D I S T R I B U T I O N S O LU T I O N S
VD4
Medium voltage vacuum circuit breakers
12...40.5 kV - 630...4000 A - 16...63 kA
—
VD4 medium voltage circuit breakers
use vacuum interrupters embedded in
the poles. This construction method
makes the poles particularly sturdy and
protects the interrupter from shocks,
dust and condensation.
VD4 circuit breakers are the best choice
for the majority of modern electricity
distribution applications and are used
in transformer and distribution
substations to control and protect
motors, transformers, capacitor banks
and for protecting cables.
—
Table of contents
—
VD4:
its strengths, your benefits
—
Productivity
Maximize your output
Easy to install
• Withdrawable version available
– Circuit breaker can be rapidly racked-in/out for
maintenance
– The complete circuit breaker is ready for installation in
the switchgear
Continuous operation
• Excellent quality product thanks to high process automation
– Reliable, high quality product
6 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Reliability
Protect your assets
Global availability
• The world’s best-selling circuit breaker
– Our worldwide presence means you can rely on us for any
type of support you may require
DI ST RI BUT I ON S OLUT I ON S 7
Optimized interface
• Standardized product family up to 40.5 kV, 4000A
– A common, simplified interface and accessories for the
whole product family
• Mechanically Interchangeable with HD4
– The same switchgear configuration is used to host
breakers with both interruption technologies
• Fixed version with truck assembled and ready to be
customized
– The contact system most suited to your switchgear can
be designed and created thanks to the already
assembled interlocking system
—
Efficiency
Optimize your investments
Affordable Range
• Technical collaboration agreements
– Allow you to cut investment costs when new switchgears
are designed
Optimized logistics
• Poles in thermoplastic material make the breaker lighter
– Easily handled breakers and reduced transport charges
8 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Description
These new VD4 circuit breakers exemplify ABB’s Vacuum current interruption
proven vacuum interrupter engineering and The vacuum circuit breaker does not require an
manufacturing technology, as well as the superior interrupting and insulating medium. Interrupters
design standards employed in the production of do not, in fact, contain ionizable material.
circuit breakers. The electric arc that generates when the contacts
VD4 medium voltage circuit breakers use vacuum separate is merely formed by melted and
interrupters embedded in the poles. This vaporized contact material.
construction technique makes the poles of the Supported by the external energy, the electric arc
circuit breaker particularly sturdy and protects persists until the current annuls near natural zero
the interrupter from shocks, dust and crossing. In that instant, the dielectric properties
condensation. The vacuum interrupter houses the are very rapidly restored by the sharp reduction in
contacts and forms the interruption chamber. the density of the conveyed load and rapid
condensation of the metallic vapor.
Thus the vacuum interrupter recovers insulating
capacity and the ability to withstand transient
recovery voltage, thereby definitively extinguishing
the arc.
7 • Sealed-for-life poles
1 Upper terminal
2 Vacuum interrupter
• Sturdy and reliable
3 Enclosure/pole
4 Stem of moving contact • Limited maintenance
5 Lower terminal 8
6 Flexible connection • Circuit breaker racked in and out with door
7 Tie-rod spring fork
8 Tie-rod
closed
9 Pole fixing
9
10 Connection to operating • Incorrect and hazardous operations are
mechanism 10 prevented thanks to special locks in the
operating mechanism and truck
Since high dielectric strength can be reached in the VD4 circuit breakers have mechanical operating
vacuum, even with minimum distances, circuit mechanisms with stored energy and free trip.
breaking is also guaranteed when the contacts These characteristics allow opening and closing
separate a few milliseconds before natural current operations to be performed independently of the
zero crossing. operator. The operating mechanism is of a simple
The special shape of the contacts, the material design, easy to use and can be customized with a
used, as well as the limited duration and low wide range of accessories which are
voltage of the arc, guarantee minimum contact straightforward and rapidly installed. This
wear and long life. In addition, the vacuum also simplicity enhances the reliability of the apparatus.
prevents contact oxidation and contamination.
The structure
Operating mechanism The operating mechanism and the poles are fixed
The low speed of the contacts, their reduced travel to a metal frame which also acts as the support for
and exposed conductive part, limit the energy the fixed version of the circuit breaker.
required for the operation and therefore guarantee The compact structure is sturdy and ensures
extremely low wear on the system. mechanical reliability.
This means that the circuit breaker only requires Apart from the isolating contacts and the cord
very little maintenance. with plug for connecting the auxiliary circuits, the
withdrawable version is complete with truck for
racking it in and out of the switchgear or enclosure
with the door closed.
10 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Description
8
1. Stem/terminal
2. Twist protection
3. Metal bellows 9
4. lnterrupter enclosure
5. Centring ring
6. Ceramic insulator
7. Shield
10
8. Contacts
9. Terminal
10. lnterrupter enclosure
Vacuum interrupter
A A A
C C C
The spiral shape of ABB vacuum interrupter these latter are only eroded to a negligible extent
contacts and, above all, allows the interruption process to
The special spiral shape of the contacts generates be controlled even with very high short-circuit
a radial magnetic field in all parts of the arc current values.
column, concentrated around the circumferences ABB vacuum interrupters interrupt at natural
of the contacts. current zero crossing, thereby preventing the arc
The electromagnetic force that self-generates, from restriking after this has occurred.
acts tangentially and causes the arc to spin rapidly Rapid reduction in current density at the same
around the axis of the contacts. time as the zero current instant allow maximum
This forces the arc to turn and affect a larger area dielectric strength to be re-established between
than that of a fixed contracted arc. the interrupter contacts within a few
Besides minimizing the thermal stress to which microseconds.
the contacts are subjected, all this ensures that
Short-circuit
current
Corrent, Voltage
Arc voltage
System
voltage
Short-circuit current
interruption
Time
Contact
separation
Recovery voltage
(system frequency)
Geometry of radial magnetic field Development of current and voltage trends during a single phase vacuum interruption process.
contact with a rotating vacuum arc.
12 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Description
Accessories
VD4 circuit breakers have a complete range of
accessories able to meet all installation
requirements.
The operating mechanism has a standardized
range of accessories and replacement parts which
are easy to identify and order.
The accessories are installed conveniently from the
front of the circuit breaker. Electrical connection is
performed with plug-socket connectors.
Use, maintenance and operation of the apparatus
are simple and require limited use of resources.
DI ST RI BUT I ON S OLUT I ON S 13
A N
C
G
E
B
F
—
Description
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (12 kV) (3)
VD4 12
•
12 (2)
12
28
75
50-60
1250 1250 1250 1250 1250 1250 1250 1250
16 – – – – – – –
20 – – – – – – –
25 – – – – – – –
31.5 – – – – – – –
– 40 40 40 40 – – –
– – – – – 50 50 –
– – – – – – – 63
16 – – – – – – –
20 – – – – – – –
25 – – – – – – –
31.5 – – – – – – –
– 40 40 40 40 – – –
– – – – – 50 50 –
– – – – – – – 63
40 – – – – – – –
50 – – – – – – –
63 – – – – – – –
80 – – – – – – –
– 104 100 100 100 – – –
– – – – – 125 125 –
– – – – – – – 164
• • • • • • • –
– – – – – – – •
33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 28...40
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10...15
43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 38...55
30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 ≤55
461 589 589 589 589 610 610 615
700 450 570 570 700 600 750 750 (1) Poles in polyamide
(2) Available at 10kV
424 424 424 424 424 459 459 459 according to GOST R
275 150 210 210 275 210 275 275 52565 standard with
Ud=42kV
79 81 84 84 84 146 158 265 (3) On request, the closing
– – – – – – – – spring can be loaded
by means of a
000051 (1) – 003282 (1) 003282 (1) 003285 (1) 003440 003441 003945 removable crank
– 043108A0001 – – – – – – handle outside
operating mechanism
- 5 ... + 40
(instead of linear
• loading by a lever built
into the front of
•
operating mechanism)
18 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (12 kV) (3)
VD4 12
•
12 (2)
12
28
75
50-60
1600 1600 1600 2000 2000 2000 2000 2000
– – – – – – – –
– – – 20 20 – – –
– – – 25 25 – – –
– – – 31.5 31.5 – – –
– – – 40 40 – – –
50 50 – – – 50 50 –
– – 63 – – – – 63
– – – – – – – –
– – – 20 20 – – –
– – – 25 25 – – –
– – – 31.5 31.5 – – –
– – – 40 40 – – –
50 50 – – – 50 50 –
– – 63 – – – – 63
– – – – – – – –
– – – 50 50 – – –
– – – 63 63 – – –
– – – 80 80 – – –
– – – 100 100 – – –
125 125 – – – 125 125 –
– – 164 – – – – 164
• • – • • • • –
– – • – – – – •
33 ... 60 33...60 28...40 33...60 33...60 33...60 33...60 28...40
10 ... 15 10...15 10...15 10...15 10...15 10...15 10...15 10...15
43 ... 75 43...75 38...55 43...75 43...75 43...75 43...75 38...55
30 ... 60 30...60 ≤55 30...60 30...60 30...60 30...60 ≤55
610 610 677.5 599 599 610 610 615 (1) Poles in polyamide
(2) Available at 10kV
600 750 750 570 700 600 750 750 according to GOST R
459 459 459 424 424 459 459 459 52565 standard with
Ud=42kV
210 275 265 210 275 210 275 275 (3) On request, the closing
146 158 265 98 105 146 158 265 spring can be loaded
by means of a
– – – 7407 (1) 7408 (1) – – – removable crank
003440 003441 003945 – – 003440 003441 003945 handle outside
operating mechanism
- 5 ... + 40
(instead of linear
• loading by a lever built
into the front of
•
operating mechanism)
20 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (12 kV) (3)
VD4 12
•
12 (2)
12
28
75
50-60
3150 (4) 3150 (4) 3150 (4)
– – –
20 – –
25 – –
31.5 – –
40 – –
– 50 –
– – 63
– – –
20 – –
25 – –
31.5 – –
40 – –
– 50 –
– – 63
– – –
50 – –
63 – –
80 – –
100 – –
– 125 –
– – 164
• • –
– – •
33...60 33...60 28...40
10...15 10...15 10...15
43...75 43...75 38...55
30...60 30...60 ≤55
635 636 637
700 750 750
424 459 459
275 275 275
140 177 265
– – –
000149 (1) 003443 003945 (1) Poles in polyamide
(2) Available at 10kV according to GOST R 52565 standard with Ud=42kV
- 5 ... + 40 (3) On request, the closing spring can be loaded by means of a removable
• crank handle outside operating mechanism (instead of linear loading
by a lever built into the front of operating mechanism)
• (4) Up to 4000 A with forced ventilation (*)
22 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (17.5 kV) (2)
Rated short-time 25 25 25 25 25 25
withstand Ik [kA] 31.5 31.5 31.5 31.5 31.5 31.5
current (3s) – – – – – –
– – – – – –
– – – – – –
40 40 40 40 40 40
50 50 50 50 50 50
63 63 63 63 63 63
Making capacity Ip [kA] 80 80 80 80 80 80
– – – – – –
– – – – – –
– – – – – –
[O - 0.3 s - CO - 15 s - CO] • • • • • •
Operation sequence
[O - 0.3 s - CO - 3 min - CO] – – – – – –
Opening time [ms] 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60
Arcing time [ms] 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
Total breaking time [ms] 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75
Closing time [ms] 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60
P P H [mm] 461 461 461 461 461 461
Maximum W [mm] 450 570 700 450 570 700
overall
H D [mm] 424 424 424 424 424 424
dimensions
W D Pole center distance P [mm] 150 210 275 150 210 275
Weight [kg] 73 75 79 73 75 79
TN 7405 (1) 7406 (1) – 7405 (1) 7406 (1) –
Standardized dimensions table 1VCD – – 000051 (1) – – 000051 (1)
2RDA – – – – – –
Operating temperature [°C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC: 62271-1 •
DI ST RI BUT I ON S OLUT I ON S 23
VD4 17
•
17.5
17.5
38
95
50-60
1250 1250 1250 1250 1250 1250 1600 1600 1600 1600 1600 1600 1600
– – – – – – – – – – – – –
– – – – – – 20 20 – – – – –
– – – – – – 25 25 – – – – –
– – – – – – 31.5 31.5 – – – – –
40 40 40 – – – – – 40 40 – – –
– – – 50 50 – – – – – 50 50 –
– – – – – 63 – – – – – – 63
– – – – – – – – – – – – –
– – – – – – 20 20 – – – – –
– – – – – – 25 25 – – – – –
– – – – – – 31.5 31.5 – – – – –
40 40 40 – – – – – 40 40 – – –
– – – 50 50 – – – – – 50 50 –
– – – – – – – – – – – 63
– – – – – – – – – – – – –
– – – – – – 50 50 – – – – –
– – – – – – 63 63 – – – – –
– – – – – – 80 80 – – – – –
104 100 100 – – – – – 100 100 – – –
– – – 125 125 – – – – – 125 125 –
– – – – – 164 – – – – – – 164
• • • • • – • • • • • • –
– – – – – • – – – – – – •
33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 28 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 28 ... 40
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 38 ... 55 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 38 ... 55
30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 ≤55 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 ≤55
589 589 589 610 610 677.5 599 599 589 589 610 610 615
450 570 700 600 750 750 570 700 570 700 600 750 750
424 424 424 459 459 459 424 424 424 424 459 459 459
150 210 275 210 275 275 210 275 210 275 210 275 265
81 84 84 146 158 265 98 105 84 84 146 158 265
– – – – – – 7407 (1) 7408 (1) – – – – –
– 003282 (1) 003285 (1) 003440 003441 003945 – – 003282 (1) 003285 (1) 003440 003441 003945
043108A0001 – – – – – – – – – – – –
- 5 ... + 40
•
•
24 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (17.5 kV) (2)
VD4 17
•
17.5
17.5
38
95
50-60
2500 2500 2500 3150 (3) 3150 (3) 3150 (3)
– – – – – –
20 – – 20 – –
25 – – 25 – –
31.5 – – 31.5 – –
40 – – 40 – –
– 50 – – 50 –
– – 63 – – 63
– – – – – –
20 – – 20 – –
25 – – 25 – –
31.5 – – 31.5 – –
40 – – 40 – –
– 50 – – 50 –
– – 63 – – 63
– – – – – –
50 – – 50 – –
63 – – 63 – –
80 – – 80 – –
100 – – 100 – –
– 125 – – 125 –
– – 164 – – 164
• • – • • –
– – • – – •
33 ... 60 33 ... 60 28 ... 40 33 ... 60 33 ... 60 28 ... 40
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 38 ... 55 43 ... 75 43 ... 75 38 ... 55
30 ... 60 30 ... 60 ≤55 30 ... 60 30 ... 60 ≤55
599 610 677.5 635 636 637
700 750 750 700 750 750 (1) Poles in polyamide
424 459 459 424 459 459 (2) On request, the closing
spring can be loaded
275 275 275 275 275 275 by means of a
105 163 265 140 177 265 removable crank
handle outside
7408 (1) – – – – – operating mechanism
– 003441 003945 000149 (1) 003443 003945 (instead of linear
loading by a lever built
- 5 ... + 40 into the front of
• operating mechanism)
(3) Up to 4000 A with
•
forced ventilation
26 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (24 kV) (2)
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (40.5 kV)
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker (38 kV) - IEEE C37.09 Standards
—
Selection and ordering
Fixed circuit breakers
Types of fixed circuit breakers available
Complete the circuit breaker selected with the optional accessories indicated on the following pages.
VD4 fixed circuit breaker without bottom and top terminals (12 kV)
VD4 fixed circuit breaker without bottom and top terminals (12 kV)
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker without bottom and top terminals (17.5 kV)
VD4 fixed circuit breaker without bottom and top terminals (17.5 kV)
—
Selection and ordering
Fixed circuit breakers
VD4 fixed circuit breaker without bottom and top terminals (24 kV)
VD4 fixed circuit breaker without bottom and top terminals (36 kV)
—
Selection and ordering
Fixed circuit breakers
VD4 (36 kV) fixed circuit breaker
Standard equipment of fixed circuit breakers • closing pushbutton, opening pushbutton and
The basic versions of the fixed circuit breakers are operation counter
three-pole and equipped with: • set of ten auxiliary circuit breaker break/make
• EL or Classic manual operating mechanism contacts
Note: three break contacts (signaling circuit breaker open) and five
• mechanical signaling device for closing springs make contacts (signaling circuit breaker closed) are available with the
loaded/discharged group of ten auxiliary contacts supplied as standard and the maximum
number of electrical applications.
• mechanical signaling device for circuit breaker
• lever built into operating mechanism for linear
open/closed
loading of closing spring.
VD4 - up to 24 kV VD4 - 36 kV
40 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for UniGear ZS1 switchgear (12 kV) (4)
VD4/P 12
•
12 (2)
12
28
75
50-60
1600 1600 1600 1600 1600 1600 1600
– – – – – – –
20 20 – – – – –
25 25 – – – – –
31.5 31.5 – – – – –
– – 40 40 – – –
– – – – 50 50 –
– – – – – – 63
– – – – – – –
20 20 – – – – –
25 25 – – – – –
31.5 31.5 – – – – –
– – 40 40 – – –
– – – – 50 50 –
– – – – – – 63 (5)
– – – – – – –
50 50 – – – – –
63 63 – – – – –
80 80 – – – – –
– – 100 100 – – –
– – – – 125 125 –
– – – – – – 164
• • • • • • –
– – – – – – •
33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 28 ... 40
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 38 ... 55
30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 ≤55
691 691 691 691 691 691 735 (1) Rated current guaranteed with
circuit breaker installed in UniGear
653 853 653 853 681 853 851
ZS1 switchgear and with 40 °C
642 642 641 642 643 643 650 ambient temperature.
( ) Available at 10kV according to GOST
2
210 275 210 275 210 275 275
R 52565 standard with Ud=42kV
160 166 174 176 180 193 270 (3) Poles in polyamide
7415(3) 7416(3) – – – – – ( ) On request, the closing spring can
4
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for UniGear ZS1 switchgear (12 kV) (4)
VD4/P 12
•
12 (4)
12
28
75
50-60
2500 2500 2500 3150 (6) 3150 (6) 3150 (6)
– – – – – –
20 – – 20 – –
25 – – 25 – –
31.5 – – 31.5 – –
40 – – 40 – –
– 50 – – 50 –
– – 63 – – 63
– – – – – –
20 – – 20 – –
25 – – 25 – –
31.5 – – 31.5 – –
40 – – 40 – –
– 50 – – 50 –
– – 63 (5) – – 63 (5)
– – – – – –
50 – – 50 – –
63 – – 63 – –
80 – – 80 – –
100 – – 100 – –
– 125 – – 125 –
– – 164 – – 164
• • – • • –
– – • – – •
33 ... 60 33 ... 60 28 ... 40 33 ... 60 33 ... 60 28 ... 40
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 38 ... 55 43 ... 75 43 ... 75 38 ... 55
(1) Rated current guaranteed with
30 ... 60 30 ... 60 ≤55 30 ... 60 30 ... 60 ≤55 circuit breaker installed in UniGear
691 691 735 730 742 735 ZS1 switchgear and with 40 °C
ambient temperature.
853 853 851 853 853 851
( ) Available at 10kV according to GOST
2
640 643 650 640 643 650 R 52565 standard with Ud=42kV
(3) Poles in polyamide
275 275 275 275 275 275
( ) On request, the closing spring can
4
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for UniGear ZS1 switchgear (17.5 kV) (4)
VD4/P 17
•
17.5
17.5
38
95
50-60
1600 1600 1600 1600 1600 1600 1600
– – – – – – –
20 20 – – – – –
25 25 – – – – –
31.5 31.5 – – – – –
– – 40 40 – – –
– – – – 50 50 –
– – – – – – 63
– – – – – – –
20 20 – – – – –
25 25 – – – – –
31.5 31.5 – – – – –
– – 40 40 – – –
– – – – 50 50 –
– – – – – – 63 (5)
– – – – – – –
50 50 – – – – –
63 63 – – – – –
80 80 – – – – –
– – 100 100 – – –
– – – – 125 125 –
– – – – – – 164
• • • • • • –
– – – – – – •
33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 28 ... 40
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 38 ... 55
30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 ≤55
691 691 691 691 691 691 735 (1) Rated current guaranteed with circuit
breaker installed in UniGear ZS1
653 853 653 853 681 853 851
switchgear and with 40 °C ambient
642 642 641 642 643 643 650 temperature.
( ) Please consult drawing 2RDA032149
2
210 275 210 275 210 275 275
of “Overall dimensions” section for
160 166 174 176 180 193 270 210 mm pole center distance.
7415(3) 7416(3) – – – – – ( ) Poles in polyamide
3
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for UniGear ZS1 switchgear (17.5 kV) (4)
VD4/P 17
•
17.5
17.5
38
95
50-60
2500 2500 2500 3150 (2) 3150 (2) 3150 (2)
– – – – – –
20 – – 20 – –
25 – – 25 – –
31.5 – – 31.5 – –
40 – – 40 – –
– 50 – – 50 –
– – 63 – – 63
– – – – – –
20 – – 20 – –
25 – – 25 – –
31.5 – – 31.5 – –
40 – – 40 – –
– 50 – – 50 –
– – 63 (5) – – 63 (5)
– – – – – –
50 – – 50 – –
63 – – 63 – –
80 – – 80 – –
100 – – 100 – –
– 125 – – 125 –
– – 164 – – 164
• • – • • –
– – • – – •
33 ... 60 33 ... 60 28 ... 40 33 ... 60 33 ... 60 28 ... 40
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
43 ... 75 43 ... 75 38 ... 55 43 ... 75 43 ... 75 38 ... 55
30 ... 60 30 ... 60 ≤55 30 ... 60 30 ... 60 ≤55
691 691 735 730 742 735
(1) Rated current guaranteed with circuit
853 853 851 853 853 851
breaker installed in UniGear ZS1
640 643 650 640 643 650 switchgear and with 40 °C ambient
temperature.
275 275 275 275 275 275
( ) Up to 4000 A with forced ventilation.
2
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for UniGear ZS1 switchgear (24 kV) (5)
(1) Rated current guaranteed with circuit breaker installed in UniGear ZS1 switchgear and with 40 °C ambient temperature.
(2) 2300 A rated current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
(3) 2700 A rated current guaranteed with natural ventilation; 3150 A rated current guaranteed with forced ventilation.
(4) 31.5 kA version.
(5) On request, the closing spring can be loaded by means of a removable crank handle outside the operating mechanism (instead of linear loading, only possible with the door open, by
means of a lever built into the front of the operating mechanism).
(6) Contact ABB for the 27 kV version
DI ST RI BUT I ON S OLUT I ON S 49
( ) 2500 A with forced ventilation and 79 mm diameter tulip contacts TN 1VYN300901 RA.
1
2500A without forced ventilation and 109 mm diameter tulip contacts TN 1VYN300901-RB available for UniGear ZS2 only.
(2) 3150 A with forced ventilation.
Available for UniGear ZS2 only.
50 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers in floor rolling version
for UniGear ZS3.2 switchgear and Powerbloc modules
(36 kV)(*)
(*) Up to 31.5 kA for UniGear ZS3.2.
W D Pole center distance P [mm] 280 280 280 280 280 280
Weight [kg] 290 290 340 340 340 380
Standardized dimensions table TN GCEM 700198
Operating temperature [°C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC: 62271-1 •
(1) version only available with forced ventilation and assembled pole
DI ST RI BUT I ON S OLUT I ON S 51
—
Selection and ordering
Withdrawable circuit breakers
Types of withdrawable circuit breakers available for UniGear ZS1 switchgear
Complete the circuit breaker selected with the optional accessories indicated on the following pages.
VD4 (17.5 kV) withdrawable circuit breaker for UniGear ZS1 switchgear
—
Selection and ordering
Withdrawable circuit breakers
VD4 (24 kV) withdrawable circuit breaker for UniGear ZS1 switchgear
W = Switchgear width.
P = Horizontal center distance of poles.
u/l = Distance between bottom and top terminals.
ø = Diameter of isolating contact.
(1) 2500 A rated current guaranteed with forced ventilation.
(2) 3150 A rated current guaranteed with forced ventilation.
DI ST RI BUT I ON S OLUT I ON S 55
—
Selection and ordering
Withdrawable circuit breakers
VD4 (36 kV) withdrawable circuit breaker
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for PowerCube modules (12 kV) (5)
VD4/P 12 VD4/W 12
PB2 PB3 PB3
• • •
12 (4) 12 (4) 12
12 12 12
28 28 28
75 75 75
50-60 50-60 50-60
1600 1600 1600 2000 2000 2500 2500 3150 (2) 3150 (2)
– – – – – – – – –
20 – – 20 – 20 – 20 –
25 – – 25 – 25 – 25 –
31.5 – – 31.5 – 31.5 – 31.5 –
– 40 – 40 – 40 – 40 –
– – 50 – 50 – 50 – 50
– – – – – – – – –
20 – – 20 – 20 – 20 –
25 – – 25 – 25 – 25 –
(1) Rated current
31.5 – – 31.5 – 31.5 – 31.5 – guaranteed with circuit
breaker installed in
– 40 – 40 – 40 – 40 – PowerCube enclosure
– – 50 – 50 – 50 – 50 and with 40 °C
ambient temperature
– – – – – – – – – ( ) Up to 4000 A with
2
50 – – 50 – 50 – 50 – forced ventilation.
(3) Poles in polyamide
63 – – 63 – 63 – 63 – ( ) Available in 10 kV
4
voltage version to
80 – – 80 – 80 – 80 –
GOST standards
– 100 – 100 – 100 – 100 – ( ) On request, the closing
5
642 641 643 642 643 640 643 640 643 insulation for the feed-
through and tulip
210 210 210 210 210 275 275 275 275
contacts in module
160 174 180 160 190 186 225 221 240 PB2. On request, the
same circuit breaker
7415 (3) – – 7415 (3) – 7417 (3) – – – with insulated feed-
– 003284 (3) 003444 – 003444 – 003445 000152 (3) 003596 through and tulip
contacts is available
- 5 ... + 40 - 5 ... + 40 - 5 ... + 40 for installation in
• • • enclosures not
produced by ABB
• • • (version VD4/PW)
60 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for PowerCube modules (17.5 kV) (4)
VD4/P 17 VD4/W 17
PB2 PB3 PB3
• • •
17.5 17.5 17.5
17.5 17.5 17.5
38 38 38
95 95 95
50-60 50-60 50-60
1600 1600 1600 2000 2000 2500 2500 3150 (2) 3150 (2)
– – – – – – – – –
20 – – 20 – 20 – 20 –
25 – – 25 – 25 – 25 –
31.5 – – 31.5 – 31.5 – 31.5 –
– 40 – 40 – 40 – 40 –
– – 50 – 50 – 50 – 50
– – – – – – – – –
20 – – 20 – 20 – 20 –
25 – – 25 – 25 – 25 –
31.5 – – 31.5 – 31.5 – 31.5 –
– 40 – 40 – 40 – 40 –
– – 50 – 50 – 50 – 50 (1) Rated current
– – – – – – – – – guaranteed with circuit
breaker installed in
50 – – 50 – 50 – 50 – PowerCube enclosure
and with 40 °C
63 – – 63 – 63 – 63 –
ambient temperature.
80 – – 80 – 80 – 80 – (2) Up to 4000 A with
forced ventilation.
– 100 – 100 – 100 – 100 –
(3) Poles in polyamide.
– – 125 – 125 – 125 – 125 (4) On request, the closing
spring can be loaded
• • • • • • • • • by means of a
33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60 removable crank
handle outside the
10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15 operating mechanism
43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75 (instead of linear
loading, only possible
30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60 with the door open, by
means of a lever built
691 691 691 690 691 691 691 730 691
into the front of the
653 653 681 653 681 853 853 853 853 operating mechanism).
(5) VD4/W does not need
642 641 643 642 643 640 643 640 643 insulation for the feed-
210 210 210 210 210 275 275 275 275 through and tulip
contacts in module
160 174 180 160 190 186 225 221 240 PB2. On request, the
7415 (3) – – 7415 (3) – 7417 (3) – – – same circuit breaker
with insulated feed-
– 003284 (3) 003444 – 003444 – 003445 000152 (3) 003596 through and tulip
- 5 ... + 40 - 5 ... + 40 - 5 ... + 40 contacts is available
for installation in
• • • enclosures not
produced by ABB
• • •
(version VD4/PW).
62 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers
for PowerCube modules (24 kV) (4)
Rated short-time 20 20 20 20 20
withstand current (3s) 25 25 25 25 25
– 31.5 31.5 31.5 31.5
Ip [kA] 40 40 40 40 40
50 50 50 50 50
Making capacity
63 63 63 63 63
– 80 80 80 80
Operation sequence [O - 0.3 s - CO - 15 s - CO] • • • • •
Opening time [ms] 33 ... 60 33 ... 60 33 ... 60 33 ... 60 33 ... 60
Arcing time [ms] 10 ... 15 10 ... 15 10 ... 15 10 ... 15 10 ... 15
Total breaking time [ms] 43 ... 75 43 ... 75 43 ... 75 43 ... 75 43 ... 75
Closing time [ms] 30 ... 60 30 ... 60 30 ... 60 30 ... 60 30 ... 60
P P
H [mm] 794 794 838 838 838
Maximum W [mm] 653 653 853 853 853
overall
H D [mm] 802 802 790 790 790
dimensions
W D Pole center distance P [mm] 210 210 275 275 275
Weight [kg] 140 140/146 (3) 228 228 228
TN 7413 7413 7418 7418 7418
Standardized dimensions table
1VCD – 000173 (3) – – –
Operating temperature [°C] - 5 ... + 40
Tropicalization IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility IEC: 62271-1 •
( ) Rated current guaranteed with circuit breaker installed in PowerCube enclosure and with 40 °C ambient temperature.
1
(2) 2300 A rated uninterrupted current guaranteed with natural ventilation; 2500 A rated uninterrupted current guaranteed with forced ventilation.
(3) 31.5 kA version.
(4) On request, the closing spring can be loaded by means of a removable crank handle outside the operating mechanism
(instead of linear loading, only possible with the door open, by means of a lever built into the front of the operating mechanism).
64 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
Types of withdrawable circuit breakers available for PowerCube modules
Complete the circuit breaker selected with the optional accessories indicated on the following pages.
W = Enclosure width.
P = Horizontal center distance of poles.
u/l = Distance between bottom and top terminal.
ø = Diameter of isolating contact.
(1) Up to 4000 A with forced ventilation.
DI ST RI BUT I ON S OLUT I ON S 65
W = Enclosure width.
P = Horizontal center distance of poles.
u/l = Distance between bottom and top terminals.
ø = Diameter of isolating contact.
(1) Up to 4000 A with forced ventilation.
66 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
VD4 (24 kV) withdrawable circuit breaker
W = Enclosure width.
P = Horizontal center distance of poles.
u/l = Distance between bottom and top terminals.
ø = Diameter of isolating contact.
(1) Up to 2500 A rated current guaranteed with forced ventilation.
DI ST RI BUT I ON S OLUT I ON S 67
Standard equipment of withdrawable circuit • lever built into the operating mechanism for
breakers for PowerCube modules linear loading of closing spring
The basic versions of the withdrawable circuit • isolating contacts
breakers are always three-pole and equipped with: • cord with connector (plug only) for auxiliary
• EL manual operating mechanism circuits, with striker pins which prevent the plug
• mechanical signaling device for closing springs from being inserted into the socket if the rated
loaded/discharged current of the circuit breaker is different from
• mechanical signaling device for circuit breaker the rated current of the switchgear
open/closed • racking-in/out lever (the quantity depends on
• closing pushbutton the number of apparatuses ordered)
• opening pushbutton • locking electromagnet in the truck. This prevents
• operation counter the circuit breaker from being racked into the
• set of ten circuit breaker open/closed auxiliary switchgear when the auxiliary circuits are not
contacts connected (plug not in in the socket).
Note: three break contacts (signaling circuit breaker open) and four
make contacts (signaling circuit breaker closed) are available with the
• door interlock (mandatory for ABB switchgear);
group of ten auxiliary contacts supplied as standard and the maximum this device prevents the circuit breaker from
number of electrical applications.
being racked into the switchgear when the
switchgear door is open.
68 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
Withdrawable circuit breakers for ZS8.4
switchgear (12 - 17.5 - 24 kV)
VD4/ZT8 VD4/ZS8
– – – – – – – – – –
• • • • • • – – – –
– – – – – – • • • •
650 650 650 650 800 800 650 650 800 800
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
• •
12 12 17.5 17.5 24 24 12 12 24 24
12 12 17.5 17.5 24 24 12 12 24 24
28 28 38 38 50 50 28 28 50 50
75 75 95 95 125 125 75 75 125 125
50-60 50-60
630 1250 630 1250 630 1250 630 1250 630 1250
– – – – 16 16 – – 16 16
20 20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25
– – – – 16 16 – – 16 16
20 20 20 20 20 20 20 20 20 20
25 25 25 25 25 25 25 25 25 25
– – – – 40 40 – – 40 40
50 50 50 50 50 50 50 50 50 50
63 63 63 63 63 63 63 63 63 63
• • • • • • • • • •
33...60 33...60 33...60 33...60 33...60 33...60 33...60 33...60 33...60 33...60
10...15 10...15 10...15 10...15 10...15 10...15 10...15 10...15 10...15 10...15
43...75 43...75 43...75 43...75 43...75 43...75 43...75 43...75 43...75 43...75
30...60 30...60 30...60 30...60 30...60 30...60 30...60 30...60 30...60 30...60
579 579 579 579 680 680 579 579 680 680
503 503 503 503 653 653 503 503 653 653
638 638 638 638 646 646 638 638 646 646
150 150 150 150 210 210 150 150 210 210
116 116 116 116 140 140 116 116 140 140
000093 000134 000134 000134 000090 000136 000091 000133 000088 000135
– 5 ... + 40 – 5 ... + 40
• • • • • • • • • •
• • • • • • • • • •
• • • • • • • • • •
70 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
VD4/ZS8 - VD4/ZT8 - VD4/Z8 withdrawable circuit breakers for ZS8.4 switchgear
W = Switchgear width.
P = Horizontal center distance of poles.
u/l = Distance between bottom and top terminals.
Ø = Diameter of isolating contact.
DI ST RI BUT I ON S OLUT I ON S 71
Key
1) Device with crank handle for
loading closing spring (only
version VD4/ZS8)
1 2) Harting 64 plus socket with
mechanical interlock which
prevents circuit breaker from
being moved when socket is not
inserted
3) Interlock that prevents door from
closing if plug is not in socket
(only version VD4/ZS8))
72 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Withdrawable circuit breakers
General characteristics of withdrawable
circuit breakers for UniSec switchgear
(units WBC and WBS)
(1) Rated current guaranteed with withdrawable circuit breaker installed in switchgear with 40 °C ambient temperature.
(2) Poles in polyamide.
DI ST RI BUT I ON S OLUT I ON S 73
Standard equipment of withdrawable circuit • lever built into the operating mechanism for
breakers for UniSec switchgear linear loading of closing spring
The basic versions of the withdrawable circuit • isolating contacts
breakers are three-pole and equipped with: • cord with connector (plug only) for auxiliary
• EL manual operating mechanism circuits, with striker pins which prevent the plug
• mechanical signaling device for closing springs from being inserted into the socket if the rated
loaded/discharged current of the circuit breaker is different from
• mechanical signaling device for circuit breaker the rated current of the switchgear
open/closed • racking-in/out lever (the quantity depends on
• closing pushbutton apparatuses ordered)
• opening pushbutton
• operation counter
• set of ten circuit breaker open/closed auxiliary
contacts
Note: three break contacts (signaling circuit breaker open) and four
make contacts (signaling circuit breaker closed) are available with the
group of ten auxiliary contacts supplied as standard and the maximum
number of electrical applications.
74 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Optional accessories
For circuit breakers up to 36 kV, 50 kA with EL operating mechanism
Accessories with the same number are alternative to each other.
1 Shunt opening release (-MBO1) 2 Additional shunt opening release (-MBO2)
Allows the opening command of the apparatus to Similarly to shunt opening release -MBO1, this
be enabled by remote control. allows the opening command of the apparatus to
This release is suitable for both instantaneous and be transmitted by remote control. It can be
permanent duty. However, there is always an supplied by the same circuit as main shunt
auxiliary contact, -BGB1, that de-energizes it after opening release -MBO1 or by a circuit that is
the circuit breaker has opened. In the case of completely separate from release -MBO1.
instantaneous service, the current impulse must This release is suitable for both instantaneous and
last at least 100 ms. permanent duty. However, there is always an
This release can be controlled by the following auxiliary contact, -BGB1, that de-energizes it after
devices: coil continuity control (CCC), opening the circuit breaker has opened.
circuit supervision (TCS)(*) or the ABB STU To guarantee the release action, the current
functionality control device (see accessory 21, impulse must last at least 100 ms.
supplied on request). Continuity functionality can be checked with a
continuity control device (CCC), opening circuit
Characteristics supervision (TCS)(*) or the STU functionality
Un 24-30-48-60-110...132-220...250 V DC control device (see accessory 21, supplied on
Un 48-60-110...127-220...250 V AC 50-60 Hz request).
Operating limits 65 … 120% Un -MBO2 has the same electrical and operating
Inrush power (Ps) 60...100 W / VA
characteristics as release -MBO1.
Continuous power
1.5 W
consumption (Pc)
Electronics self-consumption
(no coil supplied); value
1.5 mA
independent of voltage
applied
Opening time 33...60 ms
Insulation voltage 2000 V 50 Hz (for 1 min)
Characteristics
Un 24-30-48-60-110...132-220...250 V DC
Un 48-60-110...127-220...250 V AC 50-60 Hz
Operating limits 65 … 120% Un
Inrush power (Ps) 60...100 W / VA
Continuous power
1.5 W
consumption (Pc)
(*) The minimum current Electronics self-consumption
that the relay with TCS (no coil supplied; value 1.5 mA
function (used for independent of voltage applied
monitoring coil
continuity) detects as a Closing time 30...60 ms
condition denoting that
Insulation voltage 2000 V 50 Hz (for 1 min)
the trip circuit is
operating correctly
(specified for each relay in
the relative manual), must
be sensibly higher than
the current consumption
of the actual coil (~1.5
mA).
If this fails to occur,
always add, in parallel to
the TCS, a circuit able to
absorb sufficient current
to compensate the gap
while preventing the total
current in the TCS circuit
from rising above the
maximum threshold up to
100mA.
A simple resistor can be
sized for the purpose,
depending on the
parameters of the TCS
and the auxiliary voltage
range used.
For further details,
consult the Guidelines
for use of the Smart Coil
1VCD601416
76 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Optional accessories
The undervoltage release is available in the
5 Undervoltage release (-MBU)
following versions:
The undervoltage release opens the circuit breaker
when there is a sensible reduction or lack of the 5A Undervoltage release (with supply shunted
voltage that powers it. The circuit breaker can only from a transformer on the supply side of the
close when the release is energized (the closing circuit breaker or from an auxiliary power
lock is obtained mechanically). supply, regardless of the state in which the
It can be used for remote release (by means of a circuit breaker is to be found).
pushbutton of the normally closed type) and for
5B Undervoltage release with -KFT electronic
locking on automatic closing/opening in the
time-lag device (0.5 - 1 - 1.5 - 2 - 3 s) (with power
absence of voltage in the auxiliary circuits.
supply as indicated for 5A); this device is
Supplied by means of the secondary output of a
supplied with a 0.5 s setting (the adjustments
voltage transformer, it provides locking upon
are described in the Circuit diagrams chapter)
automatic closing/opening in the absence of
voltage in the Medium Voltage main circuit. Characteristics
If there is the same supply voltage for shunt Un 24-30-48-60-110...132-220...250 V DC
closing release -MBC and undervoltage release
Un 48-60-110...127-220...250 V AC 50-60 Hz
-MBU and the circuit breaker must close – circuit breaker opening:
automatically when auxiliary voltage returns, there 35-70% Un
Operating limits
must be a delay of at least 50 ms between under- – circuit breaker closing:
voltage release energizing and energizing of the 85-110% Un
Inrush power (Ps) 150 W / VA
shunt closing release to allow the closing
Continuous power
operation to take place. 1.55 W
consumption (Pc)
Electronics self-consumption
(no coil supplied); value
1.5 mA
independent of voltage
applied
Insulation voltage 2000 V 50 Hz (for 1 min)
Note
As an alternative to the undervoltage release, an additional shunt
opening release (-MBO4) with the same electrical and operating
specifications as shunt opening release (-MBO1) can be installed on
request (only for 12..17.5 kV circuit breakers up to 40 kA and 24 kV up
to 31.5 kA).
Warning! Since installation of the additional shunt opening release
(-MBO4) requires a special mounting plate for releases, ask for
application (-MBO4) when ordering and not after delivery.
DI ST RI BUT I ON S OLUT I ON S 77
—
Selection and ordering
Optional accessories
7a Auxiliary contacts of the circuit breaker Consult circuit diagrams 1VCD400151 for fixed
(-BGB1) for 12 to 24 kV versions circuit breakers and 1VCD400155 for withdrawable
Electrical signaling of circuit breaker open/closed circuit breakers.
can be obtained with a group of 10, 16, 20 or 24
auxiliary contacts for the fixed version and 10 or 16 Note: The main shunt opening release and/or the
auxiliary contacts for the withdrawable version. additional shunt opening release use 1 and/or 2
The standard equipment comprises 10 auxiliary closing contacts “a”, thereby reducing the number
contacts. of auxiliary contacts available. Always check the
Note maximum number of contacts available with non-
The following are available using the standard standard equipment.
group of ten auxiliary contacts and the maximum
number of electrical accessories: The new diagrams are interchangeable with the
• for fixed circuit breakers: three closing contacts existing ones, with the following exceptions:
“a” for signaling circuit breaker open and five • diagram 1VCD400151 (substitutes 1VCD400046
opening contacts “b” for signaling circuit breaker and 1VCD400099)
closed; -- fig. 34 on the previous diagrams is represented
• for withdrawable circuit breakers: three closing by fig. 31 + fig. 32 on the new diagram;
contacts “a” for signaling circuit breaker open -- fig. 33 and fig. 35 on the previous diagrams are
and four opening contacts “b” for signalling not available with the new layout
circuit breaker closed. • diagram 1VCD400155 (substitutes 1VCD400047)
Circuit breakers in the fixed version are available Auxiliary contacts –BGB1 conform to the following
with two finishing accessories (to be specified standards/regulations/directives:
when ordering): • IEC 62271-100
• non-wired auxiliary contacts; wiring to the • IEEE C37.54
terminals of the contacts is at the customer’s • EN 61373 cat. 1 class B / impact and vibration
charge (photo at left; the terminal box to which test
the other electrical accessories are wired is at • Germanish Loyd regulation / vibrations
the top); ask for instructions 1VCD601204 envisaged by the shipping registers
(available in the main languages) which describe • UL 508
how to remove, wire the auxiliary contacts more • EN 60947 (DC-21A DC-22A DC-23A AC-21A)
easily and fit the auxiliary contact unit back into • RoHS Directive
its housing;
• auxiliary contacts already wired to the terminal
box (see photo at right)
DI ST RI BUT I ON S OLUT I ON S 79
General characteristics
8 Transient contact (-BGB4)
Insulation voltage to 660 V AC This contact closes momentarily (duration > 30 ms)
standard VDE 0110, Group C 800 V DC upon circuit breaker opening controlled remotely
Rated voltage 24 V ... 660 V with a shunt opening release.
Test voltage 2 kV for 1 min The indication is not provided when opening is
Maximum rated current 10 A - 50/60 Hz manual and local. In this case, a contact (–BGB11) is
Breaking capacity Class 1 (IEC 62271-1) activated by the manual pushbutton and cuts off
Number of contacts 5 the transient contact closing signal (–BGB4).
Groups of contacts 10 / 16 / 20 The transient contact is activated directly from the
Contact travel 90° main operating shaft, thus the indication is
Actuating force 0.66 Nm provided only on actual opening of the main circuit
Resistance <6.5 mΩ breaker contacts.
Storage temperature –30 °C ... +120 °C
–20 °C ... +70 °C
Operating temperature
(-30° ref. ANSI 37.09)
Contact overtemperature 10 K
Mechanical life 30.000 mechanical operations
Protection class IP20
Cable section 1 mm2
Electrical characteristics
(according to IEC 62271-100 class 1)
Rated voltage Un Breaking capacity
24 V DC 20 ms 18.8 mA
60 V DC 20 ms 7.4 mA
110 V DC 20 ms 4.2 mA
250 V DC 20 ms 1.8 mA
—
Selection and ordering
Optional accessories
9 Position contact (-BGT3) 10 Transmitted contacts (*) in the truck (-BGT1;
This contact is used, together with the locking -BGT2)
magnet in the operating mechanism (-RLE1), to Transmitted contacts of withdrawable circuit
prevent remote closing as the circuit breaker is breakers (installed in the circuit breaker truck -
racked into the compartment. only for VD4/P withdrawable circuit breakers).
It is only supplied for withdrawable circuit These contacts are either in addition or
breakers for UniGear ZS1 switchgear and alternatives to the position contacts (for signaling
PowerCube modules. circuit breaker racked out). They also act as
It cannot be supplied when transmitted contacts position contacts (-BGT3).
in the truck are requested (-BGT1; -BGT2).
(*) For application at 24Vdc and with currents lower than 10mA golden
contacts are recommended.
DI ST RI BUT I ON S OLUT I ON S 81
—
Selection and ordering
Optional accessories
Protections and locks
Various mechanical and electromechanical locking and protection devices are available.
13 Opening and closing pushbutton protection 14 Opening and closing pushbutton padlock
The protection only allows the opening and closing The device allows the opening and closing
pushbuttons to be operated using a special tool. pushbuttons to be locked using up to three ø 4
mm diameter padlocks (not supplied).
The padlock is available in two versions:
14A Possibility of padlocking both the pushbut-
tons without distinction
14B Separate padlocking of the opening and/or
closing pushbutton.
N.B. Lock 14A prevents closing by remote control; lock 14B does not
prevent closing by remote control.
DI ST RI BUT I ON S OLUT I ON S 83
—
Selection and ordering
Optional accessories
17 Locking magnet on the truck (-RLE2) 18 Interlock for fixed circuit breakers
Mandatory accessory for withdrawable circuit Device for fixed circuit breakers which have been
breakers for UniGear ZS1 switchgear and converted into withdrawable ones by the
PowerCube modules. Prevents the circuit breaker customer. It allows a mechanical lock to be created
from racking into the switchgear when the by the customer to prevent racking-out/in with the
auxiliary circuit plug is disconnected. circuit breaker closed and prevents circuit breaker
The plug also acts as an anti-insertion lock if the closing while moving.
rated current is different. Special striker pins Note: The device must be requested when
prevent the plug from being inserted into the ordering since it must be assembled and tested in
socket if the rated current of the circuit breaker is the factory.
lower than the rated current of the panel.
Note: a specific version for the circuit breakers of
ZS8.4 switchgear is available on request. This
accessory is not available when the motor-
operated truck is required
Characteristics
24 - 30 - 48 - 60 - 110 - 125 -
Un
127 - 132 - 220 - 240 V–
24 - 30 - 48 - 60 - 110 - 125 - 127 -
Un
220 - 230 ... 240 V~ 50/60 Hz
Operating limits 85 … 110% Un
Inrush power (Pn) DC 250 W; AC = 250 VA
Continuous power (Pc) DC = 5 W; AC = 5 VA
Inrush duration 150 ms
Insulation voltage 2000 V 50 Hz (for 1 min)
DI ST RI BUT I ON S OLUT I ON S 85
—
Selection and ordering
Optional accessories
21 STU Shunt Test Unit • TEST FAILED: signal following a failed test or in
Device which monitors the functionality and the absence of auxiliary power supply
continuity of opening/closing shunt releases. • ALARM: signal after three failed tests.
Owing to their particular construction, checking
the functionality of closing (-MBC) and opening Two relays and a changeover are also available on
(-MBO1, -MBO2) shunt releases cannot be the unit and allow the following two events to be
performed by dedicated relays (e.g. TCS Test remotely signaled:
Control Supervision, CCC Control Coil Continuity) • failure of a test (with automatic reset when
or with the REF control and protection unit. The alarm ceases)
only device able to monitor the functionality of • failure of three tests (resetting can only be
these releases is the STU device. Please contact us obtained by means of the manual - RESET – from
if this function must be provided by devices other the front of the unit).
than STU.
The STU Shunt Test Unit can be used in There is also a manual - RESET – key on the front of
conjunction with the shunt opening release the unit.
(-MBO1; -MBO2) or shunt closing release (-MBC) to
check their functionality and continuity. Characteristics
The Shunt Test Unit allows the continuity of Un 24 ... 250 V AC/DC
releases with rated operating voltage between Maximum interrupted current 6A
24 V and 250 V (AC and DC) to be monitored, as Maximum interrupted voltage 250 V AC
well as the functionality of the electronic circuit of
the release.
Continuity is monitored cyclically with intervals of 22 Extension cord for 58 pins plug
20 seconds between one test and the next. The extension cord with 58 pins available in two
The unit has optical signals with LEDs on the front. lengths 1.5m and 3m, in addition
The following information is given: to the standard plug.
• POWER ON: power supply present
• (-MO) TESTING: test in progress
DI ST RI BUT I ON S OLUT I ON S 87
1 Shunt opening release -MO1 (-Y2) 2 Additional shunt opening release -MO2 (-Y9)
The shunt opening release allows the apparatus to The additional shunt opening release has the same
be opened by remote control. function as shunt opening release -MO1 (-YO2).
An auxiliary contact -BB2 (-S4) always de-energizes The additional shunt opening release is available
it after opening. on request and requires use of auxiliary contact
-BB1 (-S3), which is part of the standard
Characteristics equipment.
Ua: 24 - 30 - 48 - 60 - 110 - 125 - 220 - 240 V-
Ua: 100 - 110 - 125 - 220 - 230 - 240 V ~ 50 … 60 Hz Characteristics
Service tolerances: DC 70 … 110% Ua Ua: 24 - 30 - 48 - 60 - 110 - 125 - 220 - 240 V-
AC 85 … 110% Ua Ua: 100 - 110 - 125 - 220 - 230 - 240 V ~ 50 … 60 Hz
Short-term power approx. DC 250 W; Service tolerances: DC 70 … 110% Ua
consumption: approx. AC 250 VA
AC 85 … 110% Ua
Admissible maximum 8s
Short-term power approx. DC 250 W;
operating time:
consumption: approx. AC 250 VA
Admissible maximum 8s
operating time:
88 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Optional accessories
3 Shunt closing release -MC (-Y3) 4 Locking magnet on operating mechanism RL1
The shunt closing release allows the circuit breaker (-Y1) with auxiliary contacts -BL1 (-S2)
to be closed by remote control. Only allows the operating mechanism to be
Auxiliary contact -BS1 (-S1) cuts off the power activated when the electromagnet is energized.
supplied to the release after the closing springs To enable the circuit breaker to close, the locking
have been loaded, while auxiliary contact -BB1 (-S3) magnet must be energized for at least 100 ms
cuts off the power supplied to the release after the before the circuit breaker closing command.
circuit breaker has closed. Auxiliary contact -BL1 (-S2) is required and is part
Both are required and are part of the standard of the standard equipment.
equipment.
The shunt closing release is optional in circuit Characteristics
breakers with manual opening mechanisms but Ua: 24 - 30 - 48 - 60 - 110 - 125 - 220 - 240 V-
mandatory for circuit breakers with motor- Ua: 100 - 110 - 125 - 220 - 230 - 240 V ~ 50 … 60 Hz
operated drives. Service tolerances: DC 85 … 110% Ua
AC 85 … 110% Ua
Application of the shunt closing release includes
Short-term power approx. DC 10 W;
anti-pumping relay -K0. consumption: approx. AC 10 VA
The permanently supplied release provides the Admissible maximum
electrical anti-pumping function with both operating time: unlimited
electrical opening and re-closing commands
maintained.
Circuit breaker closing is only re-enabled once the
active closing command has been interrupted.
Characteristics
Ua: 24 - 30 - 48 - 60 - 110 - 125 - 220 - 240 V-
Ua: 100 - 110 - 125 - 220 - 230 - 240 V ~ 50 … 60 Hz
Service tolerances: DC 70 … 110% Ua
AC 70 … 110% Ua
Short-term power approx. DC 250 W;
consumption: approx. AC 250 VA
Admissible maximum
operating time: 8s
DI ST RI BUT I ON S OLUT I ON S 89
5 Undervoltage release -MU (-Y4) 5.1 Electronic time-lag device -KT (-RN3U)
The undervoltage release opens the circuit breaker Use of the delayed undervoltage release is useful
when there is an appreciable drop or lack of the for preventing trips when the supply network of
voltage that supplies it. the release may be subject to power cuts or brief
It trips when the auxiliary voltage is between 70% voltage dips.
and 30% of its rated value. The voltage of the undervoltage release must be
The circuit breaker can only close again when the within the operating range of the electronic time-
voltage reaches 85% of its rated value. lag device (a coupler transformer must be
The undervoltage release trips instantaneously, connected in series for rated voltages other than
but can also be accompanied by an electronic 100-110 V AC).
time-lag device. The electronic time-lag device must be assembled
externally in relation to the circuit breaker. It allows
Characteristics of the non-delayed version the tripping action of the release to be delayed on
Ua: 24 - 30 - 48 - 60 - 110 - 125 - 220 V- the basis of preset and adjustable time settings.
Ua: 100 - 110 - 125 - 220 V ~ 50 … 60 Hz
Power consumption: approx. DC 10 W
Characteristics
approx. AC 11 VA
Ua: 100 - 110 V ~ 50 … 60 Hz
Maximum service tolerance: 110% Ua
Power consumption: approx. AC 10 VA
Voltage for readiness closing: > 85% UN
Service tolerances: 110% Ua
Trip voltage: 30 … 70% Ua
Voltage for readiness closing: > 70% Ua
Operating time: immediate
Trip voltage: < 70% Ua
Admissible maximum operating time: none
a) standard: operating time 0.5... 4 s, adjustable in 0.5 s steps
b) when closing is performed by means of auxiliary contacts:
operating time is 0.5... 2s, adjustable in 0.5s steps with
suitable coil
Admissible maximum operating time: none
90 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Optional accessories
6 Opening solenoid -MO3 (-Y7) 7 Auxiliary contacts of circuit breaker -BS1,
Use of the overcurrent release may be advisable in -BB1, -BB2, -BB3 (S1, S3, S4, S5)
systems where the auxiliary voltage is unable to The circuit breaker can be equipped with five-pole
provide reliable continuity of service. auxiliary contacts for monitoring, interlocking and
The release must receive the opening pulse on the signaling. Auxiliary contact -BB2 (-S4) is part of the
basis of the current from the secondary winding of basic equipment of all circuit breakers with motor-
an intermediate current transformer or a delayed driven operating mechanisms.
overvoltage relay. Auxiliary contact -BB3 (-S5) is optional.
During continuous service, the secondary winding Also consult the circuit-diagram.
of the MO3 is short-circuited by an auxiliary
contact. Characteristics
Ua: 24 (*) … 250 V
Characteristics Test voltage: 2.5 kV
Power consumption in connection to 2 phases 35 VA Rated current: Ith2 = 10 A
continuous service mode: connection to 3 phases 2 VA (*) For application at 24Vdc and with currents lower than 10 mA
Trippping power consumption: approx. 15 VA golden contacts are recommended.
Readiness tripping: 70% IN
Power consumption of
intermediate current Winding A 1 VA
transformer at IN = 5 A and Winding B 1 VA
continuous operation (short- Winding C 1.5 VA
circuited secondary winding):
Power consumption of
intermediate current Winding A 15 VA
transformer at IN = 5 A and Winding B 15 VA
continuous operation (open Winding C 25 VA
secondary winding):
Primary current of intermediate
3x5
current transformer:
Secondary current of
intermediate current ~ 0.4 A
transformer:
DI ST RI BUT I ON S OLUT I ON S 91
8 Auxiliary contact for signaling effective 9 Transmitted contacts in truck -BT1, -BT2
opening -BB4 (-S7) (-S8, -S9)
Auxiliary contact -BB4 (-S7), also known as The auxiliary contacts signal whether the circuit
transient contact, is part of the basic equipment breaker is racked in or out.
of all circuit breakers. In the intermediate position, the circuit breaker is
It is used for signaling effective opening of the mechanically interlocked.
circuit breaker (the transient signal lasts 30ms).
Characteristics
Characteristics Ua: 24 (*) … 250 V
Ua: 24 (*) … 250 V Test voltage: 2.5 kV
Test voltage: 2.5 kV Rated current: Ith2 = 10 A
Rated current: Ith2 = 10 A (*) For application at 24Vdc and with currents lower than 10 mA
golden contacts are recommended.
(*) For application at 24Vdc and with currents lower than 10 mA
golden contacts are recommended.
92 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Selection and ordering
Optional accessories
10 Motor-operated drive -MS (-M0) Properties of Gefeg motor
The spiral spring of circuit breakers with motor- Ua: 24 - 48 - 60 - 110 - 125 - 220 - 240 V-
operated drive is automatically loaded by an Ua: 110 - 240 V ~ 50 … 60 Hz
electric motor installed in the actual drive on the Loading time: max. 15 s
load side of each closing operation. Reloading time: max. 15 s
Service tolerances: 85 … 110% Ua
Power consumption app. DC 130 … 140 W;
Characteristics during loading: app. AC 150 – 170 VA
Ua: 24 - 30 - 48 - 60 - 110 - 125 - 220 - 240 V- Weight: 1.5 kg
Ua: 110 - 240 V ~ 50 … 60 Hz
Loading time: max. 15 s
Fuse motor:
Reloading time: max. 15 s
rated supply power Fuse motor loading time
Service tolerances: 85 … 110% Ua voltage consumption (ABB-Stotz (maximum)
Power consumption approx. DC 230 … 260 W; mcb)
during loading: approx. AC 260 VA V VA/W A S
Weight: 1.5 kg AC 110 150 1.6 S 281 UC-K 15
220 150 0.75 15
Fuse motor: 240 170 0.75 15
rated supply power Fuse motor loading time DC 24 130 4.0 S 282 UC-K 15
voltage consumption (ABB-Stotz (maximum) 48 130 3.00 15
mcb)
60 130 2.00 15
V VA/W A S
110 140 1.00 / 1.60 * 10
AC 110 260 1.6 S 281 UC-K 10
125 160 1.00 / 1.60 * 15
220 260 0.75 10
220 140 0.75 15
240 260 0.75 10
240 150 0.75 15
DC 110 230 1.60 10
* VD4 63 kA motor
125 260 1.60 10
220 240 0.75 10
240 260 0.75 10
24 15
30 15
48 15
60 15
DI ST RI BUT I ON S OLUT I ON S 93
Characteristics
Ua: 24 - 30 - 48 - 60 - 110 - 125 - 220 - 240 V-
Ua: 100 - 110 - 125 - 220 - 230 - 240 V ~ 50 … 60 Hz
Service tolerances: DC; AC 85 … 110% Ua
Power consumption: approx. DC 10 W;
approx. AC 10 VA
Admissible maximum
unlimited
operating time:
94 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Specific product characteristics
Vibration resistance
VD4 circuit breakers are designed to provide high
levels of resistance to stress caused by mechanical
vibrations.
Many versions comply with the type-approval
criteria of the major International Shipping
Registers (DNV, Lloyd’s Register, RINA) and the
qualification criteria of the International Seismic
Standards (IEEE 344, IEEE 323 and IEC 60980).
Please contact us if you wish to know which
versions have been type-approved by the shipping
registers.
Tropicalization
VD4 circuit breakers are manufactured in
compliance with the most stringent specifications
concerning their use in hot-humid-saline climates.
All the more important metal parts are treated
against corrosive substances in compliance with
atmospheric corrosivity class C5 of standard BS
EN 12500.
Galvanizing treatment is applied in accordance
with ISO 2081 Standards, classification code
Fe/Zn 12, thickness 12x10-6 m, protected by a
conversion layer formed mainly by chromates in
compliance with ISO 4520 Standards.
DI ST RI BUT I ON S OLUT I ON S 95
Altitude
The insulating property of air decreases as the
altitude increases, therefore this must always be
considered with regard to the external insulation
of the apparatus (the internal insulation of the
interrupters is not liable to change since it is
guaranteed by the vacuum).
Altitude must always be taken into account when
the insulating components of apparatus to be
installed over 1000 m above sea level is designed.
In these cases a correction coefficient must be
applied. This can be found from the graph on the
next page, which has been created on the basis of
the indications in Standard IEC 62271-1.
The following example provides a clear
interpretation of the indications given above.
Graph for determining the Ka correction factor according to altitude, Example (IEC):
—
Specific product characteristics
Environmental protection
programme
VD4 circuit breakers are manufactured in
accordance with the ISO 14000 Standards
(Guidelines for environmental management).
The production processes are implemented in
accordance with the environmental protection
standards as to the reduction of energy
consumption and the production of waste.
All this is achieved thanks to the environmental
management system applied in the medium
voltage apparatus manufacturing facility.
Assessment of the environmental impact during
the life-cycle of the product obtained by reducing
the overall energy consumption and use of raw
• three user levels: “operator” (display only, with materials to the minimum, is put into effect during
free access by keeping this key pressed for at the design engineering stage through an accurate
least 5 sec.), “configurator” (same as the choice of materials, processes and packaging.
previous level) but also with authorization to set This to allow the products and components to be
the protection parameters (i.e. times and recycled to the utmost degree at the end of their
thresholds), and communication if present useful life.
(access limited by a password), “administrator”
(same as the previous levels), but also with Spare parts
authorization to set the password and configure • Shunt opening release
the basic settings of the device, such as the • Additional shunt opening release
rated current (access limited by a password) • Undervoltage release
• continuous display of the current on the most • Time-lag device for undervoltage release
highly loaded phase and of the earth current • Shunt closing release
• recording of the value of the currents which • Spring loading geared motor with electrical
caused the device to trip signaling of spring loaded
• storage of the number of openings carried out • Contact signaling geared motor protection
by the device circuit breaker open/closed
• event log (storage of the parameters described • Contact signaling closing spring loaded/
above in the last 5 trips of the device) in a non- discharged
volatile memory • Transient contact with momentary closing
• curves “ß = 1” or “ß = 5” and curve “RI” specifically during circuit breaker opening
designed for the Belgian market (only REF 601 • Circuit breaker auxiliary contacts
IEC) • Locking electromagnet on the operating
• circuit breaker opening by means of an mechanism
undervoltage release (only REF 601 CEI) • Position contact of the withdrawable truck
• version, on request, with RS485 4-wire serial • Contacts signaling connected/isolated
communication • Opening solenoid
• MODBUS RTU full duplex protocol • Open position key lock
• multi-voltage feeder 24 … 240 V AC- DC • Isolation interlock with door
• REF 601 is also available in a version specifically • Protection for opening pushbutton
designed for the Italian market to CEI 0-16 • Protection for closing pushbutton
standards (see brochure entitled “Solutions for • Locking electromagnet on withdrawable truck
upgrading to CEI 0-16 standards”) , with 80 or • Set of six isolating contacts.
250 A rated current which can be selected via the
keyboard. It is always supplied with 3 sensors for Ordering
installation on insulated MV cable, a 40/1 A ring- For availability and to order spare parts, please
type CT for homopolar protection and contact our Service department, specifying the
undervoltage release for the circuit breaker circuit breaker serial number.
opening operation.
98 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
52
TN 7405 32
12 kV
65
Ur
17.5 kV
205
115
205
630 A
30
16
Ir
451
1250 A
65
461
435
56
16 kA
52
20 kA
Isc
25 kA
56
31.5 kA 236 28
49 28 424
45 250 114 12
25 400
409
45 424 45
22
150 150
22
22
161
22
12
22
308
52
TN 7406 32
12 kV
Ur
17.5 kV
205
115
205
630 A
30
16
Ir
1250 A
461
451
435
56
16 kA
52
65
20 kA
Isc
25 kA
31.5 kA
24
296 28 424
345 44
49 28
22
25 520 45 250 114 12
22
409
45
424
210 210
22
160
22
45
12
22
52
32
12 kV
Ur
65
17.5 kV
205
205
115
630 A
30
16
Ir
475
461
451
1250 A
435
56
16 kA
52
65
14
20 kA
171
Isc
24
97
25 kA
5 236 28 424
31.5 kA 49 28 345 44
25 650
45 250 114 12
409
424
275 275
213 22 22
45
22
22
45
12
22
VD4
TN 2RDA043108
12 kV
Ur
17.5 kV
In 1250 A
Isc 40 kA
100 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
DETAIL A DETAIL B
SCALE 1 : 2 SCALE 1 : 2
(*) Fixing interchangeability with previous series (345 x 650). VD4 p210 PT2 12-17.5 kV 1250A-1600A 40kA EL free standing installation
600
VD4 323
459
4xM12 deep 25
TN 1VCD003440 300 130
2xM10 deep 20
12 kV
20
12
Ur 74
17.5 kV
12
32 20
20
1250 A 20
310
Ir 1600 A
610
2000 A
30
16
475
Isc 50 kA
435
56
237
171
24
77.5
2.5
135 116 28
2.5
156
40 165 28 31 172 142
520 404
428
210 210
22
12
750 459
VD4 398 4xM12 deep 25
130
TN 1VCD003441 375 2xM10 deep 20
20
12 kV
12
74
Ur
17.5 kV 32 20
12
20
20
1250 A
310
1600 A
Ir
610
30
16
2000 A
475
435
2500 A
56
Isc 50 kA
237
24
171
24
78
135 116 28
2.5
2.5
12
22
12
102 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
VD4
TN 1VCD000050
Ur 12 kV
Ir 1600 A
20 kA
Isc 25 kA
31.5 kA
TN 7407
Ur 12-17.5 kV
Ir 1600 A
A
20 kA
Isc 25 kA
31.5 kA
VD4
TN 7407
Ur 12-17.5 kV
Ir 2000 A
20 kA
25 kA
Isc
31.5 kA
40 kA
VD4
TN 7407
Ur 12 kV
Ir 2500 A
20 kA
25 kA
Isc
31.5 kA
40 kA
Operating
Type Pole Un In Isc Version for
Mechanism
P2 12-17.5kV 1600A-2000-2500A 20-25-31.5kA EL2
VD4 p.210 12-17.5kV 2000A 40kA EL3
12kV 2500A 40kA EL3
VD4 12/**/**/G p.210 12kV 1600A-2000-2500A 20-25-31.5kA EL2 free standing
P2 12-17.5kV 1600A-2000-2500A 20-25-31.5kA EL3 version
—
Overall dimensions
VD4
TN 7408
12 kV
Ur
17.5 kV
2000 A
Ir
2500 A
20 kA
25 kA
Isc
31.5 kA
40 kA
Operating Version
Type Poles UnType: In
Poles Un In Isc Isc Operating Mechanism: Version for:
12-17.5kV 1600-2000-2500A 20-25-31.5kA
Mechanism
EL2
for
VD4 p.275 P2
12-17.5kV 2000-2500A 40kA EL3
12-17.5kV 1600A-2000-2500A
12kV
20-25-31.5kA
1600-2000-2500A 20-25-31.5kA
EL2 EL2
VD4 p.275 P2 VD4 12/**/** G p.275 P2
12kV 2000-2500A 40kA EL3 FREE STANDING
12-17.5kV 2000-2500A
12-17.5kV 40kA
1600-2000-2500A 20-25-31.5kA EL3 EL3 INSTALLATION
VD4 p.275 PT2
12-17.5kV 2000-2500A 40kA EL3S
12kV
VD4 12/**/** G p.275
1600A-2000-2500A
PT2
12kV 20-25-31.5kA EL2
1600-2000-2500A 20-25-31.5kA EL3
VD4 12/**/**/G p.275 P2 12kV 2000-2500A 40kA EL3S
12kV 2000-2500A 40kA EL3 free
standing
12-17.5kV 1600A-2000-2500A 20-25-31.5kA EL3 version
VD4 p.275 PT2
12-17.5kV 2000-2500A 40kA EL3S
12kV 1600A-2000-2500A 20-25-31.5kA EL3
VD4 12/**/**/G p.275 PT2
(*) Fixing interchangeability with previous series (345 x 650). 12kV 2000-2500A 40kA EL3S
DI ST RI BUT I ON S OLUT I ON S 105
VD4
TN 1VCD000149
12 kV
Ur
17.5 kV
Ir 3150 A
20 kA
25 kA
Isc
31.5 kA
40 kA
Ur 74
17.5 kV
32
12
20
20
Ir 3150 A (*) 20
310
Isc 50 kA
636
30
16
475
435
56
237
171
24
24
2,5
135 172
2,5
116 28
69,5 270 64,5 225
30,5 165 28
404 24
689 31 428
275 275
22
12
—
Overall dimensions
VD4
TN 1VCD003945
12 kV
Ur
17 kV
1250 A
1600 A
Ir 2000 A
2500 A
3150 A (*)
Isc 63 kA
570
VD4 95
308
45
TN 7409
A
Ur 24 kV 2XM10 PROF.20
M12 PROF.25
32
630 A
Ir
1250 A
310
22
115
16 kA 22
631
Isc 20 kA
30
16
22
25 kA
475
435
56
282,5
171
DETAIL A
77,5
SCALE 1:2
24
210 210
160
DI ST RI BUT I ON S OLUT I ON S 107
570
VD4 95 85
308
TN 1VCD000172
40
4XM12 DEEP25
Ur 24 kV
32 2XM10 DEEP 20
630 A
Ir
12 12
1250 A
72
310
Isc 31,5 kA
647
22
31
475
435
72
56
16
282,5
DETAIL A
170
SCALE 1:2
77,5
24
45 250 114
296 28 344,5* 39*
49 28 409
424
25 520
210 210
160
700 95
VD4 22
45
373 2XM10 PROF.18
TN 7410 A 32
M12 PROF.25
Ur 24 kV
22
630 A
310
Ir 115
1250 A
631
30
16 kA
16
475
435
Isc 20 kA
282.5
25 kA
77.5
424
56
171
DETAIL A
SCALE 1:2
24
361 28
345* 44*
49 28
45 250 114 12
25 650 409
275 275
213
12
22
108 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
1600-2000A 2500A
VD4 700 95 95 20 20
TN 7411 373
2XM10 DEEP 20 4XM12 DEEP 25
Ur 24 kV
20
12
1600 A
310
Ir 2000 A
12
20
661
647
2500 A
30
16
475
435
16 kA
77,5
282,5
56
20 kA
171
Isc DETAIL A
25 kA 361 28
SCALE 1:2
24
345* 44*
31.5 kA 49 28
25 650 45 250 114
409
424
275 275
213
22
784
VD4
245
TN 1VYN300901-RF
Ur 36 kV R16 (INTERNAL)
1250 A
328
1600 A
Ir
2000 A
31,2
56,4
883,3
2500 A
20 kA
612
577,4
143,5
93,5
489,5
15,5
Isc 25 kA
111,5
307,5
31.5 kA
778
A 28 331
VD4 49 28 338
448
TN 1VYN300901-RF 796
470 22
Ur 38 kV
275 275 Auxiliary View A
1200 A 700
Ir
2000 A
34
Isc 31.5 kA
500,6
485
470
275
699
430
DI ST RI BUT I ON S OLUT I ON S 109
VD4
TN 2RDA043326A
Ur 40 kV
1250 A
Ir 1600 A
2000 A
20 kA
Isc 25 kA
31.5 kA
110 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
1000 62 390
VD4 TW
260
TN GCEM700198
Ur 36-40.5 kV
1250 A 360 360
A
Anschlussflächen/
1600 A Connecting planes
Ir
2000 A
2500 A
45
A
35
20 kA
M12
328
GA
max. 30 tief/deep
25 kA
Isc 40
31.5 kA
40
40 kA
1575
E-Cu 70
Schiene / band: 80x10
DIN 46433
900
M12 T
516
TE
200
5
925 405
1065 438
1105 435 60
555
535 75
685
DI ST RI BUT I ON S OLUT I ON S 111
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB1 modules
10
306
91
79
91
78
12 kV 306
Ur
17.5 kV
630 A
627
Ir
35
35
1250 A
626
619
16 kA
74
35 29
20 kA
Isc
23
25 kA 78
31.5 kA 25 320
19
23
370
503 14 P1 POLES 1250A
383 PT1 POLES 1250A
417 53
531
100
2
98
438 0
501 36
661
490
608
55
39
47
VD4/P
TN 2RDA032149
Ur 17.5 kV
630 A
Ir
1250 A
25 kA
Isc
31.5 kA
112 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
VD4/W
TN 7420
12 kV
Ur
17.5 kV
630 A
Ir
1250 A
16 kA
20 kA
Isc
25 kA
31.5 kA
VD4/P
TN 2RDA040163A
12 kV
Ur
17.5 kV
Ir 1250 A
Isc 40 kA
DI ST RI BUT I ON S OLUT I ON S 113
VD4/W
TN 1VCD601243
12 kV
Ur
17 kV
Ir 1250 A
Isc 40 kA
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB2 modules
VD4/P
1250A-1600A 1250A -1600A
TN 1VCD003284
12 kV
Ur
17.5 kV
1250 A
Ir
1600 A
Isc 40 kA
—
Overall dimensions
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB2 modules
1250 A
310 ±1
20
Ir 1600 A
79
691
688
2000 A
688
Isc 50 kA
478
26
280 ±1
165 ±1
25
12
19
76
605 25 320
19,5
4
21,5
14 653 14 4
650 370
640 0
29 360+2 49,5
626 ±2
34 383
550
416 53
36 554 ±1,5
210 ±1 210 ±1 643
29
590
360
303
23
12
DI ST RI BUT I ON S OLUT I ON S 115
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB2 modules
TN 7415
12 kV
Ur
17.5 kV
1600 A
Ir
2000 A
20 kA
Isc 25 kA
31.5 kA
VD4/P
TN 7415
12 kV
Ur
17.5 kV
Ir 2000 A
Isc 40 kA
1600A-2000A 20-25-31.5kA
VD4/P p.210 12-17.5kV
2000A 40kA PT2 EL PowerCube PB2 UniGear
—
Overall dimensions
VD4/P
TN 7416
12 kV
Ur
17.5 kV
1600 A
Ir
2000 A
20 kA
Isc 25 kA
31.5 kA
VD4/P
TN 7416
12 kV
Ur
17.5 kV
Ir 2000 A
Isc 40 kA
1600A 20-25kA
12kV
2000A 20-25-31.5kA
VD4/P XX.XX.XX.SA p.210 PT2 EL PowerCube PB2 UniGear
1600A 20-25kA
17.5kV
2000A 20-25-31.5kA
DI ST RI BUT I ON S OLUT I ON S 117
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB3 modules
TN 7417
12 kV
Ur
17.5 kV
Ir 2500 A
20 kA
25 kA
Isc
31.5 kA
40 kA
—
Overall dimensions
P2 POLE
842 119
VD4/P
135 144 217,5 25 111 16
TN 1VCD003445
10
12 kV
Ur
17.5 kV
433
122
310 ±1
1600 A
Ir 20
2000 A
79
691
688
688
Isc 50 kA
478
280 ±1
26
165 ±1
25
19
76
805 4
25 320
12
19,5
4
21,5
4
14 853 14 370
850 0
836 29 360 + 2 49,5
806 ±2 34 383
750 416 53
36 554 ±1,5
643
275 ±1 275 ±1
29
590
360
303
12
22
DI ST RI BUT I ON S OLUT I ON S 119
842
VD4/P 143 217,5 25
119
110 16
TN 1VCD003446
10
12 kV
152
Ur
17.5 kV
Ir 2500 A
310 ±1
20
433
Isc 50 kA
109
691
688
688
478
280 ±1
27
164 ±1
25
19
12
75
805
25 320
4
19,5
21,5
4
14 853 14
370
850 0
836 29 360+2 49,5
806 ±2 34 383
750 417
36 554 ±1,5
643
275 ±1 275 ±1
29
588
360
303
4
22
11
—
Overall dimensions
10
118
12 kV
152
Ur
17.5 kV
20
310 ±1
Ir 3150 A (*) 433
109
Isc 50 kA
742
730
678
733
478
280 ±1
26
165 ±1
25
19
76
805 4
25 320
19,5
21,5
4
12
4
14 853
370
850 0
29 360+2 49,5
836
34 383
806 ±2
750 416 53
36 554 ±1,5
643
275 ±1 275 ±1
189
29
589
360
303
12
22
842 119
VD4/W 361 25 240 111 16
130
TN 1VCD003596 30
10
12 kV
152
118
Ur
17.5 kV
Ir 3150 A (*)
310 ±1
20
Isc 50 kA 433
109
742
742
730
678
732
478
280 ±1
26
165 ±1
25
19
76
805 25 320
19,5
21,5
4
12
4
4
14 853
370
850 0
836 29 360+2 49,5
806 ±2
34 383
750
416 53
36 554 ±1,5
643
275 ±1 275 ±1
189
29
588
360
303
4
22
12
VD4/P
TN 1VCD003943
12 kV
Ur
17 kV
1250 A
1600 A
Ir 2000 A
2500 A
3150 A (*)
Isc 63 kA
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB4 modules
636 119 23
VD4/P
44 232 19
20
TN 7413
98
630A 1250A
Ur 24 kV
79
79
630 A
Ir
310 ±1
1250 A 48
16 kA
35
771
35
782
770
Isc 20 kA
25 kA
71 38
325 ±1
197 ±1
25
72
25 320
4
653 14 370
383
650 0
458+ 2
641
303
610 ±2 36 710 ±1,5 53
210 ±1 210 ±1 799
746
55
122 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
842
VD4/P 119 23
144 232 19
TN 7414 630A 1250A
98
79
Ur 24 kV
20
79
630 A
Ir
310 ±1
1250 A 48
35
35
16 kA
775
770
788
Isc 20 kA
25 kA
325 ±1
71 38
197 ±1
25
72
25 320
4
4
853 14 370
383
850 0
458 + 2
836
303 53
805 ±2
36 710 ±1,5
275 ±1 275 ±1
799
746
55
53
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB4 modules
636
119 23
VD4/P 44 232 19
20
TN 1VCD000173
Ur 24 kV
79
49 28
Ir 1250 A
36 28 48
Isc 31.5 kA
310
35
775
770
770
71
31
16
56
326
213
197
72
25 320
4
4
653 13.5
303 53
650
370
641
383
610
458
800
210 210
747
55
119
19
DI ST RI BUT I ON S OLUT I ON S 123
842
VD4/P 144 232 23
TN 1VCD000174
98
20
Ur 24 kV 49 28
79
36 28
Ir 1250 A
48
Isc 31.5 kA
310±1
790
775
770
35
31
16
325 ±1
56,5
197±1
213
72
853 14 25 320
4
4
850 370
836 383
805 ±2 458±2
303 53
36 710 ±1,5
799
275 ±1 275 ±1
746
55
119
53
Withdrawable circuit breakers for UniGear ZS1 switchgear and PowerCube PB5 modules
Ur 24 kV
1600 A
310 ±1
Ir 2000 A
79
834
2500 A (1)
817
810
16 kA
345 ±1
20 kA
Isc
197 ±1
45
25 kA
72
31.5 kA 25 320
4
4
853 14 370
850 383 46
836 303
0
805 ±2 36,011 458 +2
275 ±1 275 ±1 696 ±1,5 53
784
732
55
52
(1) 2300 A rated uninterrupted current is guaranteed with natural ventilation. 2500 A rated uninterrupted current is guaranteed with forced ventilation.
124 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
842
VD4/P 141 233
TN 1VCD000177
49 28
Ur 24 kV 36 28
166
3150 A
Isc 31.5 kA
310
109
834
817
810
31
16
56
345
233
853 14 25 320 46
4
4
850 370
836
805 383
303
458 53
787
275 275
734
55
119
52
Withdrawable circuit breakers for UniGear ZS2 switchgear and Powerbloc modules
842
VD4/W 784
144
TN 1VYN300901-KG 28
36 164
28 49
Ur 36 kV 21
35
Ir 1250 A
20 kA
Isc 25 kA
380
31.5 kA
974
953
941
56 30
329
16
480
350
42
72 125
197
750 25 320
18
21,5
19,5
4
4
4 750
853 14 370
880 383 52
417
851
461
837
736
275 275
55
46
DI ST RI BUT I ON S OLUT I ON S 125
Withdrawable circuit breakers for UniGear ZS2 switchgear and Powerbloc modules
842
VD4/W
784
TN 1VYN300901RA 144
49
164
Ur 36 kV 36 28
79
28 21
1600 A
Ir 2000 A
2500 A (*)
380
20 kA
Isc 25 kA
974
30
953
941
16
31.5 kA
329
56
480
350
72 125 42
197
25 320
750
4
19,5
4
18
4 750
21,5
853 14 370
52
880 383
851 417
837 461
275 275 736
is guaranteed with
natural ventilation.
2500 A rated
uninterrupted current
is guaranteed with
46
forced ventilation.
Isc 25 kA
31.5 kA
974
953
30
941
16
329
56
480
350
42
97 84
181
750 4
320
4
750
19,5
21,5
4
853 14
18
370
880
383 52
851 417
840 433
275 275 736
55
forced ventilation.
126 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
328
25 kA
Isc
31.5 kA
40 kA
1575
1294
900
TK
K
516
TP
10
10
760 430 60
905 445
945 520
535 85
695
DI ST RI BUT I ON S OLUT I ON S 127
91
TN 1VCD000092
Ur 12 kV
Ir 630 A
20 kA
205
35
Isc
25 kA
563
510
260
503
4
53
150 150
548
55
495
84
35
20 kA
Isc
25 kA
563
507
TN 1VCD000137
260
Ur 17.5 kV
630 A
Ir
1250 A
20 kA 503
Isc 53
25 kA
150 150
55
495
128 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
91
TN 1VCD000089
Ur 24 kV
Ir 630 A
310
16 kA
35
Isc 20 kA
680
25 kA
563
325
653
4 53
210 210
640
55
583
Ur 12 kV
Ir 630 A
20 kA
205
35
Isc
25 kA
563
510
260
153
503 195
4
486 380 53
150 150
640
55
584
DI ST RI BUT I ON S OLUT I ON S 129
303 50
VD4/Z8
TN 1VCD000138
Ur 24 kV
310 ±1
Ir 1250 A
16 kA
Isc 20 kA
25 kA
677
35
325 ±1
25,5
210 ±1 210 ±1
4
548 ±0,5 53
587
640
55
587
VD4/ZT8 530
486 303 52
TN 1VCD000134 455
Ur 12 kV
Ir 1250 A
20 kA
Isc
205
98
25 kA
35
563
514
VD4/ZT8
TN 1VCD000134
260
153
Ur 17.5 kV
630 A
Ir
1250 A 503 195
4
20 kA 486 383 53
Isc 150 150 637
25 kA
55
583
130 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
310
16 kA
35
Isc 20 kA
680
25 kA
563
325
653 195
4
636
380 53
210 210
640
55
585
Ir 1250 A
310
16 kA
84
35
Isc 20 kA
677
25 kA
563
325
653
4
195
636
210 210 380 53
640
55
587
DI ST RI BUT I ON S OLUT I ON S 131
91
Ur 12 kV
5
Ir 630 A
20 kA
205
Isc
35
25 kA
563
524
510
260
153
86
69
4
195
503
486 380 53
150 150 640
55
584
67
Ir 1250 A
20 kA
98
205
Isc
35
25 kA
563
524
514
260
153
86
69 195
4
503 380 53
486 637
150 150
55
583
67
132 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Overall dimensions
VD4/ZS8 681
3 303 52
636
TN 1VCD000088
91
Ur 24 kV 611
Ir 630 A
310
16 kA
35
Isc 20 kA
680
25 kA
563
524
325
86
69
4
653 195
636 380 53
640
210 210
55
583
67
TN 1VCD000135
Ur 24 kV 611
Ir 1250 A
310
16 kA
84
35
Isc 20 kA
677
25 kA
563
524
325
86
69
4
195
653
636 380 53
640
210 210
55
587
67
DI ST RI BUT I ON S OLUT I ON S 133
626 ±1 121 ±1
VD4/Sec 604 149 41
630A 1250A
79
TN 1VCD000190
45°
3
Ur 24 kV
630 A
Ir
1250 A
310 ±1
A
16 kA
35
35
Isc 42
739
20 kA
435 ±1
38
325 ±1
18
25 320
4
653 14
370
23
650 383
303
36.3
415
648 ±1.5 53
742 DETAIL A
210 ±1 210 ±1
55
134 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Electric circuit diagram
Thermal effect Exposed conductive part, Capacitor (general Passing make contact
frame symbol) closing momentarily
during release
Pushbutton control Terminal or clamp Make contact Power circuit breaker with
automatic opening
—
Electric circuit diagram
DI ST RI BUT I ON S OLUT I ON S 137
138 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Electric circuit diagram
Incompatibility Notes
The circuits indicated in the following figures cannot be A) The circuit breaker is equipped solely with the
supplied at the same time in the same circuit breaker: applications specified in the order confirmation.
5-6-66 7-67 9-69 31-91 Consult this catalog for information about how to make
32-92 33-93 10-11 out an order.
B) The undervoltage release can be supplied for energizing
with voltage derived from the supply side of the circuit
breaker or from an independent source.
Circuit breaker closing is only allowed when the release is
energized (closing lock is obtained mechanically). If there
is the same power supply for the shunt closing and
under-voltage releases and the circuit breaker must close
automatically when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage release’s
enabling instant and energizing of the shunt closing
release.
lncompatible with -MBO4.
C) Check power of auxiliary circuit to find out whether
several motors for loading the closing springs can be
started at the same time. To prevent excessive power
draw, the springs must be loaded by hand before the
auxiliary circuit is powered.
D) The circuit for monitoring the continuity of the release
winding must only be used for that purpose. The SOR
Test Unit can be used for checking the continuity of the
various different releases.
-MBO4 incompatible with -MBU.
-MBO4 not available for VD4 50 kA.
E) When fig. 6 is required, contact -BGB1 (23-24) of fig.32
is not available.
When fig. 7 is required, contact -BGB1 (3-4) of fig. 31 is
not available.
When fig. 9 is required, contact -BGB1 (7-8) of fig. 31 is
not available.
When fig. 32 is required, it is obligatory to supply the
auxiliary contacts of fig. 31.
When fig. 33 is required, it is obligatory to supply the
auxiliary contacts of fig. 32.
When fig. 66 is required, contact -BGB1 (23-24) of fig.
92 is not available.
When fig. 67 is required, contact -BGB1 (3-4) of fig. 91
is not available.
When fig. 69 is required, contact -BGB1 (7-8) of fig. 91
is not available.
When fig. 92 is required, it is obligatory to supply the
auxiliary contacts of fig. 91.
When fig. 93 is required, it is obligatory to supply the
auxiliary contacts of fig. 92.
Figs. 33 and 93 are not available for VD4 50 kA.
F) Figs. 10 and 11 are only available for VD4 up to 31.5 kA.
G) The energizing voltage must be the same for both
signals.
140 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Electric circuit diagram
Electric circuit diagram of 36-40.5 kV fixed circuit breakers with Classic operating
mechanism 1VCD400231
The electric circuit diagram in this section concerns 36 - 40.5 kV fixed circuit breakers with Classic operating mechanism.
DI ST RI BUT I ON S OLUT I ON S 141
142 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Electric circuit diagram
-BER = Device for the supervision of shunt opening Fig. 3 = Locking magnet on the operating mechanism.
release coil continuity (see note E) If de-energized it prevents the c. breaker
closing
-BGB1,..., = Circuit breaker auxiliary contacts
-BGB3 Fig. 4 = Locking magnet on the truck. If de-energized it
prevents the c. breaker racking-in and racking-
-BGB4 = Auxiliary passing contact (closing
out mechanically.
momentarily when circuit breaker opens)
Fig. 5 = Instantaneous undervoltoge release
-BGB12 = Auxiliary contact for block closing of the
circuit breaker Fig. 7 = First shunt opening release circuit with
-BGK = Contact operated by the key lock preventing possibility of permanent supervision of coil
the c. breaker closing continuity (see note E)
-BGS = Umit switch signalling closing springs Fig. 9 = Second shunt opening release circuit with
charged or discharged possibility of permanent supervision of coil
continuity (see note E)
-BGT1 = Contacts signalling c. breaker in the
connected position Fig. 10 = Indirect overcurrent relay
-BGT2 = Contacts signalling c. breaker in the isolated Fig. 26 = Contact signalling charged or discharged
position closing springs (see note I)
-MAS = Motor for the closing charging springs Fig. 30 = Wiping contact 35ms for C.B. tripped
(see note C) indication
-MBC = Shunt closing release Fig. 32 = C. breaker available auxiliary contacts
-MB01 = First shunt opening release (see note E) Fig. 44 = Ventilation circuit
—
Electric circuit diagram
—
Electric circuit diagram
DI ST RI BUT I ON S OLUT I ON S 147
—
Electric circuit diagram
Incompatibility Notes
The circuits indicated in the following figures cannot be A) Circuit breaker is equipped solely with the applications
supplied at the same time in the same circuit breaker: specified in the order confirmation. Consult this catalog
3-4 3-33-34 4-31-32 5-6 10-11 for information about how to make out an order.
31-32-33-34 31-32-52 33-34-51 51-52 B) The undervoltage release can be supplied for
energizing with voltage derived from the supply side of
the circuit breaker or from an independent source.
Circuit breaker closing is only allowed when the release
is energized (closing lock is obtained mechanically). If
there is the same power supply for the shunt closing
and undervoltage releases and the circuit breaker must
close automatically when auxiliary voltage returns,
there must be a 50 ms delay between the undervoltage
release’s enabling instant and energizing of the shunt
closing release.
Incompatible with -MBO4.
C) Check power of auxiliary circuit to find out whether
several motors for loading the closing springs can be
operated at the same time. To prevent excessive power
draw, the springs must be loaded by hand before
auxiliary circuit is powered.
D) The circuit for monitoring the continuity of the release
windings must only be used for that purpose. The SOR
Test Unit can be used for checking the continuity of the
various different releases:
-MBO4 incompatible with -MBU.
-MBO4 not available on Vmax and VD4 50kA.
E) When fig. 6 is required, contact -BGB1 (23-24) of
fig. 32-34 is not available.
When fig. 7 is required, contact -BGB1 (3-4) of
fig. 31-32-33-34 is not available.
When fig. 9 is required, contact -BGB1 (7-8) of
fig. 31-32-33-34 is not available.
When fig. 10 or 11 are required, contact -BGB1 (31-32)
of fig. 32 and 34 is not available.
When fig. 30 is required, contact -BGB1 (25-26) of
fig. 32 and 34 is not available.
F) The contacts for electrical signaling of circuit breaker in
isolated and racked-in position (-BGT1 and BGT2)
shown in fig. 51-52 are installed on circuit breaker truck
(movable part).
G) Fig. 3 is supplied when fig. 31 or 32 are required.
Fig. 4 is supplied when fig. 33 or 34 are required (in this
case, it is obligatory to supply –BGT3).
H) Fig. 10 is only available for VD4 up to 31.5 kA and Vmax.
Fig. 11 is only available for VD4 up to 31.5 kA.
I) The energizing voltage must be the same for both
signals.
DI ST RI BUT I ON S OLUT I ON S 149
—
Electric circuit diagram
DI ST RI BUT I ON S OLUT I ON S 151
152 V D 4 - MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS 1 2...40.5 kV - 63 0...4000 A - 16...63 kA
—
Electric circuit diagram
DI ST RI BUT I ON S OLUT I ON S 153
—
Electric circuit diagram
Incompatibility Notes
The circuits indicated in the following figures cannot be A) The circuit breaker is equipped solely with the
supplied at the same time in the same circuit breaker: applications specified in the order confirmation. Consult
3-4 3-33-34 4-31-32 5-6 10-11 this catalog for information about how to make out an
order.
31-32-33-34 31-32-52 33-34-51 51-52
B) The undervoltage release can be supplied for energizing
with voltage derived from the supply side of the circuit
breaker or from an independent source.
Circuit breaker closing is only allowed when the release is
energized (closing lock is obtained mechanically). If there
is the same power supply for the shunt closing and
under-voltage releases and the circuit breaker must close
automatically when auxiliary voltage returns, there must
be a 50 ms delay between the undervoltage release’s
enabling instant and energizing of the shunt closing
release.
Incompatible with -MBO4.
C) Check power of auxiliary circuit to find out whether
several motors for loading the closing springs can be
operated at the same time. To prevent excessive power
draw, springs must be loaded by hand before auxiliary
circuit is powered.
D) The circuit for monitoring the continuity of the release
windings must only be used for that purpose. The SOR
Test Unit can be used for checking the continuity of the
various different releases.
-MBO4 incompatible with -MBU.
E) When fig. 6 is required, contact -BGB3 (41-42) of fig. 32-
34 is not available.
When fig. 9 is required, contact -BGB1 (43-44) of fig. 31-
32-33-34 is not available.
When fig. 10 or 11 are required, contact -BGB3 (31-32) of
fig. 32 and 34 is not available.
When fig. 30 is required, contact -BGB3 (53-54) of fig. 32
and 34 is not available.
F) The contacts for electrical signaling of circuit breaker in
racked-in and isolated positions (-BGT1 and -BGT2)
shown in fig. 51-52 are located on circuit breaker truck
(moving part).
G) Fig. 3 is supplied when fig. 31 or 32 are required. Fig. 4 is
supplied when fig. 33 or 34 are required (in this case, it is
obligatory for -BGT3 to be supplied).
H) Fig. 10 is only available for VD4 up to 31.5 kA.
Fig. 11 is only available for VD4 up to 31.5 kA.
l) The energizing voltage must be the same for both
signals.
DI ST RI BUT I ON S OLUT I ON S 155
—
Electric circuit diagram
DI ST RI BUT I ON S OLUT I ON S 157
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
—
More product information:
abb.com/mediumvoltage