Professional Documents
Culture Documents
Contact information
2018 to 2021 Uniform
• G.F.(jed) Scheuermann
Plumbing Code Changes
• E-mail to: jed.scheuermann@iapmo.org
Presented By: Jed Scheuermann
• Cellular: (971) 300-7649
1 2
Copyright
3 4
Disclaimers Who am I?
Background & Contact information:
5 6
Copyright©IAPMO 2022
1
5/3/2022
Question:
Who are you?
7 8
• Q&A
• Scenarios
• Many relevant photographs!
9 10
11 12
Copyright©IAPMO 2022
2
5/3/2022
• (1) The following modifications to the IBC are applicable to both the
• All of these may be found at Montana department’s enforcement program and local government building code
Department of Labor & Industry, Business enforcement programs.
Standards Division, web site under
“Current Codes” • (2) Subsection 101.4, Referenced Codes, is modified by adding the
following: “Any reference to a separate specialty code, by title, either in
this subsection or elsewhere in this code, shall be considered deleted
• http://www.mtrules.org/gateway/Subchapt
erhome.asp?scn=24%2E301.3
and replaced with the title of the model code adopted and in effect at the
time as applicable.”
• Class will sequentially incorporate all
• (3) Subsection 101.4.3, Plumbing is modified by:
Montana plumbing amendments • (a) Deleting “International Plumbing Code” and replacing with “Uniform Plumbing
Code.”
13 14
• (25) Table 2902.1 MINIMUM NUMBER OF PLUMBING FIXTURES, is • (3) Chapters 11 through 14, inclusive, are deleted in their
modified by deleting and replacing with ARM 24.301.351.
entirety and chapters 16 through 43 are deleted in their
• (26) Subsection 2902.3, Required Public Toilet Facilities, is deleted in its entirety…
entirety and replaced with “Required Public Toilet Facilities shall be
provided in accordance with the Uniform Plumbing Code 2021 Section • These chapters include IRC “plumbing” provisions. It
422.4. takes all plumbing out of the IRC, replacing them with
• This takes these minimum requirements out of the International Building UPC provisions.
Code IBC and replaces them with UPC provisions.
15 16
• (1) (a) Subsection 102.8, Referenced Codes and Standards, is • (1) (a) Subsection 102.8, Referenced Codes and Standards, is
modified by adding the following: “Any reference to a separate modified by adding the following: “Any reference to a separate
specialty building regulation, by title, either in this subsection or specialty building regulation, by title, either in this subsection or
elsewhere in this code, shall be considered deleted and replaced elsewhere in this code, shall be considered deleted and replaced
with the title of the model code adopted by the department and in with the title of the model code adopted by the department and in
effect at the time. effect at the time. For example, all references to the International
• (b) All references to the International Plumbing Code shall be Plumbing Code shall be deleted and replaced with the Uniform
deleted and replaced with the Uniform Plumbing Code. Plumbing Code.
• It takes all plumbing out of the IMC, replacing them with UPC • It takes all plumbing out of the IFGC, replacing them with UPC
provisions. provisions.
17 18
Copyright©IAPMO 2022
3
5/3/2022
24.301.301 24.301.301
Incorporation by reference of Uniform Plumbing Code Incorporation by reference of Uniform Plumbing Code
19 20
• 24.301.301 (1) (a)-(h) are modified to reflect the 2021 edition and
add additional appendices for alternative methods of compliance. • The purpose of this code is to provide minimum requirements
(d)-(h) are relabeled as (i)-(m). (i) is repealed as it now mirrors and standards for plumbing installations for the protection of the
the text in the UPC 2021. (l) is relabeled as (o). (m) is repealed public health, safety, and welfare. The Uniform Plumbing Code is
as it mirrors the text in the UPC 2021. (n)-(p) are relabeled as a nationally recognized model code setting forth minimum
(p)-(w). (x) new amendment, Plumbers rarely know where crawl standards and requirements for plumbing installations. A copy of
access holes will be located when installing the underground the Uniform Plumbing Code may be obtained from the
piping. (v) is relabeled as (y). (w) is repealed as it now mirrors International Association of Plumbing and Mechanical Officials at
the text in the UPC 2021. (x)-(ah) are relabeled as (z)-(aj). www.iapmo.org
21 22
• Subsection 103.3.1, Licensing is amended with the addition of the • (i) No permit is required for any minor replacement or repair
following language: work, the performance of which does not have a significant
• “Provision for licensing shall be determined by the Authority Having potential for creating a condition hazardous to public health and
Jurisdiction. The requirements for who must be licensed to perform safety.
plumbing work is regulated by Title 37, chapter 69, MCA.”
• (ii) No permit is required where the installation is exempt under
• (1) (e) Subsections 104.1, 104.2, 104.3, 104.3.2, 104.4, 104.5, 105.0, provisions of 50-60-503 or 50-60-506, MCA.
105.4, 106.1, 106.3 and 107.0 will be left as is for use by local
governments (i.e., municipalities and counties), but will not be used by • (iii) The requirements for permits do not apply to regularly
the department and the state of Montana. For the purposes of employed maintenance personnel doing maintenance work on
enforcement by the department, these subsections are replaced with the business premises of their employer unless work is subject to
provisions of Title 50, chapter 60, part 5, MCA. the permit provisions of these rules.
23 24
Copyright©IAPMO 2022
4
5/3/2022
• Delete Table 104.5 – PLUMBING PERMIT FEES and replace with the
following schedule:
• (i) for each plumbing fixture $10
• (iv) Factory-built buildings covered by an insignia issued by the
department need not have a plumbing permit for the construction • (ii) water service – domestic or commercial 20
of the unit; however, a permit will still be required for on-site • (iii) for each building sewer and each trailer park sewer 20
work, as provided for in these rules. • (iv) storm drains and storm drainage 20
• (v) for each water heater (replacement or new) 25
• (vi) for each industrial water pretreatment interceptor, including its tray
and vent, excepting kitchen type grease interceptors functioning as
fixture traps 30
25 26
• (vii) for alteration or repair of water piping and/or water treatment • (xi) requested plumbing inspection fee (provided that such service is not
equipment 30 in excess of one hour duration, and then in $35 for each 30 minutes or
• (viii) for repair or alteration of drainage or vent piping 30 fractional part thereof in excess of one hour. Travel and per diem may be
charged as per the state of Montana’s existing rate for these items) 75
• (ix) for each lawn sprinkler system and fire protection system or any one
meter, including backflow protection devices therefore 30 • (xii) reinspection (provided the $30 does not exceed the original permit
fee, in which case the original fee will be charged) 45
• (x) for each hose bibb, vacuum breakers, or backflow protective devices
on tanks, vats, etc., or for installation on unprotected plumbing fixtures,
including necessary water piping 6 each
27 28
29 30
Copyright©IAPMO 2022
5
5/3/2022
Chapter 1 24.301.361
104.0 Permits Montana amendment
• (1) Any person who is required under 50-60-505, MCA to obtain a plumbing
permit, and the work is not covered by a local government inspection
• This section and its sub-sections deal with the matter of program, shall do so prior to installation through the department.
plumbing permits. • (2) The exception to the plumbing permit requirement listed in 50-60-503,
MCA, for plumbing installations on farms having their own individual water
supply or sewage disposal system applies to farm and ranch installations
• Montana added several amendments which will now be used in conjunction with an agricultural or livestock raising operation which
considered… are not connected to either a public water supply or public sewer system.
Any building used as or in conjunction with a hotel, bed and breakfast
establishment, or other place where sleeping accommodations are
furnished to transient guests for a fee is subject to the requirements of ARM
24.301.301.
31 32
24.301.361 24.301.361
Montana amendment Montana amendment
33 34
Chapter 1 24.301.371
105.0 Inspections and Testing Montana amendment
• (1) When the permit holder is ready for inspection, he shall notify the
department either orally or in writing. The notification shall be given not
• This section and its sub-sections deal with the matter of less than 24 hours before the work is to be inspected. To assist the
plumbing inspections. department with its scheduling of inspections, it is asked that inspection
requests be made as much in advance of the 24-hour minimum notice
time as possible. Cover (rough-in) inspections are made by a state
• Montana added several amendments which will now be plumbing inspector wherever possible. Insulation and wallboard shall not
considered… be applied prior to inspections unless 48 hours, excluding Saturdays,
Sundays and holidays have expired after the plumbing installation is
complete and notice to inspect has been received.
35 36
Copyright©IAPMO 2022
6
5/3/2022
24.301.371 24.301.371
Montana amendment Montana amendment
• (2) The permit holder shall be responsible for assuring that the plumbing • (4) If the inspection reveals code violations, the permit holder shall be
work is not covered before the department has granted permission to given an opportunity to make corrections. If after reinspection the
cover said work. The inspection shall be made during daylight hours violation has been corrected, the permit holder shall be issued a
unless it is more convenient to all parties involved to make the inspection certificate of compliance. If such violation is not corrected, the permit
at night. holder or other responsible persons will be charged as per 50-60-110,
• (3) Upon completion of the final inspection and approval of the plumbing MCA.
work, the department shall, if requested, issue the permit holder a • (5) Plumbing inspectors shall not inspect any plumbing work in which
certificate of compliance. they have any financial or personal interest, or which they have installed
or repaired. (This is a new provision!)
37 38
• (a) liquid made by stewing bones & vegetables, as in soup broth • Foundation of UPC! Words have meaning, context & authorial
• (b) to assess, as in take “stock” of a situation intent are important!
• (c) a store of goods
• (d) farm animals, as in livestock • 18 new or modified definitions
• (e) timber frame with holes to hold criminals for public punishment
• (f) support or handle for an implement or gun • One Montana amendment
• (g) shares or financial interest in a company, as in “stock market”
• (h) reputation – his “stock” is rising as he continues to excel at work
• Plus, a selection of critically important terms to understand…
39 40
205.0
Category 3 Vacuum System
Ordinary Words
• A Category 3 vacuum distribution system that can be
either a wet system designed to remove liquids, air-gas,
See a dictionary… or solid from the treated area; or a dry system designed
to trap liquids and solids before the service inlet and to
accommodate air-gas only through the service inlet.
[NFPA 99:3.3.21]
41 42
Copyright©IAPMO 2022
7
5/3/2022
205.0 205.0
Circuit Vent (new) Commercial Modular System (new)
• The vent that connects to a horizontal drainage branch • A drinking water treatment unit system consisting of
and vents two traps to a maximum of eight traps multiple components attached to a manifold, produced
connected into a battery of fixtures. specifically for food service applications, and not
intended for use in residential applications.
43 44
• A section of potable water pipe which contains water that • Many installations are dead legs:
has no flow or does not circulate. • Capped ends
• Futures
• New definition, necessary for section 309.6
• What is the issue?
• Legionella
• Relates also to Appendix N, dealing with Legionella
• Water stagnation
45 46
207.0 209.0
Expansion Tank (new) General Anesthesia and Levels of Sedation/Analgesia (new)
47 48
Copyright©IAPMO 2022
8
5/3/2022
209.0
General Anesthesia and Levels of Sedation/Analgesia (continued)
49 50
51 52
209.0 209.0
General Anesthesia and Levels of Sedation/Analgesia (continued) General Anesthesia and Levels of Sedation/Analgesia (continued)
• Minimal Sedation (Anxiolysis). A drug-induced state during • Moderate Sedation/Analgesia (Conscious Sedation). A drug-
which patients respond normally to verbal commands. Although induced depression of consciousness during which patients
cognitive function and coordination may be impaired, ventilatory respond purposefully to verbal commands, either alone or
and cardiovascular functions are unaffected. [NFPA 99:3.3.66.4] accompanied by light tactile stimulation. No interventions are
required to maintain a patent airway, and spontaneous ventilation
is adequate. Cardiovascular function is usually maintained.
[NFPA 99:3.3.66.3]
53 54
Copyright©IAPMO 2022
9
5/3/2022
209.0
Group Wash Fixture (new)
55 56
57 58
214.0
Low-Pressure Water Dispenser (new)
59 60
Copyright©IAPMO 2022
10
5/3/2022
216.0
Nonwater Urinal with Drain Cleansing Action (new)
61 62
• (1) (l) 218.0 Definition of Plumbing System is amended to • A device serving the water distribution system of a
read: Includes all potable water and alternate water sources building for the purposes of altering, modifying, adding,
including supply and distribution pipes, all plumbing fixtures and or removing minerals, chemicals, contaminants, and
traps, all drainage and vent pipes, building drains and building
sewers, including their respective joints and connections, suspended solids in water.
devices, receptacles, and appurtenances within the property line
of any premises, and includes water heaters and vents for the
premises.
63 64
218.0 218.0
P.o.E. (continued) Point-of Use, Water Treatment Unit (new)
65 66
Copyright©IAPMO 2022
11
5/3/2022
218.0
Pre-Fabricated Shower Enclosure (new)
67 68
218.0 218.0
Private or Private Use Public Water System (new)
• Applies to plumbing fixtures in residences and • A system for the provision to the public of water for
apartments, to private bathrooms in hotels, hospitals, human consumption through pipes or other constructed
and health-care facilities, and to restrooms in commercial conveyances, if such system has at least fifteen service
establishments where the fixtures are intended for the connections or regularly serves an average of twenty-five
use of a family or an individual. individuals daily for at least 60 days per year.
69 70
224.0 Question
Vent Offset Which of these constitutes a “dead leg”?
• An arrangement of two or more fittings • (A) a 2” long section of 1” Type K copper water tube with a cap
and pipe installed for the purpose of
locating a vertical section of the vent • (B) water pipe provided for future fixtures
pipe in a different but parallel plane
with respect to an adjacent section of
vertical vent pipe. [NFPA 54:3.3.102] • (C) waterline roughed in at a non-water urinal for future retrofit of a
water-supplied urinal
71 72
Copyright©IAPMO 2022
12
5/3/2022
Chapter 3 301.2
General Regulations Minimum Standards.
73 74
Creativity abounds…
And it even “works”…
75 76
301.2.2
Standards.
77 78
Copyright©IAPMO 2022
13
5/3/2022
• This installation may fit well in • Dead legs shall have a method of flushing.
a pub, tavern or similar
establishment, however…
• What constitutes this?
• A valve?
• Sediment faucet or boiler drain?
• Removable plug or cap?
• Enforcement to ensure flushing occurs?
79 80
• Ten changes
• When is an eyewash station • Hot water temperature limitations at various fixtures:
used? • Public lavatories
• Gang showers
• Bathtubs & whirlpool bathtubs
• Does this not in effect become
• Bidets
a “dead leg”?
• New devices
• Other minor changes
81 82
402.6.3
Securing Floor-Mounted, Back-Outlet Water Closet Bowls.
83 84
Copyright©IAPMO 2022
14
5/3/2022
85 86
What is it?
WC Flange
• This is an “offset”
WC Flange:
• (A) True
• (B) False
87 88
89 90
Copyright©IAPMO 2022
15
5/3/2022
408.1 408.3.1
Application. Gang Showers.
• Manufactured shower receptors and shower bases shall • Where gang showers are supplied with a single
comply with ASME A112.19.1/CSA B45.2, ASME temperature-controlled water supply pipe, it shall be
A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4, controlled by a mixing valve that complies with ASSE
CSA B45.12/IAPMO Z402, or CSA B45.5/IAPMO Z124. 1069.
Prefabricated shower enclosures shall comply with
IAPMO IGC 154.
• Reworded, however essence remains unchanged.
91 92
93 94
408.3.2
Temperature Limiting. (Continued)
95 96
Copyright©IAPMO 2022
16
5/3/2022
408.5
Finished Curb or Threshold.
97 98
99 100
101 102
Copyright©IAPMO 2022
17
5/3/2022
• Table 422.1, Minimum Plumbing Facilities, is deleted and • Quite a few changes…
replaced with ARM 24.301.351, Minimum Required
Plumbing Fixtures.
• Focus on “plumbing” changes
103 104
105 106
Seismic strap…
107 108
Copyright©IAPMO 2022
18
5/3/2022
109 110
507.23
Combination of Appliances and Equipment.
111 112
113 114
Copyright©IAPMO 2022
19
5/3/2022
508.2.1.1 508.2.1.1
Guards and Rails. Guards and Rails.
• Guards or rails shall be required where the following • Where guards or rails are installed, they shall be
exist: constructed so as to prevent the passage of a 21inch
• (1) The clearance between the appliance and a roof (533mm) diameter ball, resist the imposed loading
edge or open end of an equipment platform is less than 6 conditions, and shall extend not less than 30 inches
feet (1829mm). (762mm) beyond each side of the equipment or
appliance.
• (2) The open end of the equipment platform is located
more than 30 inches (762mm) above the roof, floor, or • Exception: Guards shall not be required where a
grade below. permanent fall arrest anchorage connector system in
accordance with ASSE Z359.1 is installed.
115 116
• Exterior roof
• Buildings more than 15 feet (4572 mm) in access permitted
height shall have an inside means of
access to the roof, unless other means • Security
acceptable to the AHJ are used. [NFPA (unauthorized
54:9.4.3.2] access) is a real
concern…
117 118
509.4.1 509.4.1
Plastic Piping. Plastic Piping. (continued)
119 120
Copyright©IAPMO 2022
20
5/3/2022
509.4.2 Chapter 6
Plastic Vent Joints. Water Supply and Distribution
121 122
601.2 601.2
Water Supply and Flushing. Water Supply and Flushing (continued)
123 124
601.2.1 601.3.4
Hot and Cold Water Required Fixtures.
• In occupancies where plumbing fixtures are installed for private • Where vacuum breakers or backflow preventers are
use, hot water shall be required for bathing, washing, laundry, installed with fixtures listed in Table 1701.1 Chapter 17,
cooking purposes, dishwashing or maintenance. In occupancies
where plumbing fixtures are installed for public use, hot water
identification of the discharge side shall be permitted to
shall be required for bathing and washing purposes. This be omitted.
requirement shall not supersede the requirements for individual
temperature control limitations for public lavatories, and public
and private bidets, bathtubs, whirlpool bathtubs, and shower
control valves.
125 126
Copyright©IAPMO 2022
21
5/3/2022
127 128
129 130
131 132
Copyright©IAPMO 2022
22
5/3/2022
• Backflow preventer with intermediate atmospheric vent and • Laboratory faucet backflow preventer
pressure reducing valve • Applicable Standard – ASSE 1035
• Applicable standard – ASSE 1081 • Suitable for Contamination (High Hazard)
• Degree of Hazard – Pollution (Low Hazard) • Suitable for back siphonage and back pressure
• Suitable for back siphonage and back pressure • Installation includes laboratory faucets. Such devices are not for
• Installation notes: Installation of potable water connections to use under continuous pressure conditions. No valve
water boilers. No high hazard chemicals shall be introduced into downstream.4
the system using such devices. Designed to operate under • 4 Not to be subjected to operating pressure for more than 12
continuous pressure conditions. May discharge water. hours in a 24 hour period.
133 134
135 136
Major change!
Chemical dispenser…
137 138
Copyright©IAPMO 2022
23
5/3/2022
603.3.10
Dual Check Backflow Preventer.
139 140
603.3.11
Laboratory Faucet Backflow Preventers.
141 142
603.3.12 24.301.301
Backflow Preventer with Intermediate Atmospheric Vent. Montana amendment
• A backflow preventer with intermediate atmospheric vent • Delete subsection 603.4.2 Testing.
consists of two independently acting check valves force loaded
to a normally closed position, and an intermediate chamber with
a means for automatically venting to atmosphere, force loaded to • (There were minor changes to Model Code provisions.)
a normally open position.
143 144
Copyright©IAPMO 2022
24
5/3/2022
603.5.10
Steam or Hot Water Boilers.
145 146
147 148
149 150
Copyright©IAPMO 2022
25
5/3/2022
151 152
153 154
606.8
Check Valve Required.
155 156
Copyright©IAPMO 2022
26
5/3/2022
606.9 608.3
Leak Detection Devices. Expansion Tanks, Combination Temperature Pressure Relief Valves.
157 158
PRV’s
Bypass…
• Some pressure
reducing valves (PRV)
are internally bypassed,
allowing dissipation into
municipal mains
159 160
161 162
Copyright©IAPMO 2022
27
5/3/2022
608.5
Discharge piping.
163 164
TPRV discharge
Does this comply with 608.5?
165 166
TPRV discharge
Continued…
167 168
Copyright©IAPMO 2022
28
5/3/2022
609.8 609.8
Pumps. Pumps.
• Pumps shall be installed in accordance with the • 609.8.2 Potable Water Pumps.
manufacturer’s installation instructions. Pumps intended to supply
drinking water shall be in
accordance with NSF 61.
• 609.8.1 Access. Pumps shall be accessible for repairs.
169 170
• Due to a new section added, “Pipe Insulation” was re- • There are six (6) subsections, then a concluding sentence
numbered to 609.12
• No building supply pipe shall be less than ¾ of an inch (20mm)
• Delete in its entirety (19.1mm) in inside diameter.
171 172
173 174
Copyright©IAPMO 2022
29
5/3/2022
175 176
• No air gap
• Unvented P-trap
• No primer
177 178
179 180
Copyright©IAPMO 2022
30
5/3/2022
Chapter 7 Let’s see, if you can figure out what’s going on here…
Sanitary Drainage
181 182
183 184
185 186
Copyright©IAPMO 2022
31
5/3/2022
187 188
701.5
Lead.
• (See Table 1701.1) (See Chapter 17) Sheet lead shall comply
with the following:
• (1) For safe pans – not less than 4 pounds per square foot (lb/ft2)
(19 kg/m2) or 1/16 of an inch (1.6 mm) thick.
• (2) For flashings or vent terminals – not less than 3 lb/ft2 (15
kg/m2) or 0.0472 of an inch (1.2 mm) thick.
• (3) Lead bends and lead traps shall be not less than 1/8 of an
inch (3.2 mm) in wall thickness.
189 190
• Minor additions or changes: • 704.3 Commercial Sinks. Pot sinks, scullery sinks, dishwashing sinks,
silverware sinks, and other similar fixtures shall be connected directly
to the drainage system. There may not be a direct connection between
• New footnote 9 for “Shower, single-head trap”: the sewerage system and any drains originating from equipment in
• 9 For a bathtub to shower retrofit, a 1 ½ inch (40mm) trap and which food, portable equipment, or utensils are placed. Exception: A
trap arm shall be permitted with a maximum shower size of 36 warewashing (3-compartment) sink may have a direct connection only
inches (914mm) in width and 60 inches (1524mm) in length. See when used as a wash bin, rinse bin, and sanitizing bin and shall not be
Section 408.5 and Section 408.6. used for any other purpose. Establishments that use the sanitizing bin
of their warewashing sink to wash produce or conduct other food
• New Fixture – Nonwater Urinal with Drain Cleansing Action preparation must maintain an indirect connection and are not eligible
for this exception.
191 192
Copyright©IAPMO 2022
32
5/3/2022
193 194
195 196
197 198
Copyright©IAPMO 2022
33
5/3/2022
199 200
Cleanout
Proper materials?
201 202
203 204
Copyright©IAPMO 2022
34
5/3/2022
205 206
207 208
Backwater valve
209 210
Copyright©IAPMO 2022
35
5/3/2022
715.3
Existing Sewers.
211 212
213 214
Chapter 8 804.1
Indirect Wastes Standpipe Receptors.
• Plumbing fixtures or other receptors receiving the discharge of indirect waste pipe
• Three minor changes to model code shall be approved for the use proposed and shall be of such shape and capacity
as to prevent splashing or flooding and shall be located where they are readily
accessible for inspection and cleaning. No standpipe receptor for a clothes washer
• One Montana amendment shall extend more than 30 inches (762 mm), or less than 18 inches (457 mm)
above its trap weir. No trap for a clothes washer standpipe receptor shall be
installed below the floor, but shall be roughed in not less than 6 inches (152 mm)
and not more than 18 inches (457 mm) above the floor. No indirect waste receptor
shall be installed in a toilet room, closet, cupboard, or storeroom or in a portion of
the building not in general use by the occupants thereof, except standpipes for
clothes washers shall be permitted to be installed in toilet and bathroom areas
where the clothes washer is installed in the same room.
215 216
Copyright©IAPMO 2022
36
5/3/2022
Question
Any UPC violations?
• Is there a vent?
217 218
219 220
814.2
Condensate Control.
221 222
Copyright©IAPMO 2022
37
5/3/2022
• (2) ABS and DVC DWV piping installations shall be in accordance with
Chapter 14 “Firestop Protection.” Except for individual single-family
• Several minor changes dwelling units, materials exposed within ducts or plenums shall have a
flame-spread index of not more than 25 and a smoke-developed index
• Several significant changes to “Circuit Venting” section 911.0 and of not more than 50 where tested in accordance with ASTM E84 or UL
723. These tests shall comply with all requirements of the standards to
sub-sections include the sample size, for both width and length. Plastic pipe shall not
be tested filled with water. Plastic piping installed in plenums shall be
tested in accordance with all requirements of ASTM E 84 or UL 723.
• Seven (7) Montana amendments Mounting methods, supports and sample sizes of materials for testing
that are not specified in ASTM E84 or UL 723 shall be prohibited.
223 224
• Not more than one-third of the total permitted length, in • 906.1 Roof Vent Termination. Each vent pipe or stack
accordance with Table 703.2, of a minimum–sized vent shall extend through its flashing and shall terminate
shall be installed in a horizontal position. Where a vertically not less than 6 12 inches (152 mm) above the
minimum-sized vent is increased one pipe size for its roof nor less than 1 one foot (305 mm) from a vertical
entire length, the maximum length limitation shall not surface. ABS and PVC piping exposed to sunlight shall
apply. be protected by water-based synthetic latex paints.
• 2nd sentence formerly an “Exception”, now is simply part • Climate-driven amendment
of the section…
225 226
227 228
Copyright©IAPMO 2022
38
5/3/2022
229 230
231 232
• Probably means amend 908.1 (not 908.1.1) • Probably means amend 908.1.1 (not 908.1.2)
• 908.1 Vertical Wet Vent. Wet venting is limited to drainage • 908.1.1 Size. The piping between any two consecutive inlet
piping receiving discharge from the trap arm of one and two levels shall be considered a wet vented section. Each wet vented
fixture unit fixtures that also serves as a vent for not to exceed section shall be a minimum of one pipe size larger than the
four fixtures. All wet vented fixtures shall be within the same required minimum waste pipe size of the upper fixture or shall be
story; provided, further, that fixtures with a continuous vent one pipe size larger than the required minimum pipe size for the
discharging into a wet vent shall be within the same story as the sum of the fixture units served by such wet vented section,
wet vented fixtures. whichever is larger, but in no case less than two inches.
233 234
Copyright©IAPMO 2022
39
5/3/2022
• (See Table 1701.1) (See Chapter 17) Sheet lead shall comply
• 908.2 Horizontal Wet Venting for a Bathroom Groups. A with the following:
bathroom group located on the same floor level shall be • (1) For safe pans – not less than 4 pounds per square foot (lb/ft2)
permitted to be vented by a horizontal wet vent where all of the (19 kg/m2) or 1/16 of an inch (1.6 mm) thick.
conditions of Section 908.2.1 through 908.2.5 are met. Bathroom • (2) For flashings or vent terminals – not less than 3 lb/ft2 (15
group locations include private bathrooms, private patient kg/m2) or 0.0472 of an inch (1.2 mm) thick.
hospital rooms, commercial toilet rooms with only one toilet, one
lavatory and may include one floor drain. • (3) Lead bends and lead traps shall be not less than 1/8 of an
inch (3.2 mm) in wall thickness.
235 236
• New verbiage
237 238
911.1
Circuit Vent Permitted.
239 240
Copyright©IAPMO 2022
40
5/3/2022
911.1 911.2
Circuit Vent Permitted (continued) Circuit Vent Size and Connection.
241 242
911.2.1 911.3
Multiple Circuit Vents. Relief Vent.
• When multiple circuit vents are interconnected according to • A 2 inch (50 mm) relief vent shall be provided for circuit-
section 911.4.1, each individual circuit vent shall be sized vented horizontal branches receiving the discharge of
according to section 911.2. The vent pipe connecting each circuit
vent shall be sized according to Table 703.2. four or more water closets and when connecting to a
drainage stack that receives the discharge of soil or
waste from upper horizontal branches.
• Reference to Table 703.2
243 244
911.3.1 911.3.2
Connection and Installation. Fixture Drain.
• The relief vent shall connect to the horizontal branch • The relief vent is permitted to be serve as a fixture drain or fixture
between the stack and the most downstream fixture drain branch for a fixture located within the same branch interval as
the circuit-vented horizontal branch. The discharge to a relief
trap arm of the circuit vent. The relief vent shall be vent shall not exceed 4 fixture units. Fixtures discharging to a
installed on the vertical to the horizontal branch. relief vent shall be one or two fixture unit fixtures but shall not
exceed a total of 4 fixture units.
245 246
Copyright©IAPMO 2022
41
5/3/2022
911.4 911.4.1
Slope and Size of Horizontal Branch. Multiple Circuit-Vented Branches.
247 248
911.4.1.1 911.2.1.2
Size of Parallel Horizontal Branches. Size of Continuous Horizontal Branches.
• Parallel horizontal circuit vented branches shall be • Two or more circuit vented systems continuous on the
permitted to connect on the same floor level. Each same horizontal branch shall be uniformly sized for the
separate circuit-vented horizontal branch that is total discharge into the branch.
interconnected shall be sized independently in
accordance with Section 911.4.
249 250
• We will now take a brief overview of venting concepts… • A few changes to model code
• No Montana amendments
251 252
Copyright©IAPMO 2022
42
5/3/2022
1001.2
Where Required.
• …The vertical distance between a fixture outlet and the trap weir
shall be as short as practicable, but in no case shall the tailpiece
from a fixture exceed 24 inches (610 mm) in length. One trap
shall be permitted to serve a set of not more than three single
compartment sinks or laundry tubs of the same depth or three
lavatories immediately adjacent to one another and in the same
room where the waste outlets are not more than 30 inches (762
mm) apart, and the trap is centrally located where three
compartments are installed.
253 254
255 256
257 258
Copyright©IAPMO 2022
43
5/3/2022
1014.1
General.
• Where it is determined by the AHJ that waste pretreatment is required, an
approved type of grease interceptor(s) shall comply with ASME A112.14.3, ASME
A112.14.4, CSA B481, PDI G-101, or PDI GG-102, and sized in accordance with
Section 1014.2.1 or Section 1014.3.6, shall be installed in accordance with the
manufacturer’s installation instructions to receive the discharge from fixtures or
equipment that produce grease-laden waste. Grease-laden waste fixtures shall
include, but not be limited to, sinks and drains, such as floor drains, floor sinks,
and other fixtures or equipment in serving establishments, such as restaurants,
cafes, lunch counters, cafeterias, bars, clubs, hotels, hospitals, sanitariums,
factory or school kitchens located in areas of establishments where food is
prepared, or other establishments where grease is introduced into the drainage
system in quantities that can effect line stoppage or hinder sewage treatment or
private sewage disposal systems…
259 260
1014.1
General. (continued)
261 262
1014.3.3
Design.
263 264
Copyright©IAPMO 2022
44
5/3/2022
265 266
Chapter 11
Storm Drainage
• No Montana amendments
267 268
1101.4
Material Uses.
269 270
Copyright©IAPMO 2022
45
5/3/2022
Chapter 12 Chapter 13
Fuel Gas Piping HEALTH CARE FACILITIES…MEDICAL GAS & VACUUM SYSTEMS
• 24.301.301 (1) (ai) Chapter 12, Fuel piping is deleted and • Significant re-numbering or re-location of sections & sub-
replaced with International Fuel Gas Code.
sections
271 272
• Chapter 13, Health Care and Medical Gas and Vacuum Systems, is deleted except
for Subsections 1301.1, 1302.0 and 1303.0, Health Care Facilities. In lieu of Chapter
13, except for the subsections not deleted, the Department of Labor and Industry
adopts and incorporates by reference the National Fire Protection Association’s
Standard NFPA 99, 2018 edition, Chapters 1 through 5 and Chapter 15 for the
exclusive use as a standard for the installation of medical gas and vacuum systems.
The requirements for this rule shall not be construed as to replace or supersede any
additional requirements for testing and certification of medical gas and vacuum
systems, including independent third-party certification of systems, as may be
applicable. NFPA 99 is a nationally recognized standard setting forth minimum
standards and requirements for medical gas and vacuum systems. A copy of NFPA
99 may be obtained from the National Fire Protection Association at www.nfpa.org
273 274
1301.4 1302.1
Where Required. Building Risk Categories.
• Construction and equipment requirements shall be • Activities, systems, or equipment shall be designed to
applied only to new construction and new equipment, meet Category 1 through Category 4 requirements, as
except as modified in individual chapters sections of this detailed in this code chapter. [NFPA 99:4.1]
chapter. [NFPA 99:1.3.2]
275 276
Copyright©IAPMO 2022
46
5/3/2022
1302.1.1 1302.1.1.1
Processes and Operations. Risk Categories
• The health care facility’s governing body shall establish • The governing body shall conduct risk assessments and
the processes and operations that are planned for the shall determine risk categories based on the character of
health care facility. [NFPA 99:4.2.1] the processes and operations conducted in the health
care facility. [NFPA 99:4.2.1.1]
• In this context, “operations” does NOT mean surgical
procedures
277 278
1302.1.2 1302.1.2.1
Risk Assessment. Documents to the Authority Having Jurisdiction.
• Risk categories shall be classified by the health care • Where required by the Authority Having Jurisdiction
facility’s governing body by following and documenting a (AHJ), the risk assessment shall be provided to the AHJ
defined risk assessment procedure. [NFPA 99:4.2.2] for review based on the character of the processes and
operations conducted in the health care facility. [NFPA
99: 4.2.2.1]
279 280
1302.1.3 1302.2
Documented Risk Assessment. Patient Care Spaces.
281 282
Copyright©IAPMO 2022
47
5/3/2022
1302.3 1302.4
Anesthesia. Wet Procedure Locations.
• It shall be the responsibility of the health care • It shall be the responsibility of the health organization
organization facility’s governing body to designate care facility’s governing body to designate wet procedure
anesthetizing locations. [NFPA 99:1.3.4.3] locations. [NFPA 99.1.3.4.3]
283 284
1303.9 Chapter 14
Work Performed in Occupied Healthcare Facilities. Firestop Protection
285 286
Chapter 15 1501.1.1
Alternate Water Sources For Nonpotable Applications Allowable Use of Alternate Water.
287 288
Copyright©IAPMO 2022
48
5/3/2022
209.0 220.0
Gray Water. Reclaimed Water.
• Untreated wastewater that has not come into contact • Nonpotable water provided by a water/wastewater utility
with toilet waste, kitchen sink waste, dishwasher waste that, as a result of tertiary treatment of domestic
or similarly contaminated sources. Gray water includes wastewater, meets requirements of the public health AHJ
wastewater from bathtubs, showers, lavatories, clothes for its intended uses.
washers, and laundry tubs. Also, known as grey water,
graywater, and greywater.
• This is not on-site sourced (it comes from a treatment
plant) water
289 290
1501.2
System Design.
291 292
1501.2 1501.6
Exceptions: Operation and Maintenance Manual.
• (1) A registered design professional is not required to design gray • An operation and maintenance manual for gray water and on-site treated water
water systems having a maximum discharge capacity of 250 systems required to have a permit in accordance with Section 1501.3 shall be
gallons per day (gal/d) ( 0.011 L/s) for single family and multi- supplied to the building owner by the system designer. The operating operation
family dwellings. and maintenance manual shall include the following:
• (1) Detailed diagram of the entire system, and the location of system components.
• (2) Instructions for operating and maintaining the system.
• (2) A registered design professional is not required to design an
on-site treated non-potable water system for single-family • (3) Details on maintaining the required water quality as determined by the AHJ for
on-site nonpotable water systems.
dwellings having a maximum discharge capacity of 250 gal/d
(0.011 L/s). • (4) Details on deactivating the system for maintenance, repair, or other purposes.
293 294
Copyright©IAPMO 2022
49
5/3/2022
1501.7
Minimum Water Quality Requirements.
295 296
297 298
1503.2.2 1503.2.4
Diversion. Rainwater Diversion Valves.
• The gray water system shall connect to the sanitary • Rainwater diversion valves ranging from 6 inches (150
drainage system downstream of fixture traps and vent mm) to 12 inches (300 mm) in diameter shall comply with
connections through an approved a gray water diverter IAPMO IGC 352. Valves shall be accessible and include
valve. The gray water diverter valve shall comply with a filter located upstream of the valve when required.
IAPMO PS 59 and be installed in an accessible location
and clearly indicate the direction of flow.
299 300
Copyright©IAPMO 2022
50
5/3/2022
1505.12
Signs.
301 302
303 304
Chapter 16 1601.2
Nonpotable Rainwater Catchment Systems System Design.
305 306
Copyright©IAPMO 2022
51
5/3/2022
307 308
1601.2
System Design. (continued)
• Exceptions:
• (1) A person registered or licensed to perform plumbing design
work is not required to design rainwater catchment systems used
for irrigation with a maximum storage capacity of 360 gallons
(1136 L).
• (2) A person registered or licensed to perform plumbing design
work is not required to design rainwater catchment systems for
single family dwellings where outlets, piping, and system
components are located on the exterior of the building.
309 310
1602.1
General.
311 312
Copyright©IAPMO 2022
52
5/3/2022
1603.4.2
Prohibited Discharges.
313 314
1603.5
Minimum Water Quality.
315 316
317 318
Copyright©IAPMO 2022
53
5/3/2022
1603.5.1
Treatment.
319 320
1605.3.3 Chapter 17
Discovery of Cross-Connection. Referenced Standards
321 322
Appendices Appendix A
Do they or do they not apply? RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM
323 324
Copyright©IAPMO 2022
54
5/3/2022
Appendix B Appendix C
EXPLANATORY NOTES ON COMBINATION WASTE & VENT SYSTEMS ALTERNATE PLUMBING SYSTEMS
325 326
Appendix D Appendix E
SIZING STORM WATER DRAINAGE SYSTEMS MANUFACTURED/MOBILE HOME PARKS & RV PARKS
327 328
Appendix F Appendix G
FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS SIZING OF VENTING SYSTEMS
• NOT adopted by the State of Montana • NOT adopted by the State of Montana
329 330
Copyright©IAPMO 2022
55
5/3/2022
Appendix H Appendix I
PRIVATE SEWAGE DISPOSAL SYSTEMS INSTALLATION STANDARDS
• NOT adopted by the State of Montana • NOT adopted by the State of Montana
331 332
Appendix J Appendix K
COMBINATION INDOOR & OUTDOOR COMBUSTION & VENTIALTION… POTABLE RAINWATER CATCHMENT SYSTEMS
• A few, relatively minor change to model code • Several changes to model code, some substantial,
others minor
333 334
Appendix L L 101.1
SUSTAINABLE PRACTICES Applicability.
335 336
Copyright©IAPMO 2022
56
5/3/2022
L 101.2 L 201.0
Definitions. Definitions.
337 338
L 201.0 L 201.0
Definitions. (continued) Definitions. (continued)
339 340
L 201.0 L 201.0
Definitions. (continued) Definitions. (continued)
341 342
Copyright©IAPMO 2022
57
5/3/2022
L 201.0
Definitions. (continued)
• WaterSense. A voluntary
program of the U.S.
Environmental Protection
Agency, designed to identify
and promote water-efficient
products and practices.
343 344
L 301.2 L 302.1
Qualifications. Disposal.
• Where permits are required, the AHJ shall have the • It shall be unlawful for a person to cause, suffer, or
authority to require contractors, installers, or service permit the disposal of sewage, human excrement, or
technicians to demonstrate competency. Where other liquid wastes, in a place or manner, except through
determined by the AHJ, the contractor, installer, or and by means of an approved drainage system, installed
service technician shall be licensed to perform such and maintained in accordance with the provisions of this
work. code.
345 346
L 302.2 L 303.1
Connections to Plumbing System Required. General.
• Equipment and appliances, used to receive or discharge • An abandoned system or part thereof covered under the
liquid wastes or sewage, shall be connected properly to scope of this appendix shall be disconnected from
the drainage system of the building or premises, in remaining systems, drained, plugged, and capped in an
accordance with the provisions of this code. approved manner.
347 348
Copyright©IAPMO 2022
58
5/3/2022
349 350
• The effective flush volume for dual flush toilets is defined as the
composite, average flush volume of two reduced flushes and one
full flush.
351 352
L 402.3 L 402.3
Urinals. Urinals. (continued)
353 354
Copyright©IAPMO 2022
59
5/3/2022
L 402.4 L 402.5
Residential Kitchen Faucets. Lavatory Faucets.
• Shall not exceed 1.8 gpm @ 60 psi • L 402.5.1 …Residences, Apartments, & Private Baths…
• Shall not exceed 1.5 gpm @ 60 psi
• Listed to EPA WaterSense HE Lavatory Faucet Specification
355 356
L 402.6
Showerheads.
357 358
• WaterSense listed items • The total allowable flow rate of water from multiple showerheads
flowing at a given time, with or without diverters, including rain
systems, waterfalls, body sprays, and jets, shall not exceed 2.0
• Showerhead is rated 1.8 gpm gpm per shower compartment, where the floor area of the
shower compartment is less than 1800 square inches (1.161 m2).
For each increment of 1800 square inches (1.161 m2) of floor
• KS swivel aerator 1.5 gpm area after that or part thereof, additional showerheads are
allowed, provided the total flow rate of water flowing from the
devices shall not exceed 2.0 gpm (7.6 L/m) for each such
• Lavatory aerators 1.0 gpm increment.
359 360
Copyright©IAPMO 2022
60
5/3/2022
L 402.6.1 L 402.6.1
Exceptions: Observations: Multiple Showerheads Serving One Shower Compartment.
361 362
L 402.6.2
Observations: Bath and Shower Diverters.
• Left: separate
valve for each • The rate of leakage out of the tub spout of bath and
outlet shower diverters while operating in the shower mode
shall not exceed 0.1 gpm (0.4 L/m) in accordance with
• Right: Diverter ASME A112.18.1/CSA B125.1.
selects between
overhead or body
spray options
363 364
L 402.6.3
Shower Valves.
Spout Leakage
• Shower valves shall comply with
• Intended to the temperature control
minimize water not performance requirements of
useful for showering ASSE 1016 or ASME
that simply goes A112.18.1/CSA B125.1 where
down the drain… tested at 2.0 gpm (7.6 L/m).
365 366
Copyright©IAPMO 2022
61
5/3/2022
L 403.1 L 403.2
Dishwashers. Clothes Washers.
• Residential and commercial • Residential clothes washers shall comply with the Energy
dishwashers shall comply with Star program requirements. Commercial clothes washers
Energy Star program shall comply with Energy Star program requirements,
requirements. where such requirements exist.
367 368
L 404.2
Ice Makers.
369 370
L 404.3 L 404.5
Food Steamers. Grease Interceptors.
• Boilerless type steamers shall • Grease interceptor maintenance procedures shall not
consume not more than 2.0 include post-pumping/cleaning refill using potable water.
gallons (7.6 L) per Refill shall be made by connected appliances
compartment. Boiler type accumulated discharge only.
steamers shall consume not
more than 1.5 gallons (5.7 L)
per pan per hour.
371 372
Copyright©IAPMO 2022
62
5/3/2022
L 404.6 L 404.7.2
Dipper Wells. Food Waste Disposers.
• Where dipper wells are installed, the water supply to a dipper well shall • The water use for the food waste
have a shutoff valve and flow control. The flow of water into a dipper well grinder shall not exceed 8 gpm (30.3
shall be limited by not less than one of the following methods: (1) Water L/m) under full load condition and 1 gpm
flow shall not exceed the water capacity of the dipper well in one minute at (3.8 L/m) under no-load condition. Flow
a supply pressure of 60 psi (414kPa), and the maximum flow shall not
exceed 2.2 gpm (8.3 L/m) at a supply pressure of 60 psi (414 kPa). The restrictors shall be installed on the water
water capacity of the dipper well shall be the maximum amount of water supply to limit the water flow rate to a
that the fixture can hold before water flows into the drain. (2) The volume of maximum of 8 gpm (30.3 L/m). A load
water dispensed into a dipper well in each activation cycle of a self-closing sensing device shall be installed to
fixture fitting shall not exceed the water capacity of the dipper well, and the monitor current demand and regulate
maximum flow shall not exceed 2.2 gpm (8.3 L/m) at a supply pressure of water flow.
60 psi (414 kPa).
373 374
L 406.1
Use of Alternate Water Source for Special Water Features.
375 376
L 407.1
Meters Required.
377 378
Copyright©IAPMO 2022
63
5/3/2022
L 411.0
Landscape Irrigation Systems.
379 380
L 411.4 L 411.4
Irrigation Control Systems. Irrigation Control Systems. (continued)
• Where installed as part of a landscape irrigation system, irrigation • (5) The site-specific settings of the irrigation control system affecting the
controls shall: irrigation and shall be posted at the control system location. The posted
• (1) Automatically adjust the irrigation schedule to respond to plant water data, where applicable to the settings of the controller, shall include:
needs determined by weather or soil moisture conditions. • (a) Precipitation rate for each zone.
• (2) Utilize sensors to suspend irrigation during rainfall. • (b) Plant evapotranspiration coefficients for each zone.
• (3) Utilize sensors to suspend irrigation where adequate soil moisture is • (c) Soil absorption rate for each zone.
present for plant growth. • (d) Rain sensor settings.
• (4) Have the capability to program multiple and different run times for • (e) Soil moisture setting.
each irrigation zone to enable cycling of water applications and durations
to mitigate water flowing off of the intended irrigation zone. • (f) Peak demand schedule including run times for each zone and number
of cycles to mitigate runoff and monthly adjustments or percentage.
381 382
L 411.5
Low Flow Irrigation.
383 384
Copyright©IAPMO 2022
64
5/3/2022
L 411.10.3
Where pop-up type sprinkler
heads are installed, the
sprinkler heads shall rise to a
height above vegetation level
and of not less than 4 inches
(102 mm) above the soil level
where emitting water.
385 386
L 411.12 L 412.0
Depth of Irrigation Pipe. Trap Seal Protection.
• L 412.1 Water Supplied Trap Primers. Water supplied trap primers shall be
electronic or pressure activated and shall use not more than 30 gallons (114 L)
• Irrigation pipe downstream from per year per drain. Where an alternate water source, as defined by this code, is
the backflow preventer shall be used for fixture flushing or other uses in the same room, the alternate water
buried at a minimum depth source shall be used for the trap primer water supply.
according to Section L 411.12.1 • Exception: Flushometer tailpiece trap primers in accordance with IAPMO PS
76.
and Section 411.12.2.
• L 412.2 Drainage Type Trap Seal Primer Devices. Drainage type trap seal
primer devices shall not be limited in the amount of water they discharge.
387 388
L 501.0
Water Heating Design, Equipment, and Installation.
389 390
Copyright©IAPMO 2022
65
5/3/2022
• Hot water supply piping and return • Due to interconnection of conservation, water & energy
piping shall be thermally insulated. this section is large
The wall thickness of the insulation
shall be equal to the nominal
diameter of the pipe up to two • We will not go into detail…
inches (50 mm). The wall thickness
shall be not less than 2 inches (51
mm) for nominal pipe diameters
exceeding two inches (50 mm)…
391 392
L 506.0
Drain Water Heat Exchangers.
Solar Water Heating…
L 504.1 General. The • L 506.1 General. Drain water heat exchangers shall
erection, installation,
alteration, addition to, or
comply with IAPMO PS 92. The heat exchanger shall be
maintenance of solar accessible.
water heating systems
shall be in accordance
with this section and the
Uniform Solar Energy
and Hydronics Code.
393 394
L 602.0
Qualifications.
395 396
Copyright©IAPMO 2022
66
5/3/2022
Appendix M
PEAK WATER DEMAND CALCULATOR
397 398
• Plumbing fixture water demand changed drastically over time. • Convener of Emerging Water Technology Symposium (EWTS)
• Dr. Hunter’s world: • Partnered with Plumbing’s pre-eminent thought leaders:
• Water Closets – 6-8 gallons per flush • Alliance for Water Efficiency
• “Water conserving fixtures” were unheard of and unthought of… • American Society of Plumbing Engineers
• Flush and forget mentality virtually ubiquitous! • Plumbing Manufacturers International
• Today: • World Plumbing Council
• Water Closets – as low as .6 gallons per flush! • “Last Mile” studies – less liquid goes down the drain, how does
• Water conservation is the norm everywhere sewage get to the wastewater treatment plant?
• Infrastructure that was aging in Dr. Hunter’s era is ancient and failing
catastrophically!
399 400
• Cost of pipe & fittings • This appendix provides a method for estimating the
• Potable water wasted demand load for the building water supply and principal
branches for single and multi-family dwellings with water-
• Watergy = “Interconnection of water and energy” conserving fixtures, fixtures fittings, and appliances.
• Efficiency of potable water distribution systems
• Public health – reducing harborage of Legionella bacteria
401 402
Copyright©IAPMO 2022
67
5/3/2022
M102.1 M 102.2
Water-Conserving Fixtures. Water Demand Calculator.
• Plumbing fixtures, • The estimated design flow rate for the building supply
fixture fittings and and principal branches and risers shall be determined by
appliances shall not the IAPMO Water Demand Calculator available for
exceed the design download at:
flow rate in Table M
102.1. • http://www.iapmo.org/WEStand/Pages/WaterDemandCalculator.aspx
403 404
M 102.3
Meter and Building Supply.
• To determine the design flow rate for the water meter and
building supply, enter the total number of indoor
plumbing fixtures and appliances for the building in
Column [B] of the Water Demand Calculator and run
Calculator. See Table M 102.3 for an example.
405 406
M 102.4 M 102.5
Fixture Branches and Fixture Supplies. Continuous Supply Demand.
407 408
Copyright©IAPMO 2022
68
5/3/2022
M 102.6 M 102.7
Other Fixtures. Size of Water Piping per Appendix A
• Except as provided in Section M102.0 for estimating the demand load for
single- and multi-family dwellings, the size of each water piping system
• Fixtures not included on Table M 102.1 shall be added in shall be determined in accordance with the procedure set forth in
Rows 12 through 14 in the Water Demand Calculator as Appendix A. After determining the permissible friction loss per 100 feet
Other Fixture. The probability of use and flow rate for (30 480 mm) of pipe in accordance with Section A 104.0 and the demand
flow in accordance with the Water Demand Calculator, the diameter of
Other Fixtures shall be added by selecting the the building supply pipe, branches and risers shall be obtained from
comparable probability of use and flow rate from Chart A 105.1(1) through Chart A 105.1(7), whichever is applicable, in
Columns [C] and [F]. accordance with Section A 105.0 and Section A 107.0. Appendix I (IS
31), Figure 3 and Figure 4 shall be permitted when sizing PEX systems.
409 410
M 107.7.1 Appendix M
Minimum Fixture Branch Size. The rest of this appendix…
• The minimum fixture branch size shall be ½ inch (15 • Provides several examples:
mm) in diameter. • 1. Find Demand Load for Building Supply.
• 2. Determine the Pipe Size of the Building Supply.
• Note: fixture branch and fixture supply are NOT the • 3. Indoor, Outdoor and Other Fixtures Water Use.
same!
• 4. Sizing Branches and Risers
411 412
413 414
Copyright©IAPMO 2022
69
5/3/2022
CDC reports:
Hospitals at significant risk…
415 416
• Potable water was the most frequent source of exposure • Spas and hot tubs
at 56% followed by cooling towers at 22%
• Misters
• Potable water sources accounted for 67% of health-care
associated outbreaks in hospitals and long-term care
facilities • Grocery store produce counters, etc.
417 418
419 420
Copyright©IAPMO 2022
70
5/3/2022
N 101.1 N 101.1
Applicability. Applicability. Note: (continued)
• This appendix provides guidelines on the impact of water • There are additional factors associated with the potential for
temperature in minimizing both scalding and Legionella growth scalding and Legionella growth other than temperature.
potential associated with occupiable commercial, institutional, • For scalding potential, other factors include, but are not limited
multi-unit residential and industrial building plumbing systems. to, user age, health, body part, length of contact time and water
• This Appendix shall not include single-family residential source.
buildings. This appendix shall not be considered a risk • For Legionella growth potential other factors include, but are not
management guidance document for scalding or Legionella. limited to, water source and plumbing system: size, design,
• Note: Published documents which address Legionella risk circulation rate, water age, disinfectant residual, piping material
management include ASHRAE 188, ASHRAE Guideline 12, or as and component complexity.
required by the AHJ.
421 422
N 102.0 N 102.0
Definitions. Definitions. (continued)
• N 102.1 Cold Water. Water at a temperature of less than 77 0F (250C). • N 102.6 Hot Water. Water at a temperature not less than 1300F (540C)
• N 102.2 Tepid Cold Water. Water at a temperature not less than 77 0F and less than 1400F (600C).
(250C) and less than 850F (290C). • N 102.7 Very Hot Water. Water at a temperature not less than 1400F
• N 102.3 Tepid Water. Water at a temperature not less than 85 0 F (290C) (600C) and less than 1600F (710C).
and less than 1100F (430C). • N 102.8 Disinfecting Hot Water. Water at a temperature not less than
• N 102.4 Warm Water. Water at a temperature not less than 110 0F (430C) 1600F (710C).
and less than 1200F (490C). • N 102.9 Legionella Growth Potential. The likelihood that Legionella
• N 102.5 Tempered Hot Water. Water at a temperature not less than 120 0F bacteria will reproduce.
(490C) and less than 1300F (540C). • 102.10 Scald Potential. The likelihood of burning the skin.
423 424
N 103.1 N 104.1
Required Documentation. Legionella Growth Potential.
• Construction documents shall be required for new • The AHJ shall have the authority to require
construction, renovation, refurbishment, replacement, or documentation to address Legionella growth potential,
repurposing of an occupiable building water system and where water temperatures in a water distribution system
shall be submitted to the AHJ. are within ranges shown in Table N 104.1 that pose a
Legionella growth potential.
425 426
Copyright©IAPMO 2022
71
5/3/2022
N 104.2 N 105.1
Scald Potential. Disinfection Documentation.
427 428
N 105.1
Disinfection Documentation. (continued)
429 430
jed.scheuermann@iapmo.org
971-300-7649
431
Copyright©IAPMO 2022
72