Professional Documents
Culture Documents
■ ■
A refrigerant tube size that consistently Limit overall line length, including the
Equipment Selection vertical suction and liquid risers.
returns oil to the compressors.
The success of any HVAC application Enough subcooling may be lost as
■ begins with choosing the right system refrigerant travels up the liquid riser to
A refrigerant tube size that doesn’t and properly sizing the equipment. If a cause flashing. Review any
cause excessive pressure drops which split air-conditioning system best suits questionable applications with the
reduce compressor efficiency and the project, then observe these manufacturer.
capacity. guidelines:
■
Use Type L copper tubing for R-22. For
■
copper-to-copper joints, use BCuP-6
Base your selection on a minimum coil
without flux. For copper-to-steel or
suction temperature of 40°F for
copper-to-brass joints, use BAg-28 with
constant-volume systems and 43°F for
a non-acid flux.
variable-air-volume (VAV) systems.
© 2001 American Standard Inc. All rights reserved Volume 27, No. 4 (Revised) ■
■ Figure 1.
Rely on the equipment manufacturer to Recommended Suction-Line Arrangements from Evaporator Headers
size the refrigerant lines. Only they To compressor located above evaporator
know how the units interact with the
system components. Height of common riser exceeds
height of evaporator
■
If the manufacturer has not sized the
refrigerant lines, use pipe sizing
software such as Trane™ Engineering
Toolbox to quickly determine proper
sizes for refrigerant lines based on
current engineering data.
Evaporator headers join at a point lower than the
Suction Line. Pressure drop in the lowest suction header outlet
■ ■
Specify one expansion valve per To assure proper oil entrainment and
■
distributor. An expansion valve serving avoid sound transmission, size the
If the liquid line must be routed through
more than one distributor will distribute discharge line so that refrigerant
an area warmer than outdoor air
the refrigerant unevenly. velocity equals or exceeds the
temperature, insulate the line to
minimum velocity in Table 2 and
■ prevent the refrigerant from flashing.
remains below 3,500 fpm.
Provide a 1-inch pitch toward the
■
evaporator for every 10 feet of run. ■
Be sure to include a replaceable-core
Since this pitch equals that of the Prevent oil and condensed refrigerant
filter drier to permit proper system
suction line, the two may be run from flowing back into the compressor
cleanup and moisture removal. The
together. during “off” cycles by: (a) pitching the
core should be changed whenever the
discharge line toward the condenser
If the system is designed with a liquid system is opened for service.
and (b) routing the discharge line so
line rise, a column of liquid refrigerant
■ that it rises to the top of the condenser,
remains atop the volume of refrigerant
Consider adding a moisture-indicating then drops to the level of the
gas in the condenser whenever the unit
sight glass to permit a visual check of condenser inlet, creating an inverted
the liquid column for bubbles. However, trap.
never use the sight glass to
■ 4 ENEWS-27/4 (Revised)