You are on page 1of 5

Project: Poblete Date: 4/30/2021

Al: ### max. ΔU (%) 1.19%


AC Low Voltage Cu: ### ave. ΔU (%) 0.42%

Auxiliary Supply LV-Cable


Derated
Ambient Cable
Max. Conditions Cable Current ΔU ΔU
Connected Current Fuse Rating Soil (20°C) Derating Carrying Cable Core System Total per Total per
Trafo No. To Power (kW) Current (A) (+10%) (A) Air (30°C) Factor Capacity (A) Material Cable Type Length (m) Cable Core Ø (mm²) Voltage (V) Inv (V) Inv (%)
0.0 0
SE Office building 0 0.00 0.00 10 Soil 1.0 64.00 Al RV Al 34.0 16 230 0.00 0.00%
0.0 0
0.0 0

Ambient
Max. Conditions Cable ΔU ΔU
Current Fuse Rating Soil (20°C) Derating Derated Cable Current Cable Core Cable Core System Total per Inv Total per Inv
Trafo No. Inverter No. Inverter Type Power (kW) Power (kVA) Current (A) (+10%) (A) Air (30°C) Factor Carrying Capacity (A) Material Cable Type Length (m) Ø (mm²) Voltage (V) (V) (%)

1 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 54.8 150 800 2.35 0.29%
1 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 30.1 150 800 1.29 0.16%
1 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 25.6 150 800 1.10 0.14%
1 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 50.4 150 800 2.16 0.27%
1 5 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 53.6 70 800 3.08 0.39%
1 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 33.8 150 800 1.45 0.18%
1 7 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 25.5 150 800 1.09 0.14%
1 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 50.3 150 800 2.15 0.27%

2 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 54.8 150 800 2.35 0.29%
2 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 30.1 150 800 1.29 0.16%
2 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 25.7 150 800 1.10 0.14%
2 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 50.3 150 800 2.15 0.27%
2 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 58.6 150 800 2.51 0.31%
2 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 33.8 150 800 1.45 0.18%
2 7 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 25.5 150 800 1.09 0.14%
2 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 50.3 150 800 2.15 0.27%

3 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 54.9 150 800 2.35 0.29%
3 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 30.1 150 800 1.29 0.16%
3 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 25.6 150 800 1.10 0.14%
3 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 50.4 150 800 2.16 0.27%
3 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 58.6 150 800 2.51 0.31%
3 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 33.9 150 800 1.45 0.18%
3 7 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 25.6 150 800 1.10 0.14%
3 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 50.3 150 800 2.16 0.27%
Project: Poblete Date: 4/30/2021
Al: ### max. ΔU (%) 1.19%
AC Low Voltage Cu: ### ave. ΔU (%) 0.42%

Auxiliary Supply LV-Cable


Derated
Ambient Cable
Max. Conditions Cable Current ΔU ΔU
Connected Current Fuse Rating Soil (20°C) Derating Carrying Cable Core System Total per Total per
Trafo No. To Power (kW) Current (A) (+10%) (A) Air (30°C) Factor Capacity (A) Material Cable Type Length (m) Cable Core Ø (mm²) Voltage (V) Inv (V) Inv (%)
0.0 0
SE Office building 0 0.00 0.00 10 Soil 1.0 64.00 Al RV Al 34.0 16 230 0.00 0.00%
0.0 0
0.0 0

Ambient
Max. Conditions Cable ΔU ΔU
Current Fuse Rating Soil (20°C) Derating Derated Cable Current Cable Core Cable Core System Total per Inv Total per Inv
Trafo No. Inverter No. Inverter Type Power (kW) Power (kVA) Current (A) (+10%) (A) Air (30°C) Factor Carrying Capacity (A) Material Cable Type Length (m) Ø (mm²) Voltage (V) (V) (%)

4 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 54.8 150 800 2.35 0.29%
4 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 30.1 150 800 1.29 0.16%
4 3 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 20.7 70 800 1.19 0.15%
4 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 58.8 150 800 2.52 0.31%
4 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 33.9 150 800 1.45 0.18%
4 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 25.6 150 800 1.10 0.14%
4 7 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 50.4 150 800 2.16 0.27%
4 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 75.1 150 800 3.22 0.40%

5 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 109.5 150 800 4.69 0.59%
5 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 84.7 150 800 3.63 0.45%
5 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 59.9 150 800 2.56 0.32%
5 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 35.1 150 800 1.50 0.19%
5 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 28.3 150 800 1.21 0.15%
5 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 53.1 150 800 2.27 0.28%
5 7 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 77.8 150 800 3.33 0.42%
5 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 102.6 150 800 4.39 0.55%

6 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 59.8 150 800 2.56 0.32%
6 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 35.1 150 800 1.50 0.19%
6 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 28.3 150 800 1.21 0.15%
6 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 53.1 150 800 2.27 0.28%
6 5 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 94.6 70 800 5.44 0.68%
Project: Poblete Date: 4/30/2021
Al: ### max. ΔU (%) 1.19%
AC Low Voltage Cu: ### ave. ΔU (%) 0.42%

Auxiliary Supply LV-Cable


Derated
Ambient Cable
Max. Conditions Cable Current ΔU ΔU
Connected Current Fuse Rating Soil (20°C) Derating Carrying Cable Core System Total per Total per
Trafo No. To Power (kW) Current (A) (+10%) (A) Air (30°C) Factor Capacity (A) Material Cable Type Length (m) Cable Core Ø (mm²) Voltage (V) Inv (V) Inv (%)
0.0 0
SE Office building 0 0.00 0.00 10 Soil 1.0 64.00 Al RV Al 34.0 16 230 0.00 0.00%
0.0 0
0.0 0

Ambient
Max. Conditions Cable ΔU ΔU
Current Fuse Rating Soil (20°C) Derating Derated Cable Current Cable Core Cable Core System Total per Inv Total per Inv
Trafo No. Inverter No. Inverter Type Power (kW) Power (kVA) Current (A) (+10%) (A) Air (30°C) Factor Carrying Capacity (A) Material Cable Type Length (m) Ø (mm²) Voltage (V) (V) (%)

7 1 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 64.1 70 800 3.69 0.46%
7 2 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 38.1 70 800 2.19 0.27%
7 3 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 19.0 70 800 1.09 0.14%
7 4 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 31.8 70 800 1.83 0.23%
7 5 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 50.8 70 800 2.92 0.37%
7 6 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 69.9 70 800 4.02 0.50%
7 7 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 88.9 70 800 5.12 0.64%
7 8 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 108.0 70 800 6.21 0.78%
7 9 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 127.0 70 800 7.31 0.91%
7 10 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 146.0 70 800 8.40 1.05%
7 11 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 165.1 70 800 9.50 1.19%

8 1 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 109.4 70 800 6.30 0.79%
8 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 65.2 150 800 2.79 0.35%
8 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 41.4 150 800 1.77 0.22%
8 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 17.6 150 800 0.75 0.09%
8 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 36.6 150 800 1.57 0.20%
8 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 60.4 150 800 2.58 0.32%
8 7 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 33.7 70 800 1.94 0.24%
8 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 57.6 150 800 2.46 0.31%

9 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 53.3 150 800 2.28 0.29%
9 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 29.5 150 800 1.26 0.16%
9 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 24.7 150 800 1.06 0.13%
9 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 48.5 150 800 2.08 0.26%
9 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 59.6 150 800 2.55 0.32%
Project: Poblete Date: 4/30/2021
Al: ### max. ΔU (%) 1.19%
AC Low Voltage Cu: ### ave. ΔU (%) 0.42%

Auxiliary Supply LV-Cable


Derated
Ambient Cable
Max. Conditions Cable Current ΔU ΔU
Connected Current Fuse Rating Soil (20°C) Derating Carrying Cable Core System Total per Total per
Trafo No. To Power (kW) Current (A) (+10%) (A) Air (30°C) Factor Capacity (A) Material Cable Type Length (m) Cable Core Ø (mm²) Voltage (V) Inv (V) Inv (%)
0.0 0
SE Office building 0 0.00 0.00 10 Soil 1.0 64.00 Al RV Al 34.0 16 230 0.00 0.00%
0.0 0
0.0 0

Ambient
Max. Conditions Cable ΔU ΔU
Current Fuse Rating Soil (20°C) Derating Derated Cable Current Cable Core Cable Core System Total per Inv Total per Inv
Trafo No. Inverter No. Inverter Type Power (kW) Power (kVA) Current (A) (+10%) (A) Air (30°C) Factor Carrying Capacity (A) Material Cable Type Length (m) Ø (mm²) Voltage (V) (V) (%)
9 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 35.8 150 800 1.53 0.19%
9 7 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 21.9 150 800 0.94 0.12%
9 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 45.7 150 800 1.96 0.24%

10 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 53.4 150 800 2.29 0.29%
10 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 29.6 150 800 1.27 0.16%
10 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 24.1 150 800 1.03 0.13%
10 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 48.3 150 800 2.07 0.26%
10 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 59.8 150 800 2.56 0.32%
10 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 36.0 150 800 1.54 0.19%
10 7 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 17.0 70 800 0.98 0.12%
10 8 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 36.0 70 800 2.07 0.26%

11 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 53.4 150 800 2.29 0.29%
11 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 29.6 150 800 1.27 0.16%
11 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 24.6 150 800 1.05 0.13%
11 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 48.4 150 800 2.07 0.26%
11 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 72.2 150 800 3.09 0.39%
11 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 65.4 150 800 2.80 0.35%

12 1 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 83.1 70 800 4.78 0.60%
12 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 54.6 150 800 2.34 0.29%
12 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 26.1 150 800 1.12 0.14%
12 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 37.2 150 800 1.59 0.20%
Project: Poblete Date: 4/30/2021
Al: ### max. ΔU (%) 1.19%
AC Low Voltage Cu: ### ave. ΔU (%) 0.42%

Auxiliary Supply LV-Cable


Derated
Ambient Cable
Max. Conditions Cable Current ΔU ΔU
Connected Current Fuse Rating Soil (20°C) Derating Carrying Cable Core System Total per Total per
Trafo No. To Power (kW) Current (A) (+10%) (A) Air (30°C) Factor Capacity (A) Material Cable Type Length (m) Cable Core Ø (mm²) Voltage (V) Inv (V) Inv (%)
0.0 0
SE Office building 0 0.00 0.00 10 Soil 1.0 64.00 Al RV Al 34.0 16 230 0.00 0.00%
0.0 0
0.0 0

Ambient
Max. Conditions Cable ΔU ΔU
Current Fuse Rating Soil (20°C) Derating Derated Cable Current Cable Core Cable Core System Total per Inv Total per Inv
Trafo No. Inverter No. Inverter Type Power (kW) Power (kVA) Current (A) (+10%) (A) Air (30°C) Factor Carrying Capacity (A) Material Cable Type Length (m) Ø (mm²) Voltage (V) (V) (%)
12 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 65.6 150 800 2.81 0.35%
12 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 105.4 150 800 4.51 0.56%

13 1 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 67.6 70 800 3.89 0.49%
13 2 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 26.6 70 800 1.53 0.19%
13 3 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 32.5 70 800 1.87 0.23%
13 4 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 51.8 70 800 2.98 0.37%
13 5 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 71.1 70 800 4.09 0.51%
13 6 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 90.5 70 800 5.20 0.65%
13 7 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 109.8 70 800 6.32 0.79%
13 8 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 61.1 150 800 2.61 0.33%
13 9 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 85.2 150 800 3.65 0.46%
13 10 105KTL-HV 105 116 83.72 87.90 100 Soil 0.79872 115.02 Al RV Al 109.3 70 800 6.29 0.79%

14 1 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 74.0 150 800 3.17 0.40%
14 2 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 49.8 150 800 2.13 0.27%
14 3 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 29.1 150 800 1.25 0.16%
14 4 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 31.8 150 800 1.36 0.17%
14 5 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 56.1 150 800 2.40 0.30%
14 6 185KTL-H1 175 185 133.51 140.19 160 Soil 0.79872 175.72 Al RV Al 80.3 150 800 3.44 0.43%