You are on page 1of 14

This article has been accepted for inclusion in a future issue of this journal.

Content is final as presented, with the exception of pagination.

IEEE TRANSACTIONS ON SMART GRID 1

Hierarchical Structure of Microgrids Control System


Ali Bidram, Student Member, IEEE, and Ali Davoudi, Member, IEEE

Abstract—Advanced control strategies are vital components for


realization of microgrids. This paper reviews the status of hierar-
chical control strategies applied to microgrids and discusses the fu-
ture trends. This hierarchical control structure consists of primary,
secondary, and tertiary levels, and is a versatile tool in managing
stationary and dynamic performance of microgrids while incor-
porating economical aspects. Various control approaches are com-
pared and their respective advantages are highlighted. In addition,
the coordination among different control hierarchies is discussed.
Index Terms—Hierarchical control strategies, inverters, micro-
grid, primary control, secondary control, tertiary control.

I. INTRODUCTION

C ONVENTIONAL electric power systems are facing


continuous and rapid changes to alleviate environmental
concerns, address governmental incentives, and respond to the
consumer demands. The notion of the smart grid has recently
emerged to introduce an intelligent electric network. Improved
reliability and sustainability are among desired characteristics
of smart grid affecting the distribution level. These attributes
are mainly realized through microgrids which facilitate the
effective integration of Distributed Energy Resources (DER)
[1]–[6]. Microgrids can operate in both grid-connected and
islanded operating modes. Proper control of microgrid is a
prerequisite for stable and economically efficient operation
[6]–[13]. The principal roles of the microgrid control structure
are [12]–[22]:
• Voltage and frequency regulation for both operating
modes;
• Proper load sharing and DER coordination; Fig. 1. Hierarchical control levels of a microgrid.
• Microgrid resynchronization with the main grid;
• Power flow control between the microgrid and the main
grid; undesired circulating currents. This primary control level in-
• Optimizing the microgrid operating cost. cludes fundamental control hardware, commonly referred to as
These requirements are of different significances and time zero-level, which comprises internal voltage and current control
scales, thus requiring a hierarchical control structure [12] loops of the DERs. The secondary control compensates for the
to address each requirement at a different control hierarchy. voltage and frequency deviations caused by the operation of
Hierarchical control strategy consists of three levels, namely the primary controls. Ultimately, the tertiary control manages
the primary, secondary, and tertiary controls, as shown in the power flow between the microgrid and the main grid and
Fig. 1. The primary control maintains voltage and frequency facilitates an economically optimal operation [12], [13].
stability of the microgrid subsequent to the islanding process. Given the large body of published work on microgrid con-
It is essential to provide independent active and reactive power trol, a thorough survey on existing approaches would be of para-
sharing controls for the DERs in the presence of both linear and mount value. This paper is an attempt to bring together different
nonlinear loads. Moreover, the power sharing control avoids control methods for each control hierarchy and address the fu-
ture trends. This paper is intended to provide a comprehensive
and solid knowledge of the microgrid control for the researchers
Manuscript received November 30, 2011; revised March 16, 2012; accepted
April 09, 2012. This material is based in part upon work supported by the Na- and practicing engineers working in the field. Due to the sub-
tional Science Foundation under Grant 1137354. Paper no. TSG-00664-2011. stantial technical challenges in the primary control, most of the
The authors are with the Renewable Energy and Vehicular Technology Lab- published works have focused on this control hierarchy. Ad-
oratory, University of Texas, Arlington, TX 76011 USA (e-mail: davoudi@uta.
edu). vantages and disadvantages of different methods are determined
Digital Object Identifier 10.1109/TSG.2012.2197425 and compared.

1949-3053/$31.00 © 2012 IEEE


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE TRANSACTIONS ON SMART GRID

Fig. 3. Reference voltage determination for voltage control mode [17].

Fig. 2. PQ control mode with active and reactive power [17].

II. HIERARCHICAL CONTROL LEVEL I: PRIMARY CONTROL


Fig. 4. Voltage and current control loops in voltage control mode [28].
The primary control is designed to satisfy the following re-
quirements [12], [13], [15], [21], [23]:
• To stabilize the voltage and frequency. Subsequent to an is-
landing event, the microgrid may lose its voltage and fre-
quency stability due to the mismatch between the power
generated and consumed.
• To offer plug and play capability for DERs and properly
share the active and reactive power among them, prefer-
ably, without any communication links.
• To mitigate circulating currents that can cause over-current
phenomenon in the power electronic devices and damage
the DC-link capacitor.
The primary control provides the reference points for the
voltage and current control loops of DERs. These inner control
loops are commonly referred to as zero-level control. The zero-
level control is generally implemented in either PQ or voltage
control modes [17].
In the PQ control mode, the DER active and reactive power
delivery is regulated on the pre-determined reference points, as
shown in Fig. 2. The control strategy is implemented with a cur-
rent-controlled voltage source converter (VSC). In Fig. 2,
controller regulates the DC-link voltage and the active power
through adjusting the magnitude of the output active current
of the converter, . controller regulates the output reactive
power by adjusting the magnitude of the output reactive current,
i.e., [17], [24].
In the voltage control mode, the DER operates as a voltage- Fig. 5. Zero-level control loops for a set of energy sources connected to an AC
controlled VSC where the reference voltage, , is determined bus [28].
by the primary control, conventionally via droop characteris-
tics [17], as shown in Fig. 3. The nested voltage and frequency
control loops in the voltage control mode are shown in Fig. 4. this figure, denotes the transfer function of a low-pass
This controller feeds the current signal as a feedforward term filter. Each converter has an independent current control loop,
via a transfer function (e.g., virtual impedance). To fine-tune the and a central voltage control loop that is adopted to distribute
transient response, proportional-integral-derivative (PID) [25], the fundamental component of the active and reactive powers
adaptive [26], and proportional resonant controllers [27] are among different sources. The reference point for the voltage
proposed for the voltage controller. control loop is determined by the primary control. The indi-
Power quality of small-scale islanded systems is of particular vidual current controllers ensure power quality by controlling
importance due to the presence of nonlinear and single-phase the harmonic contents of the supplied currents to the common
loads and the low inertia of the microgrid [28]–[30]. To im- AC bus [28].
prove the power quality for a set of energy sources connected to The DER’s control modes are usually implemented using the
a common bus, the control structure shown in Fig. 5 is used. In active load sharing and droop characteristic techniques [31].
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

BIDRAM AND DAVOUDI: HIERARCHICAL STRUCTURE OF MICROGRIDS CONTROL SYSTEM 3

Fig. 7. Simplified diagram of a converter connected to the microgird.

Fig. 6. Conventional droop method. (2)

A. Active Load Sharing If the effective line impedance, , is assumed to be purely


inductive, , then (2) can be reduced to
The active load sharing is a communication-based method
used in parallel configuration of converters. Current or ac-
tive/reactive power reference point is determined through (3)
different approaches such as centralized [32], master-slave
[33], average load sharing [34], [35], and circular chain control
methods [36]. In a centralized control method, the overall load
If the phase difference between the converter output voltage
current is evenly distributed among the sources by assigning the
and the common AC bus, , is small enough, then,
same current set points for all converters. In the master-slave
and . Thus, one can apply the frequency and voltage
control, the master converter operates as a VSC and regulates
droop characteristics to fine-tune the voltage reference of the
the output voltage while the slave converters behave as indi-
VSC [31], [38]–[43], as shown in Fig. 6 based on
vidual current source converters that follow the current pattern
of the master converter. In the average load sharing control, (4)
the current reference for individual converters is continuously
updated as the weighted average current of all converters (but
where and are the DER output voltage RMS value and
not the load current). In the circular chain control, converter
angular frequency at the no-load, respectively. The droop co-
modules are considered to be connected like links of a chain,
efficients, and , can be adjusted either heuristically or
and the current reference for each converter is determined by
by tuning algorithms (e.g., particle swarm optimization [44]).
that of the previous converter [37]. The active load sharing
In the former approach, and are determined based on
method requires communication links and high bandwidth
the converter power rating and the maximum allowable voltage
control loops. However, it offers precise current sharing and
and frequency deviations. For instance, in a microgrid with
high power quality [31].
DERs, corresponding and should satisfy following con-
straints [45], [46]
B. Droop Characteristic Techniques
(5)
The droop control method has been referred to as the inde-
pendent, autonomous, and wireless control due to elimination where and are the maximum allowable angular
of intercommunication links between the converters. The con- frequency and voltage deviations, respectively. and are
ventional active power control (frequency droop characteristic) the nominal active and reactive power of the th DER.
and reactive power control (voltage droop characteristic), those During the grid-tied operation of microgird, the DER voltage
illustrated in Fig. 6, are used for voltage mode control. and angular frequency, and , are enforced by the gird. The
Principles of the conventional droop methods can be ex- DER output active and reactive power references, and
plained by considering an equivalent circuit of a VSC connected , can hence be adjusted through and [17] as
to an AC bus, as shown in Fig. 7. If switching ripples and high
frequency harmonics are neglected, the VSC can be modeled
as an AC source, with the voltage of . In addition, assume (6)
that the common AC bus voltage is and the converter
output impedance and the line impedance are lumped as a
single effective line impedance of . The complex power Dynamics response of the conventional primary control, on
delivered to the common AC bus is calculated as the simplified system of Fig. 7, can be studied by linearizing (3)
and (4). For instance, the linearized active power equation in (3)
(1) and frequency droop characteristic in (4) are

(7)
from which the real and reactive powers are achieved as
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE TRANSACTIONS ON SMART GRID

Fig. 8. Small-signal model of the conventional active power control. Fig. 9. The small signal model of the adjustable active power control [47].

where at the operating point of , and 1) Adjustable Load Sharing Method: In this technique,
the time constant of the proposed active and reactive power
controllers can be adjusted without causing any impact on the
(8) DER voltage and frequency [47]. The proposed active power
controller uses the conventional controller in (4); however, the
and phase angle of the VSC, , in Fig. 7 is determined by
(9)
(11)
Therefore, the small-signal model for the active power control
in (4) is where is an integral gain. Given (11), the small signal model
of the proposed controller can be derived as
(10)
(12)
A similar procedure can be adopted to extract the small signal
model of the reactive power control. where is defined in (8). Block diagram of this model is illus-
The block diagram of the small-signal model for the active trated in Fig. 9. The eigenvalue of the linearized control system
power control of (4) is demonstrated in Fig. 8. As seen in (10), of (12) is
time constant of the closed loop control can only be adjusted by (13)
tuning . On the other hand, as seen in (4), also affects the
DER frequency. Thus, a basic tradeoff exists between the time Equation (13) shows this eigenvalue depends on the inte-
constant of the control system and the frequency regulation. gral gain, , and the droop coefficient, . Therefore, the
As opposed to the active load sharing technique, the conven- closed loop time constant can be directly adjusted by tuning .
tional droop method can be implemented with no communica- Since is remained intact, the resulting frequency of the ac-
tion links, and therefore, is more reliable. However, it has some tive power control in (4) will no longer be affected by the con-
drawbacks as listed below: troller time constant adjustment.
• Since there is only one control variable for each droop char- Similarly, at the operating point of , and the
acteristic, e.g., for frequency droop characteristic, it small-signal control for the reactive power control in (4) can
is impossible to satisfy more than one control objectives. be found by perturbing (3) and (4)
As an example, a design tradeoff needs to be considered
between the time constant of the control system and the (14)
voltage and frequency regulation [47], [48].
• The conventional droop method is developed assuming
highly inductive effective impedance between the VSC where
and the AC bus. However, this assumption is challenged
in microgrid applications since low-voltage transmission (15)
lines are mainly resistive. Thus, (3) is not valid for micro-
grid applications [12], [45]. As seen in (14), is a linear function of a reference signal,
• As opposed to the frequency, the voltage is not a global . Since is a function of , line impedance, and the op-
quantity in the microgrid. Thus, the reactive power control erating point, performance of the conventional reactive power
in (4) may adversely affect the voltage regulation for crit- control in (4) tightly depends on the microgrid operational pa-
ical loads [45]. rameters. In the adjustable reactive power sharing method, an
• In case of nonlinear loads, the conventional droop method integral controller is used that regulates the common bus voltage
is unable to distinguish the load current harmonics from in Fig. 7, , to match a reference voltage, [47]
the circulating current. Moreover, the current harmonics
distorts the DER output voltage. The conventional droop (16)
method can be modified to reduce the total harmonic dis-
tortion (THD) of the output voltages [49]–[52]. where is the integral gain and
These potential drawbacks have been widely discussed in the
literature. Proposed solutions are discussed here. (17)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

BIDRAM AND DAVOUDI: HIERARCHICAL STRUCTURE OF MICROGRIDS CONTROL SYSTEM 5

Fig. 10. The small-signal model of the adjustable reactive power control [47].
Fig. 11. Droop/boost characteristics for low-voltage microgrids: (a) voltage-
active power droop characteristic; (b) frequency-reactive power boost charac-
teristic.
In steady state, and are equal. Moreover, the steady
state reactive power can be calculated as
Similar to the adjustable load sharing method, the VPD/FQB
(18) technique can be modified to adjust the controller time constant
without causing voltage and frequency deviation [47], [48]. In
Thus, as opposed to (14)–(15), microgrid operational param- the VPD control mode, the common bus voltage, , is con-
eters will no longer affect the reactive power control. Addition- trolled to follow a reference voltage, .
ally, voltage regulation of the common bus is guaranteed. The
small-signal model for the proposed reactive power control is (22)
shown in Fig. 10 and is expressed by
where
(23)
(19)
and and are the proportional and integral gains of the
The closed loop transfer function of (19) is a function of both active power controller, respectively. In steady state,
and . Therefore, the dynamic response of the proposed
(24)
reactive power control can be directly adjusted by . Since
is remained intact, the resulting voltage of the reactive power In the FQB control mode, is determined by another propor-
control in (4) will no longer be affected by the controller time tional-integral (PI) controller as
constant adjustment.
2) VPD/FQB Droop Method: Low voltage transmission (25)
lines are basically resistive. Thus, one can consider a resistive
effective line impedance, i.e., , and also can assume where and are the proportional and integral gains
the to be small enough that . Considering these of the reactive power controller, respectively. In the modified
assumptions, (2) can be simplified as VPD/FQB method, the time constants of the closed loop con-
trollers are directly adjusted by the proportional and integral
gains, , and .
(20) 3) Virtual Frame Transformation Method: An orthogonal
linear transformation matrix, , is used to transfer the ac-
tive/reactive powers to a new reference frame where the powers
Thus, the voltage-active power droop and frequency-reactive are independent of the effective line impedance [53]–[55]. For
power boost (VPD/FQB) characteristics are alternatively con- the system shown in Fig. 7, is defined as
sidered [40]
(26)
(21)
The transformed active and reactive powers, and , are then
where and are the output voltage amplitude and angular used in droop characteristics in (4). The block diagram of this
frequency of the DER at no-load condition, respectively. technique is shown in Fig. 12.
and are the droop and boost coefficients, respectively. Similarly, a virtual frequency/voltage frame transformation is
Droop and boost characteristics of VPD/FQB method are defined as
shown in Fig. 11. This approach offers an improved perfor-
mance for controlling low-voltage microgrids with highly (27)
resistive transmission lines. However, it strongly depends on
system parameters and this dependency confines its application. where and are calculated through the conventional droop
Additionally, the VPD/FQB technique may face a malfunction equations in (4). The transformed voltage and frequency, and
in the presence of nonlinear loads and cannot guarantee the , are then used as reference values for the VSC voltage control
voltage regulation. loop [56]–[58].
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE TRANSACTIONS ON SMART GRID

Fig. 14. Virtual output impedance with voltage unbalance compensator.


Fig. 12. Droop method with virtual power frame transformation.

where is the cutoff frequency of the high-pass filter [41].


If the virtual impedance, , is properly adjusted, it can pre-
vent occurrence of current spikes when the DER is initially con-
nected to the microgrid. This soft starting can be facilitated by
considering a time-variant virtual output impedance as

Fig. 13. Block diagram of the virtual output impedance method [41]. (31)

where and are the initial and final values of the virtual
output impedance, respectively. is the time constant of the
The virtual frame transformation method decouples the active
start up process [31].
and reactive power controls. However, the applied transforma-
Most recently, the virtual output impedance method has been
tion requires a prior knowledge of the effective line impedance.
modified for voltage unbalance compensation, caused by the
Moreover, the control method does not consider possible neg-
presence of unbalanced loads in the microgrid [60]. The block
ative impacts of nonlinear loads, does not ensure a regulated
diagram of the modified virtual output impedance method is
voltage, and comprises a basic tradeoff between the control loop
shown in Fig. 14. As can be seen, the measured DER output
time constant adjustment and voltage/frequency regulation.
voltage and current are fed into the positive and negative se-
4) Virtual Output Impedance: An intermediate control loop
quence calculator (PNSC). Outputs of the PNSC, ,
can be adopted to adjust the output impedance of the VSCs [12],
and , are used to find the positive and negative sequence of
[41], and [59]. In this control loop, as depicted in Fig. 13, the
the DER active and reactive power. The negative sequence of
VSC output voltage reference, , is proportionally drooped
the reactive power, , is multiplied by the and then a con-
with respect to the output current, , i.e.,
stant gain, . The result is then used to find the voltage refer-
ence. The constant gain needs to be fine-tuned to minimize the
(28)
voltage unbalance without compromising the closed-loop sta-
bility.
where is the virtual output impedance, and is the
The virtual output impedance method alleviates the depen-
output voltage reference that is obtained by the conventional
dency of the droop techniques on system parameters. Addition-
droop techniques in (4).
ally, this control method properly operates in the presence of
If is considered, a virtual output inductance
nonlinear loads. However, this method does not guarantee the
is emulated for the VSC. In this case, the output voltage refer-
voltage regulation, and, adjusting the closed loop time constant
ence of the VSC is drooped proportional to the derivative of its
may result in an undesired deviation in the DER voltage and
output current. In the presence of nonlinear loads, the harmonic
frequency.
currents can be properly shared by modifying (28) as
5) Adaptive Voltage Droop Control: In this method, two
(29) terms are added to the conventional reactive power control
in (4). Additional terms are considered to compensate for the
voltage drop across the transmission lines that deliver power
where is the th current harmonic, and is the inductance
from the DER to critical loads. For a typical 2-DER system
associated with . values need to be precisely set to effec-
shown in Fig. 15, the voltages at first and second buses are
tively share the current harmonics [38].
Since the output impedance of the VSC is frequency depen-
(32)
dent, in the presence of nonlinear loads, THD of the output
voltage would be relatively high. This can be mitigated by using
where is the output current of the th DER. Using (4)
a high-pass filter instead of in (28)
one can write
(30) (33)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

BIDRAM AND DAVOUDI: HIERARCHICAL STRUCTURE OF MICROGRIDS CONTROL SYSTEM 7

Fig. 16. Block diagram of the signal injection method for reactive power
Fig. 15. A typical two-DER system. sharing [61].

where . The bus voltage of the th DER can also where is the RMS value of the no-load voltage of the DER,
be formulated in terms of its active and reactive powers, and and is the droop coefficient. This procedure is repeated until
, as all VSCs produce the same frequency for the control signal.
Here, this technique is elaborated for a system of two DERs
(34) shown in Fig. 15. It is assumed that is the same for both
DERs. Initially, first and second DERs inject low voltage signals
to the system with the following frequencies
The terms and represent the voltage drop on
the internal impedance . These terms can be incorporated
(39)
in the conventional reactive power control of (4) to compensate
for the voltage drops on the transmission lines as
Assuming
(35) (40)

Although, the reactive power control in (35) improves the The phase difference between the two voltage signals can be
voltage regulation of the farther buses, it is still dependent on obtained as
the active power control in (4). This problem is resolved by
adopting the voltage droop coefficient as a nonlinear function (41)
of active and reactive powers [45]
Due to the phase difference between the DERs, a small
amount of active power flows from one to the other. Assuming
(36) inductive output impedances for DERs, the transmitted active
power from DER1 to DER2, , is
where , and are droop coefficients. The terms (42)
and mitigate the negative impacts of the ac-
tive power control and the microgrid parameters on the reactive where and are the RMS values of the injected voltage
power control. signals. Moreover, the transmitted active power in reverse di-
The adaptive droop method is particularly desirable when the rection, from DER2 to DER1, , is
voltage regulation of some buses is not feasible. The higher-
order terms in (36) significantly improve the reactive power (43)
sharing under heavy loading conditions. The potential disad-
vantage, however, is the required prior knowledge of the trans- The DER voltages are adjusted as
mission line parameters [45]. This control method is not fully
functional in the presence of nonlinear loads. Moreover, given (44)
the basics discussed for the adjustable load sharing method, ad-
justing the time constant may result in undesired deviations in Herein, it is assumed that is the same for both DERs. The
DER voltage and frequency. difference between the DERs output voltages is
6) Signal Injection Method: In this approach, each DER in-
jects a small AC voltage signal to the microgrid. Frequency (45)
of this control signal, , is determined by the output reactive
Thus, one can write
power, , of the corresponding DER as

(37)

where is the nominal angular frequency of injected voltage


signals and is the boost coefficient. The small real power (46)
transmitted through the signal injection is then calculated and
the RMS value of the output voltage of the DER, , is accord- where is the load voltage. The block diagram of the proposed
ingly adjusted as controller is shown in Fig. 16.
In the presence of nonlinear loads, parallel DERs can be con-
(38) trolled to participate in supplying current harmonics by prop-
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE TRANSACTIONS ON SMART GRID

Fig. 18. Control block diagram for the harmonic cancellation technique.

Fig. 17. Block diagram of the updated signal injection method [61].
In the second approach, the conventional droop method is
modified to compensate for the harmonics of the DER output
erly adjusting the voltage loop bandwidth [61]. For that, first, voltage. These voltage harmonics are caused by the distorted
frequency of the injected voltage is drooped based on the total voltage drop across the VSC output impedance and are due to
distortion power, the distorted nature of the load current [52]. As shown in Fig. 18,
first, the DER output voltage and current are used to calculate
(47) the fundamental term and harmonics of the DER output active
and reactive power, and respectively. It is
where is the nominal angular frequency of the injected noteworthy that distorted voltage and current usually do not
voltage signals, is the droop coefficient, and is DER carry even harmonics, and thus, is usually an odd number.
apparent power. A procedure similar to (39)–(42) is adopted to and , are fed to the conventional droop characteristics in
calculate the power transmitted by the injected signal, . The (4) to calculate the fundamental term, , of the VSC voltage
bandwidth of VSC voltage loop is adjusted as reference, . As shown in Fig. 18, to cancel out the output
voltage harmonics, a set of droop characteristics are considered
(48) for each individual harmonic. Each set of droop characteristics
determines an additional term to be included in the VSC output
where is the nominal bandwidth of the voltage loop and voltage reference, , to cancel the corresponding voltage har-
is the droop coefficient. The block diagram of the signal monic. Each current harmonic, , is considered as a constant
injection method is shown in Fig. 17. current source, as shown in Fig. 19. In this figure, de-
Signal injection method properly controls the reactive power notes a phasor for the corresponding voltage signal that is in-
sharing, and is not sensitive to variations in the line impedances cluded in the voltage reference, . represents the VSC
[61], [62]. It also works for linear and nonlinear loads, and over output impedance associated with the th current harmonic. The
various operating conditions. However, it does not guarantee the active and reactive powers delivered to the harmonic current
voltage regulation. source, and , are
7) Nonlinear Load Sharing: Some have challenged the func-
tionality of droop techniques in the presence of nonlinear loads (50)
[50]–[52]. Two approaches for resolving this issue are discussed
here. In the first approach [50], the DERs equally share the
linear and nonlinear loads. For this purpose, each harmonic of When is small enough (i.e., and are
the load current, , is sensed to calculate the corresponding roughly proportional to and , respectively. Therefore, the
voltage droop harmonic, , at the output terminal of the DER. following droop characteristics can be used to eliminate the th
The voltage harmonics are compensated by adding 90 leading DER output voltage harmonic
signals, corresponding to each current harmonic, to the DER
voltage reference. Therefore, the real and imaginary parts of the (51)
voltage droop associated with each current harmonic are
where is the rated fundamental frequency of the microgrid.
(49) and are the droop coefficients. As can be seen in
Fig. 18, the harmonic reference voltage, , for eliminating
where is the droop coefficient for the th harmonic. As a the th output voltage harmonic, can be formed with and
result, the output voltage THD is significantly improved. the phase angle generated from the integration of .
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

BIDRAM AND DAVOUDI: HIERARCHICAL STRUCTURE OF MICROGRIDS CONTROL SYSTEM 9

(52)

Fig. 19. th harmonic equivalent circuit of a DER.


where , and are the controllers param-
eters. An additional term, , is considered in frequency
C. Discussion of Primary Control Level Techniques controller in (52) to facilitate synchronization of the microgird
to the main gird. In the islanded operating mode, this additional
Primary control techniques are application specific and bring term is zero. However, during the synchronization, a PLL
specific features. The active load sharing method provides tight module is required to measure [64]–[68]. During the
current sharing and high power quality; however, it requires grid-tied operation, voltage and frequency of the main grid are
communication links and high bandwidth control loops. On the considered as the references in (52).
other hand, the droop methods provide local controls without Most recently, potential function-based optimization tech-
any communication infrastructures. The potential advantages nique has been suggested for the secondary control [13]. In this
and disadvantages of the conventional droop method and its method, a potential function is considered for each DER. This
modifications are outlined in Table I, based on which the fol- function is a scalar cost function that carries all the information
lowing statements can be concluded: on the DER measurements, constraints, and control objectives
• System identification is required to find the line parameters as
for some techniques, e.g., adaptive voltage droop or virtual
frame transformation methods.
(53)
• Modified droop techniques, excluding the ones for low
voltage microgrids, decouple the active and reactive power
controls. where is the potential function related to each DER, and
• Adjustable load sharing and adaptive voltage droop comprises the measurements from the DER unit (e.g., voltage,
methods are the only techniques that offer voltage regula- current, real and reactive power). denotes the partial poten-
tion. tial functions that reflect the measurement information of the
• Nonlinear loads need to be accommodated with the com- DER. denotes the operation constraints that ensure the stable
plicated control techniques such as the virtual impedance, operation of microgrid. is used to mitigate the DER measure-
the signal injection, or the nonlinear load sharing methods ments from the pre-defined set points. , and are the
to achieve a mitigated level of harmonics in the microgrid. weighted factors for the partial potential functions.
• The adjustable load sharing is the only technique where The block diagram of the potential function-based technique
the system time constant can be independently adjusted is shown in Fig. 21. In this technique, when the potential func-
without affecting the DER voltage and frequency. tions approach their minimum values, the microgrid is about to
operate at the desired states. Therefore, inside the optimizer in
Fig. 21, set points of the DER are determined such that to min-
III. HIERARCHICAL CONTROL LEVEL II: SECONDARY imize the potential functions, and thus, to meet the microgrid
CONTROL control objectives.
The potential function-based technique requires bidirectional
Primary control, as discussed, may cause frequency deviation communication infrastructure to facilitate data exchange from
even in steady state. Although the storage devices can compen- the DER to the optimizer (measurements) and vice versa (calcu-
sate for this deviation, they are unable to provide the power for lated set points). The data transfer links add propagation delays
load-frequency control in long terms due to their short energy to the control signals. This propagation delay is tolerable, since
capacity. The secondary control, as a centralized controller, re- the secondary controllers are slower than the primary ones.
stores the microgrid voltage and frequency and compensate for The secondary control can also be designed to satisfy the
the deviations caused by the primary control. This control hier- power quality requirements, e.g., voltage balancing at critical
archy is designed to have slower dynamics response than that buses [69]. Block diagram of the voltage unbalance compen-
of the primary, which justifies the decoupled dynamics of the sator is shown in Fig. 22. First, the critical bus voltage is trans-
primary and the secondary control loops and facilitates their in- formed to the reference frame. Once the positive and nega-
dividual designs [63]. tive sequence voltages for both d and q axis are calculated, one
Fig. 20 represents the block diagram of the secondary con- can find the voltage unbalance factor (VUF) as
trol. As seen in this figure, frequency of the microgrid and
the terminal voltage of a given DER are compared with the
corresponding reference values, and , respectively. (54)
Then, the error signals are processed by individual controllers
as in (52); the resulting signals ( and ) are sent to the
primary controller of the DER to compensate for the frequency where and are the positive and negative sequence volt-
and voltage deviations [12] ages of the direct component, and and are the positive
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

10 IEEE TRANSACTIONS ON SMART GRID

TABLE I
POTENTIAL ADVANTAGES AND DISADVANTAGES OF THE DISCUSSED DROOP METHODS

and negative sequence voltages of the quadrature component, output powers of the microgrid, and , are measured.
respectively. As depicted in Fig. 22, the calculated VUF is com- These quantities are then compared with the corresponding
pared with the reference value, , and the difference is fed reference values, and , to obtain the frequency and
to a PI controller. The controller output is multiplied by the neg- voltage references, and based on
ative sequence of the direct and quadrature voltage components,
and , and the results are added to the references of DER
voltage controllers to compensate for the voltage unbalance. (55)

IV. HIERARCHICAL CONTROL LEVEL III: TERTIARY CONTROL


where , and are the controllers parame-
Tertiary control is the last (and the slowest) control level that ters [12]. and are further used as the reference values
considers the economical concerns in the optimal operation of to the secondary control, as in (52).
the microgrid, and manages the power flow between microgrid The tertiary control also provides an economically optimal
and main grid [12]. In the grid-tied mode, the power flow be- operation, e.g., by using a gossiping algorithm. Generally, the
tween microgrid and main grid can be managed by adjusting the economically optimal operation is satisfied if all the DERs
amplitude and frequency of DERs voltages. The block diagram operate at equal marginal costs (variation of the total cost with
of this process is shown in Fig. 20. First, active and reactive respect to the variation of the generated power), [15],
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

BIDRAM AND DAVOUDI: HIERARCHICAL STRUCTURE OF MICROGRIDS CONTROL SYSTEM 11

Fig. 20. Block diagram of the secondary and tertiary controls [12].

Fig. 23. Marginal cost function matching between two DERs [70].

Fig. 21. The potential function-based technique block diagram [13]. and , are determined. At this time, each of the two DERs
changes its output power to generate at the optimal point.
The aforementioned procedure is illustrated in Fig. 23. The
same procedure is repeated for other pairs of DERs until the
whole DERs in the microgrid operate optimally. Additionally,
evolutionary game theory-based techniques are proposed to
facilitate the power management by local information, and thus,
to simplify the required communication infrastructures [71].

V. FUTURE TRENDS
In this section, the technical challenges and future trends for
conventional AC microgrid control are briefly discussed. As an
emerging trend, DC microgrid is also briefly explained and its
control requirements are discussed.

A. AC Microgrids
Fig. 22. Voltage unbalance compensation in the secondary control. Given the difference in microgrid dynamics for grid-con-
nected and islanded operational modes, individual control
strategies have been so far proposed in the literature for each
[70]–[75]. In the gossiping algorithm, initially, random output mode. These individual control systems require wiring and
power set points, and , are considered for the th DER circuitry for each mode, which significantly increase the micro-
and its random gossiping partner, th DER, respectively. Then, gird control complexity and cost. Furthermore, the switching
considering the prior knowledge about the marginal cost curves between grid-connected and islanded modes highly depends on
of the DERs, the optimal output power of the two DERs, the speed and accuracy of the islanding detection scheme. Thus,
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

12 IEEE TRANSACTIONS ON SMART GRID

it is highly desired to figure out a unified control methodology (58)


with a single circuit configuration, that also facilitates a smooth
transition between modes. A unified controller is given in [76],
where , and are the nominal output voltage. The
where each DER is considered as a current controlled voltage
maximum allowed voltage deviation, and the maximum output
source. The controller comprises both droop characteristics
current of each DER, respectively. The secondary control can be
and active feedback compensation. The active feedback com-
designed to restore the voltage of the internal DC buses to the
pensator controls the active and reactive power of DERs in the
nominal value. Once the microgrid is connected to a stiff DC
grid-connected mode. Once the microgrid is islanded, the active
grid, the tertiary control level manages the power flow between
feedback compensator is deactivated and droop characteristics
the microgrid and the stiff DC grid.
control the DERs’ voltage amplitude and frequency. Recent
DC microgrids are naturally susceptible to stability issues;
works on the unified control systems for DERs [38], [76]–[78],
the connection of a large number of DC-DC converters intro-
indicate ongoing efforts to fully address flexible DER’s control
duces stability problems. With a high penetration of DERs, the
systems with smooth mode transitions.
tightly regulated DC-DC converters act as a constant power
At the secondary control level, most of existing works have
load with a negative resistance. This effect significantly de-
focused on centralized control with communication infrastruc-
creases the stability margins of the system and necessitates effi-
tures [12], [13], [69]. The presence of communication links in-
cient solutions for stability improvement [81]–[83]. Moreover,
creases the microgrid cost and deteriorates the system relia-
to improve system reliability, multiple bus configurations with
bility. Therefore, decentralized control methods with minimum
various voltage levels are usually adopted in DC microgrids.
communication infrastructure have paramount value. In a smart
With multiple bus configurations, sensitive loads can be sup-
grid environment, all DERs and loads can be assumed as fully
plied from multiple buses, simultaneously or sequentially, or
controllable players, with plug-and-play capabilities. A differ-
from a specific bus. The bus selection procedure requires persis-
ential game theoretic platform would facilitate the implemen-
tent switching and results in discontinuous currents at each bus
tation of a decentralized controller [79], and would be an ap-
leading to the undesired voltage oscillations. Therefore, appro-
propriate option to control all players simultaneously for main-
priate control approaches are required to enable a smooth bus se-
taining the voltage and frequency stability of microgird.
lection. In one approach proposed in [84], the automatic bus se-
At the tertiary control level, the multi-agent based control
lection can be provided through auctioneering diodes where the
structures can be adopted for microgrid power management.
bus with the highest voltage supplies the load. In the emergency
The intelligent agents optimize the given performance index
conditions, another bus can be chosen to increase the system re-
(minimizing operation, maintenance, and fuel costs, or mini-
liability. This approach results in a lower bus current interrup-
mizing the environmental impacts) [80].
tion and power dissipations.
Wide adoption of microgrid concept would require simulta-
neous connection of several microgrids to the electric power
systems [12]. This would cause some new technical challenges, VI. CONCLUSION
e.g., voltage and frequency oscillations in the electric power With recent interests in reliable and economical power
system, protection issues, and source and load assets manage- delivery, microgrids have been conceived as practical and
ment. effective solutions. Robust control of a microgrid in both
grid-tied and isolated operating modes encounters many chal-
B. DC Microgrids lenges. This paper reviews existing methodologies to enhance
DC microgirds have recently earned significant attention. The the control performance of the microgrid. These approaches lie
technical challenges associated with AC microgrids (e.g., syn- within the context of hierarchical control structure consisting of
chronization of DERs, reactive power control, harmonic cur- primary, secondary, and tertiary control. The bulk of literature
rents, and voltage unbalance at critical buses) no more exist in is devoted to the primary control, in particular to the conven-
DC microgrids. Moreover, DC microgrids facilitate seamless in- tional droop control method and its modifications. Various
terfacing of DC sources such as photovoltaic panels, fuel cells, techniques are discussed to address the challenges associated
and battery storage devices without the requirement of DC-AC with droop methods, namely decoupling the active and reactive
converters. Therefore, DC microgrids are a suitable solution for control laws, robustness with respect to the system parameters,
the sensitive applications that require high power quality. Sim- addressing nonlinear loads, and proper voltage regulation.
ilar to AC microgrids, a hierarchical control structure can be Potential functions and gossiping algorithms are discussed for
adopted to control DC microgrids [12]. In the primary control, the secondary and tertiary control levels, respectively. The
the DER output voltages are controlled to reduce the circulating potential research lines, technical challenges, and future trends
currents. For this purpose, the appropriate voltage references, for both AC and DC microgrids are briefly discussed.
, for each power supply is determined as
REFERENCES
(56)
[1] G. A. Pagani and M. Aiello, “Towards decentralization: A trpological
investigation of the medium and low voltage grids,” IEEE Trans. Smart
where is the output current of each DER and Grid, vol. 2, pp. 538–547, Sep. 2011.
[2] T. L. Vandoorn, B. Renders, L. Degroote, B. Meersman, and L. Van-
develde, “Active load control in islanded microgrids based on the grid
(57) voltage,” IEEE Trans. Smart Grid, vol. 2, pp. 139–151, Mar. 2011.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

BIDRAM AND DAVOUDI: HIERARCHICAL STRUCTURE OF MICROGRIDS CONTROL SYSTEM 13

[3] Q. Yang, J. A. Barria, and T. C. Green, “Advanced power electronic [29] Y. W. Li, D. M. Vilathgamuwa, and P. C. Loh, “Robust control method
conversion and control system for universal and flexible power man- for a microgrid with PFC capacitor connected,” IEEE Trans. Ind. Appl.,
agement,” IEEE Trans. Smart Grid, vol. 2, pp. 231–243, Jun. 2011. vol. 43, pp. 1172–1182, Sep./Oct. 2007.
[4] B. Fahimi, A. Kwasinski, A. Davoudi, R. S. Balog, and M. Kiani, [30] Y. W. Li, D. M. Vilathgamuwa, and P. C. Loh, “A grid-interfacing
“Charge it,” IEEE Power Energy Mag., vol. 9, pp. 54–64, Jul./Aug. power quality compensator for three-phase three-wire microgrid ap-
2011. plications,” IEEE Trans. Power Electron., vol. 21, pp. 1021–1031, Jul.
[5] M. E. Elkhatib, R. El-Shatshat, and M. M. A. Salama, “Novel coordi- 2006.
nated voltage control for smart distributed networks with DG,” IEEE [31] J. M. Guerrero, L. Hang, and J. Uceda, “Control of distributed uninter-
Trans. Smart Grid, vol. 2, pp. 598–605, Dec. 2011. ruptible power supply systems,” IEEE Trans. Ind. Electron., vol. 55,
[6] The Smart Grid: An Introduction United States Department of Energy, pp. 2845–2859, Aug. 2008.
Office of Electricity Delivery and Energy Reliability, Washington, DC, [32] T. Iwade, S. Komiyama, and Y. Tanimura, “A novel small-scale UPS
2008 [Online]. Available: http://www.oe.energy.gov/1165.htm using a parallel redundant operation system,” in Proc. Int. Telecommu-
[7] R. H. Lasseter, “Microgrid,” in Proc. IEEE Power Eng. Soc. Winter nications Energy Conf., 2003, pp. 480–483.
Meeting, New York, 2002, vol. 1, pp. 305–308. [33] Y. J. Cheng and E. K. K. Sng, “A novel communication strategy for de-
[8] F. Katiraei, R. Iravani, N. Hatziargyriou, and A. Dimeas, “Microgrids centralized control of paralleled multi-inverter systems,” IEEE Trans.
management,” IEEE Power Energy Mag., vol. 6, pp. 54–65, May/Jun. Power Electron., vol. 21, pp. 148–156, Jan. 2006.
2008. [34] X. Sun, Y. S. Lee, and D. Xu, “Modeling, analysis, and implementation
[9] N. Hatziargyriou, H. Asano, R. Iravani, and C. Marnay, “Microgrids,” of parallel multi-converter system with instantaneous average-current-
IEEE Power Energy Mag., vol. 5, pp. 78–94, Jul./Aug. 2007. sharing method,” IEEE Trans. Power Electron., vol. 18, pp. 844–856,
[10] P. Piagi and R. H. Lasseter, Industrial Applications of Microgrids. May 2003.
Madison, WI: Power System Engineering Research Center, Univ. Wis- [35] S. Sun, L. K. Wong, Y. S. Lee, and D. Xu, “Design and analysis of
consin, 2001. an optimal controller for parallel multi-inverter systems,” IEEE Trans.
[11] J. Driesen and F. Katiraei, “Design for distributed energy resources,” Circuit Syst. II, vol. 52, pp. 56–61, Jan. 2006.
IEEE Power Energy Mag., vol. 6, pp. 30–40, May/Jun. 2008. [36] T. F. Wu, U. K. Chen, and Y. H. Huang, “3C strategy for inverters in
[12] J. M. Guerrero, J. C. Vásquez, J. Matas, M. Castilla, L. G. D. Vicuña, parallel operation achieving an equal current distribution,” IEEE Trans.
and M. Castilla, “Hierarchical control of droop-controlled AC and DC Ind. Electron., vol. 47, pp. 273–281, Apr. 2000.
microgrids—A general approach toward standardization,” IEEE Trans. [37] C. Mark and L. Bolster, “Bus-tie synchronization and load share tech-
Ind. Electron., vol. 58, pp. 158–172, Jan. 2011. nique in a ring bus system with multiple power inverters,” in Proc.
[13] A. Mehrizi-Sani and R. Iravani, “Potential-function based control of a IEEE Applied Power Electron. Conf., APEC, 2005, pp. 871–874.
microgrid in islanded and grid-connected models,” IEEE Trans. Power [38] J. M. Guerrero, J. C. Vásquez, J. Matas, M. Castilla, and L. G. D.
Syst., vol. 25, pp. 1883–1891, Nov. 2010. Vicuña, “Control strategy for flexible microgrid based on parallel
[14] C. Yuen, A. Oudalov, and A. Timbus, “The provision of frequency line-interactive UPS systems,” IEEE Trans. Ind. Electron., vol. 56, pp.
control reserves from multiple microgrids,” IEEE Trans. Ind. Electron., 726–736, Mar. 2009.
vol. 58, pp. 173–183, Jan. 2011. [39] J. M. Guerrero, J. Matas, L. G. D. Vicuna, M. Castilla, and J. Miret,
[15] K. D. Brabandere, K. Vanthournout, J. Driesen, G. Deconinck, and R. “Wireless-control strategy for parallel operation of distributed gener-
Belmans, “Control of microgrids,” in Proc. IEEE Power & Energy So- ation inverters,” IEEE Trans. Ind. Electron., vol. 53, pp. 1461–1470,
ciety General Meeting, 2007, pp. 1–7. Oct. 2006.
[16] Y. A. R. I. Mohamed and A. A. Radwan, “Hierarchical control system [40] J. M. Guerrero, J. Matas, L. G. D. Vicuna, M. Castilla, and J. Miret,
for robust microgrid operation and seamless mode transfer in active “Decentralized control for parallel operation of distributed generation
distribution systems,” IEEE Trans. Smart Grid, vol. 2, pp. 352–362, inverters using resistive output impedance,” IEEE Trans. Ind. Elec-
Jun. 2011. tron., vol. 54, pp. 994–1004, Apr. 2007.
[17] J. A. P. Lopes, C. L. Moreira, and A. G. Madureira, “Defining control [41] J. M. Guerrero, L. G. D. Vicuna, J. Matas, M. Castilla, and J. Miret,
strategies for microgrids islanded operation,” IEEE Trans. Power Syst., “Output impedance design of parallel-connected UPS inverters with
vol. 21, pp. 916–924, May 2006. wireless load-sharing control,” IEEE Trans. Ind. Electron., vol. 52, pp.
[18] P. Piagi and R. H. Lasseter, “Autonomous control of microgrids,” in 1126–1135, Aug. 2005.
Proc. IEEE Power Eng. Soc. General Meeting, 2006. [42] J. M. Guerrero, L. G. D. Vicuna, J. Miret, J. Matas, and J. Cruz, “Output
[19] F. Katiraei, M. R. Iravani, and P. W. Lehn, “Microgrid autonomous impedance performance for parallel operation of UPS inverters using
operation during and subsequent to islanding process,” IEEE Trans. wireless and average current-sharing controllers,” in Proc. Power Elec-
Power Del., vol. 20, pp. 248–257, Jan. 2005. tron. Specialist Conf., 2004, pp. 2482–2488.
[20] Y. Li, D. M. Vilathgamuwa, and P. C. Loh, “Design, analysis, and [43] F. Katiraei and M. R. Iravani, “Power management strategies for a mi-
real-time testing of a controller for multibus microgrid system,” IEEE crogrid with multiple distributed generation units,” IEEE Trans. Power
Trans. Power Electron., vol. 19, pp. 1195–1204, Sep. 2004. Syst., vol. 21, pp. 1821–1831, Jan. 2005.
[21] H. Nikkhajoei and R. H. Lasseter, “Distributed generation interface [44] I. Y. Chung, W. Liu, D. A. Cartes, and K. Schoder, “Control parameter
to the CERTS microgrid,” IEEE Trans. Power Del., vol. 24, pp. optimization for a microgrid system using particle swarm optimiza-
1598–1608, Jul. 2009. tion,” in Proc. IEEE Int. Conf. Sustainable Energy Technologies, 2008,
[22] M. C. Chandorkar, D. M. Divan, and R. Adapa, “Control of parallel pp. 837–842.
connected inverters in standalone AC supply systems,” IEEE Trans. [45] E. Rokrok and M. E. H. Golshan, “Adaptive voltage droop method
Ind. Appl., vol. 29, pp. 136–143, Jan./Feb. 1993. for voltage source converters in an islanded multibus microgrid,” IET
[23] H. Karimi, H. Nikkhajoei, and M. R. Iravani, “Control of an elec- Gen., Trans., Dist., vol. 4, no. 5, pp. 562–578, 2010.
tronically-coupled distributed resource unitsubsequent to an islanding [46] G. Diaz, C. Gonzalez-Moran, J. Gomez-Aleixandre, and A. Diez,
event,” IEEE Trans. Power Del., vol. 23, pp. 493–501, Jan. 2008. “Scheduling of droop coefficients for frequency and voltage regula-
[24] M. D. Ilic and S. X. Liu, Hierarchical Power Systems Control: Its Value tion in isolated microgrids,” IEEE Trans. Power Syst., vol. 25, pp.
in a Changing Industry. London, U.K.: Springer, 1996. 489–496, Feb. 2010.
[25] M. J. Ryan, W. E. Brumsickle, and R. D. Lorenz, “Control topology [47] C. K. Sao and W. Lehn, “Autonomous load sharing of voltage source
options for single-phase UPS inverters,” IEEE Trans. Ind. Appl., vol. converters,” IEEE Trans. Power Del., vol. 20, pp. 1009–1016, Apr.
33, pp. 493–501, Mar./Apr. 1997. 2005.
[26] G. Escobar, P. Mattavelli, A. M. Stankovic, A. A. Valdez, and J. L. [48] C. K. Sao and W. Lehn, “Control and power management of converter
Ramos, “An adaptive control for UPS to compensate unbalance and fed microgrids,” IEEE Trans. Power Syst., vol. 23, pp. 1088–1098,
harmonic distortion using a combined capacitor/load current sensing,” Aug. 2008.
IEEE Trans. Ind. Appl., vol. 54, pp. 839–847, Apr. 2007. [49] M. N. Marwali, J. W. Jung, and A. Keyhani, “Control of distributed
[27] A. Hasanzadeh, O. C. Onar, H. Mokhtari, and A. Khaligh, “A pro- generation systems–Part II: Load sharing control,” IEEE Trans. Power.
portional-resonant controller-based wireless control strategy with a re- Electron., vol. 19, pp. 1551–1561, Nov. 2004.
duced number of sensors for parallel-operated UPSs,” IEEE Trans. [50] U. Borup, F. Blaabjerg, and P. N. Enjeti, “Sharing of nonlinear load
Power Del., vol. 25, pp. 468–478, Jan. 2010. in parallel-connected three-phase converters,” IEEE Trans. Ind. Appl.,
[28] M. Prodanović and T. C. Green, “High-quality power generation vol. 37, pp. 1817–1823, Nov./Dec. 2001.
through distributed control of a power park microgrid,” IEEE Trans.
Ind. Electron., vol. 53, pp. 1471–1482, Oct. 2006.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

14 IEEE TRANSACTIONS ON SMART GRID

[51] T. L. Lee and P. T. Cheng, “Design of a new cooperative harmonic [72] T. Tanabe et al., “Optimized operation and stabilization of microgrids
filtering strategy for distributed generation interface converters in with multiple energy resources,” in Proc. 7th Int. Conf. Power Elec-
an islanding network,” IEEE Trans. Power. Electron., vol. 22, pp. tron., 2007, pp. 74–78.
1919–1927, Sep. 2007. [73] E. Barklund, N. Pogaku, M. Prodanović, C. Hernandez-Aramburo, and
[52] Q. C. Zhong, “Harmonic droop controller to reduce the voltage har- T. C. Green, “Energy management in autonomous microgrid using sta-
monics of inverters,” IEEE Trans. Ind. Electron., 2012, DOI: 10.1109/ bility-constrained droop control of inverters,” IEEE Trans. Power Elec-
TIE.2012.2189542, to be published. tron., vol. 23, pp. 2346–2352, Sep. 2008.
[53] J. C. Vasquez, J. M. Guerrero, A. Luna, P. Rodriguez, and R. Teodor- [74] C. A. Hernandez-Aramburo, T. C. Green, and N. Mugniot, “Fuel con-
escu, “Adaptive droop control applied to voltage-source inverters op- sumption minimization of a microgrid,” IEEE Trans. Ind. Appl., vol.
erating in grid-connected and islanded modes,” IEEE Trans. Ind. Elec- 41, pp. 673–681, May/Jun. 2005.
tron., vol. 56, pp. 4088–4096, Oct. 2009. [75] K. Vanthournout, “A Semantic Overlay Network Based Robust Data-
[54] K. D. Brabandere, B. Bolsens, J. V. D. Keybus, A. Woyte, J. Driesen, Infrastructure, Applied to the Electric Power Grid,” Ph.D. dissertation,
and R. Belmans, “A voltage and frequency droop control method Facultiet Ingenieurswetenschappen, Leuven, Belgium, 2006.
for parallel inverters,” IEEE Trans. Power Electron., vol. 22, pp. [76] M. B. Delghavi and A. Yazdani, “A unified control strategy for elec-
1107–1115, Jul. 2007. tronically interfaced distributed energy resources,” IEEE Trans. Power
[55] Z. Jiang and X. Yu, “Active power-voltage control method for islanding Del., vol. 27, pp. 803–812, Apr. 2012.
operation of inverter-interfaced microgrids,” in Proc. IEEE Power & [77] J. Kim, J. M. Guerrero, P. Rodriguez, R. Teodorescu, and K. Nam,
Energy Society General Meeting, 2009, pp. 1–7. “Mode adaptive droop control with virtual output impedances for an
[56] Y. Li and Y. W. Li, “Decoupled power control for an inverter based inverter-based flexible AC microgrid,” IEEE Trans. Power Electron.,
low voltage microgrid in autonomous operation,” in Proc. IEEE 6th vol. 26, pp. 689–701, Mar. 2011.
Int. Power Electron. and Motion Control Conf., 2009, pp. 2490–2496. [78] Y. W. Li and C. N. Kao, “An accurate power control strategy for power-
[57] Y. Li and Y. W. Li, “Virtual frequency-voltage frame control of in- electronics-interfaced distributed generation units operating in a low-
verter based low voltage microgrid,” in Proc. IEEE Electrical Power voltage multibus microgrid,” IEEE Trans. Power Electron., vol. 24, pp.
& Energy Conf., 2009, pp. 1–6. 2977–2988, Dec. 2009.
[58] Y. Li and Y. W. Li, “Power management of inverter interfaced au- [79] W. W. Weaver and P. T. Krein, “Game-theoretic control of small-scale
tonomous microgrid based on virtual frequency-voltage frame,” IEEE power systems,” IEEE Trans. Power Del., vol. 24, pp. 1560–1567, Jul.
Trans. Smart Grid, vol. 2, pp. 30–40, Mar. 2011. 2009.
[59] W. Yao, M. Chen, J. Matas, J. M. Guerrero, and Z. Qian, “Design and [80] C. M. Colson and M. H. Nehrir, “A review of challenges to real-time
analysis of the droop control method for parallel inverters considering power management of microgirds,” in Proc. IEEE Power & Energy
the impact of the complex impedance on the power sharing,” IEEE Society General Meeting, 2009, pp. 1–8.
Trans. Ind. Electron., vol. 58, pp. 576–588, Feb. 2011. [81] R. S. Balog, W. W. Weaver, and P. T. Krein, “The load as an energy
[60] M. Savaghebi, A. Jalilian, J. Vasquez, and J. Guerrero, “Autonomous asset in a distributed DC smartgrid architecture,” IEEE Trans. Smart
voltage unbalance compensation in an islanded droop-controlled mi- Grid, vol. 3, pp. 253–260, Mar. 2011.
crogrid,” IEEE Trans. Ind. Electron., 2012, DOI: 10.1109/TIE.2012. [82] A. A. A. Radwan and Y. A. I. Mohamed, “Linear active stabilization
2185914, to be published. of converter-dominated DC microgrids,” IEEE Trans. Smart Grid, vol.
[61] A. Tuladhar, H. Jin, T. Unger, and K. Mauch, “Control of parallel 3, pp. 203–216, Mar. 2011.
inverters in distributed AC power systems with consideration of line [83] A. Kwasinski and C. N. Onwuchekwa, “Dynamic behavior and stabi-
impedance effect,” IEEE Trans. Ind. Appl., vol. 36, pp. 131–138, Jan./ lization of DC microgrids with instantaneous constant power loads,”
Feb. 2000. IEEE Trans. Power Electron., vol. 26, pp. 822–834, Mar. 2011.
[62] A. Tuladhar, H. Jin, T. Unger, and K. Mauch, “Parallel operation of [84] R. S. Balog and P. T. Krein, “Bus selection in multibus DC micro-
single phase inverter modules with no control interconnections,” in grids,” IEEE Trans. Power Electron., vol. 26, pp. 860–867, Mar. 2011.
Proc. Applied Power Electron. Conf. and Exposition, APEC, 1997, pp.
94–100.
[63] B. Marinescu and H. Bourles, “Robust predictive control for the Ali Bidram (S’09) received the B.S. (Hon.) and M.S.
flexible coordinated secondary voltage control of large scale power (Hon.) degree in electrical engineering from Isfahan
system,” IEEE Trans. Power Syst., vol. 14, pp. 1262–1268, Nov. 1999. University of Technology, Isfahan, Iran, in 2008 and
[64] D. Yazdani, A. Bakhshai, G. Joos, and M. Mojiri, “A nonlinear adap- 2010, respectively. He is currently pursuing the Ph.D.
tive synchronization technique for grid-connected distributed energy degree at the University of Texas at Arlington, Ar-
sources,” IEEE Trans. Power Electron., vol. 23, pp. 2181–2186, Jul. lington, TX.
2008. His research interests include power systems dy-
[65] B. P. McGrath, D. G. Holmes, and J. J. H. Galloway, “Power converter namics and stability, micro-grid, and renewable en-
line synchronization using a discrete fourier transform (DFT) based ergy resources.
ona variable sample rate,” IEEE Trans. Power Electron., vol. 20, pp.
877–884, Jul. 2005.
[66] S. J. Lee, H. Kim, S. K. Sul, and F. Blaabjerg, “A novel control algo-
rithm for static series compensators by use of PQR instantaneous power
theory,” IEEE Trans. Power Electron., vol. 19, pp. 814–827, May 2004.
[67] D. Jovcic, “Phase-locked loop system for FACTS,” IEEE Trans. Power Ali Davoudi (S’04–M’11) received the B.Sc. and
Syst., vol. 18, pp. 1116–1124, Aug. 2003. M.Sc. degrees in electrical and computer engineering
[68] A. Yazdani and R. Iravani, “A unified dynamic model and control for from Sharif University of Technology, Tehran, Iran,
the voltage source converter under unbalanced grid conditions,” IEEE and The University of British Columbia, Vancouver,
Trans. Power Del., vol. 21, pp. 1620–1629, Jul. 2006. Canada, in 2003 and 2005, respectively. He received
[69] M. Savaghebi, A. Jalilian, J. Vasquez, and J. Guerrero, “Secondary con- the Ph.D. in electrical and computer engineering
trol scheme for voltage unbalance compensation in an islanded droop- from the University of Illinois, Urbana-Champaign,
controlled microgrid,” IEEE Trans. Smart Grid, 2012, DOI: 10.1109/ in 2010. His research interests are all aspects of mod-
TSG.2011.2181432, to be published. eling, simulation, and control of power electronics
[70] K. Vanthournout, K. D. Brabandere, E. Haesen, J. Driesen, G. Decon- and energy conversion systems, renewable energy
inck, and R. Belmans, “Agora: Distributed tertiary cotrol of distributed sources, and transportation electrification.
resources,” in Proc. 15th Power Systems Computation Conf., 2005, pp. He is currently an Assistant Professor at the Electrical Engineering Depart-
1–7. ment of the University of Texas, Arlington. He worked for Solar Bridge Tech-
[71] A. Pantoja and N. Quijano, “A population dynamics approach for the nologies, Texas Instruments Inc., and Royal Philips Electronics.
dispatch of distributed generators,” IEEE Trans. Ind. Electron., vol. 58, Dr. Davoudi is an Associate Editor for IEEE TRANSACTIONS ON VEHICULAR
pp. 4559–4567, Oct. 2011. TECHNOLOGY and IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS.

You might also like