
accordance with the manufacturer’s
installation instructions. Plastic pipe
venting materials listed and labeled in • Several amended or re-arranged sections
accordance with UL 1738 shall be
installed in accordance with the vent
manufacturer’s installation instructions. • One new table; significant changes to another
Where primer is required, it shall be of
a contrasting color. [NFPA 54:12.5.3]
• Several Montana amendments

Copyright © IAPMO 2021 121 Copyright © IAPMO 2021 122

121 122

601.2 601.2
Water Supply and Flushing. Water Supply and Flushing (continued)

• (formerly “Hot and Cold Water Required”)


• Except where not deemed necessary for safety or • Exceptions:
sanitation by the AHJ, Each plumbing fixture shall be • (1) Listed fixtures that do not require water for their
provided with an adequate supply of potable running operation and are not connected to the water supply.
water piped thereto in an approved manner, so arranged
as to flush and keep it in a clean and sanitary condition
without danger of backflow or cross-connection. Water • (2) Where not deemed necessary for safety and
closets and urinals shall be flushed using an approved sanitation by the AHJ.
flush tank or flushometer valve.

Copyright © IAPMO 2021 123 Copyright © IAPMO 2021 124

123 124

601.2.1 601.3.4
Hot and Cold Water Required Fixtures.

• In occupancies where plumbing fixtures are installed for private • Where vacuum breakers or backflow preventers are
use, hot water shall be required for bathing, washing, laundry, installed with fixtures listed in Table 1701.1 Chapter 17,
cooking purposes, dishwashing or maintenance. In occupancies
where plumbing fixtures are installed for public use, hot water
identification of the discharge side shall be permitted to
shall be required for bathing and washing purposes. This be omitted.
requirement shall not supersede the requirements for individual
temperature control limitations for public lavatories, and public
and private bidets, bathtubs, whirlpool bathtubs, and shower
control valves.

Copyright © IAPMO 2021 125 Copyright © IAPMO 2021 126

125 126

Copyright©IAPMO 2022

21
5/3/2022

AVB at shower… Speaking of AAV’s


See anything wrong?

Copyright © IAPMO 2021 127 Copyright © IAPMO 2021 128

127 128

24.301.301 (1) (k) Table 603.2


Montana amendment - REPEAL BACKFLOW PREVENTION DEVICES, ASSEMBLIES AND METHODS

• 603.2 Approval of Devices or Assemblies. Before any devices or


assembly is installed for the prevention of backflow, it shall have first • There are four (4) significant additions to this table:
been tested for conformity with recognized standards or other standards
acceptable to the AHJ, so long as those standards are consistent with • Dual check backflow preventer
the intent of this code. All devices or assemblies installed in a potable • Backflow preventer with intermediate atmospheric vent
water supply system for protection against backflow shall be maintained • Backflow preventer with intermediate atmospheric vent and pressure
in good working condition by the person or persons having control of reducing valve
such devices or assemblies. If found to be defective or inoperative, the • Laboratory faucet backflow preventer
device or assembly shall be repaired or replaced. No device or assembly
shall be removed from use or relocated or other device or assembly
substituted, without the approval of the AHJ. • Each will be considered now…

Copyright © IAPMO 2021 129 Copyright © IAPMO 2021 130

129 130

Table 603.2 Table 603.2


BACKFLOW PREVENTION DEVICES, ASSEMBLIES AND METHODS BACKFLOW PREVENTION DEVICES, ASSEMBLIES AND METHODS

• Backflow preventer with intermediate atmospheric vent


• Dual check backflow preventer • Applicable standard – ASSE 1012
• Applicable standard – ASSE 1024 • Degree of Hazard – Pollution (Low Hazard)
• Degree of Hazard – Pollution (Low Hazard) • Suitable for back siphonage and back pressure
• Suitable for back siphonage and back pressure • Installation notes: Installation of potable water connections to
• Installation notes: Installation does not include carbonated drink water boilers. No high hazard chemicals shall be introduced into
dispensers. the system using such devices. Designed to operate under
continuous pressure conditions. May discharge water.

Copyright © IAPMO 2021 131 Copyright © IAPMO 2021 132

131 132

Copyright©IAPMO 2022

22
5/3/2022

Table 603.2 Table 603.2


BACKFLOW PREVENTION DEVICES, ASSEMBLIES AND METHODS BACKFLOW PREVENTION DEVICES, ASSEMBLIES AND METHODS

• Backflow preventer with intermediate atmospheric vent and • Laboratory faucet backflow preventer
pressure reducing valve • Applicable Standard – ASSE 1035
• Applicable standard – ASSE 1081 • Suitable for Contamination (High Hazard)
• Degree of Hazard – Pollution (Low Hazard) • Suitable for back siphonage and back pressure
• Suitable for back siphonage and back pressure • Installation includes laboratory faucets. Such devices are not for
• Installation notes: Installation of potable water connections to use under continuous pressure conditions. No valve
water boilers. No high hazard chemicals shall be introduced into downstream.4
the system using such devices. Designed to operate under • 4 Not to be subjected to operating pressure for more than 12
continuous pressure conditions. May discharge water. hours in a 24 hour period.

Copyright © IAPMO 2021 133 Copyright © IAPMO 2021 134

133 134

Tentative Interim Amendment (TIA) Temporary Interim Amendment (TIA)


What is this? TIA UPC-001-21

• TIA indicates that the revision is the result of a Tentative Interim


Amendment. For further information on tentative interim
amendments see Section 5 of the IAPMO Regulations Governing
Committee Projects available at http://codes.iapmo.org
• Proposal requests are balloted through Plumbing Technical
Committee (TC), where ¾ majority must pass
• TC makes a recommendation
• IAPMO Standards Council performs full review, hears testimony,
votes then renders their decision

Copyright © IAPMO 2021 135 Copyright © IAPMO 2021 136

135 136

Major change!
Chemical dispenser…

• Often connected directly to mop (janitor’s) sink to spout,


downstream of integral AVB

• Also common in commercial kitchens in dishwashing


area

Copyright © IAPMO 2021 137 Copyright © IAPMO 2021 138

137 138

Copyright©IAPMO 2022

23
5/3/2022

603.3.10
Dual Check Backflow Preventer.

• A dual check backflow preventer consists of two independently


acting check valves, force loaded to a normally closed position.

Copyright © IAPMO 2021 139 Copyright © IAPMO 2021 140

139 140

603.3.11
Laboratory Faucet Backflow Preventers.

• Laboratory faucet backflow preventers shall comply with


ASSE 1035.

Copyright © IAPMO 2021 141 Copyright © IAPMO 2021 142

141 142

603.3.12 24.301.301
Backflow Preventer with Intermediate Atmospheric Vent. Montana amendment

• A backflow preventer with intermediate atmospheric vent • Delete subsection 603.4.2 Testing.
consists of two independently acting check valves force loaded
to a normally closed position, and an intermediate chamber with
a means for automatically venting to atmosphere, force loaded to • (There were minor changes to Model Code provisions.)
a normally open position.

Copyright © IAPMO 2021 143 Copyright © IAPMO 2021 144

143 144

Copyright©IAPMO 2022

24
5/3/2022

603.5.10
Steam or Hot Water Boilers.

• Potable water connections to steam or hot water boilers shall be


protected from backflow by a double check valve assembly,
backflow preventer with intermediate atmospheric vent and
pressure reducing valve, or reduced pressure principle backflow
prevention assembly in accordance with Table 603.2. Where
chemicals are introduced into the system a reduced pressure
principle backflow prevention assembly shall be provided in
accordance with Table 603.2.
• Change brings model code more closely in line with Montana
amendment, similar yet different, next slide…

Copyright © IAPMO 2021 145 Copyright © IAPMO 2021 146

145 146

24.301.301 (1) (o)


Montana amendment

• 603.5.10 is amended by adding the following language:

• Boiler feed lines, in single-family dwellings on their own private


well, may be protected with a dual check valve with intermediate
atmospheric vent when a nontoxic transfer fluid is utilized in the
boiler.

• Note: This is a different device than Model Code added and is


restricted to SFR applications only

Copyright © IAPMO 2021 147 Copyright © IAPMO 2021 148

147 148

24.301.301 (1) (m) Anything wrong with this picture?


Montana amendment - REPEAL

• 603.5.12 Beverage Dispensers. Potable water


supply to carbonated beverage dispensers, or
coffee machines that may produce back
pressure shall be protected by an air gap or
approved backflow preventer that complies with
ASSE 1022. For carbonated beverage
dispensers, piping material installed downstream
of the backflow preventer shall not be affected by
carbon dioxide gas.
• Reverts to model code verbiage

Copyright © IAPMO 2021 149 Copyright © IAPMO 2021 150

149 150

Copyright©IAPMO 2022

25
5/3/2022

TIA – 603.5.21 24.301.301 (1) (p)


Montana amendment

• 604.3 Copper or Copper Alloy Tube. Copper or copper


alloy tube for water piping shall have a weight of not less
than Type L.
• Exception: Type M copper tubing may be used for water
piping when piping is above ground in, or on a building.

Copyright © IAPMO 2021 151 Copyright © IAPMO 2021 152

151 152

Table 604.1 24.301.301 (1) (q)


MATERIALS FOR BUILDING SUPPLY AND WATER DISTRIBUTION… Montana amendment

• 605.12.2 Solvent Cement Joints. Solvent cement joints for PVC


• Several changes having to do with new, updated pipe and fittings shall be clean from dirt and moisture. Pipe shall
be cut square and pipe shall be deburred. Where surfaces to be
standards
joined are cleaned and free of dirt, moisture, oil, and other
foreign material, apply approved primer purple in color that
complies with ASTM F656. Primer shall be applied to the surface
of the pipe and fitting is softened. Solvent cement that complies
with ASTM D2564 shall be applied to all joint surfaces. Joints
shall be made while both the inside of the socket surface and the
outside surface of the pipe are wet with solvent cement. Hold the
joint in place and undisturbed for 1 minute after assembly.

Copyright © IAPMO 2021 153 Copyright © IAPMO 2021 154

153 154

606.8
Check Valve Required.

• All systems that circulate water by means of a pump or


other mechanical device or method shall have a check
valve(s) or equal device(s) installed so as to ensure the
direction of flow.

Copyright © IAPMO 2021 155 Copyright © IAPMO 2021 156

155 156

Copyright©IAPMO 2022

26
5/3/2022

606.9 608.3
Leak Detection Devices. Expansion Tanks, Combination Temperature Pressure Relief Valves.

• A water system provided with a check valve, backflow preventer,


• Where leak detection devices for water supply and or other normally closed device that prevents dissipation of
distribution are installed, they shall comply with IAPMO building pressure back into the water main, independent of the
type of water heater used, shall be provided with an approved,
IGC 115 or IAPMO IGC 349. listed, and adequately sized expansion tank or other approved
device having similar function to control thermal expansion. Pre-
pressurized water expansion tanks shall comply with IAPMO
• Key word, “where”! Z1088. Such expansion tank or other approved device shall be
installed on the building side of the check valve, backflow
preventer, or other device and shall be sized and installed in
accordance with the manufacturer’s installation instructions.

Copyright © IAPMO 2021 157 Copyright © IAPMO 2021 158

157 158

PRV’s
Bypass…

• Some pressure
reducing valves (PRV)
are internally bypassed,
allowing dissipation into
municipal mains

Copyright © IAPMO 2021 159 Copyright © IAPMO 2021 160

159 160

Copyright © IAPMO 2021 161 Copyright © IAPMO 2021 162

161 162

Copyright©IAPMO 2022

27
5/3/2022

608.5
Discharge piping.

• The discharge piping serving a temperature relief valve,


pressure relief valve, or combination of both shall have
no valves, obstructions, or means of isolation and be
provided with the following:
• (1) Equal to Not less than the size of the valve outlet and
shall discharge full size to the flood level of the area
receiving the discharge and pointing down.
• (8) The discharge termination point shall be readily
observable.
Copyright © IAPMO 2021 163 Copyright © IAPMO 2021 164

163 164

TPRV discharge
Does this comply with 608.5?

• No! several code violations:

• PEX within first 18” of HWT


• PEX uses insert fittings (not full size,
although nominally same size)
• If TPRV activates, will this remain pointed
toward ground, or will it whip about?

Copyright © IAPMO 2021 165 Copyright © IAPMO 2021 166

165 166

TPRV discharge
Continued…

• Before & after

Copyright © IAPMO 2021 167 Copyright © IAPMO 2021 168

167 168

Copyright©IAPMO 2022

28
5/3/2022

609.8 609.8
Pumps. Pumps.

• Pumps shall be installed in accordance with the • 609.8.2 Potable Water Pumps.
manufacturer’s installation instructions. Pumps intended to supply
drinking water shall be in
accordance with NSF 61.
• 609.8.1 Access. Pumps shall be accessible for repairs.

Copyright © IAPMO 2021 169 Copyright © IAPMO 2021 170

169 170

24.301.301 (1) (r) 24.301.301 (1) (s)


Montana amendment Montana amendment

• 610.8 Size of Meter and Building Supply Pipe Using Table


610.4. The size of the meter and the building supply pipe shall be
• 609.11 Pipe Insulation. determined as follows:

• Due to a new section added, “Pipe Insulation” was re- • There are six (6) subsections, then a concluding sentence
numbered to 609.12
• No building supply pipe shall be less than ¾ of an inch (20mm)
• Delete in its entirety (19.1mm) in inside diameter.

Copyright © IAPMO 2021 171 Copyright © IAPMO 2021 172

171 172

611.0 Table 611.1


Drinking Water Treatment Units. DRINKING WATER TREATMENT UNITS

• Re-formatted, some content moved to new table 611.1.


• 611.1 Application. Drinking water treatment units shall
comply with the applicable referenced standards in Table
611.1.
• 611.1.1 Alkaline Water Treatment. Alkaline water
treatment devices shall comply with IAPMO IGC 322.
• 611.1.2 Scale Reduction Devices. Scale reduction
devices shall comply with IAPMO Z601.

Copyright © IAPMO 2021 173 Copyright © IAPMO 2021 174

173 174

Copyright©IAPMO 2022

29
5/3/2022

Water softener Softener drain…


What do they do? Direct connect to inlet side of trap, no air gap…

• Used in areas of “hard”


water
• Remove primarily calcium
and magnesium from water
• Employs ion exchange
from salt in a resin bed,
and flushes hardness away
• Automatic operation

Copyright © IAPMO 2021 175 Copyright © IAPMO 2021 176

175 176

Softener drain… Softener drain…


Multiple code violations… UPC compliant?

• No air gap

• Unvented P-trap

• No primer

• San tee in horizontal branch

Copyright © IAPMO 2021 177 Copyright © IAPMO 2021 178

177 178

24.301.301 (1) (t) Supplementary Session


Montana amendment Water pipe sizing review…

• We will now take some time to do a very basic review of


• 612.0 Residential Fire Sprinkler Systems. Chapter 6, pipe sizing requirements…

• Delete in its entirety

Copyright © IAPMO 2021 179 Copyright © IAPMO 2021 180

179 180

Copyright©IAPMO 2022

30
5/3/2022

Chapter 7 Let’s see, if you can figure out what’s going on here…
Sanitary Drainage

• Several model code changes

• Six Montana amendments

Copyright © IAPMO 2021 181 Copyright © IAPMO 2021 182

181 182

Copyright © IAPMO 2021 183 Copyright © IAPMO 2021 184

183 184

Copyright © IAPMO 2021 185 Copyright © IAPMO 2021 186

185 186

Copyright©IAPMO 2022

31
5/3/2022

701.2 Table 701.2


Drainage Piping. MATERIALS FOR DRAIN, WASTE,VENT PIPE AND FITTINGS

• (2) ABS and PVC DWV piping installation shall be installed in


accordance with applicable standards referenced in Table 701.2 • Minor additions and changes, primarily having to do with
and Chapter 14 “Firestop Protection.” Except for individual new or updated standards
single-family dwelling units, materials exposed within ducts or
plenums shall have a flame-spread index of not more than 25
and a smoke-developed index of not more than 50, where tested
in accordance with ASTM E84 or UL 723. Plastic piping installed
in plenums shall be tested in accordance with all requirements of
ASTM E84 or UL 723. Mounting methods, supports and sample
sizes of materials for testing that are not specified in ASTM E84
or UL 723 shall be prohibited.

Copyright © IAPMO 2021 187 Copyright © IAPMO 2021 188

187 188

701.5
Lead.

• (See Table 1701.1) (See Chapter 17) Sheet lead shall comply
with the following:
• (1) For safe pans – not less than 4 pounds per square foot (lb/ft2)
(19 kg/m2) or 1/16 of an inch (1.6 mm) thick.
• (2) For flashings or vent terminals – not less than 3 lb/ft2 (15
kg/m2) or 0.0472 of an inch (1.2 mm) thick.
• (3) Lead bends and lead traps shall be not less than 1/8 of an
inch (3.2 mm) in wall thickness.

Copyright © IAPMO 2021 189 Copyright © IAPMO 2021 190

189 190

Table 702.1 24.301.301 (1) (u)


DRAINAGE FIXTURE UNIT VALUES (DFU) Montana amendment

• Minor additions or changes: • 704.3 Commercial Sinks. Pot sinks, scullery sinks, dishwashing sinks,
silverware sinks, and other similar fixtures shall be connected directly
to the drainage system. There may not be a direct connection between
• New footnote 9 for “Shower, single-head trap”: the sewerage system and any drains originating from equipment in
• 9 For a bathtub to shower retrofit, a 1 ½ inch (40mm) trap and which food, portable equipment, or utensils are placed. Exception: A
trap arm shall be permitted with a maximum shower size of 36 warewashing (3-compartment) sink may have a direct connection only
inches (914mm) in width and 60 inches (1524mm) in length. See when used as a wash bin, rinse bin, and sanitizing bin and shall not be
Section 408.5 and Section 408.6. used for any other purpose. Establishments that use the sanitizing bin
of their warewashing sink to wash produce or conduct other food
• New Fixture – Nonwater Urinal with Drain Cleansing Action preparation must maintain an indirect connection and are not eligible
for this exception.

Copyright © IAPMO 2021 191 Copyright © IAPMO 2021 192

191 192

Copyright©IAPMO 2022

32
5/3/2022

24.301.301 (1) (u) (continued) Montana Amendment


Montana amendment Commercial Kitchen

• 704.3 Commercial Sinks. … A floor drain shall be • Note:


provided adjacent to the fixture and shall be connected
on the sewer side of the sink. No other drainage shall be • No direct connection
connected between the floor drain waste connection and
the fixture drain. The fixture and floor drain shall be
trapped and vented in accordance with this code. • Adjacent floor drain

Copyright © IAPMO 2021 193 Copyright © IAPMO 2021 194

193 194

Copyright © IAPMO 2021 195 Copyright © IAPMO 2021 196

195 196

Table 703.2 24.301.301 (1) (v)


MAXIMUM UNIT LOADING & LENGTH OF DRAINAGE/VENT PIPING Montana amendment

• 705.6.2 Solvent Cement Joints. Solvent cement joints for PVC


• Change to footnote 4: Only four water closets or six-unit traps pipe and fittings shall be clean from dirt and moisture. Pipe shall
allowed on a vertical pipe or stack, and not to exceed three water be cut square and pipe shall be deburred. Where surfaces to be
closets or six-unit traps on a horizontal branch or drain. Not to joined are cleaned and free of dirt, moisture, oil, and other
exceed five water closets or six-unit traps. foreign material, apply approved primer purple in color that
complies with ASTM F656. Primer shall be applied to the surface
of the pipe and fitting is softened. Solvent cement that complies
• New footnote 7: Up to 8 public lavatories are permitted to be with ASTM D2564 shall be applied to all joint surfaces. Joints
installed on a 1½ inch (40mm) vertical branch or horizontal shall be made while both the inside of the socket surface and the
sanitary branch sloped at ¼ inch per foot (20.8mm/m) outside surface of the pipe are wet with solvent cement. Hold the
joint in place and undisturbed for 1 minute after assembly.

Copyright © IAPMO 2021 197 Copyright © IAPMO 2021 198

197 198

Copyright©IAPMO 2022

33
5/3/2022

707.2 Table 707.2


Approved. New!

• Each cleanout fitting and each cleanout plug or cap shall


be of an approved type. A list of approved standards for
cleanouts are referenced in Table 707.2.

Copyright © IAPMO 2021 199 Copyright © IAPMO 2021 200

199 200

Cleanout
Proper materials?

• Just because “it works”, does


NOT mean it is an approved
method…

Copyright © IAPMO 2021 201 Copyright © IAPMO 2021 202

201 202

24.301.301 (1) (w)


Montana amendment

• 707.4 Location. Each horizontal drainage pipe shall be provided


with a cleanout at its upper terminal, and each run of piping, that
is more than 100 50 feet (30 480 mm) in total developed length ,
shall be provided with a cleanout for each 100 50 feet (30 480
mm), or fraction thereof, in length of such piping. An additional
cleanout shall be provided in a drainage line for each aggregate
horizontal change in direction exceeding 135 degrees (2.36 rad).
A cleanout shall be installed above the fixture connection fitting,
serving each urinal, regardless of the location of the urinal in the
building.

Copyright © IAPMO 2021 203 Copyright © IAPMO 2021 204

203 204

Copyright©IAPMO 2022

34
5/3/2022

24.301.301 (1) (x) 24.301.301 (1) (y)


Montana amendment Montana amendment

• 708.1 General. Horizontal drainage piping shall be run in


practical alignment and a uniform slope of not less than 1/4 of an
• 707.9 Clearance. Each cleanout in piping…No under- inch per foot or 2 percent toward the point of disposal provided
floor cleanout shall be located exceeding 5 feet from an that, where it is impractical due to the depth of the street sewer
access door, trap door, or crawl hole. No under-floor or to the structural features or to the arrangement of any building
cleanout shall be located exceeding 20 feet from an or structure to obtain a slope of 1/4 of an inch per foot or 2
access door, trap door, or crawl hole. percent, any such pipe or piping 2 inches or larger in diameter
may have a slope of not less than 1/8 of an inch per foot or 1
percent.

Copyright © IAPMO 2021 205 Copyright © IAPMO 2021 206

205 206

24.301.301 (1) (w)


Montana amendment - REPEAL

• 710.1 Backflow Protection. Where a fixture is installed on a


floor level that is lower than the next upstream manhole cover of
the public or private sewer serving such drainage piping may be
protected from the backflow of sewage by installing an approved
type backwater valve. Fixtures on floor levels above such
elevation shall not discharge through the backwater valve.
• Montana verbiage was permissive, one “may” install a backwater
valve; whereas model UPC uses the mandatory term “shall”
• This is a significant difference!

Copyright © IAPMO 2021 207 Copyright © IAPMO 2021 208

207 208

Backwater valve

Copyright © IAPMO 2021 209 Copyright © IAPMO 2021 210

209 210

Copyright©IAPMO 2022

35
5/3/2022

715.3
Existing Sewers.

• Replacement of existing building sewer and building


storm sewers using trenchless methodology and
materials shall be installed in accordance with ASTM
F1216, ASTMF2561, ASTM F2599, or ASTM F3240.
Cast-iron soil pipes and fittings shall not be replaced
using this method aboveground or belowground.
Replacement using cured-in-place pipe liners shall not
be used on collapsed piping or when the existing piping
is compromised.

Copyright © IAPMO 2021 211 Copyright © IAPMO 2021 212

211 212

24.301.301 (1) (z) Montana Amendment – 1% slope


Montana amendment

• 718.1 Slope. Building sewers shall be run in practical alignment


and at a uniform slope of not less than ¼ of an inch per foot
(20.8 mm/m) toward the point of disposal.
• Exception: Where it is impractical, due to the depth of the street
sewer or to the structural features or to the arrangement of any
building or structure, to obtain a slope of 1/4 of an inch per foot,
any pipe or piping 3 inches or larger in diameter may have a
slope of 1/8 of an inch per foot and any such pipe or piping 8
inches in diameter or larger may have a slope of 1/16 of an inch
per foot.

Copyright © IAPMO 2021 213 Copyright © IAPMO 2021 214

213 214

Chapter 8 804.1
Indirect Wastes Standpipe Receptors.

• Plumbing fixtures or other receptors receiving the discharge of indirect waste pipe
• Three minor changes to model code shall be approved for the use proposed and shall be of such shape and capacity
as to prevent splashing or flooding and shall be located where they are readily
accessible for inspection and cleaning. No standpipe receptor for a clothes washer
• One Montana amendment shall extend more than 30 inches (762 mm), or less than 18 inches (457 mm)
above its trap weir. No trap for a clothes washer standpipe receptor shall be
installed below the floor, but shall be roughed in not less than 6 inches (152 mm)
and not more than 18 inches (457 mm) above the floor. No indirect waste receptor
shall be installed in a toilet room, closet, cupboard, or storeroom or in a portion of
the building not in general use by the occupants thereof, except standpipes for
clothes washers shall be permitted to be installed in toilet and bathroom areas
where the clothes washer is installed in the same room.

Copyright © IAPMO 2021 215 Copyright © IAPMO 2021 216

215 216

Copyright©IAPMO 2022

36
5/3/2022

Question
Any UPC violations?

• Is there a vent?

• OR is this another drain


into a standpipe?

• What sort of trap is this?

Copyright © IAPMO 2021 217 Copyright © IAPMO 2021 218

217 218

24.301.301 (1) (aa)


Montana amendment
• 807.3 Domestic Dishwashing Machine. No domestic dishwashing
machine shall be directly connected to a drainage system or food waste
disposer without the use of an approved dishwasher air gap fitting on the
discharge side of the dishwashing machine. Listed airgaps shall be
installed with the flood-level (FL) marking at or above the flood level of
the sink or drainboard, whichever is higher.
• Exception #1: The waste connection of a residential dishwasher shall
connect directly to a wye branch fitting on the tailpiece of the kitchen
sink, directly to the dishwasher connection of a food waste disposer, or
through an air break to a standpipe. The waste line of a residential
dishwasher shall rise and be securely fastened to the underside of the
sink rim or countertop.

Copyright © IAPMO 2021 219 Copyright © IAPMO 2021 220

219 220

814.2
Condensate Control.

• Where an any equipment or appliance is installed in a space


where damage is capable of resulting from condensate overflow,
other than damage to replaceable lay-in ceiling tiles a drain line
shall be provided and shall be drained in accordance with section
814.1. An additional protection method for condensate overflow
shall be provided in accordance with one of the following:

• Options (1) through (4) are listed…

Copyright © IAPMO 2021 221 Copyright © IAPMO 2021 222

221 222

Copyright©IAPMO 2022

37
5/3/2022

Chapter 9 903.1 (2)


Vents Applicable Standards.

• (2) ABS and DVC DWV piping installations shall be in accordance with
Chapter 14 “Firestop Protection.” Except for individual single-family
• Several minor changes dwelling units, materials exposed within ducts or plenums shall have a
flame-spread index of not more than 25 and a smoke-developed index
• Several significant changes to “Circuit Venting” section 911.0 and of not more than 50 where tested in accordance with ASTM E84 or UL
723. These tests shall comply with all requirements of the standards to
sub-sections include the sample size, for both width and length. Plastic pipe shall not
be tested filled with water. Plastic piping installed in plenums shall be
tested in accordance with all requirements of ASTM E 84 or UL 723.
• Seven (7) Montana amendments Mounting methods, supports and sample sizes of materials for testing
that are not specified in ASTM E84 or UL 723 shall be prohibited.

Copyright © IAPMO 2021 223 Copyright © IAPMO 2021 224

223 224

904.2 24.301.301 (1) (ab)


Length. Montana amendment

• Not more than one-third of the total permitted length, in • 906.1 Roof Vent Termination. Each vent pipe or stack
accordance with Table 703.2, of a minimum–sized vent shall extend through its flashing and shall terminate
shall be installed in a horizontal position. Where a vertically not less than 6 12 inches (152 mm) above the
minimum-sized vent is increased one pipe size for its roof nor less than 1 one foot (305 mm) from a vertical
entire length, the maximum length limitation shall not surface. ABS and PVC piping exposed to sunlight shall
apply. be protected by water-based synthetic latex paints.
• 2nd sentence formerly an “Exception”, now is simply part • Climate-driven amendment
of the section…

Copyright © IAPMO 2021 225 Copyright © IAPMO 2021 226

225 226

24.301.301 (1) (aa)


Montana amendment

• 906.3 Use of Roof. Vent pipes shall be extended separately or


combined, of full required size, not less than 6 12 inches (152
mm) above the roof or firewall. Flagpoling of vents shall be
prohibited except where the roof is used for assembly purposes
or parking. Vents within 10 feet (3048 mm) of a part of the roof
that is used for assembly purposes or parking shall extend not
less than 7 feet (2134 mm) above such roof and shall securely
stay.

Copyright © IAPMO 2021 227 Copyright © IAPMO 2021 228

227 228

Copyright©IAPMO 2022

38
5/3/2022

24.301.301 (1) (ad)


Montana amendment

• 906.7 Frost or Snow Closure: Where frost or snow closure is


likely to occur in locations having a minimum design temperature
below zero degrees Fahrenheit vent terminals shall be a
minimum of 3 inches in diameter, but in no event smaller than the
required vent pipe. The change in diameter shall be made inside
the building at least 1 foot below the roof and terminate not less
than 12 inches above the roof, or as required by the
administrative authority.
• Climate-driven amendment

Copyright © IAPMO 2021 229 Copyright © IAPMO 2021 230

229 230

24.301.301 (1) (ae)


Montana amendment

• 908.1 Vertical Wet Venting.

Copyright © IAPMO 2021 231 Copyright © IAPMO 2021 232

231 232

24.301.301 (1) (af) 24.301.301 (1) (ag)


Montana amendment Montana amendment

• Probably means amend 908.1 (not 908.1.1) • Probably means amend 908.1.1 (not 908.1.2)

• 908.1 Vertical Wet Vent. Wet venting is limited to drainage • 908.1.1 Size. The piping between any two consecutive inlet
piping receiving discharge from the trap arm of one and two levels shall be considered a wet vented section. Each wet vented
fixture unit fixtures that also serves as a vent for not to exceed section shall be a minimum of one pipe size larger than the
four fixtures. All wet vented fixtures shall be within the same required minimum waste pipe size of the upper fixture or shall be
story; provided, further, that fixtures with a continuous vent one pipe size larger than the required minimum pipe size for the
discharging into a wet vent shall be within the same story as the sum of the fixture units served by such wet vented section,
wet vented fixtures. whichever is larger, but in no case less than two inches.

Copyright © IAPMO 2021 233 Copyright © IAPMO 2021 234

233 234

Copyright©IAPMO 2022

39
5/3/2022

24.301.301 (1) (ah) 906.6


Montana amendment Lead.

• (See Table 1701.1) (See Chapter 17) Sheet lead shall comply
• 908.2 Horizontal Wet Venting for a Bathroom Groups. A with the following:
bathroom group located on the same floor level shall be • (1) For safe pans – not less than 4 pounds per square foot (lb/ft2)
permitted to be vented by a horizontal wet vent where all of the (19 kg/m2) or 1/16 of an inch (1.6 mm) thick.
conditions of Section 908.2.1 through 908.2.5 are met. Bathroom • (2) For flashings or vent terminals – not less than 3 lb/ft2 (15
group locations include private bathrooms, private patient kg/m2) or 0.0472 of an inch (1.2 mm) thick.
hospital rooms, commercial toilet rooms with only one toilet, one
lavatory and may include one floor drain. • (3) Lead bends and lead traps shall be not less than 1/8 of an
inch (3.2 mm) in wall thickness.

Copyright © IAPMO 2021 235 Copyright © IAPMO 2021 236

235 236

911.0 Circuit Venting Circuit venting, a new concept?


Substantially changed… Not really…

• Increased clarity • Look at this Montana


installation dating back over
• New sub-sections added 100 years…

• New verbiage

• Several section or sub-section re-numberings

Copyright © IAPMO 2021 237 Copyright © IAPMO 2021 238

237 238

911.1
Circuit Vent Permitted.

• A maximum of eight fixtures floor-outlet water closets, showers, bathtubs,


or floor drains connected to a horizontal branch shall be permitted to be
circuit vented. Each fixture drain trap arm shall connect horizontally to
the horizontal branch being circuit vented in accordance with Table
1002.2. The horizontal branch shall be classified as a drain and a vent
from the most downstream trap arm connection to the most upstream
trap arm connection to the horizontal branch.
• Change from any 8 fixtures to 8 with trap arm in same elevational plane
• Specific mention of trap arm length
• Horizontal pipe identified as both drain & vent (dual-purpose pipe)

Copyright © IAPMO 2021 239 Copyright © IAPMO 2021 240

239 240

Copyright©IAPMO 2022

40
5/3/2022

911.1 911.2
Circuit Vent Permitted (continued) Circuit Vent Size and Connection.

• The circuit vent size shall be in accordance with Table 703.2


• Exception: Back-outlet and wall-hung water closets shall be according to the number of circuit vented fixtures connected to
permitted to be circuit vented provided that no floor-outlet fixtures the horizontal branch but shall be not less than 2 inches (50 mm)
are connected to the same horizontal branch. in diameter. The vent shall connect to the horizontal branch on
the vertical between the two most upstream trap arms. The
circuit vent pipe shall not receive the discharge of soil or waste.
• Does NOT prohibit wall-mounted fixtures
• Reinforces that all fixtures in a circuit vented group have trap arm • New reference to Table 703.2
in same elevational plane

Copyright © IAPMO 2021 241 Copyright © IAPMO 2021 242

241 242

911.2.1 911.3
Multiple Circuit Vents. Relief Vent.

• When multiple circuit vents are interconnected according to • A 2 inch (50 mm) relief vent shall be provided for circuit-
section 911.4.1, each individual circuit vent shall be sized vented horizontal branches receiving the discharge of
according to section 911.2. The vent pipe connecting each circuit
vent shall be sized according to Table 703.2. four or more water closets and when connecting to a
drainage stack that receives the discharge of soil or
waste from upper horizontal branches.
• Reference to Table 703.2

Copyright © IAPMO 2021 243 Copyright © IAPMO 2021 244

243 244

911.3.1 911.3.2
Connection and Installation. Fixture Drain.

• The relief vent shall connect to the horizontal branch • The relief vent is permitted to be serve as a fixture drain or fixture
between the stack and the most downstream fixture drain branch for a fixture located within the same branch interval as
the circuit-vented horizontal branch. The discharge to a relief
trap arm of the circuit vent. The relief vent shall be vent shall not exceed 4 fixture units. Fixtures discharging to a
installed on the vertical to the horizontal branch. relief vent shall be one or two fixture unit fixtures but shall not
exceed a total of 4 fixture units.

Copyright © IAPMO 2021 245 Copyright © IAPMO 2021 246

245 246

Copyright©IAPMO 2022

41
5/3/2022

911.4 911.4.1
Slope and Size of Horizontal Branch. Multiple Circuit-Vented Branches.

• The vented section of the horizontal branch drain shall be


uniformly sloped and not more than 1 inch per foot (83.3 mm/m).
The entire length of the vented section of the horizontal branch • Circuit-vented horizontal branches are permitted to be
shall be sized for the total drainage discharge to the branch connected together. Each group of a maximum of eight
according to Table 703.2. fixtures shall be considered a separate circuit vent and
shall be in accordance with Section 911.4.1.1 and
• “uniformly sloped” means no variations in slope
Section 911.4.1.2.
• Reference to Table 703.2

Copyright © IAPMO 2021 247 Copyright © IAPMO 2021 248

247 248

911.4.1.1 911.2.1.2
Size of Parallel Horizontal Branches. Size of Continuous Horizontal Branches.

• Parallel horizontal circuit vented branches shall be • Two or more circuit vented systems continuous on the
permitted to connect on the same floor level. Each same horizontal branch shall be uniformly sized for the
separate circuit-vented horizontal branch that is total discharge into the branch.
interconnected shall be sized independently in
accordance with Section 911.4.

Copyright © IAPMO 2021 249 Copyright © IAPMO 2021 250

249 250

Basic venting Chapter 10


Let’s take a look… Traps and Interceptors

• We will now take a brief overview of venting concepts… • A few changes to model code

• No Montana amendments

Copyright © IAPMO 2021 251 Copyright © IAPMO 2021 252

251 252

Copyright©IAPMO 2022

42
5/3/2022

1001.2
Where Required.

• …The vertical distance between a fixture outlet and the trap weir
shall be as short as practicable, but in no case shall the tailpiece
from a fixture exceed 24 inches (610 mm) in length. One trap
shall be permitted to serve a set of not more than three single
compartment sinks or laundry tubs of the same depth or three
lavatories immediately adjacent to one another and in the same
room where the waste outlets are not more than 30 inches (762
mm) apart, and the trap is centrally located where three
compartments are installed.

Copyright © IAPMO 2021 253 Copyright © IAPMO 2021 254

253 254

Copyright © IAPMO 2021 255 Copyright © IAPMO 2021 256

255 256

Copyright © IAPMO 2021 257 Copyright © IAPMO 2021 258

257 258

Copyright©IAPMO 2022

43
5/3/2022

1014.1
General.
• Where it is determined by the AHJ that waste pretreatment is required, an
approved type of grease interceptor(s) shall comply with ASME A112.14.3, ASME
A112.14.4, CSA B481, PDI G-101, or PDI GG-102, and sized in accordance with
Section 1014.2.1 or Section 1014.3.6, shall be installed in accordance with the
manufacturer’s installation instructions to receive the discharge from fixtures or
equipment that produce grease-laden waste. Grease-laden waste fixtures shall
include, but not be limited to, sinks and drains, such as floor drains, floor sinks,
and other fixtures or equipment in serving establishments, such as restaurants,
cafes, lunch counters, cafeterias, bars, clubs, hotels, hospitals, sanitariums,
factory or school kitchens located in areas of establishments where food is
prepared, or other establishments where grease is introduced into the drainage
system in quantities that can effect line stoppage or hinder sewage treatment or
private sewage disposal systems…

Copyright © IAPMO 2021 259 Copyright © IAPMO 2021 260

259 260

1014.1
General. (continued)

• Previous “general” verbiage has been stricken

• Verbiage now clearly enumerates specific fixtures that


shall discharge through a grease interceptor

Copyright © IAPMO 2021 261 Copyright © IAPMO 2021 262

261 262

1014.3.3
Design.

• Gravity grease interceptors shall be constructed in


accordance with the applicable standard in Table 1701.1
Chapter 17 or the design approved by the AHJ.

Copyright © IAPMO 2021 263 Copyright © IAPMO 2021 264

263 264

Copyright©IAPMO 2022

44
5/3/2022

Copyright © IAPMO 2021 265 Copyright © IAPMO 2021 266

265 266

Chapter 11
Storm Drainage

• One model code change

• No Montana amendments

Copyright © IAPMO 2021 267 Copyright © IAPMO 2021 268

267 268

1101.4
Material Uses.

• …ABS and PVC DWV piping installations shall be installed in accordance


with applicable standards referenced in Table 1701.1 Chapter 17 and
Chapter 14 “Firestop Protection.” Except for individual single-family dwelling
units, materials exposed within ducts or plenums shall have a fame-spread
index of not more than 25 and a smoke-developed index of not more than
50, where tested in accordance with ASTM E84 or UL 723. These tests shall
comply with all requirements of the standards to include the sample size,
both for width and length. Plastic pipe shall not be tested filled with water.
Plastic piping installed in plenums shall be tested in accordance with ASTM
E84 or UL 723. Mounting methods, supports and sample sizes of materials
for testing that are not specified in ASTM E84 or UL 723 shall be prohibited.

Copyright © IAPMO 2021 269 Copyright © IAPMO 2021 270

269 270

Copyright©IAPMO 2022

45
5/3/2022

Chapter 12 Chapter 13
Fuel Gas Piping HEALTH CARE FACILITIES…MEDICAL GAS & VACUUM SYSTEMS

• Deleted • Several model code changes

• 24.301.301 (1) (ai) Chapter 12, Fuel piping is deleted and • Significant re-numbering or re-location of sections & sub-
replaced with International Fuel Gas Code.
sections

• Montana only adopts three portions

Copyright © IAPMO 2021 271 Copyright © IAPMO 2021 272

271 272

24.301.301 (1) (aj)


Health Care Facilities and Medical Gas and Vacuum Systems

• Chapter 13, Health Care and Medical Gas and Vacuum Systems, is deleted except
for Subsections 1301.1, 1302.0 and 1303.0, Health Care Facilities. In lieu of Chapter
13, except for the subsections not deleted, the Department of Labor and Industry
adopts and incorporates by reference the National Fire Protection Association’s
Standard NFPA 99, 2018 edition, Chapters 1 through 5 and Chapter 15 for the
exclusive use as a standard for the installation of medical gas and vacuum systems.
The requirements for this rule shall not be construed as to replace or supersede any
additional requirements for testing and certification of medical gas and vacuum
systems, including independent third-party certification of systems, as may be
applicable. NFPA 99 is a nationally recognized standard setting forth minimum
standards and requirements for medical gas and vacuum systems. A copy of NFPA
99 may be obtained from the National Fire Protection Association at www.nfpa.org

Copyright © IAPMO 2021 273 Copyright © IAPMO 2021 274

273 274

1301.4 1302.1
Where Required. Building Risk Categories.

• Construction and equipment requirements shall be • Activities, systems, or equipment shall be designed to
applied only to new construction and new equipment, meet Category 1 through Category 4 requirements, as
except as modified in individual chapters sections of this detailed in this code chapter. [NFPA 99:4.1]
chapter. [NFPA 99:1.3.2]

Copyright © IAPMO 2021 275 Copyright © IAPMO 2021 276

275 276

Copyright©IAPMO 2022

46
5/3/2022

1302.1.1 1302.1.1.1
Processes and Operations. Risk Categories

• The health care facility’s governing body shall establish • The governing body shall conduct risk assessments and
the processes and operations that are planned for the shall determine risk categories based on the character of
health care facility. [NFPA 99:4.2.1] the processes and operations conducted in the health
care facility. [NFPA 99:4.2.1.1]
• In this context, “operations” does NOT mean surgical
procedures

Copyright © IAPMO 2021 277 Copyright © IAPMO 2021 278

277 278

1302.1.2 1302.1.2.1
Risk Assessment. Documents to the Authority Having Jurisdiction.

• Risk categories shall be classified by the health care • Where required by the Authority Having Jurisdiction
facility’s governing body by following and documenting a (AHJ), the risk assessment shall be provided to the AHJ
defined risk assessment procedure. [NFPA 99:4.2.2] for review based on the character of the processes and
operations conducted in the health care facility. [NFPA
99: 4.2.2.1]

Copyright © IAPMO 2021 279 Copyright © IAPMO 2021 280

279 280

1302.1.3 1302.2
Documented Risk Assessment. Patient Care Spaces.

• The health care facility’s governing body or its designee shall


• A documented risk assessment shall not be required for establish the following areas in accordance with the type of
patient care anticipated (see definition of patient care space in
where Category 1 is selected. [NFPA 99:4.2.3] Chapter 2):
• (1) Category 1 spaces
• (2) Category 2 spaces
• (3) Category 3 spaces
• (4) Category 4 spaces [NFPA 99:1.3.4.1]

Copyright © IAPMO 2021 281 Copyright © IAPMO 2021 282

281 282

Copyright©IAPMO 2022

47
5/3/2022

1302.3 1302.4
Anesthesia. Wet Procedure Locations.

• It shall be the responsibility of the health care • It shall be the responsibility of the health organization
organization facility’s governing body to designate care facility’s governing body to designate wet procedure
anesthetizing locations. [NFPA 99:1.3.4.3] locations. [NFPA 99.1.3.4.3]

Copyright © IAPMO 2021 283 Copyright © IAPMO 2021 284

283 284

1303.9 Chapter 14
Work Performed in Occupied Healthcare Facilities. Firestop Protection

• In existing, occupied, inpatient healthcare facilities, all


plumbing systems installation and remodel work shall be • No model code changes
performed by personnel certified in accordance with
ASSE/IAPMO 12010, ASSE/IAPMO 12030 and
ASSE/IAPMO 12040. • No Montana amendments

• These are PQ standards for Medical Gas installer


(brazer); inspector and verifier

Copyright © IAPMO 2021 285 Copyright © IAPMO 2021 286

285 286

Chapter 15 1501.1.1
Alternate Water Sources For Nonpotable Applications Allowable Use of Alternate Water.

• Several model code changes


• Where approved or required by the AHJ, alternate water
• No Montana amendments sources [reclaimed (recycled) water, gray water, and on-
site treated nonpotable water] shall be permitted to be
used instead of potable water for the applications defined
• This chapter looks at:
• Gray water
in this chapter.
• Reclaimed water
• On-site treated water

Copyright © IAPMO 2021 287 Copyright © IAPMO 2021 288

287 288

Copyright©IAPMO 2022

48
5/3/2022

209.0 220.0
Gray Water. Reclaimed Water.

• Untreated wastewater that has not come into contact • Nonpotable water provided by a water/wastewater utility
with toilet waste, kitchen sink waste, dishwasher waste that, as a result of tertiary treatment of domestic
or similarly contaminated sources. Gray water includes wastewater, meets requirements of the public health AHJ
wastewater from bathtubs, showers, lavatories, clothes for its intended uses.
washers, and laundry tubs. Also, known as grey water,
graywater, and greywater.
• This is not on-site sourced (it comes from a treatment
plant) water

Copyright © IAPMO 2021 289 Copyright © IAPMO 2021 290

289 290

1501.2
System Design.

• Alternate water source systems shall be designed in


accordance with this chapter by a licensed plumbing
contractor or a registered design professional or a
licensed person who demonstrates competency to
design the alternate water source system as required
aby the AHJ. Components, piping, and fittings used in
any alternate water source systems shall be listed.

Copyright © IAPMO 2021 291 Copyright © IAPMO 2021 292

291 292

1501.2 1501.6
Exceptions: Operation and Maintenance Manual.

• (1) A registered design professional is not required to design gray • An operation and maintenance manual for gray water and on-site treated water
water systems having a maximum discharge capacity of 250 systems required to have a permit in accordance with Section 1501.3 shall be
gallons per day (gal/d) ( 0.011 L/s) for single family and multi- supplied to the building owner by the system designer. The operating operation
family dwellings. and maintenance manual shall include the following:
• (1) Detailed diagram of the entire system, and the location of system components.
• (2) Instructions for operating and maintaining the system.
• (2) A registered design professional is not required to design an
on-site treated non-potable water system for single-family • (3) Details on maintaining the required water quality as determined by the AHJ for
on-site nonpotable water systems.
dwellings having a maximum discharge capacity of 250 gal/d
(0.011 L/s). • (4) Details on deactivating the system for maintenance, repair, or other purposes.

Copyright © IAPMO 2021 293 Copyright © IAPMO 2021 294

293 294

Copyright©IAPMO 2022

49
5/3/2022

1501.7
Minimum Water Quality Requirements.

• The minimum water quality for alternate water source systems


shall meet the applicable water quality requirements for the
intended application as determined by the AHJ. In the absence of
water quality requirements, for on-site treated nonpotable
systems, the water quality requirements of NSF 350 shall apply.
The EPA/625/R-04/108 contains recommended water reuse
guidelines to assist regulatory agencies to develop, revise, or
expand alternate water source water quality standards.

Copyright © IAPMO 2021 295 Copyright © IAPMO 2021 296

295 296

Copyright © IAPMO 2021 297 Copyright © IAPMO 2021 298

297 298

1503.2.2 1503.2.4
Diversion. Rainwater Diversion Valves.

• The gray water system shall connect to the sanitary • Rainwater diversion valves ranging from 6 inches (150
drainage system downstream of fixture traps and vent mm) to 12 inches (300 mm) in diameter shall comply with
connections through an approved a gray water diverter IAPMO IGC 352. Valves shall be accessible and include
valve. The gray water diverter valve shall comply with a filter located upstream of the valve when required.
IAPMO PS 59 and be installed in an accessible location
and clearly indicate the direction of flow.

Copyright © IAPMO 2021 299 Copyright © IAPMO 2021 300

299 300

Copyright©IAPMO 2022

50
5/3/2022

1505.12
Signs.

• Signs in rooms and water closet tanks in buildings using


reclaimed (recycled) water shall be in accordance with
Section 1501.9 and Section 1501.9.1.

Copyright © IAPMO 2021 301 Copyright © IAPMO 2021 302

301 302

Copyright © IAPMO 2021 303 Copyright © IAPMO 2021 304

303 304

Chapter 16 1601.2
Nonpotable Rainwater Catchment Systems System Design.

• Rainwater catchment systems shall be designed in


• Several model code changes accordance with this chapter by a person registered or
licensed to perform plumbing design work or who
demonstrate competency to design the rainwater
• Significant relocation and re-numbering catchment system as required by the AHJ plumbing
contractor or a registered design professional.
• No Montana amendments Components, piping, and fittings used in a rainwater
catchment system shall be listed.

Copyright © IAPMO 2021 305 Copyright © IAPMO 2021 306

305 306

Copyright©IAPMO 2022

51
5/3/2022

Copyright © IAPMO 2021 307 Copyright © IAPMO 2021 308

307 308

1601.2
System Design. (continued)

• Exceptions:
• (1) A person registered or licensed to perform plumbing design
work is not required to design rainwater catchment systems used
for irrigation with a maximum storage capacity of 360 gallons
(1136 L).
• (2) A person registered or licensed to perform plumbing design
work is not required to design rainwater catchment systems for
single family dwellings where outlets, piping, and system
components are located on the exterior of the building.

Copyright © IAPMO 2021 309 Copyright © IAPMO 2021 310

309 310

1602.1
General.

• The installation, construction, alteration, and repair of


rainwater catchments systems intended to supply uses
such as water closets, urinals, trap primers for floor
drains and floor sinks, irrigation, industrial processes,
water features, cooling tower makeup and other uses
shall be approved by the AHJ. Rainwater catchment
systems for collecting precipitation from rooftops shall
comply with ARCSA/ASPE 63.

Copyright © IAPMO 2021 311 Copyright © IAPMO 2021 312

311 312

Copyright©IAPMO 2022

52
5/3/2022

1603.4.2
Prohibited Discharges.

• Overflows and bleed-off pipes from roof-mounted


equipment and appliances shall not discharge onto roof
surfaces that are intended to collect rainwater without
prior approval from the AHJ.

Copyright © IAPMO 2021 313 Copyright © IAPMO 2021 314

313 314

1603.5
Minimum Water Quality.

• The minimum water quality for harvested rainwater shall meet


the applicable water quality requirements for the intended
applications as determined by the AHJ. In the absence of water
quality requirements determined by the AHJ, the minimum
treatment and water quality shall be in accordance with Table
1603.5.
• Exception: No treatment is required for rainwater used for
subsurface or nonsprinklered surface irrigation where the
maximum storage volume is less than 360 gallons (1136 L).

Copyright © IAPMO 2021 315 Copyright © IAPMO 2021 316

315 316

Copyright © IAPMO 2021 317 Copyright © IAPMO 2021 318

317 318

Copyright©IAPMO 2022

53
5/3/2022

1603.5.1
Treatment.

• If the quality of the tested water cannot consistently be


maintained at the minimum levels specified in Table
1603.5, then the system shall be equipped with an
appropriate treatment device meeting applicable NSF
standards referenced in Chapter 17.

Copyright © IAPMO 2021 319 Copyright © IAPMO 2021 320

319 320

1605.3.3 Chapter 17
Discovery of Cross-Connection. Referenced Standards

• In the event that a cross-connection is discovered, the • Many changes


following procedure, in the presence of the AHJ shall be • New standards
activated immediately: • Updated standards (newer editions)
• (1) Rainwater catchment water piping to the building • Deleted standards (obsolete)
shall be shutdown at the meter, and the rainwater water
riser shall be drained.

Copyright © IAPMO 2021 321 Copyright © IAPMO 2021 322

321 322

Appendices Appendix A
Do they or do they not apply? RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

• In general, an appendix must be specifically adopted otherwise is


does not constitute part of the plumbing code • Adopted by the State of Montana

• Some unchanged – A, B, C, F, I & J


• No changes to model code
• Some essentially unchanged – D, E, G & H
• Three significantly changed – K, L & M
• One new – N “Impact of Water Temperature on the Potential for • More accurate and real than Chapter 6 provisions
Scalding and Legionella Growth”

Copyright © IAPMO 2021 323 Copyright © IAPMO 2021 324

323 324

Copyright©IAPMO 2022

54
5/3/2022

Appendix B Appendix C
EXPLANATORY NOTES ON COMBINATION WASTE & VENT SYSTEMS ALTERNATE PLUMBING SYSTEMS

• Now adopted! Previously NOT adopted by the State of


• Adopted by the State of Montana Montana

• No changes to model code • A few, relatively minor changes to model code

• Pertains to chapter 9, Section 910.0 and sub-sections

Copyright © IAPMO 2021 325 Copyright © IAPMO 2021 326

325 326

Appendix D Appendix E
SIZING STORM WATER DRAINAGE SYSTEMS MANUFACTURED/MOBILE HOME PARKS & RV PARKS

• Adopted by the State of Montana • NOT adopted by the State of Montana

• No changes to model code • A few, relatively minor changes to model code

Copyright © IAPMO 2021 327 Copyright © IAPMO 2021 328

327 328

Appendix F Appendix G
FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS SIZING OF VENTING SYSTEMS

• NOT adopted by the State of Montana • NOT adopted by the State of Montana

• No changes to model code • Several relatively minor changes to model code

Copyright © IAPMO 2021 329 Copyright © IAPMO 2021 330

329 330

Copyright©IAPMO 2022

55
5/3/2022

Appendix H Appendix I
PRIVATE SEWAGE DISPOSAL SYSTEMS INSTALLATION STANDARDS

• NOT adopted by the State of Montana • NOT adopted by the State of Montana

• No changes to model code • No changes to model code

Copyright © IAPMO 2021 331 Copyright © IAPMO 2021 332

331 332

Appendix J Appendix K
COMBINATION INDOOR & OUTDOOR COMBUSTION & VENTIALTION… POTABLE RAINWATER CATCHMENT SYSTEMS

• NOT adopted by State of Montana • Adopted by State of Montana

• A few, relatively minor change to model code • Several changes to model code, some substantial,
others minor

Copyright © IAPMO 2021 333 Copyright © IAPMO 2021 334

333 334

Appendix L L 101.1
SUSTAINABLE PRACTICES Applicability.

• The purpose of this appendix is to provide a


• Adopted by State of Montana comprehensive set of technically sound provisions that
encourage sustainable practices and works towards
enhancing the design and construction of plumbing
• Several changes to model code, some substantial, systems that result in positive, long-term environmental
others minor impact. This appendix is not intended to circumvent
public health, safety, and general welfare requirements of
this code.

Copyright © IAPMO 2021 335 Copyright © IAPMO 2021 336

335 336

Copyright©IAPMO 2022

56
5/3/2022

L 101.2 L 201.0
Definitions. Definitions.

• Energy Star. A joint program of the U.S. Environmental


• For the purposes of this code, the definitions in Section L Protection Agency and the U.S. Department of Energy. Energy
Star is a voluntary program designed to identify and promote
201.1 shall apply to this appendix. energy-efficient products and practices.

• Note distinction: Chapter 2 definitions apply to this


Appendix, however, Appendix definitions do not
necessarily apply to the rest of UPC...

Copyright © IAPMO 2021 337 Copyright © IAPMO 2021 338

337 338

L 201.0 L 201.0
Definitions. (continued) Definitions. (continued)

• Lavatory. (1) A basin or vessel for


washing. (2) A plumbing fixture, as
defined by (1), especially for use in • Maintenance. The upkeep of property or equipment by
personal hygiene. Principally not the owner of the property in compliance with the
used for laundry purposes and requirements of this appendix.
never used for food preparation, or
utensils, in food services. (3) A
fixture designed for the washing of
hands and face. Sometimes called
a wash basin.

Copyright © IAPMO 2021 339 Copyright © IAPMO 2021 340

339 340

L 201.0 L 201.0
Definitions. (continued) Definitions. (continued)

• Metering Faucet. A self-closing faucet


that dispenses a specific volume of water
for each actuation cycle. The volume or • Storage Tank. The central
cycle duration can be fixed or adjustable. component of the rainwater,
stormwater, or dry weather runoff
• Self Closing Faucet. A faucet that catchment system. Also known as
closes itself after the actuation control a cistern or rain barrel.
mechanism is deactivated. The actuation
or control mechanism can be mechanical
or electronic.

Copyright © IAPMO 2021 341 Copyright © IAPMO 2021 342

341 342

Copyright©IAPMO 2022

57
5/3/2022

L 201.0
Definitions. (continued)

• WaterSense. A voluntary
program of the U.S.
Environmental Protection
Agency, designed to identify
and promote water-efficient
products and practices.

Copyright © IAPMO 2021 343 Copyright © IAPMO 2021 344

343 344

L 301.2 L 302.1
Qualifications. Disposal.

• Where permits are required, the AHJ shall have the • It shall be unlawful for a person to cause, suffer, or
authority to require contractors, installers, or service permit the disposal of sewage, human excrement, or
technicians to demonstrate competency. Where other liquid wastes, in a place or manner, except through
determined by the AHJ, the contractor, installer, or and by means of an approved drainage system, installed
service technician shall be licensed to perform such and maintained in accordance with the provisions of this
work. code.

Copyright © IAPMO 2021 345 Copyright © IAPMO 2021 346

345 346

L 302.2 L 303.1
Connections to Plumbing System Required. General.

• Equipment and appliances, used to receive or discharge • An abandoned system or part thereof covered under the
liquid wastes or sewage, shall be connected properly to scope of this appendix shall be disconnected from
the drainage system of the building or premises, in remaining systems, drained, plugged, and capped in an
accordance with the provisions of this code. approved manner.

Copyright © IAPMO 2021 347 Copyright © IAPMO 2021 348

347 348

Copyright©IAPMO 2022

58
5/3/2022

L 401.0 Water Conservation and Efficiency L 402.0


L 401.1 Scope. Water Conserving Plumbing Fixtures and Fittings.

• L 402.2 Water Closets.


• The provisions of this section establish the means of • L 402.3 Urinals.
conserving potable and nonpotable water in and around • L 402.4 Residential Kitchen Faucets.
a building. • L 402.5 Lavatory Faucets.
• L 402.6 Showerheads.
• L 402.7 Recirculating Shower Systems.
• L 402.8 Commercial Pre-Rinse Spray Valves.
• L 402.9 Emergency Safety Showers and Eye Wash Stations.
• L 402.10 Drinking Fountains.

Copyright © IAPMO 2021 349 Copyright © IAPMO 2021 350

349 350

L 402.2 1.28 gpf Toilet


Water Closets.

• 1.28 Gallons (4.8 Lpf) maximum

• The effective flush volume for dual flush toilets is defined as the
composite, average flush volume of two reduced flushes and one
full flush.

• This applies to both tank-type and flushometer operated WC’s

Copyright © IAPMO 2021 351 Copyright © IAPMO 2021 352

351 352

L 402.3 L 402.3
Urinals. Urinals. (continued)

• .5 Gallons (1.9 Lpf) • Nonwater urinals:


maximum for “flush” type • Require roughed-in waterline
fixtures • Not less than one water-supplied, 1 DFU fixture
upstream

• H.E.U.’s may use as little • Question?


as one pint and qualify for • Is the roughed in waterline a “dead end”?
LEED points

Copyright © IAPMO 2021 353 Copyright © IAPMO 2021 354

353 354

Copyright©IAPMO 2022

59
5/3/2022

L 402.4 L 402.5
Residential Kitchen Faucets. Lavatory Faucets.

• Shall not exceed 1.8 gpm @ 60 psi • L 402.5.1 …Residences, Apartments, & Private Baths…
• Shall not exceed 1.5 gpm @ 60 psi
• Listed to EPA WaterSense HE Lavatory Faucet Specification

• L 402.5.2 …other than “Residential (above)


• (1) Shall not exceed .5 gpm @ 60 psi
• (2) Metering faucets shall deliver not more than 0.25 gallons of water per
cycle

Copyright © IAPMO 2021 355 Copyright © IAPMO 2021 356

355 356

L 402.6
Showerheads.

• Shall not exceed 2.0 gpm (7.6 L/m) at 80 psi (552kPa),


and shall be listed to ASME A112.18.1/CSA B125.1 and
the EPA WaterSense Specification for Showerheads.

Copyright © IAPMO 2021 357 Copyright © IAPMO 2021 358

357 358

Saving water… L 402.6.1


Packages. Multiple Showerheads Serving One Shower Compartment.

• WaterSense listed items • The total allowable flow rate of water from multiple showerheads
flowing at a given time, with or without diverters, including rain
systems, waterfalls, body sprays, and jets, shall not exceed 2.0
• Showerhead is rated 1.8 gpm gpm per shower compartment, where the floor area of the
shower compartment is less than 1800 square inches (1.161 m2).
For each increment of 1800 square inches (1.161 m2) of floor
• KS swivel aerator 1.5 gpm area after that or part thereof, additional showerheads are
allowed, provided the total flow rate of water flowing from the
devices shall not exceed 2.0 gpm (7.6 L/m) for each such
• Lavatory aerators 1.0 gpm increment.

Copyright © IAPMO 2021 359 Copyright © IAPMO 2021 360

359 360

Copyright©IAPMO 2022

60
5/3/2022

L 402.6.1 L 402.6.1
Exceptions: Observations: Multiple Showerheads Serving One Shower Compartment.

• (1) Gang showers in nonresidential occupancies. Singular


showerheads of multiple shower outlets serving one showering • 1800 Sq. in. = area of typical bathtub (30” x 60”)
position in gang showers shall have not more than 2.0 gpm (7.6
L/m) total flow. • Each increment is permitted 2.0 gpm flow at any given time
• If increased to 1801 square inches, one could have two x 2.0
gpm “outlets” operating at one time
• (2) Where provided, shower compartments required for persons
with disabilities in accordance with Chapter 17 shall not have • Just because one is limited to 2.0 maximum at any one time,
more than 4.0 gpm (15 L/m) total flow, where one outlet is the does NOT mean there cannot be more than one 2.0 gpm “outlet”,
hand shower. rather it means that only 2.0 gpm are allowed at one time…

Copyright © IAPMO 2021 361 Copyright © IAPMO 2021 362

361 362

L 402.6.2
Observations: Bath and Shower Diverters.

• Left: separate
valve for each • The rate of leakage out of the tub spout of bath and
outlet shower diverters while operating in the shower mode
shall not exceed 0.1 gpm (0.4 L/m) in accordance with
• Right: Diverter ASME A112.18.1/CSA B125.1.
selects between
overhead or body
spray options

Copyright © IAPMO 2021 363 Copyright © IAPMO 2021 364

363 364

L 402.6.3
Shower Valves.
Spout Leakage
• Shower valves shall comply with
• Intended to the temperature control
minimize water not performance requirements of
useful for showering ASSE 1016 or ASME
that simply goes A112.18.1/CSA B125.1 where
down the drain… tested at 2.0 gpm (7.6 L/m).

Copyright © IAPMO 2021 365 Copyright © IAPMO 2021 366

365 366

Copyright©IAPMO 2022

61
5/3/2022

L 403.1 L 403.2
Dishwashers. Clothes Washers.

• Residential and commercial • Residential clothes washers shall comply with the Energy
dishwashers shall comply with Star program requirements. Commercial clothes washers
Energy Star program shall comply with Energy Star program requirements,
requirements. where such requirements exist.

Copyright © IAPMO 2021 367 Copyright © IAPMO 2021 368

367 368

L 404.2
Ice Makers.

• Ice makers shall be air


cooled and shall be in
accordance with Energy Star
for commercial ice machines.

Copyright © IAPMO 2021 369 Copyright © IAPMO 2021 370

369 370

L 404.3 L 404.5
Food Steamers. Grease Interceptors.

• Boilerless type steamers shall • Grease interceptor maintenance procedures shall not
consume not more than 2.0 include post-pumping/cleaning refill using potable water.
gallons (7.6 L) per Refill shall be made by connected appliances
compartment. Boiler type accumulated discharge only.
steamers shall consume not
more than 1.5 gallons (5.7 L)
per pan per hour.

Copyright © IAPMO 2021 371 Copyright © IAPMO 2021 372

371 372

Copyright©IAPMO 2022

62
5/3/2022

L 404.6 L 404.7.2
Dipper Wells. Food Waste Disposers.

• Where dipper wells are installed, the water supply to a dipper well shall • The water use for the food waste
have a shutoff valve and flow control. The flow of water into a dipper well grinder shall not exceed 8 gpm (30.3
shall be limited by not less than one of the following methods: (1) Water L/m) under full load condition and 1 gpm
flow shall not exceed the water capacity of the dipper well in one minute at (3.8 L/m) under no-load condition. Flow
a supply pressure of 60 psi (414kPa), and the maximum flow shall not
exceed 2.2 gpm (8.3 L/m) at a supply pressure of 60 psi (414 kPa). The restrictors shall be installed on the water
water capacity of the dipper well shall be the maximum amount of water supply to limit the water flow rate to a
that the fixture can hold before water flows into the drain. (2) The volume of maximum of 8 gpm (30.3 L/m). A load
water dispensed into a dipper well in each activation cycle of a self-closing sensing device shall be installed to
fixture fitting shall not exceed the water capacity of the dipper well, and the monitor current demand and regulate
maximum flow shall not exceed 2.2 gpm (8.3 L/m) at a supply pressure of water flow.
60 psi (414 kPa).

Copyright © IAPMO 2021 373 Copyright © IAPMO 2021 374

373 374

L 406.1
Use of Alternate Water Source for Special Water Features.

• Special water features such as ponds and water


fountains shall be provided with reclaimed (recycled)
water, rainwater, or on-site treated nonpotable water
where the source and capacity are available on the
premises and approved by the AHJ.

Copyright © IAPMO 2021 375 Copyright © IAPMO 2021 376

375 376

L 407.1
Meters Required.

• A water meter shall be required for buildings connected


to a public water system, including municipally supplied
reclaimed (recycled) water. In other than single-family
houses, multifamily structures of three or fewer stories
above grade, and modular houses, a separate meter or
submeter shall be installed in the following locations:
• There are six (6) specific locations that follow…

Copyright © IAPMO 2021 377 Copyright © IAPMO 2021 378

377 378

Copyright©IAPMO 2022

63
5/3/2022

L 411.0
Landscape Irrigation Systems.

• L 411.2 Backflow Protection.


• L 411.3 Use of Alternate Water Sources for Landscape
Irrigation.
• L 411.4 Irrigation Control Systems.
• L 411.5 Low Flow Irrigation.
• L 411.10 Sprinkler Head Installation.
• L 411.12 Depth of Irrigation Pipe.

Copyright © IAPMO 2021 379 Copyright © IAPMO 2021 380

379 380

L 411.4 L 411.4
Irrigation Control Systems. Irrigation Control Systems. (continued)

• Where installed as part of a landscape irrigation system, irrigation • (5) The site-specific settings of the irrigation control system affecting the
controls shall: irrigation and shall be posted at the control system location. The posted
• (1) Automatically adjust the irrigation schedule to respond to plant water data, where applicable to the settings of the controller, shall include:
needs determined by weather or soil moisture conditions. • (a) Precipitation rate for each zone.
• (2) Utilize sensors to suspend irrigation during rainfall. • (b) Plant evapotranspiration coefficients for each zone.
• (3) Utilize sensors to suspend irrigation where adequate soil moisture is • (c) Soil absorption rate for each zone.
present for plant growth. • (d) Rain sensor settings.
• (4) Have the capability to program multiple and different run times for • (e) Soil moisture setting.
each irrigation zone to enable cycling of water applications and durations
to mitigate water flowing off of the intended irrigation zone. • (f) Peak demand schedule including run times for each zone and number
of cycles to mitigate runoff and monthly adjustments or percentage.

Copyright © IAPMO 2021 381 Copyright © IAPMO 2021 382

381 382

L 411.5
Low Flow Irrigation.

Copyright © IAPMO 2021 383 Copyright © IAPMO 2021 384

383 384

Copyright©IAPMO 2022

64
5/3/2022

L 411.10.3
Where pop-up type sprinkler
heads are installed, the
sprinkler heads shall rise to a
height above vegetation level
and of not less than 4 inches
(102 mm) above the soil level
where emitting water.

Copyright © IAPMO 2021 385 Copyright © IAPMO 2021 386

385 386

L 411.12 L 412.0
Depth of Irrigation Pipe. Trap Seal Protection.

• L 412.1 Water Supplied Trap Primers. Water supplied trap primers shall be
electronic or pressure activated and shall use not more than 30 gallons (114 L)
• Irrigation pipe downstream from per year per drain. Where an alternate water source, as defined by this code, is
the backflow preventer shall be used for fixture flushing or other uses in the same room, the alternate water
buried at a minimum depth source shall be used for the trap primer water supply.
according to Section L 411.12.1 • Exception: Flushometer tailpiece trap primers in accordance with IAPMO PS
76.
and Section 411.12.2.
• L 412.2 Drainage Type Trap Seal Primer Devices. Drainage type trap seal
primer devices shall not be limited in the amount of water they discharge.

Copyright © IAPMO 2021 387 Copyright © IAPMO 2021 388

387 388

L 501.0
Water Heating Design, Equipment, and Installation.

• L 501.1 Scope. The provisions of this section shall establish the


means of conserving potable and nonpotable water and the
energy associated with generation and use of hot water in a
building. This includes provisions for the hot water distribution
system between a water heating device and the plumbing
fixtures, including dedicated return piping and appurtenances to
the water heating device in a recirculation system.

Copyright © IAPMO 2021 389 Copyright © IAPMO 2021 390

389 390

Copyright©IAPMO 2022

65
5/3/2022

L 501.2 Hot Water


Insulation. Extensive section…

• Hot water supply piping and return • Due to interconnection of conservation, water & energy
piping shall be thermally insulated. this section is large
The wall thickness of the insulation
shall be equal to the nominal
diameter of the pipe up to two • We will not go into detail…
inches (50 mm). The wall thickness
shall be not less than 2 inches (51
mm) for nominal pipe diameters
exceeding two inches (50 mm)…

Copyright © IAPMO 2021 391 Copyright © IAPMO 2021 392

391 392

L 506.0
Drain Water Heat Exchangers.
Solar Water Heating…
L 504.1 General. The • L 506.1 General. Drain water heat exchangers shall
erection, installation,
alteration, addition to, or
comply with IAPMO PS 92. The heat exchanger shall be
maintenance of solar accessible.
water heating systems
shall be in accordance
with this section and the
Uniform Solar Energy
and Hydronics Code.

Copyright © IAPMO 2021 393 Copyright © IAPMO 2021 394

393 394

L 602.0
Qualifications.

• L 602.1 General. Where permits


are required the AHJ shall have
the authority to require
contractors, installers, or service
technicians to demonstrate
competency. Where determined by
the AHJ, the contractor, installer,
or service technician shall be
licensed to perform such work.

Copyright © IAPMO 2021 395 Copyright © IAPMO 2021 396

395 396

Copyright©IAPMO 2022

66
5/3/2022

Appendix M
PEAK WATER DEMAND CALCULATOR

• Entirely new in 2018, however with 2021 adopted by Montana

• Absolute innovation! 1st substantial update to water sizing in 80


years!

• HUGE implications for:


• Pipe sizing
• Water conservation

Copyright © IAPMO 2021 397 Copyright © IAPMO 2021 398

397 398

Why Appendix M? IAPMO Engagement:


What drove this initiative? Leader in innovation and collaboration…

• Plumbing fixture water demand changed drastically over time. • Convener of Emerging Water Technology Symposium (EWTS)
• Dr. Hunter’s world: • Partnered with Plumbing’s pre-eminent thought leaders:
• Water Closets – 6-8 gallons per flush • Alliance for Water Efficiency
• “Water conserving fixtures” were unheard of and unthought of… • American Society of Plumbing Engineers
• Flush and forget mentality virtually ubiquitous! • Plumbing Manufacturers International
• Today: • World Plumbing Council
• Water Closets – as low as .6 gallons per flush! • “Last Mile” studies – less liquid goes down the drain, how does
• Water conservation is the norm everywhere sewage get to the wastewater treatment plant?
• Infrastructure that was aging in Dr. Hunter’s era is ancient and failing
catastrophically!

Copyright © IAPMO 2021 399 Copyright © IAPMO 2021 400

399 400

Implications of pipe sizing… is bigger really better? M101.1


Consider: Applicability.

• Cost of pipe & fittings • This appendix provides a method for estimating the
• Potable water wasted demand load for the building water supply and principal
branches for single and multi-family dwellings with water-
• Watergy = “Interconnection of water and energy” conserving fixtures, fixtures fittings, and appliances.
• Efficiency of potable water distribution systems
• Public health – reducing harborage of Legionella bacteria

Copyright © IAPMO 2021 401 Copyright © IAPMO 2021 402

401 402

Copyright©IAPMO 2022

67
5/3/2022

M102.1 M 102.2
Water-Conserving Fixtures. Water Demand Calculator.

• Plumbing fixtures, • The estimated design flow rate for the building supply
fixture fittings and and principal branches and risers shall be determined by
appliances shall not the IAPMO Water Demand Calculator available for
exceed the design download at:
flow rate in Table M
102.1. • http://www.iapmo.org/WEStand/Pages/WaterDemandCalculator.aspx

Copyright © IAPMO 2021 403 Copyright © IAPMO 2021 404

403 404

M 102.3
Meter and Building Supply.

• To determine the design flow rate for the water meter and
building supply, enter the total number of indoor
plumbing fixtures and appliances for the building in
Column [B] of the Water Demand Calculator and run
Calculator. See Table M 102.3 for an example.

Copyright © IAPMO 2021 405 Copyright © IAPMO 2021 406

405 406

M 102.4 M 102.5
Fixture Branches and Fixture Supplies. Continuous Supply Demand.

• Continuous supply demands in gallons per minute (gpm) for lawn


• To determine the design flow rate for fixture branches sprinklers, air conditioners, hose bibbs, etc., shall be added to
the total estimated demand for the building supply as determined
and risers, enter the number of plumbing fixtures and by Section M 102.3. Where there is more than one hose bibb
appliances for the fixture branch or riser in Column [B] of installed on the plumbing system, the demand for only one hose
the Water Demand Calculator and run Calculator. The bibb shall be added to the total estimated demand for the
flow rate for one fixture branch and one fixture supply building supply. Where a hose bibb is installed on a fixture
shall be the design flow rate of the fixture according to branch, the demand of the hose bibb shall be added to the
Table M 102.1. design flow rate for the fixture branch as determined by Section
M 102.4.

Copyright © IAPMO 2021 407 Copyright © IAPMO 2021 408

407 408

Copyright©IAPMO 2022

68
5/3/2022

M 102.6 M 102.7
Other Fixtures. Size of Water Piping per Appendix A

• Except as provided in Section M102.0 for estimating the demand load for
single- and multi-family dwellings, the size of each water piping system
• Fixtures not included on Table M 102.1 shall be added in shall be determined in accordance with the procedure set forth in
Rows 12 through 14 in the Water Demand Calculator as Appendix A. After determining the permissible friction loss per 100 feet
Other Fixture. The probability of use and flow rate for (30 480 mm) of pipe in accordance with Section A 104.0 and the demand
flow in accordance with the Water Demand Calculator, the diameter of
Other Fixtures shall be added by selecting the the building supply pipe, branches and risers shall be obtained from
comparable probability of use and flow rate from Chart A 105.1(1) through Chart A 105.1(7), whichever is applicable, in
Columns [C] and [F]. accordance with Section A 105.0 and Section A 107.0. Appendix I (IS
31), Figure 3 and Figure 4 shall be permitted when sizing PEX systems.

Copyright © IAPMO 2021 409 Copyright © IAPMO 2021 410

409 410

M 107.7.1 Appendix M
Minimum Fixture Branch Size. The rest of this appendix…

• The minimum fixture branch size shall be ½ inch (15 • Provides several examples:
mm) in diameter. • 1. Find Demand Load for Building Supply.
• 2. Determine the Pipe Size of the Building Supply.
• Note: fixture branch and fixture supply are NOT the • 3. Indoor, Outdoor and Other Fixtures Water Use.
same!
• 4. Sizing Branches and Risers

Copyright © IAPMO 2021 411 Copyright © IAPMO 2021 412

411 412

Appendix N Recent Legionella Outbreaks


…LEGIONELLA & SCALDING… Everywhere…

• NEW in 2021 UPC; adopted in Montana • University of Washington


• Portland, OR
• Monumental step forward in minimizing (eliminating?) potential • Columbus, OH
exposure to health risks posed by: • Flint, MI
• Legionella • Pekin, IL
• Scalding • Montréal, PQ
• New Westminster, BC
• Dynamic tension - really hot water really kills Legionella • New South Wales, AUS
bacteria… however, it scalds! • Hong Kong

Copyright © IAPMO 2021 413 Copyright © IAPMO 2021 414

413 414

Copyright©IAPMO 2022

69
5/3/2022

CDC reports:
Hospitals at significant risk…

• Legionella in hospitals accounted for 57% of all cases


and 88% of deaths

Copyright © IAPMO 2021 415 Copyright © IAPMO 2021 416

415 416

Potable Water versus Utility (Cooling Towers) Other sources


Statistics Less common, however, real…

• Potable water was the most frequent source of exposure • Spas and hot tubs
at 56% followed by cooling towers at 22%
• Misters
• Potable water sources accounted for 67% of health-care
associated outbreaks in hospitals and long-term care
facilities • Grocery store produce counters, etc.

Copyright © IAPMO 2021 417 Copyright © IAPMO 2021 418

417 418

Copyright © IAPMO 2021 419 Copyright © IAPMO 2021 420

419 420

Copyright©IAPMO 2022

70
5/3/2022

N 101.1 N 101.1
Applicability. Applicability. Note: (continued)

• This appendix provides guidelines on the impact of water • There are additional factors associated with the potential for
temperature in minimizing both scalding and Legionella growth scalding and Legionella growth other than temperature.
potential associated with occupiable commercial, institutional, • For scalding potential, other factors include, but are not limited
multi-unit residential and industrial building plumbing systems. to, user age, health, body part, length of contact time and water
• This Appendix shall not include single-family residential source.
buildings. This appendix shall not be considered a risk • For Legionella growth potential other factors include, but are not
management guidance document for scalding or Legionella. limited to, water source and plumbing system: size, design,
• Note: Published documents which address Legionella risk circulation rate, water age, disinfectant residual, piping material
management include ASHRAE 188, ASHRAE Guideline 12, or as and component complexity.
required by the AHJ.

Copyright © IAPMO 2021 421 Copyright © IAPMO 2021 422

421 422

N 102.0 N 102.0
Definitions. Definitions. (continued)

• N 102.1 Cold Water. Water at a temperature of less than 77 0F (250C). • N 102.6 Hot Water. Water at a temperature not less than 1300F (540C)
• N 102.2 Tepid Cold Water. Water at a temperature not less than 77 0F and less than 1400F (600C).
(250C) and less than 850F (290C). • N 102.7 Very Hot Water. Water at a temperature not less than 1400F
• N 102.3 Tepid Water. Water at a temperature not less than 85 0 F (290C) (600C) and less than 1600F (710C).
and less than 1100F (430C). • N 102.8 Disinfecting Hot Water. Water at a temperature not less than
• N 102.4 Warm Water. Water at a temperature not less than 110 0F (430C) 1600F (710C).
and less than 1200F (490C). • N 102.9 Legionella Growth Potential. The likelihood that Legionella
• N 102.5 Tempered Hot Water. Water at a temperature not less than 120 0F bacteria will reproduce.
(490C) and less than 1300F (540C). • 102.10 Scald Potential. The likelihood of burning the skin.

Copyright © IAPMO 2021 423 Copyright © IAPMO 2021 424

423 424

N 103.1 N 104.1
Required Documentation. Legionella Growth Potential.

• Construction documents shall be required for new • The AHJ shall have the authority to require
construction, renovation, refurbishment, replacement, or documentation to address Legionella growth potential,
repurposing of an occupiable building water system and where water temperatures in a water distribution system
shall be submitted to the AHJ. are within ranges shown in Table N 104.1 that pose a
Legionella growth potential.

Copyright © IAPMO 2021 425 Copyright © IAPMO 2021 426

425 426

Copyright©IAPMO 2022

71
5/3/2022

N 104.2 N 105.1
Scald Potential. Disinfection Documentation.

• Where required by the AHJ, documentation for


• Where the water distribution system’s water disinfection of all building water systems shall be
temperature(s) range poses a scald potential in provided by the registered design professional in the
accordance with Table 104.1, protection shall be construction documents.
provided in accordance with Chapter 4. • Methods for new construction and any repaired system
disinfection shall include, the chlorination methods and
procedures for flushing and disinfection in accordance
with Section 609.10.

Copyright © IAPMO 2021 427 Copyright © IAPMO 2021 428

427 428

N 105.1
Disinfection Documentation. (continued)

• Other or alternative water treatment methods for disinfection shall


include, but not be limited to, one of the following methods:
• (1) Copper-silver ionization methods and procedures including the
following documentation:
• (a) Copper and silver ionization concentrations shall be included in the documentation.
• (b) Methods and documentation for monitoring ion levels.
• (c) Electrode cleaning cycles and methods shall be reported.
• (2) Ultraviolet light methods shall include the following documentation:
• (a) Location of ultraviolet light units.
• (b) Cleaning cycles and methods of the quartz sleeves and housing shall be
documented.

Copyright © IAPMO 2021 429 Copyright © IAPMO 2021 430

429 430

G.F. (jed) Scheuermann

jed.scheuermann@iapmo.org

971-300-7649

Copyright © IAPMO 2021 431

431

Copyright©IAPMO 2022

72

You might also like