© Norsk Hydro
protection in the oil and gas industry;
the first choice for all the world's How do Chartek epoxy passive Chartek materials help to protect steel from reaching its
oil majors. fire protection materials work? “critical core temperature” within a certain time period.
Chartek epoxy passive fire protection materials swell or This critical core temperature is the temperature when steel
Part of AkzoNobel, the world’s largest coatings company, we can supply our ‘intumesce’ in a fire providing an insulating durable char starts to lose its load bearing capacity and can depend on
high quality Chartek products and services to projects anywhere in the world. layer that slows the temperature rise of the steel substrate. the grade of steel used and its load bearing requirement.
0.7
1000
Reduction Factor
0.6
800 0.5
0.4
600
0.3
Critical core temperature
400
0.2
This extra time
allows people 0.1
to evacuate
200
5 20 40 60 80 90 100 120 200 400 600 800 1000 1200
minutes minutes
Time (minutes) Temperature (ºC)
2 3
The Chartek Product Range Epoxy Passive Fire Protection
Second to None
Since the introduction of Chartek in the 1970s the Chartek Extensive Certification to the Most Up-to-date Fire Standards
product range has evolved to offer trusted solutions for Chartek is the most extensively 3rd party qualified epoxy intumescent material available today
hydrocarbon fires right across the oil and gas industry The following list of external agencies provides an example of our qualifications:
Chartek 7 Chartek 8 Chartek 1709 • BAM • American Bureau of Shipping • Underwriters Laboratories
• Det Norske Veritas • NORSOK • Bureau Veritas
Material 2 pack 100% solids epoxy 2 pack 100% solids epoxy 2 pack 100% solids epoxy
• Lloyd’s Register of Shipping • GASAFE • GOST
Target Oil & Gas Market Offshore & Onshore Offshore Onshore
VOC 0g/L 0g/L 0g/L Jet fire testing Pool fire testing Blast testing
The Chartek brand has an un-equalled track record of protecting oil and gas installations against explosion, hydrocarbon pool
and jet fires. Chartek products can be found on the world's offshore platforms, FPSOs, refineries, petrochemical plants,
LNG terminals and LPG storage facilities in environments as diverse as the North Sea, the Tropics and Antarctica.
Chartek products can be used to protect the following safety critical items:
• Structural steelwork
• Fire and blast divisions
(firewalls, under-decks, bulkheads, etc)
• Process pipework and supports
• Vessels (walls and saddles/skirts)
• Accommodation modules
• Jetties
• Temporary refuge areas
• Flare towers
• Heli-decks
• Risers
• Actuators
© BP Plc
6 7
No Need for Topcoats to
Guarantee Corrosion Protection
Virtually maintenance free giving real life cycle cost savings
© PK Technology 2012
Chartek technology is in full compliance with both the ageing and fire protection
requirements documented in ISO20340 and NORSOK M501 Edition 6 System 5A
Condition Based Surveys Given that for most of its life epoxy passive
fire protection acts as an anti-corrosive system
The NORSOK M501 Edition 6 System 5A pre-qualification
requirements recognise that the epoxy passive fire protection
coating system itself must remain mechanically robust and
it is important that it has excellent long term
able to provide both optimum corrosion protection and fire
durability and anti-corrosion protection properties. performance. For this reason the standard expects the epoxy
Industry standards mandate that the owner is to have a plan in place for Chartek meets, arguably, the most demanding accelerated passive fire protection coating system to pass System 5A
Passive Fire Protection inspection and repair corrosion standard used in the oil and gas industry today: without a topcoat. This means that the epoxy passive fire
protection coating system:
Our Interplan system is a condition based survey program carried out by our specialist team of surveyors. The system provides ISO20340 “Performance requirements for • Must have a minimum adhesion pull off value
a documented and site specific fire protection condition survey, designed to provide the maintenance engineer with all the protective paint systems for offshore and greater than 3MPa which is also more than 50%
information required to understand: related structures.” of its original unexposed value
• Must exhibit a corrosion creep value less than
What needs to be repaired? How to repair it? In which order?
The ISO20340 standard: 3mm when using a zinc primer
We can provide you with a condition Our customised surface preparation You will get a detailed year on year • Must have low water absorption (Chartek is
• Is used by NORSOK M501 Edition 6 System 5A
survey and specific surface areas and coating repair specifications address prioritised maintenance schedule to consistently less than 1% by weight) after
to pre-qualify passive fire protection systems
needing attention differing situations and locations help you budget test completion
• Assesses epoxy passive fire protection systems
• After exposure testing must demonstrate that
after exposure to 25 weeks of QUV/condensation,
the temperature does not rise greater than
continuous salt spray and -20ºC freeze cycles
10% with respect to a control
© PK Technology 2012
The ISO20340 accelerated corrosion test requires 25 repeated cycles
© PK Technology 2012
underlying steel substrate to corrode and corrosion protection. So once Chartek to replace failed passive fire
3.0
lose its structural integrity. has been installed, you can benefit from protection without the need for
low product life cycle costs compared dry blasting. 2.5
If left untreated concrete cracking and
to other conventional fire protection 2.0
disbondment can lead to: Demountable pre-cast Chartek
products. 1.5
• Dangerous fall drop hazards that solutions can also be installed
1.0
can cause serious injury to innocent when frequent inspection is
0.5
employees. required.
0 Another commercially available epoxy
Chartek shows low
• A drop in fire protection performance. 5ºC 5ºC 25ºC 25ºC passive fire protection product showing
deionised water salt water deionised water salt water corrosion creep (<3mm) extensive corrosion creep (>10mm)
8 9
A Range of Insulation Options
A range of insulation options allow Chartek’s outstanding
properties to be employed in some of the most demanding
environments in the oil and gas industry
10 11
Our Complete System
With a comprehensive range of primers
and topcoats we can provide you with
one point of contact for all your protective
coating and fire protection needs.
Blasted
• Consistent product performance
Steel
• Products are manufactured
Primer and stocked globally
• All products are made to ISO9001
Chartek and ISO14001 quality standards
HK-1 Mesh
“The key factors we considered with regards to
specifying the right coating and fire protection
Chartek systems were worldwide availability, the provision
of technical support, quality control during
application and relevant offshore references such
Technical Service and Support Topcoat
as NORSOK approval. Choosing Chartek as
the Passive Fire Protection product to be used
Every Step of the Way throughout the project and being able to utilise
protective coatings from the same manufacturer
who provided excellent technical support during
engineering and design phase was a great benefit.”
The Chartek brand is not just about product performance, Rolf Schwerdtfeger,
it is also about the associated services and support we Senior Construction Engineer, Linde AG
provide to complement our fire protection offer.
Experienced on-site technical
support teams around the world
We have a network of dedicated Chartek technical service
representatives with:
• Many years of experience in supporting Chartek projects
Global Manufacture and Availability
O FFICE
around the world LO CATIO NS
• Full understanding of yard practices and operating conditions
Ensuring passive fire protection is applied correctly is vital to ensure
long term fire and durability expectations are met. This is why, since
the early days of Chartek fireproofing we only use qualified application
companies trained in all aspects of Chartek installation.
Bespoke Project Testing
Our state-of-the-art 10 million US$ R&D facility allows us to carry out
bespoke testing to satisfy our customers’ individual project needs.
The facility contains:
• Screening furnaces
• Full scale furnaces
• Dedicated application facilities
• Environmentally controlled conditioning areas
Fire Engineering
Right from the very beginning of your project our industry leading
structural and fire engineering specialist team can work with you
to review the passive fire protection requirements for your asset,
providing:
• State-of-the-art computer modelling for structural response in a fire
• Bespoke structural member heat transfer modelling
• Optimised passive fire protection specifications
12
Chartek®
The Original and Most Widely Requested Total Asset Fire Protection Package
www.international-pc.com
pc.communication@akzonobel.com
G14_CHARTEK_UK
AN02801_141209
and and all product names mentioned in this publication are trademarks of, or licensed to, AkzoNobel. © AKZONOBEL 2012.
02/13
International Paint has used its best endeavours to ensure that the information contained in this publication is correct at the time of printing.
Please contact your local International Paint representative if you have any questions.
Unless otherwise agreed by us in writing, any contact to purchase products referred to in this brochure and any advice which we give in connection with
the supply of products are subject to our standard conditions of sale and the provisions of the relevant product data sheet.