You are on page 1of 4

engineers newsletter providing insights for today’s

hvac system designer

As Equipment Evolves, So Must Piping Practices …


Split Systems And Interconnecting Refrigerant Lines
from the editor … Some of the piping techniques These limits promote stable
This newsletter was originally published discussed in this newsletter wouldn’t performance over the system’s entire
in December 1998. We reviewed and have been considered good practice in operating range.
updated its content to complement an the past, but they work best and most

Engineers Newsletter Live telecast, reliably for modern commercial Trane
Select the system using design
which airs on December 5, 2001. equipment with scroll compressors.
conditions and check for proper
operation at the expected operating
This Engineers Newsletter previews
extremes.
The efficiency and reliability of an R-22, the selection and refrigerant piping
split air-conditioning system hinges guidelines now recommended for ■
largely on the piping that connects the Trane’s current line of commercial split- Avoid using hot gas bypass in comfort
refrigerant-condensing and air-handling system/scroll-compressor equipment. cooling applications. It squanders
sides of the system. Operational energy and is seldom necessary for
difficulties are inevitable if this properly designed systems. If coil-
interconnecting piping is improperly “Double risers frosting is a concern, consider adding
designed or installed, regardless of an evaporator defrost control such as
and riser traps are
how carefully the equipment was Frostat™ coil frost protection.
selected and applied. good examples of
conventional piping
Interconnecting piping designs that
successfully avoid these difficulties practices no longer Interconnecting Piping
share several common traits: needed …” Keep these general guidelines in mind
as you review the recommendations
■ specific to suction, liquid, discharge and
A simple, direct layout that reduces the hot gas bypass lines:
amount of system refrigerant.

■ ■

A refrigerant tube size that consistently Limit overall line length, including the
Equipment Selection vertical suction and liquid risers.
returns oil to the compressors.
The success of any HVAC application Enough subcooling may be lost as
■ begins with choosing the right system refrigerant travels up the liquid riser to
A refrigerant tube size that doesn’t and properly sizing the equipment. If a cause flashing. Review any
cause excessive pressure drops which split air-conditioning system best suits questionable applications with the
reduce compressor efficiency and the project, then observe these manufacturer.
capacity. guidelines:

Use Type L copper tubing for R-22. For

copper-to-copper joints, use BCuP-6
Base your selection on a minimum coil
without flux. For copper-to-steel or
suction temperature of 40°F for
copper-to-brass joints, use BAg-28 with
constant-volume systems and 43°F for
a non-acid flux.
variable-air-volume (VAV) systems.

© 2001 American Standard Inc. All rights reserved Volume 27, No. 4 (Revised) ■
■ Figure 1.
Rely on the equipment manufacturer to Recommended Suction-Line Arrangements from Evaporator Headers
size the refrigerant lines. Only they To compressor located above evaporator
know how the units interact with the
system components. Height of common riser exceeds
height of evaporator

If the manufacturer has not sized the
refrigerant lines, use pipe sizing
software such as Trane™ Engineering
Toolbox to quickly determine proper
sizes for refrigerant lines based on
current engineering data.
Evaporator headers join at a point lower than the
Suction Line. Pressure drop in the lowest suction header outlet

suction line adversely affects unit


capacity and efficiency. A pressure drop To compressor located below evaporator
of 6 psid in matched commercial Trane
RAUC units reduces system capacity
by 2.5 percent and efficiency by ■ suction lines from the evaporator
1.5 percent over the standard 3 psid Double risers are unnecessary. The headers should join at a point lower
design. steps of unloading for commercial than the lowest suction header outlet.
Trane units with scroll compressors are This arrangement drains the coils and
With that in mind, consider these such that a single, carefully selected prevents oil and refrigerant from
suction-line recommendations: riser can maintain oil circulation at any “backfeeding” from one coil to the
load condition. other(s).

■ The common connection should then
Route the suction line from the
Even the most careful installation rise above the height of the coil before
evaporator to the compressor by the
allows foreign matter into the system. proceeding to the compressor to
shortest path.
That’s why it’s critical to install suction prevent the refrigerant and oil in the
■ filters and properly maintain them. evaporator from “free-draining” toward
Use different pipe sizes for horizontal Once cleanup is complete, a fresh core the compressor.
and vertical lines to make it easier to should be installed in the shell to

match line pressure drop and prevent oil trapping.
Provide a 1-inch pitch toward the
refrigerant velocity to suction-line
■ evaporator for every 10 feet of run to
requirements.
Figure 1 illustrates one method of prevent any refrigerant that condenses
■ trapping the evaporator coil. The in the suction line from flowing to the
To assure proper oil entrainment and compressor when the unit is off.
avoid sound transmission, size the
Table 1. ■
suction line so that the refrigerant
Minimum Suction-Line Velocities Specify suction-line insulation if
velocity equals or exceeds the required
for Oil Entrainment moisture condensation and dripping
minimum velocity stated in Table 1 and
Refrigerant Velocity, fpm pose a problem, or to prevent
remains below 4,000 fpm. Nominal
Pipe Size, in. Riser Horizontal refrigerant from condensing inside the
■ lines if long runs will be exposed to low
1-1/8 700 525
Riser traps are unnecessary. If the riser temperatures.
1-3/8 780 585
is properly sized to maintain velocity,
1-5/8 840 630 ■
adding a trap only increases the
2-1/8 980 735 Don’t install suction lines underground.
suction-line pressure drop.
2-5/8 1080 810
The likelihood of corrosion, vibration,
condensation of water outside—and
3-1/8 1180 885
refrigerant inside—the line, combined

■ 2 Trane Engineers Newsletter — Vol. 27, No. 4


with inaccessibility and difficulty in stops. The liquid refrigerant will determine whether the system is
maintaining cleanliness, make this eventually drain down the line and may properly charged! Instead, either
practice unwise. If underground fill the condenser … perhaps even charge the system based on the
installation is unavoidable, make overflow to the compressor. Sloping required subcooling or calculate the
provisions to insulate, waterproof and the liquid line toward the evaporator amount of refrigerant needed and add it
encase the lines in a hard sleeve. creates a gas trap at the line’s highest based on weight.
point, preventing liquid refrigerant from
Liquid Line. Sufficient subcooling passing. Discharge Line. Limit the pressure
must be maintained at the expansion drop in the discharge line to 6 psid

valve. To provide proper operation whenever possible to minimize the
Solenoid valves are required. They
throughout the range of operating adverse effect on unit capacity and
prevent liquid refrigerant from filling the
conditions, the liquid-line pressure drop efficiency. While a pressure drop of as
evaporator when the compressor stops
should not exceed the unit’s minimum much as 10 psid is usually permissible,
and slugging when the compressor
subcooling value less 5°F. To achieve note that a 6-psid pressure drop
restarts. Adding solenoid valves also
this objective, keep these liquid-line reduces unit capacity by 0.9 percent
prevents siphoning which could allow
considerations in mind: and efficiency by 3 percent.
an elevated column of liquid to
overcome the gas trap and flow back
■ To design the discharge line properly,
into the condenser and compressor.
Select the smallest, practical line size follow the guidelines recommended
for the application. Limiting the below:
refrigerant charge improves
compressor reliability. ■
“It’s prudent to
Choose the shortest route from the

avoid hot gas bypass compressor to the condenser.
When designing the liquid line for a
typical air-conditioning application (i.e. in comfort cooling ■
one with an operating range of 40°F to applications, especially Use different pipe sizes for horizontal
115°F), remember that every 10 feet of and vertical lines to make it easier to
vertical rise will reduce subcooling by
those with variable-air- match line pressure drop and
2.8°F, while every 10 feet of vertical volume (VAV) systems.” refrigerant velocity to discharge-line
drop will add 1.1°F of subcooling. requirements.

■ ■
Specify one expansion valve per To assure proper oil entrainment and

distributor. An expansion valve serving avoid sound transmission, size the
If the liquid line must be routed through
more than one distributor will distribute discharge line so that refrigerant
an area warmer than outdoor air
the refrigerant unevenly. velocity equals or exceeds the
temperature, insulate the line to
minimum velocity in Table 2 and
■ prevent the refrigerant from flashing.
remains below 3,500 fpm.
Provide a 1-inch pitch toward the

evaporator for every 10 feet of run. ■
Be sure to include a replaceable-core
Since this pitch equals that of the Prevent oil and condensed refrigerant
filter drier to permit proper system
suction line, the two may be run from flowing back into the compressor
cleanup and moisture removal. The
together. during “off” cycles by: (a) pitching the
core should be changed whenever the
discharge line toward the condenser
If the system is designed with a liquid system is opened for service.
and (b) routing the discharge line so
line rise, a column of liquid refrigerant
■ that it rises to the top of the condenser,
remains atop the volume of refrigerant
Consider adding a moisture-indicating then drops to the level of the
gas in the condenser whenever the unit
sight glass to permit a visual check of condenser inlet, creating an inverted
the liquid column for bubbles. However, trap.
never use the sight glass to

“providing insights for today’s HVAC system designer” 3 ■


■ For other types of applications, observe
Double risers are unnecessary. The these guidelines:
scroll compressors in current Trane
commercial units unload to the extent ■
that a single, properly sized riser can Size the HGBP line to carry only the
transport oil at any load condition. desired amount of gas at a pressure
drop equalling the sum (usually 20 to Bottom Line …

40 psid) of the pressure drops for the Reliability determines the success of a
Riser traps are also unnecessary. Avoid split air-conditioning system.
discharge line plus the condenser and
using riser traps. If the discharge riser is Interconnecting refrigerant lines play an
subcooler plus the liquid line.
sized to maintain the proper refrigerant instrumental role in that success. It’s up
Oversizing the line can cause the HGBP
velocity, adding a trap will only increase to us to ensure that our system design
and thermal expansion valves to
the pressure drop. practices evolve with equipment
“hunt.”
technologies.

Hot Gas Bypass Line. “Hot gas
bypass” (HGBP) describes the To assure proper oil entrainment, size This article revisited split-system
refrigerant system design historically the HGBP line so that refrigerant application guidelines in light of current
used to provide stable operation at low velocity equals or exceeds the scroll compressor technology. They can
loads while avoiding coil freeze-up and minimum velocity recommended in be summarized as five fundamental
compressor cycling problems. When Table 2. “rules”:
the load falls below the compressor’s ■
minimum stage of loading, the Elevate the HGBP valve above the 1 Choose the right system, i.e. don’t
modulating HGBP valve attempts to discharge line and the distributor inlet specify split-system equipment
maintain suction pressure by diverting to promote free drainage away from when a chiller is best suited for the
hot gas from the compressor discharge the HGBP valve and toward the job.
to the evaporator inlet. distributor or discharge line. 2 Size the interconnecting lines to
■ avoid the use of traps and double
This strategy reduces the system’s
Insulate the HGBP line to prevent the risers.
cooling capacity since the diverted
refrigerant bypasses the evaporator. It refrigerant from condensing during low 3 Slope the suction and liquid lines
also increases compressor energy loads. toward the evaporator.
consumption significantly and can
4 Minimize the length of the
cause unstable operation if improperly Table 2. Minimum Discharge-Line
Velocities for Oil Entrainment interconnecting tubing.
applied.
Refrigerant Velocity, fpm 5 Keep the system clean. ■
Nominal
It’s good design practice to avoid hot Pipe Size, in. Riser Horizontal
gas bypass for comfort cooling 7/8 375 285 By Paul Solberg, applications engineer,
applications, particularly those with 1-1/8 430 325 and Brenda Bradley, information
variable-air-volume (VAV) systems. designer, Trane.
1-3/8 480 360
1-5/8 520 390
2-1/8 600 450
If you’d like to comment on this
article, send a note to Trane, Engineers
Newsletter Editor, 3600 Pammel Creek
Road, La Crosse WI 54601, or e-mail us
at comfort@trane.com.

An American Standard Company


www.trane.com
Trane believes the facts and suggestions presented here to be accurate. However,
For more information, contact your
local district office or e-mail us at final design and application decisions are your responsibility. Trane disclaims
comfort@trane.com any responsibility for actions taken on the material presented.

■ 4 ENEWS-27/4 (Revised)

You might also like