PB1

SCHEDULE OF BEAMS :- NOTES:-


PB2 ALL DIMENSIONS ARE IN MM, CHECK LAYOUT AS / ARCHITECT.
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT VERTICAL STIRRUPS
BEAM DO NOT SCALE THE DRAWING. ONLY WRITTEN DIMENSIONS
S2 DRESSER WIDTH DEPTH STRAIGHT EXTRA EXTRA STRAIGHT EXTRA EXTRA EXTRA NOMINAL CONFINING REMARKS
3'6" NAME ARE TO BE FOLLOWED.
HB X (mm) (mm) ( BStr ) ( Bext ) LENGTH ( TStr ) (Left Support) (Right Support) LENGTH RINGS RINGS
5' UNLESS SPECIFIED CONCRETE MIX IS TO BE M25 (IS: 456-2000)
PB1, 230 300 2-12 # 1-12 # 0.7L 2-12 # 1-12 # 1-12 # 0.25L 8 # @ 150 C/C 8 # @ 100 C/C
PB1 OVERLAP LENGTH IN COLUMN VERTICAL REINFORCEMENT SHALL
PB1 S1 PB1 S2 BEDROOM
13'
X BED
PB2 230 230 2-12 # ----- ----- 2-12 # ----- ----- ----- 8 # @ 150 C/C 8 # @ 100 C/C NOT BE LESS THAN DEVELOPMENT LENGTH IN COMPRESSION.
12'' TOILET
8' PB3 230 230 2-12 # ----- ----- 3-12 # ----- ----- ----- 8 # @ 150 C/C 8 # @ 100 C/C NOT MORE THAN 50 % OF BARS SHALL BE OVERLAP AT A SECTION.
X
5' HB 150 SLAB THICK 2-12 # ----- ----- 2-12 # ----- ----- ----- 8 # @ 150 C/C 8 # @ 100 C/C PROVIDE CONFINING LATERAL TIES 8 # @ 100 MM C/C IN COLUMN
PB1 PB2
ABOVE AND BELOW BEAM UPTO 500 MM AS SHOWN IN SECTION.
PB3
STEEL GRADE TO BE USED MUST BE Fe 500.
FOR ALL OTHER DIMENSIONS AND LEVELS ,REFER
BED ARCHITECTURAL DETAILS.
PASSAGE BEDROOM
PB2 S1 PB2 5' 13' REFER RELEVENT I.S. CODES FOR EXECUTION & QUALITY CONTROL.
W X
11''
PB1 S2 IF IN DOUBT, ASK UNDERSIGNED.
THE COARSE AGGREGATE & FINE AGGREGATES MUST BE CLEAN,
PB1
FREE OF DUST & OIL.
WATER USED SHOULD BE CLEAN & POTABLE.
PB2
S2
PB2
C.TOILET
8'
SCHEDULE OF SLABS :
CEMENT USED SHOULD BE FRESH & GOOD QUALITY.
X
4'3"'
SLAB THICK MAIN SPAN REINFORCEMENT OTHER SPAN REINFORCEMENT ALL CONCRETE SHOULD BE WELL MIXED & VIBRATED WITH NEEDLE VIBRATOR.
PB3 PB2 PB1
TYPE -NESS REMARKS
MAIN REINF. EXTRA TOP BENT @ MAIN REINF. EXTRA TOP BENT @ CONCRETE COVER : (FOR MILD ENVIRONMENTAL CONDITIONS )

PB2 S1 KITCHEN UTILITY S1 100 8 # @ 300 C/C 8 # @ 300 C/C L/5, L/5 8 # @ 300 C/C 8 # @ 300 C/C L/5, L/5 TWO WAY SLAB S.N. STRCUTURAL ELEMENT TYPE COVER IN MM
&
PB2 DINNING
S2 100 8 # @ 300 C/C ----- ----- 8 # @ 300 C/C ----- ----- SINGLE JALI SLAB 1 PILES / PILE CAPS 75
16'3"
X
10' 2 RAFT FOUNDATION 75
PB2 PB1
2 ISOLATED FOOTING 50

3 COLUMNS/ PEDESTALS 40

4 BEAMS (PLINTH, LINTEL, FLOOR) 25 (SIDE), 40 (BOTTOM)

PB1 S2 PB1 5 BASEMENT / FLOOR SLAB 50 / 20


PB1
S1 DEVELOPEMENT LENGTHS AS PER IS 456 : 2000 (Ld) : FOR M25 / Fe500
UP DRAWING UP
PB1 ROOM
12'1" PARKING
PB2 X 6'1" DIA. OF
14'3" X
BARS IN TENSION (MM) IN COMPRESSION (MM)
PB3 14'10"
PB2
8 MM 388 (390) 311 (315)

10 MM 485 (485) 388 (390)

12 MM 583 (585) 466 (550)

16 MM 777 (780) 621 (625)

20 MM 971 (975) 777 (780)


L1 L2
25 MM 1214 (1215) 971 (975)

(1:100) DETAILS AT PLINTH BEAM LEVEL 32 MM 1554 (1555) 1243 (1245)

40 MM 1942 (1945) 1554 (1555)

B B B SR.
TYPE OF FORM & SPAN MINIMUM PERIOD BEFORE DESHUTTERING
ALT.BENT UP @ 0.2 MAINSPAN ALT.BENT UP @ 0.2 MAINSPAN NO. (EXCLUDING THE DAY OF CASTING)
ALT.BENT UP@ 0.2 X OTHER SPAN
1 SLAB SPANS UPTO 4.50 M 07 DAYS
2 SLAB SPANS ABOVE 4.50 M 14 DAYS
3 BEAM SPANS UPTO 6.00 M 14 DAYS
TYPICAL DETAILS OF SLABS ( SINGLE JALI) 4 BEAM SPANS ABOVE 6.00 M 21 DAYS
5 WALL/BEAM/COLUMN VERTICAL FACES 01 DAY

STRUCTURAL DESIGNER SHALL NOT REMAIN RESPONSIBLE FOR FOLLOWING:


L1 L2
1. SAFETY OF ANY ADJOINING BUILDING AND PEOPLE LIVING IN IT & PROPERTIES
ON ADJOINING ROAD.
2. SAFETY OF OLD STRUCTURE DURING EXCAVATION OR DEMOLITION.
B B B 3. SAFETY OF ANY STRUCTURE OTHER THAN THIS DRAWING SCAFFOLDING OR
MAIN SPAN R/F MAIN SPAN R/F OTHER SPAN R/F SHUTTERING ERECTED AT SITE AND UNFORTUNATE ACCIDENTS.
OTHER SPAN R/F
4. SUPERVISION WILL BE PROVIDED IF ASKED TO THE EXTENT OF INSPECTION
OF REINFORCEMENT ON SITE.
TYPICAL DETAILS OF SLABS ( SINGLE JALI)
5. RESPONSIBILITY OF CORRECT AND SOUND CONSTRUCTION SHALL
SOLELY REST WITH CONTRACTOR / BUILDER / OWNER.

SECONDARY BEAM

Ld Ld
D

75
10 EXT
300 # @ RA
BENT UP HANGER TYPE BARS 25 TOP
0C
MAIN BEAM 2-12 # / AS SPECIFIED /C
13
5
HANGER BAR AT THE JUNCTION AL 10 #
T.B @
EN 12
TU 5C ST 0.
CLOSELY SPACED RINGS P /C 25
NOMINAL VERTICAL RINGS @ L
8 # @ 100 C/C / AS SPEC. 0.2
L
0.2
0L
D

STAIRCASE DETALS PB42


Ld IN TENSION SECTION @ X-X

TENSION SPLICE IN BEAMS

SHEET : 1
CONCRETE GRADE : M25 REIN. STEEL GRADE : Fe500
ARCHITECT :
MANAN BELE
L1 L2

SECONDARY BEAM
0.25L2 0.25L2
PROVIDE HANGER BARS 2-12#
0.25L1 0.25L1
TStr TStr+Text TStr TStr+Text >50
TStr+Text TStr+Text STRUCTURAL CONSULTANT :
BEAM
>50
CEAD CONSULTANCY
D1 NOMINAL RINGS NOMINAL V.S.
Er. Swapnil Bokade
D2
PLOT NO 28 JAYRAJ NAGAR TUKUM CHANDRAPUR
END COLUMN MO. NO 9370089519
0.7L1
BStr BStr+Bext BStr 0.7L2
BStr PROJECT :
2D1 2D1 BStr+Bext BStr PROPOSED RESIDENTIAL SCHEME
CONFINING RINGS CONFINING RINGS 2D2 2D2
8 # @ 100 C/C 8 # @ 100 C/C ANCHORAGE DETAILS FOR MR.ANIL SHARMA
BEAM-1 CONFINING RINGS BEAM-2 CONFINING RINGS
8 # @ 100 C/C 8 # @ 100 C/C
END BEAM & COLUMN JUNCTION
TITLE :
DETAILS AT PLINTH BEAM LEVEL
SWAPNIL
TYPICAL SECTION OF BEAM WITH REINFORCEMENT CURTAILMENT ANALYZED BY:
SCALE : 1:100, 1:25
DESIGNED BY: SWAPNIL
ADM/TR1/04
M25 DEALT :
DATE : 30/08/2021
REVISION: ORIGINAL

CHECKED BY : SWAPNIL PATH : ...................


Fe500 VERIFIED BY : SWAPNIL