N7 Series Products

EN B22
“CHIN” indicates ”CHINA”,and ”T” represents “TOMORROW”,
proclaiming its signification-”Tomorrow of China”.

Zhejiang CHINT Electrics Co.,Ltd. (public company, SHA:601877) is


the largest-selling low-voltage electrics manufacturers in China. The company
mainly engages in the research & development, manufacturing and sales of over
100 series low-voltage products with over 10,000 specification, such as
modular Din-rail products, Moulded Case Circuit Breaker, Control products, Relays,
Inverters, Soft Starters, Transformers, Automatic Voltage Regulators, Capacitors,
Switch Disconnections, etc. and provides integrated electrical system solution
for the industries of electric power,machinery, building, communication, HVAC,
metallurgy, petrochemical, railway and etc.

With its worldwide presence of distrbution network,


CHINT is capable of delivering high quality and professional services
for its customers at home and abroad.

CHINT is consistently committed to developing itself into a world-class electric


supplier of integrated system solutions in this era of economic globalization.
By adhering to the development strategy of “internationalization,
High-Technology and Industr8ialization”, the company has persistently devoted
itself to the innovation measures in corporate system, technology, and
management with a vision of offering global customers with high-performance,
intelligent and energy-saving electric products, technologies and services.
CIS Region

Europe

Asia-Pacific

China
West Asia & Africa

Marketing Network
Chint not only has advanced production equipment, strict quality management and innovative research and
development team, but also a worldwide marketing network consisting of 5 international marketing areas,
13 domestic marketing offices, 12 logistics centers, more than 280 specialty stores and more than 1000 sales
companies, which are always ready to provide the users with high-quality professional services.
America

Europe America CIS Region West Asia & Africa Asia-Pacific


CHINT Electric Systems

Solar Farm
Public Cable Net KWH Meter

Microcomputer Protection-
Control Device
Main Station Concentrator
Automatic Meter Reading System Prefabricated Substation

Solar Inverter

HV SF6 Circuit Breaker HV Switch-Disconnector


HV Switchgear
Array Combiner Box
HV Power Transformer Power Transformer

HV Switchgear

GIS

Outdoor HV AC Switch-Disconnector
Distrivuted Solar Inv
HV Power Factor Compensation
HV Power Factor Compensation

HV Current/Voltage Transformer
Power Transformer Power Capicitor

Power Factor Compensation(Outdoor)

Surge Arrester Insulator Reactor

KWH Meter
HV Capacitor

Power of Dedication has transformed CHINT from a simple electric component manufacturer
into a leading electric system solution provider, enabling all users from power transmission,
distribution and usage sectors to access more reliable, secure, energy-saving, precise,
eco-friendly, and intelligent electric products and services.
CHINT highly values all personalized demands of electric power, machinery, construction,
communications, HVAC, metallurgy, petrochemical, railway, and other industries all the time,
and devote itself to facilitating technical innovations and building a green future by
providing users with world-class tailor-made electric system solutions.
Automatic monitoring
and management power system

Modular Din-Rail Device

Intelligent Measurement-
Control Unit
DP Contactor

LV Switchgear Switch Disconnector DCS Intelligent Meter


Power Distribution Apparatus
AVR Switch and Socket

AC Contactor Control Transformer Control Relay

LV Power Factor Compensation


verter Indoor LV AC Disconnector Inverter
Power Factor Intelligent
Measurement-Control Device

LV Capacitor Motor
Soft Starter
Push-button/Indicator Light

Change-over Switch
Motor Starter Motor Protection Device
itch
Sw

LV Current Transformer
vel

Measure
Tra

Panel Meter

Welding Machine Intelligent Motor Control and


Protection Device
N7 Series Products

NA8G Series
Air Circuit Breaker

Page 01

NM7 Series
Moulded Case Circuit Breaker

Page 34

NZ7 Series
Automatic Transfer
Switching Equipment

Page 44

NB7 Series
Miniature Circuit Breaker

Page 55

NB7LE Series
Residual Current Operated
Circuit Breaker

Page 57

NC7 Series AC Contactor

Page 60
N7 Series Products
NA8G
2. Type designation
N A 8G - □/□

No. of poles
(pole 3 may be omitted)

Frame size rated current

Improved product code

Design sequence number

ACB

Company code

3. Operation conditions

3.1 When the ambient air temperature is -5℃ - +40℃ , the


mean value is no greater than +35℃ within 24 hours.
NA8G Series Air Circuit Breaker Note: If the upper limit is higher than +40℃ or lower limit
lower than -5℃ in work, discussions shall be made
1. General between the user and the manufacturer.
3.2 Altitude: not higher than 2000m for the installation site.
With a rated current from 200A to 6300A, and rated 3.3 When the ambient air temperature is +40℃ , the relative
operational voltage 415V, 690V, 50Hz, the NA8G series humidity of the air shall not be higher than 50%;
air circuit breaker (hereinafter referred to as “breaker”) a higher relative humidity is allowed at a lower
is mainly used in the distribution network to distribute temperature; for example, for the wettest month, the
electric energy and protect lines and power equipment maximum relative humidity averaged shall be 90% while
from being damaged by overload, under voltage, short the lowest temperature averaged in that month +20℃ ,
circuit, single-phase grounding and other failures. and special measures shall be taken for the condensation
occasionally produced due to temperature change.
Having art-oriented appearance, high breaking capacity, 3.4 Class of pollution: 3
zero arcover and varities of intellectualized protection 3.5 The installation category of the breaker’ main circuit is IV;
functions, that breaker can be used for selective protection when the rated operational voltage of the main circuit is
with accurate action, no unnecessary power cut, and less than or equal to AC400V, The installation category
better power supply reliability. of the control circuit and auxiliary circuit is Ⅲ, apart
from the similarity between the under voltage release
The product allows the wire to enter or enter from the coil and the intellectual controller’s power transformer
lower port, and the open frame (draw-out) circuit breaker primary coil and the breaker;
has isolation function. When the rated operational voltage of the major loop is
greater than AC400V and less than or equal to AC690V, it is
That breaker can be widely used for power stations, necessary for the control circuit and auxiliary circuit to be
factories, mines and modern tall buildings, especially isolated from the major loop, and the highest operational
the distribution system in the intelligent building, voltage of the control circuit and auxiliary circuit is AC400V,
and also widely used in green projects such as wind the installation category of the control circuit and auxiliary
and solar power generation. circuit being Ⅲ.

This product meets the requirements in


IEC/EN 60947-2

> >> 01
N7 Series Products
NA8G
4. Product structure
Body structure

Wiring terminals of the secondary circuit Shunt release


Closing electromagnet
Under voltage release

OFF pushbutton

Energy storage handle

ON/OFF indication

ON pushbutton

Energy storage motor

Intellectual controller Energy storage indication Operating mechanism

Wiring terminals of the secondary circuit Zero arcover hood

Fault-breaking indicator reset button

Energy storage handle


Breaking button Making button

Breaking/Making indicator Energy storage &


release indicator

Intelligent controller
Data plate

Breaker off and energy storage over Breaker off and no energy storage Breaker off and energy storage over Breaker off and no energy storage

Depress Depress Depress Depress Depress Depress Depress Depress

Energy Energy Energy Energy


storage storage storage storage

02 > >>
N7 Series Products
NA8G

Drawout structure

Wiring terminals of the secondary circuit

Side panel

Safety separator

Baffle push rod

Guide rail
Rocking handle work hole

Extraction draw plate

Rocking handle deposit hole

Position indication Locking device

Connected Connected

Test Test

Disconnected Disconnected

Connected: both main circuit and secondary circuit are connected Test: the main circuit is disconnected,
the safety separator works well,
and the secondary circuit is connected.

Connected

Test

Disconnected

Disconnected: neither main circuit nor secondary circuit is connected

> >> 03
N7 Series Products
NA8G

(1)Draw-out socket placed horizontally (2)Pull out the guide rail

(3)Place the breaker body on the guide rail (4)Move the breaker body onto the guide rail with a snap

(5)Push the breaker body in, and turn the break body to the working position

5. Main technical parameters


5.1 Main technical parameters
Shell grade rated current Inm A 1600 3200 6300
200,400,630,800, 1600,2000,2500,
Rated current In A 4000,5000,6300 6300
1000,1250,1600 2900,3200
Nominal insulation voltage Ui V 690 1000 1000
Rated operational voltage Ue V 415 690 415 690 415
Rated ultimate short circuit breaking capacity Icu kA 50 25 100 65 120
Rated service short circuit breaking capacity Ics kA 40 20 80 65 100
Rated short time withstand current Icw,1s kA 40 20 80 65 100
Frequency of operation (number of times/h) 20 10 10
Mechanical life 3000 3000 2000
Number of operations
Electrical Life 1000 1000 500
Flashover distance mm 0 0 0
Line incoming pattern Wire to enter from the Wire to enter from the Wire to enter from the
upper or lower port upper or lower port upper or lower port

fixed type kg 22/26.5 52.5/66.5 -


Weight (3 poles/4 poles)
draw-out type kg 38/55 98/121 210/233 233
Size(3 poles/4 poles) fixed type 320×(254/324)×258 406×(422/537)×329 -
Height × width × depth draw-out type 351×(282/352)×352 439×(435/550)×445 439×(835/928)×501 439×928×501

04 > >>
N7 Series Products
NA8G
5.2 Capacity-reducing usage
5.2.1 Capacity-reducing at different temperatures
The following table shows the continual current-loading capacity of the circuit breakers and buses in each wiring mode
at the corresponding ambient environment temperatures and under the conditions of the satisfaction of conventional heating
with a similarity in capacity reducing between the breaker connected in a mixed way and the breaker connected horizontally.
Style wiring Draw-out type
mode ambient Front/rear horizontal wiring mode Rear vertical wiring mode
temperature℃
-5~40 45 50 55 60 -5~40 45 50 55 60
200 200 200 200 200 200 200 200 200 200
400 400 400 400 400 400 400 400 400 400
630 630 630 630 550 630 630 630 630 580
1600 800 800 800 800 700 800 800 800 800 700
1000 1000 1000 950 900 1000 1000 1000 950 900
1250 1250 1250 1150 1050 1250 1250 1250 1200 1100
1600 1550 1500 1450 1350 1600 1600 1550 1500 1450
1600 1600 1600 1600 1600 1600 1600 1600 1600 1600
2000 2000 2000 2000 1900 2000 2000 2000 2000 1950
3200 2500 2500 2500 2450 2350 2500 2500 2500 2500 2400
2900 2900 2900 2800 2700 2900 2900 2900 2900 2800
3200 3200 3100 3000 2900 3200 3200 3200 3050 2900
4000 4000 4000 3900 3800 4000 4000 4000 3900 3800
6300 5000 5000 4700 4600 4400 5000 5000 4800 4650 4500
6300 6100 6000 5500 5200 6300 6100 6000 5500 5200
5.2.2 Capacity-reducing at different altitudes
When the altitude is higher than 2000m, there will appear changes in insulation property, cooling performance, pressure,
and the performance can be modified in reference to the following table.
Altitude(m) 2000 3000 4000 5000
Insulation withstand voltage(V) 3500 3000 2500 2000
Insulation voltage(V) 1000 800 700 600
Rated operational voltage(V) 690 580 500 400
Rated operational current(A) 1×In 0.96×In 0.92×In 0.87×In

5.3 Power loss


Power loss is the loss at each pole which is measured when the breaker is charged with the rated current.
Power loss
Breaker type Rated current Draw-out type Fixed type
200 115 45
400 140 80
630 161 100
NA8G-1600 800 215 110
1000 230 120
1250 250 130
1600 460 220
1600 390 170
2000 470 250
NA8G-3200
2500 600 260
2900 600 260
3200 670 420
4000 550 -
NA8G-6300 5000 590 -
6300 950 -

Note: The data and parameters in the above technical documentation results from tests and theoretical calculation,
and can only be used as a general type selection guide.They cannot replace industrial practical experience or proof test.

5.4 Recommended bus for the breaker and recommendation for users to install the buses
Inm(A) NA8G-1600 NA8G-3200 NA8G-6300
In(A) 200 400 630 800 1000 1250 1600 1600 2000 2500 2900 3200 4000 5000 6300
Thickness(mm) 5 5 5 5 5 8 10 6 6 5 10 10 10 10 10
Busbar Width(mm) 20 50 40 50 60 60 60 100 100 100 100 100 100 100 100
Number of buses 1 1 2 2 2 2 2 2 3 4 3 4 5 7 8

> >> 05
N7 Series Products
NA8G
6. Dimensions and connection
NA8G-1600 (In=200A ~1250A) Draw-out type
(horizontal connection is the default by the factory, vertical one to be made by users themselves).

210 36
a

275
149

310
7
351

78.5
95 76

345(Connecting position)
391(Separating position)

Wires connected horizontally


282(3P)
Separator between phases
352(4P) (to be ordered separately)

2-φ6.5

149(3P)
155(4P)
95

2-φ6.5×10
7
35

75.5(4P)
78.5(3P)

95 76
145(3P) 63
215(4P) 345(Connecting position)
4P Central line 391(Separating position)
3P Central line Wires connected vertically
12×φ11(3P) 60
16×φ11(4P)
15

25
N Pole
In(A) a(mm) Note: If users intend to change the
35

200, 400, 630 5 horizontal connection into vertical one


76 76 76 800, 1000 10 on site, they need to replace the upper
1250 15
Drawing illustrating the distance between mounting holes and lower buses on both sides with
the same one as the central bus.

NA8G-1600 (In=1600A) Draw-out type


(horizontal connection is the default by the factory, vertical one to be made by users themselves).

210 36 Separator between phases


(to be ordered separately)
15

275
310
179

7
351

63.5

95 76

435(Connecting position)
481(Separating position)
282(3P)
352(4P)
Wires connected horizontally

Separator between phases


2-φ6.5
(to be ordered separately)
95

2-φ6.5×10
35

149(3P)
155(4P)

145(3P) 63 7
215(4P)
78.5(3P)
75.5(4P)

4P Central line
3P Central line 95 76
24×φ11(3P) 85
15

32×φ11(4P) 35
N pole 435(Connecting position)
481(Separating position)
35

80.5

Wires connected vertically


Note: If users intend to change the
horizontal connection into vertical one
on site, they need to replace the upper
101 101 101
Drawing illustrating the distance between mounting holes
and lower buses on both sides with
the same one as the central bus.

06 > >>
N7 Series Products
NA8G

NA8G-1600 (200A~1250A) Fixed type


(horizontal connection is the default by the factory, vertical one to be made by users themselves).

210 22
Separator between phases
(to be ordered separately)

a
320

149
281
275
7

48.5
100 92
237(3P) 251
307(4P)
254(3P) Wires connected horizontally
324(4P)

Separator between phases


(to be ordered separately)
4-φ7
100

149(3P)
155(4P)
237(3P)
307(4P)
7
48.5(3P)
45.5(4P)

100 92
4P Central line
251
12×φ11(3P) 3P Central line
16×φ11(4P) 60 Wires connected vertically
N Pole 25
15

Note: If users intend to change the


35

In(A) a(mm)
horizontal connection into vertical one
76 76 76
200, 400, 630 5 on site, they need to replace the upper
Drawing illustrating the distance between mounting holes 800, 1000 10 and lower buses on both sides with
1250 15 the same one as the central bus.

NA8G-1600 (In=1600A) Fixed type


(horizontal connection is the default by the factory, vertical one to be made by users themselves).

210 22

Separator between phases


(to be ordered separately)
320

275

149(3P)

155(4P)
281

7
48.5(3P)
45.5(4P)

237(3P) 100 92
307(4P) 341
254(3P)
324(4P) Wires connected vertically

4-φ7
100

Separator between phases


(to be ordered separately)
237(3P)
307(4P)
15

4P Central line
3P Central line
179

24-φ11(3P)
32-φ11(4P) 85
15

N Pole 35
7
35

80.5

33.5

100 92 Note: If users intend to change the


341
101 101 101
horizontal connection into vertical one
Wires connected horizontally
on site, they need to replace the upper
Drawing illustrating the distance between mounting holes
and lower buses on both sides with
the same one as the central bus.

> >> 07
N7 Series Products
NA8G
NA8G-1600 Draw-out type NA8G-1600 Fixed type
Size of the hole to be drilled on the panel Size of the hole to be drilled on the panel

220 220
10-φ5 8-φ5
118
120

322

285
320

Breaker mounting panel Breaker mounting panel


118

6
78 118.5

From the center of the mounting hole on the right side of the breaker From the center of the mounting hole on the right side of the breaker
258 258

NA8G-3200 Draw-out type


size of the hole to be drilled on the panel

217.5(3P) 217.5
332.5(4P) 52 386 7
385
240

258
Datum line 2
199.5

Datum line 1

308

371
328
155

11×17
φ11
175

Datum line 2

φ14
268
376

φ1 4 7
11×1
18
145

21.5
97

Installation panel
10

47

162.5(3P) 162.5 10×φ6


277.5(4P) Datum line 1
Datum line
Size of the hole to be drilled on the panel

08 > >>
N7 Series Products
NA8G

NA8G-3200(In=1600A~2500A) Draw-out type


(horizontal connection is the default by the factory).

52

78 50 φ11
25

14

29
133

115 115 115

Datum line
84

445(Connecting position)
492(Separating position)

Note: If users want to change the horizontal connection into vertical one on site, they only have to turn the bus by 90°

NA8G-3200(In=1600A~2500A) Draw-out type


(vertical connection to be made by users themselves).

42
25
14

φ11
78
55

115 115 115

Datum line
25

445(Connecting position)
57.5

492(Separating position)

Note: If users want to change the vertical connection into horizontal one on site, they only have to turn the bus by 90°

NA8G-3200 Draw-out type; Front connection

C 86 25 12-φ13
15
29

115 115 115


Datum line
301

In(A) C
1600, 2000, 2500 20
2900, 3200 30
29

16.5

> >> 09
N7 Series Products
NA8G
NA8G-3200(In=2900, 3200A) Draw-out type (horizontal connection is the default by the factory)

C
7

52
C
25

φ11 100 25

29
14
112

126 126 126

Datum line
90

445(Connecting position)
492(Separating position)

NA8G-3200(In=2900、 3200A) Draw-out type (vertical connection to be made by users themselves)

C 7
52

14
φ11 C
25
100
57

115 115 115

Datum line
25

35.5

445(Connecting position)
492(Separating position)

Note: If users want to change the horizontal connection into vertical one on site,
it is necessary to replace the upper and lower buses for the N and B phases with the same one as the A and C phases.

NA8G-3200 Fixed type

308

N
402
258
Datum line 2
163.5
13

11 200(3P) 200 11 246 44 7


315(4P)
Datum line 1

10 > >>
N7 Series Products
NA8G
NA8G-3200 Fixed type, size of the hole to be drilled on the panel

4×φ 12 371
328
150

311
268
72.5

29.5
21.5
200(3P) 200
8×φ6
315(4P) Installation
panel
Datum line Datum line

NA8G-3200 Fixed type (horizontal connection is the default by the factory)

Ferrous materia l

C
32

C
a

86 50 12-φ13
18.5
112

In(A) a(mm)
115 115 115 1600~2500 20
Datum line 2900~3200 30
55

Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.

NA8G-3200 Fixed type (vertical connection to be made by users themselves)

Ferrous materia l

C
32
29
a C
14
φ11
100
57

115 115 115


In(A) a(mm)
1600~2500 20
25
55

Datum line
2900~3200 30
45

Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.

> >> 11
N7 Series Products
NA8G
NA8G-6300 In=(4000A~5000A) Draw-out type
size of the hole to be drilled on the panel

710.5(4P)
232 617.5(3P) 217.5 391

Datum line 2
199

Datum line 1

371
328

φ14

155
175

268
11×17

376

Datum line 2
145

18
97

162.5

21.5
703(3P)

47
10×φ6
Datum line 1
Datum line 1
818(4P)
Size of the hole to be drilled on the panel

NA8G-6300 In=(6300A) Draw-out type


size of the hole to be drilled on the panel

710.5 217.5 391 7


240

Datum line 2
199

Datum line 1

371
328

φ14
155
175

268

11×17
376

Datum line 2
145

18
97

162.5
21.5

818
47

10×φ6
Datum line 1
Datum line 1

Size of the hole to be drilled on the panel

12 > >>
N7 Series Products
NA8G
NA8G-6300(In=4000A~5000A) Draw-out type
(vertical connection to be made by users themselves)

29
115 N pole
φ11 103 129.5 105 142 105 142 105
125 30

25
57

14
10.5

Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.

NA8G-6300(In=4000A~5000A) Draw-out type


(horizontal connection is the default by the factory)

N pole
28-Φ13
100 155 210

20
40
103
30
112

55
182 247 247 170.5
92

Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.

NA8G-6300(In=6300A) Draw-out type


(vertical connection to be made by users themselves)

14
115
φ11 103 130 207 130 207 130
30
125

25
57

29
10.5

Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.

NA8G-6300(In=63000A) Draw-out type


horizontal connection is the default by the factory

180 260
20
40
103
112 30

24-Φ13

80
320 320 140
92

Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.

> >> 13
N7 Series Products
NA8G
7. Secondary circuit wiring

Connection diagram for the secondary circuit of the NA8G-1600 optional standard type intellectual controller

Fault indication
N A B C

HL2 HL3 HL4


HL1 SB2 SB1

XT 3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55 FU

Breaker body

M L1
QF F DT Q/QY
SAL
Intellectual controller
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12 Control power supply

SA L2(N)
TA

FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

+DC24V -
S

Power
Energy -driven ON OFF
Main circuit Intellectual controller Open Close Under storage
energy indication indication Auxiliary contact available for users AC auxiliary contact for standby application
voltage indication storage

DT——closing electromagnet F——shunt release Q/QY—under voltage release SAL—sensitive switch


SA——travel switch M——energy storage motor DF1 - DF12—auxiliary contact FU—fuse
SB1~SB2——pushbutton HL1~HL4——indicator light XT—connection terminal TA—current transformer
QF——breaker S——power module
#
1 and #2: input (terminals) for intellectual controller auxiliary power supply
# # # #
4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)

Notes: 1. Four open (contacts) and four close from DF1 to DF8
with a common point available conventionally, two open
and two close from DF9 to DF12 with a common point available
additionally for Inm = 1600 when special order is made
for alternating current, four open and four close from
DF1 to DF8 with a common point available only for
Inm = 1600 in case of direct current,
contact capacity (DC220V 0.5A).
2. Various control voltages of the 1600 has to be put
to #1 and #2 after the power module inputs DC24V.
3. The wiring for the part indicated by dashed lines shall be made by users.

14 > >>
N7 Series Products
NA8G

Connection diagram for the secondary circuit of the NA8G-3200 to 6300 optional standard type intellectual controller

Fault indication
N A B C

HL2 HL3 HL4


HL1 SB2 SB1

XT 3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
FU

Breaker body

M L1
QF F DT Q/QY
SAL Intellectual controller
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12 Control power supply
SA L2(N)
TA

FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

3200 and 6300 shell controller power supply: AC230V and AC400V
+DC24V -
S
3200, 6300 shell controller power supply: DC220V,DC110V; 1600 shell controller power supply
Power
Under Energy -driven ON OFF
Main circuit Intellectual controller Open Close storage
voltage indication energy indication indication
Auxiliary contact available for users AC auxiliary contact for standby application
storage

DT——closing electromagnet F——shunt release Q/QY—under voltage release SAL—sensitive switch


SA——travel switch M——energy storage motor DF1 - DF12—auxiliary contact FU—fuse
SB1~SB2——pushbutton HL1~HL4——indicator light XT—connection terminal TA—current transformer
QF——breaker S——power module
#
1 and #2: input (terminals) for intellectual controller auxiliary power supply
# # # #
4, 5 and 6: faulty tripping contact output ( 5 is the common terminal, AC250V 5A)

Notes: 1. Four open (contacts) and four close from DF1 to DF8
with a common point available conventionally, one open and
one close from DF9 to DF10 with a common point available additionally,
contact capacity (DC220V 0.5A)
2. When the controller voltage of the 3200 and 6300 shells
is AC230V/400V, it can be directly put to #1 and #2; if the voltage
is DC220V/110V, it has to be put to #1 and #2 after the power module inputs DC24V.
3. The wiring of the part indicated by dashed lines shall be made by users.

> >> 15
N7 Series Products
NA8G

Connection diagram for the secondary circuit of the NA8G-1600 optional type multifunctional controller

FU
L1
N
PE

L N PE
Profibus-DP
ST-4 power module
- + - + - + - +
ST-DP
Device
12 13 14 15 16 17 18 19

N A B C
Fault indication 1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V
ST201 SB2 SB1

D01 D02 D03

HL1 12 13 14 15 16 17 HL2 HL3 HL4

Green Red

XT 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55

PE
QF M
D14 F DT Q/QY
Intellectual controller
SAL D13 D15 D16
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12

SA
TA
Breaker body

XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

+DC24V-
S

Power
Under Energy -driven ON OFF
Main circuit Intellectual controller Open Close voltage
storage
energy indication indication
Auxiliary contact available for users AC auxiliary contact for standby application
indication
storage

DT——closing electromagnet F——shunt release Q/QY—under voltage release SAL—sensitive switch


SA——travel switch M——energy storage motor DF1 - DF12—auxiliary contact FU—fuse
SB1~SB2——pushbutton HL1~HL4——indicator light XT—connection terminal TA—current transformer
QF——breaker S——power module ST-DP —communication module ST201—relay module (optional)
ST-4——power module (optional)

# #
1 and 2: input (terminals) for intellectual controller auxiliary power supply
#
3:PE
#
4, #5 and #6: faulty tripping contact output ( #5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliary contact output ( #8 is the common terminal, AC250V 5A)
#
10, #11 and #12: auxiliary contact output ( #11 is the common terminal, AC250V 5A)
#
14 and #15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V,5A)
#
20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
#
24 and #25: to be externally connected to the mutual inductor input

Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally,
two open and two close from DF9 to DF12 with a common point available additionally for Inm = 1600 when
special order is made for alternating current. Four open (contacts) and four close from DF1 to DF8 with a
common point available only for Inm = 1600 in case of direct current, contact capacity (AC250V 5A).
2. The wiring of the part indicated by dashed lines to be made by users.

16 > >>
N7 Series Products
NA8G

Connection diagram for the secondary circuit of the NA8G-3200 and 6300 optional type multifunctional intellectual controller

FU
L1
N
PE

L N PE
Profibus-DP
ST-4 power module
- + - + - + - +
ST-DP
Device
12 13 14 15 16 17 18 19

N A B C
Fault indication 1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V
ST201 SB2 SB1

D01 D02 D03

HL1 12 13 14 15 16 17 HL2 HL3 HL4

Green Red

XT 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55

PE
QF M
D14 F DT Q/QY
Intellectual controller
SAL D13 D15 D16
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12

SA
TA
Breaker body

XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56

3200 and 6300 shell controller power supply: AC230V and AC400V
+ DC24V -
S

3200, 6300 shell controller power supply: DC220V,DC110V; 1600 shell controller power supply

Power
Under Energy -driven ON OFF Auxiliary contact
Main circuit Intellectual controller Open Close voltage
storage
energy indication indication available for users
AC auxiliary contact for standby application
indication
storage

DT——closing electromagnet F——shunt release Q/QY—under voltage release SAL—sensitive switch


SA——travel switch M——energy storage motor DF1 - DF12—auxiliary contact FU—fuse
SB1~SB2——pushbutton HL1~HL4——indicator light XT—connection terminal TA—current transformer
QF——breaker S——power module ST-DP —communication module ST201—relay module (optional)
ST-4——power module (optional)

# #
1 and 2: input (terminals) for intellectual controller auxiliary power supply
#
3:PE
#
4, #5 and #6: faulty tripping contact output ( #5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliary contact output ( #8 is the common terminal, AC250V 5A)
#
10, #11 and #12: auxiliary contact output ( #11 is the common terminal, AC250V 5A)
#
14 and #15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V,5A)
#
20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
#
24 and #25: to be externally connected to the mutual inductor input

Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally,
one open and one close from DF9 to DF10 with a common point available additionally when special order is made
for alternating current. Contact capacity AC250V 5A
2. When the controller voltage of the 3200 and 6300 shells is AC230V/400V, it can be directly put to #1 and #2;
if the voltage is DC220V/110V, it has to be put to #1 and #2 after the power module inputs DC24V.
3. The wiring of the part indicated by the dashed lines shall be made by users.

> >> 17
N7 Series Products
NA8G
8. Intelligent controller and protective characteristics
8.1 User interface of the standard type controller

10

11

12

13

14

15

16

1 LED window LCD window capable of showing the current for each phase, various setting parameters,
rated current, fault current, tripping time, and the like
2 “ Ig ” limp Asymmetric grounding, neutral line fault indication
Over current long time delay fault indication
3 “ IR ” limp
Short-circuit short-time delay fault indication
4 “ Isd ” limp Short-circuit instantaneous fault indication
5 “ Ii ” limp Successively access to submenus at various levels by pressing the MENU key
To inquire the current for each phase at present:
6 “ MENU ” Pushbutton recurrently select the contents in the menus at various levels
Return to previous menu; the intellectual controller software is reset;
7 “ “ Pushbutton
RESET key must be pressed after the encoder switch position is adjusted;
the intellectual controller faulty tripping results in fault memory which
8 “ RESET ” Pushbutton
can be cleared only by pressing the RESET key;
There are (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 0.98, 1.0)In,
nine settings altogether, for the over current long time delay current multiple setting
9 “ IR ” Knob switch There are (1, 2, 4, 8, 12, 16, 20, 24, 30)s, nine settings altogether,
for the over current long time delay time setting in case of 6Ir
10 “ tR ” Knob switch
There are (1.5, 2, 2.5, 3, 4, 5, 6, 8, 10)Ir, nine settings altogether,
11 “ Isd ” Knob switch for the short-circuit short-time delay current multiple setting
For the short-circuit short-time delay time setting, there are nine settings:
12 “ tsd ” Knob switch the inverse time limit, i.e., I2t on(0.1, 0.2, 0.3, 0.4)s, the definite-time limit,
i.e., I2t OFF (0.1 0.2 0.3 0.4)s and X, i.e., closing the short-time delay
13 “ Ig ” Knob switch There are (A, B, C, D, E, F G, H, J), nine settings altogether, for the asymmetric grounding
(neutral line) current multiple setting
For the typical numerical values thereof, see the characteristic parameter table
14 “ test ” Pushbutto n Button for simulating instantaneous tripping test
15 “ tg ” Knob switch For the asymmetric grounding (neutral line) time setting, there are nine settings: the inverse time limit,
i.e., I2t on(0.1, 0.2, 0.3, 0.4)s, and the definite-time limit, i.e., I2t OFF(0.1 0.2 0.3 0.4)s, and X,
i.e., closing the asymmetric grounding (neutral line)
16 “ Ii ” Knob switch Short-circuit instantaneous current multiple setting.

18 > >>
N7 Series Products
NA8G
8.2 Default interface and menu structure for the standard type controller
The default interface for the standard type controller is described as Default interface for the standard type controller
follows (the current for each phase to be selected by pressing “ ”)
Operation method: Press MENU to go to the primary menu,
then press “ ” selection menu, and than press MENU Go to the 158A
secondary menu, press “ ” selection menu or modify the parameter, 150 N A B C
press RESET to return to the previous menu
100

50

Primary menu Secondary menu Third menu


Ia= 1000A
Ib= 1001A
Instantaneous value Ic= 998A
In= 0A
Ig= 0A
Magnitude of current Ia= 1300A
Ib= 1400A Simultaneously press MENU
Ic= 1380A
Maximum and “ ” to reset
In= 200A
Ig= 0A
Current thermal capacitance 0%
Long time delay setting current
Ir=1600A
and long time delay setting time
tr=Is@6Ir
Short time delay setting current
Isd=9600A
short time delay setting time
tsd=0.4s
Instantaneous setting current
Ii=16000A
Grounding setting current
Ig=1600A
Protection parameter
grounding setting time
tg=OFF
Instantaneous
10min
20min
Long time delay thermal capacitance 30min
cooling time = instantaneous 45min
1h
2h
3h
Long time delay protection = open Open
Close
For example: Long time-lag tripping
Ib=2894A
For example, long time-lag tripping actuation time 12.06s
Fault recording
Note: Up to 8 times of failures can be recorded Ir=1600A
the event having taken place, the time being 0:21 on the date of 0

Self-diagnostic alarm Alarm free


Contrast adjustment 45 (default) note: adjustable range from 35 to 60

Notes: a. The actual menu will very depend on the function selected by a user.
b. The controller starts screensaver automatically 10min after it is energized.

> >> 19
N7 Series Products
NA8G
8.3 User interface of the multifunctional controller

5
3
6

10

11

13 12

1 Brand "CHINT" Brand


LCD window capable of showing the current for each phase, various setting parameters, rated current,
2 LED window fault current, tripping time and the like

Switch to the set default menu (left arrow key, when it is necessary to move leftwards or rightwards
3 SET key
for the set interface).
Move the box select menu under the current menu to change the position of said box upwards,
4 UP key
and perform the setting of the parameter ADD in the parameter setup menu.
5 RETURN key Exit the current menu and go to the previous menu, or cancel the value of the current setup parameter.
Go to the next menu of the currently selected select box (go to the set state under the set interface, a
6 ACK key
nd exit the set state by double pressing the key).
Move the box select menu under the current menu to change the position of said box downwards,
7 DOWN key
and perform the setting of the parameter SUBTRACT in the parameter setup menu.
Switch to the inquiry default menu (right arrow key, when it is necessary to move leftwards
8 INQUIRY key
or rightwards for the set interface).
9 “ IR “ limp Over current long time delay fault indication
10 “ Isd “ limp Short-circuit short-time delay fault indication
11 “ test ” Button for simulating instantaneous tripping test
12 “ Ii “ limp Short-circuit instantaneous fault indication
13 “ Ig “ limp Asymmetric grounding, neutral line fault indication

20 > >>
N7 Series Products
NA8G

8.4 Default interface and menu structure for the multifunctional controller Default interface for the multifunctional controller
The multifunctional controller provides 4 title menus (measurement
menu, parameter setup menu, protection parameter setup menu, 1002A
N A B C
and history record and maintenance menu) and 1 default menu. 150

100

50

8.4.1 Structure of the measurement menu

Primary menu Secondary menu Third menu Fourth menu Fifth menu
Ia Ia= 1000A
Ib Ib= 1001A
Ic Ic= 998A
In In= 0A
Ig= 0A or I△n=0.00A
Ia= 1300A
Ib= 1400A
Instantaneous value
Ic= 1380A
Maximum
In= 200A
Ig= 0A or I△n=0.00A
Reset(+/-)
Ia= 3%
Magnitude of currentⅠ Ib= 5%
Unbalance rate
Ic= 1%
Current thermal capacitance 100%
15min
Ia= 1000A
Real-time value
Ib= 1000A
Ia,Ib,
Ic= 998A
Ic,In
In= 0A
Required value Ia= 1050A
Ib= 1040A
Maximum
Ic= 1010A
In= 0A
Reset(+/-)
Uab= 380V
Ubc= 380V
Instantaneous value Uca= 380V
Uan= 220V
Voltage U Ubn= 220V
Ucn= 220V
Mean value Uav= 380V
Unbalance rate 0%
Phase sequence A,B,C
FrequencyF 50Hz
EP= 200kWh
Total electric energy EQ= 10kvarh
ES= 200kVAh
EP= 200kWh
Electric energy E Input electric energy
EQ= 200kvarh
EP= 0kWh
Output electric energy
EQ= 0kvarh
Electric energy reset Reset

> >> 21
N7 Series Products
NA8G

Primary menu Secondary menu Third menu Fourth menu Fifth menu
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
-1.00
Perceptual
Power factor
PFa= 1.00
PFb= 1.00
PFc= 1.00
Instantaneous value Pa= 220kW
Pa, Qa, Sa Qa= 0kvar
Sa= 220kVA
Pb= 220kW
Power P
Pb, Qb, Sb Qb= 0kvar
Sb= 220kVA
Pc= 220kW
Pc, Qc, Sc Qc= 0kvar
Sc= 220kVA
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
Required value P= 661kW
Q= 2kvar
Maximum
S= 662kVA
Reset(+/-)
Ia
Ib
Ia,Ib
Harmonic H Ic,In Ic
In
Waveform
Uan
Uan,Ubn Ubn
Ucn
Ucn

Ia= 1000A
I(A) Ib= 1000A
Ic= 1000A
In= 1000A
Uab= 380V
Base form
Ubc= 380V
U(V) Uca= 380V
Uan= 220V
Ubn= 220V
Ucn= 220V
Ia= 0.0%
Ib= 0.0%
I(%)
Ic= 0.0%
In= 0.0%
Uab= 0.0%
THD
Ubc= 0.0%
Uca= 0.0%
U(%)
Uan= 0.0%
Ubn= 0.0%
Ucn= 0.0%
Ia= 0.0%
Ib= 0.0%
thd I(%)
Ic= 0.0%
In= 0.0%

22 > >>
N7 Series Products
NA8G

Primary menu Secondary menu Third menu Fourth menu Fifth menu
Uab= 0.0%
Ubc= 0.0%
Uca= 0.0%
thd
Uan= 0.0%
U(%)
Ubn= 0.0%
Ucn= 0.0%
Ia FFT THD=0.0%
0.0%
Ia(3, 5, 7...31)
3 5 7 9 11...31)

Ib FFT THD=0.0%
0.0%
Ib(3, 5, 7...31)
3 5 7 9 11...31)
I(3, 5, 7...31)
Ic FFT THD=0.0%
0.0%
Ic(3, 5, 7...31)
3 5 7 9 11...31)

In FFT THD=0.0%
0.0%
In(3, 5, 7...31)
3 5 7 9 11...31)
FFT
Uab FFT THD=0.0%
0.0%
Uab(3, 5, 7...31)
3 5 7 9 11...31)

Ubc FFT THD=0.0%


0.0%
Ubc(3, 5, 7...31)
3 5 7 9 11...31)
U(3, 5, 7...31)
Ubc FFT THD=0.0%
0.0%
Ubc(3, 5. 7...31)
3 5 7 9 11...31)

Uca FFT THD=0.0%


0.0%
Uca(3, 5, 7...31)
3 5 7 9 11...31)

8.4.2 Structure of the parameter setup menu


Primary menu Secondary menu Third menu Fourth menu Fifth menu
Setting of the System type =3Φ4W 4CT
measurement meter Line incoming pattern =Wire to enter from the upper port
Test type =three section protection
Test tripping Test parameter =I:9999A
Test initiation =start
Remote locking Remote locking =unlock
Test & lock
Parameter locking
Parameter locking =locking
Parameter locking
(input) user password User password (change)
=0000 =0000
Address =3
Communication setting
Baud rate =9.6K
=DO1
Function setting
=regional interlocking
=DO1
Executive mode =N.O. pulse
I/O setting
=360s
I/O state
I/O state DO1 DO2 DO3 DI1
1 1 1 1

8.4.3 Structure of the protection parameter setup menu


Primary menu Secondary menu Third menu Fourth menu Fifth menu
Ir e.g.: =1000A=100%In
Current protection e.g.: =ON
Current protection Long time delay
Delay time e.g.: =C1,Is@6Ir
Cooling time e.g.: =3h

> >> 23
N7 Series Products
NA8G

Primary menu Secondary menu Third menu Fourth menu Fifth menu
e.g. =5000A=5.0Ir
Definite-time limit Operating current
e.g. =0.1s
Short-time delay
e.g. =2000A=2.0Ir
Inverse-time limit Delay time
e.g. =C1,0.Is@6Ir
Instantaneous Operating current e.g. =10000A=10.0In
Neutral phase protection Neutral phase protection e.g. =200%
Operating current e.g. =800A
Ground protection Delay time e.g. =0.4s
Coefficient of earthing e.g. =6.0
Current protection Starting current e.g. =600A
Starting time e.g. =0.1s
Grounding alarm
Return current e.g. =100A
Return time e.g. =0.1s
Operating current e.g. =8.0A
Leakage protection
Setup delay time e.g. =0.75s
Starting current e.g. =5.0A
Starting time e.g. =0.1s
Electric leakage alarm
Return current e.g. =4.0A
Return time e.g. =0.1s
Executive mode e.g. =I the first method
Unloading value 1 e.g. =800A
Load Monitoring Unloading time 1 e.g. =50%tr
Unloading value 2 e.g. =700A
Unloading time 2 e.g. =25%tr
Executive mode e.g. =Alarm
Startup value e.g. =200V
Under voltage Starting time e.g. =0.2s
Return value e.g. =320V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =480V
Voltage protection Over voltage Starting time e.g. =1s
Return value e.g. =400V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =10%
U unbalanced Starting time e.g. =1s
Return value e.g. =5%
Return time e.g. =60.0s

8.4.4 Structure of the history record and maintenance menu


Primary menu Secondary menu Third menu Fourth menu Fifth menu
Current alarm e.g. phase sequence alarm, Inverse power alarm, over frequency alarm...
Total number of times e.g.: 300
Number of operations
Number of operations e.g.: 219(ACK key, reset)
Total wear e.g.: 120
Contact wear
lContact wear e.g.: 20(ACK key, reset)
Product information Zhejiang CHINT electrics co., LTD
Under voltage tripping
T=0.20s
Umax=0V
11:24:59
e.g.:
6/17
Tripping record 1 Under voltage tripping
F=0.00Hz
2004/06/17
Uab= 0V
Ubc= 0V
Uca= 0V
...... ......

24 > >>
N7 Series Products
NA8G

Primary menu Secondary menu Third menu Fourth menu Fifth menu
A phase short-circuit definite-time limit
T= 0.4s
I= 4300A
e.g. 15:28:25
8 (for) short-circuit definite-time limit
Tripping record 5/30
2004/05/30
Ia= 4300A
Ib= 4200A
Ic= 4000A
In= 150A
Di input alarm
e.g.
Di1
1 DI (for) DI input alarm 2004/07/16
2004/07/16 20:38:45
Alarm logging ...... ......
e.ge Under voltage alarm
8 Under voltage alarm Umax= 0V
2004/06/20 2004/06/20
Note: Up to 8 times of alarms can be recorded 22:29:40
e.g. local switch on
1 (for) local switch on 2002/06/18
2002/06/18 9:30:56
Position changing record ...... ......
e.g. Test tripping
8 (for) testing tripping
2002/06/15
2002/06/15
10:30:20
Note: Up to 8 times can be recorded

Notes: a. The actual menu will very depend on the function selected by the user.
b. The controller starts screensaver automatically 10min later.
8.5 List of the controller functions
Standard configuration
Standard type (M type) Multifunction type (H type)

1.Quadruple over current protection (for overload, 1.Quadruple over current protection (for overload, short-time delay time,
short-time delay time, instantaneous, grounding); instantaneous, grounding); grounding corresponds to vector sum (T type);
grounding corresponds to vector sum (T type); 2.Parameter setup: fixed value keyboard setting function;
2.Parameter setup: fixed value setting position setting function 3.Current measurement function;
3.Current measurement 4.Current unbalance rate measurement function;
4.Test function; 5.Two test functions:
5.Fault recording function: 8 times of failures can be recorded; (1)Instantaneous tripping test simulated on the panel;
6.Self-diagnostic function; (2)Triple over current, grounding/leakage and operating time tests
7.MCR make/break function; simulated by software;
8.Human-machine interface: 33×22 LCD; 6.Fault recording function: 8 times of failures can be recorded;
9.Heat capacity measurement 7.Self-diagnostic function
8.MCR make/break function
9.Communication function: MODBUS protocol;
10.Alarm logging function;
11.Recording number of operations;
12.Contact wear
13.Position changing record
14.Human-machine interface: 28×43 LCD;
15.Heat capacity measurement

> >> 25
N7 Series Products
NA8G
Heat capacity measurement
Multifunction type (H type)
Standard type (M type)
P Function H Function

1.Voltage measurement; 1.Voltage measurement;


2.Voltage unbalance measurement; 2.Voltage unbalance measurement;
3.Frequency measurement; 3.Frequency measurement;
4.Phase sequence measurement; 4.Phase sequence measurement;
5.Electric energy measurement; 5.Electric energy measurement;
6.Power measurement; 6.Power measurement;
None
7.Power factor measurement; 7.Power factor measurement;
8.Earth-current grounding protection; 8.Earth-current grounding protection;
9.Leakage protection; 9.Leakage protection;
10.Load monitoring function; 10.Load monitoring function;
11.Quadruple D0 output function; 11.Quadruple DO output function;
12.DI input function; 12.DI input function;
13.Regional interlocking function; 13.Regional interlocking function;
14.Under and over voltage protection; 14.Under and over voltage protection;
15.Measurement of harmonic current;
16.Neutral phase protection

8.6 Characteristic parameters of the standard type intelligent controller

Over current protection characteristics


10000

5000

IR=(0.4-1)In
1000

500

200
TR=(1~30)s
100

50

20
T(s) 10
I2t ON
5
2 Isd=(1.5~10)IR
Isd=(1.5~10)IR
1
I2t OFF
0.5

0.2
0.1
Ii=(2~15)In
0.05

0.02
0.01
0.2 0.3 0.5 0.6 0.8 1 2 3 4 5 8 10 20 30 40 50 60 80 1.5 2 3 4 5 6 8 10 20 30

X IR

Neutral line (grounding) fault protection characteristic


10000

5000

Ig=(0.2-1)In
1000 MAX 1200A
MIN 120A
500

200
100

50
20
T(s) 10
I2 ON
5

1
0.5

0.2
0.1
I2 t OFF
0.05
0.02
0.01
0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30

X In

26 > >>
N7 Series Products
NA8G
8.6.1 Over current long time delay characteristic
Rated current range IR Error Line current I Operating time tR(s) Time (delay) error
≤1.05IR No actuation within 2h
>1.30IR <1h and then actuate
(0.4~1)In ±10% 1.5IR 16 32 64 128 192 256 320 384 480
2.0 IR 9 18 36 72 108 144 180 216 270 ±15%
6.0 IR 1 2 4 8 12 16 20 24 30

Explanation for parameter setting

Long-time delay operating current adjustable:


IR=(0.4-0.5-0.6-0.7-0.8-0.9-0.95-0.98-1)×In, IR tR
and there are nine settings for option. (s)
.7 .8 .9 8 12 16
.6 .95 4 20
The long-time delay tripping time represents the inverse-time limit .5 .98 2 24
characteristic, and nine optional settings are readily available for .4 1 1 30
tripping time in case of 6IR: tR=(1-2-4-8-12-16-20-24-30)s. ×In a 6IR

For setting, insert a small slotted screwdriver to the knob groove


as shown in the right drawing, gently turn it to make the arrow
of the knob point at the current and time set as required. Example 1: If it is known that in condition of I=6IR,
As shown in the figure, the over current long time delay protection the tripping time setting value is 2s,
current setting value IR=0.6In,and the delay tripping time is 2s and now the line current I=1.5IR,
(in the condition of 6IR). then the actual tripping time TR can be worked out by:
(1.5IR)2×TR=(6IR)2×2. The answer is obtained as TR=32s.

8.6.2 Short-circuit short-time delay inverse-time or definite-time limit protection


Rated current range Isd Error Line current I Operating time tsd(s) Time (delay) error

<0.85Isd No actuation
> 1.15Isd Time-delay action
I 2t OFF 0.1 0.2 0.3 0.4
(1.5~10)IR
±15% I 2t ON ±15%
+OFF(Power off) 0.1 0.2 0.3 0.4
I>10IR
I 2t ON
anti-time-limit delay:I 2Tsd=(10IR) 2tsd
I≤10IR

Explanation for parameter setting

The short-circuit short-time delay protection operating current adjustable: Isd tsd
3 4 5 (s)
Isd=(1.5-2-2.5-3-4-5-6-8-10)×IR, and there are nine settings for option. .4 .4 .3
2.5 6 .3 .2
There are nine settings for the short-time delay tripping time, wherein 4 2 8 .2 .1
1.5 10 .1 X
settings represent the definite-time limit characteristic (i.e., I2t OFF), ON 2
OFF
×IR It
4 settings the inverse-time limit characteristic, and 1 setting the function
of closing the short-time delay (X).

When the tripping time is set as definite-time limit operating characteristic


Example 2: If it is known that the short-time delay
(i.e., the arrow points at the off area), the tripping time can be selected as
setting current is Isd=3IR,
tsd=0.1s-0.2s-0.3s-0.4s-x (i.e., the function of closing the short-time delay).
then the tripping time is set as tsd=0.2s
in the setting position of inverse
When the tripping time is set as inverse-time limit operating characteristic
time limit (I2t ON). Now the current is 7IR
(i.e., I2t ON), there are two cases: ① the case of I>1.15Isd and I>10IR
in the line current, then the short-time delay tripping time
represents the definite-time limit; ② the case of I>1.15Isd and I≤10IR
can be worked out by calculation:
represents the inverse-time limit characteristic and the actual tripping time
1.5Isd=1.15×3IR=3.45IR
is calculated according to the formula I2Tsd=(10IR)2tsd, wherein I is the
Then I=7IR>1.15Isd
line current, Tsd the actual tripping time, and tsd the setting tripping time.
The method for setting the current and time for the short-circuit And because I=7IR<10IR
short-time delay protection is similar to that for over current long time So according to I2×Tsd=(10I)2tsd
delay protection. As shown in the figure, the current for the short-circuit (7IR)2×Tsd=(10IR)2×0.2
short-time delay protection is 3IR, and the tripping time is set as tsd=0.2s Tsd=0.41s
in the setting position of inverse time limit (I2t ON).

> >> 27
N7 Series Products
NA8G
8.6.3 Short-circuit instantaneous protection

Rated current range Ii Error Line current I Operating Characteristics


(2~15)In ≤0.85Ii no-action
±15%
+OFF(Power off) >1.15Ii action

Explanation for parameter setting

The instantaneous protection operating current is adjustable:


Ii
Ii=[2-3-4-6-8-10-12-15-OFF]×In, and there are nine settings
8
for option. 6 10
4 12
3 15
The method for setting the current for the instantaneous protection 2 Off
is similar to that for over current long time delay protection setting.
As shown in the figure, the instantaneous protection current
setting value is 8In.
8.6.4 Single-phase grounding fault protection
Rated current range Ig Error Line current I Operating time tg(s) Time (delay) error
<0.9Ig no-action
>1.1Ig time-delay action
2
I T OFF 0.1 0.2 0.3 0.4
(A~J)In 2
±10% I T ON
+OFF(Power off) 0.1 0.2 0.3 0.4 ±15%
I>J
I 2T ON
anti-time-limit delay I 2Tg= ( J) 2tg
I≤J

Meaning of each setting position for Ig

Rated current In A B C D E F G H J Note


In≤400A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 ×In
400A<In≤1200A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 ×In
1200A<In 500A 640A 720A 800A 880A 960A 1040A 1120A 1200A

Explanation for parameter setting

The single-phase grounding protection operating current is adjustable: Ig Tg


(s)
Ig=(A-B-C-D-E-F-G-H-J)×In, and there are nine settings for option. D
E F .4 .4 .3
C G .3 .2
B H .2 .1
There are nine setting positions for the protective delay tripping time, A J
.1 X
wherein 4 settings represent the definite-time limit characteristic ON 2 Off
×In It
(i.e., I2t OFF), 4 settings the inverse-time limit characteristic (I2t ON),
and 1 setting the function of closing the grounding protection (X).

When the tripping time is set as definite-time limit operating


characteristic (i.e., the arrow points at the OFF area), the tripping Example 3: If it is known that the grounding fault protection
time can be selected as tg=0.1s-0.2s—0.3s-0.4s-x (i.e., the function setting current for the intellectual controller with a rated current
of closing the grounding protection). of In=800A is as the setting position of C, the tripping time is set
as the inverse time limit 0.4s.
When the tripping time is set as inverse-time limit operating Now there is a failure in the circuit, the line current I=400A,
characteristic (i.e., I2t ON), there are two cases: then the actual tripping time can be worked out; it can be seen
① in the case of I>1.1Ig and I>J, the result of the automatic from the table that the result is
changeover process is the definite-time limit operating characteristic, C=0.4 Ig=C×In=0.4×800=320A
tg=0.1s-0.2s-0.3s-0.4s; So I=400A>1.1Ig
② The case of the current meeting the condition of 1.1Ig<I≤J According to the formula I2Tg=(J)2tg
represents the inverse-time limit characteristic and the actual (400)2×Tg=(1.0×800)2×0.4
tripping time is calculated according to the formula I2Tg=(J)2tg.
Tg=1.6s
In the formula, I is the line current, Tg the actual operating time,
J the setting current, and tg the setting tripping time. The method
Note: For the intellectual controller, the current settings for the
for setting the parameter is similar to that for over current long
long- and the short-time delay and the instantaneous protection
time delay protection. As shown in the figure, the grounding
should not come across each other, and the condition of
protection current is C×In,and the tripping time setting is
IR<Isd<Ii must be ensured.
tg=0.4s in the setting position of inverse time limit (I2t ON).

28 > >>
N7 Series Products
NA8G
8.7 Explanation for auxiliary functions 8.8 Explanation for display function
a. Explanation for test functions When the rated current is greater than or equal to 400A,
When onsite adjustment, periodical inspection or overhaul is the primary current shall not be lower than 0.4In for single phase,
made with the controller supported by the breaker, breaking several and 0.2In for three phases for normal operation of the breaker.
times is necessary by using the test functions of the controller to
check the cooperation of the controller and the breaker. When the rated current is less than 400A, the primary current shall
With the breaker on, press the T key, and the intellectual controller not be lower than 0.8In for single phase,and 0.4In for three
will trip instantaneously to cut off the breaker. phases for normal operation of the breaker.
Note: ① This function can be used only when onsite adjustment
or overhaul for the breaker is made, and shall not be used during Note: When the AC220V ST power module is energized, and the
the normal operation. voltage falls to AC120V, there will be no display on the controller
② Each time before the controller is switched on, it is necessary When the AC380V ST power module is energized, and the
to press the reset button in the upper position of the controller voltage falls to AC200V, there will be no display on the controller
panel so that the breaker can be switched on again for operation. a. Current display
Error range for current display: ±5%
b. Explanation for fault memory b. Voltage display
The controller still has the function of fault memory after reset Error range for voltage display: ±1.5%
or de-energized to keep a latest historical event for post analysis.
Only when there is a new fault again, the original information is
cleared with the current latest faulty data saved.
For the inquiry method, refer to the above explanation about fault
display

9. Accessories
9.1 Under voltage release
When the under voltage release is not energized, neither
power-driven nor manual operation can make the breaker on.
For the under voltage release, there are two varieties:
instantaneous and time delay operations.
The time for the under voltage time delay release is Inm=1600A,
the time can be selected from but not adjusted in the range of 0 – 7s;
Inm=3200A or 6300A, the time can be selected from but not
adjusted among 0.5s, 1s, 3s, and 5s. When, within 1/2 delay time,
the power voltage returns to 85%Ue or above, the breaker will
not get disconnected.

Operating characteristic: Under-voltage release Under-voltage release


Rated operational voltage Ue(V) AC230 AC400 (Inm=1600A) (Inm=3200A, 6300A)
Operating voltage(V) (0.35~0.7)Ue
Reliable switching voltage(V) (0.85~1.1)Ue
Reliable not-switching voltage(V) ≤0.35Ue
Power consumption(W) 20VA

9.2 Shunt release


After the shunt release is energized, the breaker is switched off
instantaneously to allow remote operation.

Operating characteristic:
Rated control supply voltage Us(V) AC230 AC400 DC220 DC110
(0.7~1.1)Us Shunt release Shunt release
Operating voltage (V)
(Inm=1600A) (Inm=3200A, 6300A)
Power consumption (W) 200VA 200W
Breaking time 50±10ms

9.3 Closing electromagnet


After the motor energy storage is ended, energizing the closing
electromagnet will make the energy storage spring force of the
operating mechanism to be released instantaneously to rapidly
switch the breaker on.

Operating characteristic:
Rated control supply voltage Us(V) AC230 AC400 DC220 DC110 Closing electromagnet Closing electromagne
Operating voltage (V) (0.85~1.1)Us (Inm=1600A) (Inm=3200A, 6300A)
Power consumption (W) 200VA 200W
Closing time 50±10ms

> >> 29
N7 Series Products
NA8G
9.4 Power operating mechanism
The functions of motor energy storage and automatic energy
re-storage after the breaker comes on are available to ensure that
the breaker can come on immediately after it gets disconnected.
Operating characteristic:
Rated control supply voltage Us(V) AC230 AC400 DC220 DC110
Operating voltage (V) (0.85~1.1)Us
Power consumption (W) 75/150VA 75/150W
Energy storage time <4s (Inm=1600A) (Inm=3200A, 6300A )
Frequency of operation At most 3 times in a minute

9.5 Auxiliary contact (with a common point)


4 groups of changeover contacts (2 N.O. and 2 N.C.) are provided
for the standard form of auxiliary contacts, and 6 groups of
changeover contacts (3 N.O. and 3 N.C.) for the special form
(Inm=1600A not available for DC).
(Inm=1600A) (Inm=3200A, 6300A )
Technical parameters:
Rated voltage(V) Rated thermal current Ith(A) Rated control capacity
230
AC 6 300VA
400
DC 220 6 60W

9.6 Separator between phases


The separator is installed between the phases of the line bank to
improve the insulating ability between the phases of the breaker.

9.7 Key lock


The OFF pushbutton of the breaker can be locked in the position of depress, and at this time,
the breaker cannot be closed for operation; after the user selects the option, the factory provides
locks and keys; one breaker is provided with one independent lock and one key for the one lock;
two breakers, two independent locks and one key for the two locks; three breakers, three same
locks and two same keys for the three locks.
Note:
a.For the air circuit breaker with key interlock, when the key has to be pulled out, it is necessary
to first press the OFF key, turn the key anticlockwise, and then pull out the key.
b.The key for the 1600 does not work for the 3200 and 6300 shell breakers and vise versa,
so be on guard against the distinction between them.

9.8 Pushbutton lock


It is used to lock the button for opening and closing the breaker with the padlock used for
such a purpose. (Padlocks to be provided by users themselves)

9.9 Door frame and lining pad


They are installed on the door of the distribution cabinet room to seal it with a protection
level of up to IP40.

9.10 Drawer type of air circuit breaker “separation” position locking device
For the “separation” position of the open frame (draw-out) circuit breaker, a lock rod can be
pulled out to lock the matter, and the breaker locked will be unable to be turned towards
the TEST or CONNECTION position. Padlocks have to be provided by users themselves.

9.11 The drawer type of air circuit breaker about any working position locking device
After the breaker body is locked automatically in any working position, it is necessary to turn
the key to unlock the matter so that the break body can be moved to the next working position
by turning the handle. (this function available for 3200 to 6300).

9.12 Interlock with the door


Interlock with the door for the break status
When the breaker is closed, the cabinet door must not be opened; when the breaker is
switched off, the cabinet door is allowed to be opened.
Interlock with the door for the breaker position
When the breaker is in the position of connection and test, the cabinet door must not be
opened; when the breaker is the separation position, the cabinet door is allowed to be opened.

9.13 Mechanical interlock


Steel cable interlock for two breakers placed horizontally or joint rod interlock for two
superimposed breakers.

30 > >>
N7 Series Products
NA8G
10. Installation 10.4 Installation of the fixed type breaker
10.1 Following items to be checked before installation Place the breaker into the distribution cabinet, and fasten it by
Check the label plate on the breaker panel to see if it is using 4 pieces of M6(In=1600A) or M10(In=3200A or more)
conform to the specifications of the ordered goods. bolts and washers. The breaker shall be installed stably with no
a.Rated current additional mechanical stress to avoid damage of the breaker or
b.Under voltage release voltage and delay time bad contact of the main bus bar.
c.Shunt release voltage
d.Closing electromagnet voltage 10.5 Installation of the open frame (draw-out) circuit breaker
e.Motor voltage Take the breaker body out of the draw-out socket, and install
the socket in the distribution cabinet, and fasten it by using 4 pieces
10.2 Before installation, operation, maintenance and inspection, of M6(In=1600A) or M10(In=3200A or more) bolts and washers;
you shall read this manual, and consult the manufacturer for the breaker shall be installed stably with no additional mechanical
questions, if any. stress to avoid damage of the breaker or bad contact of the main
bus bar. After the work is completed, mount the body into the
10.3 Preparations before installation draw-out socket.
Before the breaker is installed, check the insulation resistance
of the breaker by using a 1000V megohmmeter according to 10.6 The specifications of the wiring copper bars for the primary
regulations; when the surrounding media temperature is 25℃±5℃ circuit of the breaker shall meet the copper bar specifications used
and the relative humidity 50% - 70%, the insulation resistance under the conditions of conventional heating in IEC/EN 60947-2
shall not be less than 20 megohm.
The place with the insulation resistance to be tested includes: 10.7 The breaker shall be grounded substantially.
the place between various phases and between various phases
and the frame when the breaker is closed; the place between
in- and out- lines of various phases.

11. Common faults and troubleshooting


Listed below are the problems which users may encounter
during installation, adjustment, and operation of the breaker,
and the possible reasons and elimination methods.

No. Technical problems Possible causes


Diagnosis and trouble shooting
1 Check the breaking current and operating time on the intellectual controller
2 Analyze the operation of the load and power network
Overload fault tripping 3 Promptly find and shoot the trouble if overload is confirmed
(long time delay indicator on) 4 For lack of match between the actual running current and the long time delay
operating current, please modify the long-time delay operating current setting
for a proper match and protection according to the actual running current
5 Press the reset button to close the breaker again

1 Check the breaking current and operating time on the intellectual controlle
Breaker tripping Short-circuit fault tripping 2 Promptly find and shoot the trouble if overload is confirmed
(fault indicator on) (short time delay or 3 Check the setting value of the intellectual controller
1
instantaneous indicator on) 4 Check to see whether the breaker is in good condition, and determine whether
it can be closed for operation
5 Press the reset button to close the breaker again

1 Check the breaking current and operating time on the intellectual controller
Grounding fault tripping 2 Promptly find and shoot the trouble if it is confirmed that there is a grounding fault
(grounding fault indicator on) 3 If no grounding fault is detected, please determine whether the grounding
fault current setting is proper, and can be well matched with the actual protection;
if not, the setting shall be modified
4 Press the reset button to close the breaker again
Under voltage release 1 Check to see if the power voltage is lower than 70%Ue
Tripping 2 Check the under voltage release and control unit for fault

Mechanical interlock action Check the working condition of two breakers equipped with mechanical interlock.
1 Whether the under voltage release has been energized
Under voltage release 2 Whether the power voltage is lower than 85%Ue
No attracting 3 Whether the under voltage release or control unit malfunctions,
if so, the release shall be replaced.
Reset button fails to reset Press the reset button to close the breaker again.
Breaker fails Open frame (draw-out) circuit breaker f Check the contract status of the secondary circuit,
2 to close ails to be put to the right position by rocking and shoot the trouble, if any
1 Check the motor control power supply and see if it is well
Open frame (draw-out) circuit breaker
providing power, and the voltage must be ≥85%Us
Bad contact for the secondary circuit 2 Check the status of the motor energy storage mechanism.

Put the open frame (draw-out) circuit breaker to the right position
Breaker fails to pre-store energy
by rocking (with it locked in the connection position)
1 Check the power voltage of the closing electromagnet,
and it must be higher than or equal to 85%Us
Closing electromagnet trouble
2 If there is any trouble in the closing electromagnet to enable the attracting,
it shall be replaced.

> >> 31
N7 Series Products
NA8G

No. Technical problems Possible causes


1 There may be short circuit current when the matter is switched on,
and in this case you shall find and shoot the trouble
2 Check to see if there is any overload current in the circuit,
Breaker trips Tripping immediately
find and shoot the trouble, if any
3 after closed Delay tripping
3 Check the setting value of the intellectual controller for reasonability,
and a re-setting process is necessary if not reasonable
4 Press the reset button to close the breaker again

1 Check the shunt release circuit for reliable connection


Breaker fails The breaker fails to open in power-driven mode and the shunt release for trouble, and the release shall
4 to open be replaced if the fault is confirmed
The breaker fails to open in manual mode
2 Check he operating mechanism for mechanical fault.

1 Check the motor energy storage mechanism control


Energy failed to be stored in power-driven mode power voltage, and the voltage shall be ≥85%Us;
5 Breaker fails to store energy
check the status of the circuit connection
2 Check the motor

Can't achieve manual energy storage Energy storage mechanism malfunction

Breaker fails to be pulled out when the Pull out the rock rod
Rock rod fails to be pulled out
6 open frame (draw-out) circuit breaker is Put the breaker completely
Breaker fails to completely reach the SEPERATION position to the SEPERATION position by rocking
in the SEPARATION position

Open frame (draw-out) circuit The "drawer” has seized up for foreign matters fall in it; Check it for foreign matters and for condition
7 breaker fails to be put to the damage in the mechanism for putting in by rocking or the of the rack and gear
CONNECTION position by rocking gear thereof; Position locking device fails to be unlocked Turn the key on the “drawer” to unlock the matter

Intellectual controller fails to be energized by power supply: 1 Check to see if the intellectual controller
power supply is well be connected and works well
Improper input voltage for the auxiliary power supply
No display on the 2 Cut off the intellectual controller control
8 Improper secondary output voltage for the transmitter
intellectual controller screen power supply, and then connect the power supply;
Unreliable connection between the secondary output If the fault is still present, there may be some
terminal of the transmitter and the controller troubles in the controller which has to be replaced

32 > >>
N7 Series Products
NA8G
12. Specifications for ordering

User Order amount Order date Tel


Type and size □NA8G-1600 □NA8G-3200 □NA8G-6300
Rated current □200 □400 □630 □800 □1600 □2000 □2500 □4000 □5000
(In)A □1000 □1250 □1600 □2900 □3200 □6300(don’t have 4P)
Installation mode □draw-out type □Fixed type (no such products for over 4000A)
Connection mode □Horizontal connection □Vertical connection □Front connection □mixed connection (connection mode to be noted)
Number of poles □3P □4P
Factory’s setting values: IR=1In, 2s(6IR); Isd=8IR, inverse-time limit 0.4s; Ii=12In; In>1200A Ig=800A; In≤1200A Ig=D×In, OFF
If the user has some requirements different from the defaulting, please write the numerical values on the line below

Operating current setting______In (0.4,0.5,0.6,0.7,0.8,0.9,0.95,0.98,1)


Long-time delay protectionIR
Operating time setting______s (1,2,4,8,12,16,20,24,30)
Setting of the Short-circuit short-time delay protectionIsd Operating current setting______IR (1.5,2,2.5,3,4,5,6,8,10)
protection Operating time setting □inverse time______s (0.1,0.2,0.3,0.4,OFF)
parameter hort-circuit instantaneous protectionIi Operating current setting______In (2,3,4,6,8,10,12,15,OFF)
Intelligent controller

Operating current setting______In See Manual, p. 24


Ground protectionIg
Operating time setting □inverse time______s □Definite-time limit______s
Selecting the type □Standard type □Multifunctional type
Power input □AC400V □AC230V □DC220V □DC110V □DC24V
Three-section protection against over current Neutral line or grounding fault protection Voltage measurement
Basic function
Test function Fault inquiry/memory function Self-diagnostic function

Optional function □Over voltage protection □Under voltage protection □Over frequency protection □Under frequency protection
(this function to □Voltage unbalance measurement □Phase sequence protection □Voltage measurement □Frequency measurement
be added as □Measurement of harmonic current □Power factor measurement □Power measurement □Phase sequence detection
required by the
□Voltage unbalance rate measurement □Electric energy measurement □Contact equivalent
user, and to be
matched with the □Power network history parameter recording function □MCR make/break function □Load monitoring function
controller type) □Signal contact output function □Communication function □ZSI regional interlocking protection

Note: when the product is a multifunctional controller as arranged by the user,


the communication function and the like are the basic function configuration
Accessories for standard

Under voltage □Instantaneous □Time delay______s (1-2-3-4-5-6-7s provided for the 1600 shell, optional but not adjustable;
release 0.5-1-3-5s for the 3200 and 6300 shell, optional and adjustable) □AC400V □AC230V

Shunt release □AC400V □AC230V □DC220V □DC110V


configuration

Closing electromagnet □AC400V □AC230V □DC220V □DC110V


Energy storage motor □AC400V □AC230V □DC220V □DC110V
Auxiliary contact □2 NO and 2 NC □3 NO and 3 NC(Inm=1600not available for DC)

□One breaker is provided with one lock and one key


OFF locking
Accessories for optional

device □Two breakers is provided with two same locks and one key (the same key/lock not available
for the 1600 and 3200/6300 shell breakers)
□Three breakers is provided with three same locks and two keys (the same key/lock not available
configuration

for the 1600 and 3200/6300 shell breakers)


Mechanical
Two-breaker interlock solution □Steel cable interlock □Joint rod
interlock
□BUTTON locking device □Three-position locking device for the draw-out socket □Door interlock
□Separator between phases □Door frame □Auxiliary power module

Note: Extra costs are needed for the optional functions, optional accessories and the like for the breaker.

> >> 33
N7 Series Products
NM7
2. Type designation
N M 7- □ □ /□ / □ □ □□□

Operation mode codes:


D for motor operation;
Z for operation by turning
the handle;
nothing for operation directly
by the handle.

Types of quadrupole circuit breakers:


4A-N pole with no over-current
release component,
N pole always on;
4B-N pole with no over-current
release component,
N pole to be closed and opened
together with the other three poles
(N pole closed first and then opened);
4C-N pole with over-current
release component,
N pole to be closed and opened
together with the other three poles
NM7 (N pole closed first and then opened)
4D-N pole with over-current
Moulded Case Circuit Breaker release component,
N pole always on.
1. General
After successively developing NM8 and NM6, our company Codes for applications: nothing for
launched another new product, the NM7 series moulded distribution; 2 for motor protection
case circuit breaker upgraded from the NM1 series, by
further taking the structural features and design style of the
NM1 series products, modifying the accessories, wiring Release (of a mechanical switching device)
mode, appearance and the like in an individualization way, mode and accessory code (see table 1)
allowing the product not only to be set by the manufacturer
before delivery but also replaced by users themselves, which Number of poles
is really an improvement, and integrating the up-to-date
design concept to make the product more people-oriented. Rated current
Certificate: KEMA, CE.
Rated operation range 10A~800A. Breaking capacity codes:
Several modes available: 3P, 4P, fixed type, C – economic type, S – standard type
plug-in type, H – relatively high type, R – current limiting type
front connection, rear connection.
The product can be installed vertically or horizontally. Frame size rated current
Isolating function is available.
This product meets the requirements in
Design serial number
IEC 60947-2.

Moulded case circuit breaker

Company code

34 > >>
N7 Series Products
NM7
3. Operation conditions
3.1 Ambient air temperature
3.2 The upper limit for the ambient air temperature is+40℃,
lower limit -5℃, and the average temperature is not higher
than+35℃ within 24 hours. Ambient temperature

3.3 Altitude: not higher than 2000m for the installation site.
3.4 Atmospheric conditions:
When the ambient air temperature is +40℃, the relative

2000m
humidity of the air shall not be higher than 50%; a higher
relative humidity is allowed at a lower temperature; Altitude
for the wettest month, the maximum relative humidity
averaged shall be 90% while the lowest temperature
averaged in that month +25℃, and the condensation
produced due to temperature change shall be taken into
consideration.
3.5 Class of pollution: 3 No Pollution

Table 1
Accessory code Accessory installation and mode of wirings

Accessory name Compound release NM7-125 NM7-250 NM7-400, 630 NM7-800

3P 4P 3P 4P 3P 4P 3P 4P

No accessories 300

Alarm contact 308

Shunt release 310

Auxiliary contact 320

Under voltage release 330

Shunt release,
340
auxiliary contact

Shunt release,
350
under voltage release
Two groups of
360
auxiliary contacts

Auxiliary contact,
370
under voltage release

Shunt release,
318
alarm contact

Auxiliary contact,
328
alarm contact

Under voltage release,


338
alarm contact

Shunt release, auxiliary


348
contact, alarm contact

Two groups of auxiliary


368
contacts, alarm contact

Auxiliary contact, under


378
voltage release, alarm contact

Note: a. 200 for the breaker body only with the magnetic release;
300 for thermal release + magnetic release body;
000 for the breaker body with no release and inner accessory.
b. ●alarm contact; ○auxiliary contact; ■shunt release; ▲under voltage release.

> >> 35
N7 Series Products
NM7
4. Technical data

NM7 NM7-125
Rated currentIn(A) 16,20,25,32,40,50,63,80,100,125
Rated insulation voltage Ui(V) 800
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 380/400/415/690

Appearance

Breaking capacity feature code S


Number of poles 3 4
Rated ultimate short circuit breaking AC380/400/415V 35 35
capacityIcu(kA) AC690V - -
Rated service short circuit breaking AC380/400/415V 17.5 17.5
capacityIcs(kA) - -
AC690V
Service life Mechanical 25000
(C-O cycle) Electric 8000
Usage category

Overall dimensions 3P(L×W×H) 155×90×74


(mm) 4P(L×W×H) 155×120×74
Isolating function ●
Front connection panel ▇
Rear connection panel ▇ *
Cage type connection terminal ▇ *
Plug-in type ▇ *
Draw-out type ▇ *
Rotary manual operating handle ▇
Motor driven operating handle ▇
Shunt, under voltage release ▇
Auxiliary, alarm contact ▇
Terminal cover ▇ *

Note: ●Standard configuration ■Selected configuration; the one with * is unconfiguration.

36 > >>
N7 Series Products
NM7

NM7-250
100,125,160,180,200,225,250
800
8
380/400/415/690

S
3 4
35 35
- -
17.5 17.5
- -
20000
2500
A
165×105×74
165×140×74


▇ *
▇ *
▇ *
▇ *




▇ *

> >> 37
N7 Series Products
NM7

NM7 NM7-400
Rated currentIn(A) 250,315,350,400
Rated insulation voltage Ui(V) 800
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 380/400/415/690

Appearance

Breaking capacity feature code S H


Number of poles 3 4 3 4
Rated ultimate short circuit breaking AC380/400/415V 50 50 65 65
capacityIcu(kA) AC690V - - 12 12
Rated service short circuit breaking AC380/400/415V 25 25 32.5 32.5
capacityIcs(kA) - - 6 6
AC690V
Service life Mechanical 4000
(C-O cycle) Electric 1000
Usage category A
Overall dimensions 3P(L×W×H) 257×150×107
(mm) 4P(L×W×H) 257×198×107
Isolating function ●
Front connection panel ●
Rear connection panel ▇ *
Cage type connection terminal ▇ *
Plug-in type ▇ *
Draw-out type
Rotary manual operating handle ▇
Motor driven operating handle ▇
Shunt, under voltage release ▇
Auxiliary, alarm contact ▇
Terminal cover ▇ *

Note: ●Standard configuration ■Selected configuration; the one with * is unconfiguration

38 > >>
N7 Series Products
NM7

NM7-630 NM7-800
400,500,630 500,630,700,800
800 800
8 8
380/400/415/690 380/400/415/690

S H S H
3 4 3 4 3 4 3 4
50 50 65 65 50 50 75 75
- - 15 15 - - 15 15
25 25 32.5 32.5 25 25 37.5 37.5
- - 7.5 7.5 - - 10 10
4000 2500
1000 500
A A
280×182×112 275×210×112
280×240×112 275×280×112
● ●
● ●
▇ * ▇*
▇ * ▇*
▇ *
▇*
▇ ▇
▇ ▇
▇ ▇
▇ ▇
▇ * ▇*

> >> 39
N7 Series Products
NM7
5. Inverse-time overcurrent protection curve for the
breaker for distribution (see Fig. 1 – 10)

Fig.1 NM7-125(16A~32A) operation characteristic curve Fig.2 NM7-125(16A~32A) temperature compensation curve

10000
7200
3600 130
1200
600 120
300
Tripping time(S)

Rated current(%)
120
60 110
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 -5 0 10 20 30 40 50 60

1 2 3 4 5 7 8 12 20

Rated current times Ambient temperature (℃)

Fig.2 NM7-125(40A~125A) operation characteristic curve Fig.4 NM7-125(40A~125A) temperature compensation curve

10000
7200
3600 130
1200
600 120
300
Tripping time(S)

Rated current(%)

120
60 110
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 -5 0 10 20 30 40 50 60

1 2 3 4 5 7 8 12 20
Rated current times Ambient temperature (℃)

Fig.3 NM7-250 operation characteristic curve Fig.6 NM7-250 temperature compensation curve

10000
7200
3600 130
1200
600 120
300
Tripping time(S)

Rated current(%)

120
60 110
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 -5 0 10 20 30 40 50 60

1 2 3 4 5 7 8 12 20

Rated current times Ambient temperature (℃)

40 > >>
N7 Series Products
NM7

Fig.7 NM7-400 operation characteristic curve Fig.8 NM7-400 temperature compensation curve

10000 130
7200
3600
1200 120

Rated current(%)
600
300
120
110
Tripping time(S)

60
30
20
100
10
5
2
90
1
0.5
0.2 80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60

1 2 3 4 5 7 8 12 20

Rated current times Ambient temperature (℃)

Fig.9 NM7-630 operation characteristic curve Fig.10 NM7-630 temperature compensation curve

10000
7200
3600 130
1200
600 120
300
120
Rated current(%)
Tripping time(S)

60 110
30
20
10 100
5
2
90
1
0.5
0.2
80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20

Rated current times Ambient temperature (℃)

Fig.11 NM7-800 operation characteristic curve Fig.12 NM7-800 temperature compensation curve

10000
7200 130
3600
1200 120
600
Rated current(%)
Tripping time(S)

300
110
120
60
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60

1 2 3 4 57 8 12 20

Rated current times Ambient temperature (℃)

> >> 41
N7 Series Products
NM7
6. Overall and mounting dimensions

NM7-125

96
74
120(4P) 70
90(3P) 61.5
30 30 30 24.5

1 3 5 N

23

102
155

135

132
45

29

2 4 6 N

30(3P)

60(4P)

NM7-250

96
74
140(4P) 70
105(3P) 61.5
35 35 35 24.5

1 3 5 N

21
105
52

126
165
145

31

2 4 6 N

35(3P)

70(4P)

NM7-400

160

198(4P) 107

106
150(3P)
98.5
52.5 48 52.5
48

1 3 5 N
150
90
225
257

194
311

50

2 4 6 N

28 44(3P)
45.5
94(4P)

42 > >>
N7 Series Products
NM7

NM7-630

165
112
240(4P)
182(3P)
110
103
58 58 58
52

1 3 5

160
92

210
280
245
405

50

2 4 6

50 58(3P)
116(4P)

NM7-800

169
112
280(4P) 105.5
210(3P) 95
70 70 70
41.5

1 3 5 N
243
329.5

240.5

221
275

88

67

2 4 6 N

70(3P)
140(4P)

7. Ordering information
Users shall order goods in the following way:
Product type + rated current + code of the inner accessory
(00 for no inner accessories) + application code + operation mode
+ (word description, accessory voltage, type and the like to be
described in detail).
Order Sample: 10 pcs of NM7-250S, 250A, three poles,
shunt release (AC230V), for motor protection, power operating
mechanism (DC220V), plug-in type.
10 pcs of NM7-250S/250/3310 2 D (shunt AC230V,
power operating mechanism DC220V, plug-in type).

> >> 43
N7 Series Products
NZ7
2. Type designation
N Z 7-□□/□□□□□□□

Transfer mode without code:


Users can set the matter
R: self-throwing and self-reset
(power network to power network)
S: self-throwing and not self-reset
(power network to power network)
F: self-throwing and self-reset
(power network to power generation)

Controller type
A: basic type

Structure
NZ7 Series Y: integrated (type)
Without code: separated (type)
Automatic Transfer
Switching Equipment Actuator circuit breaker type
Without code: NM1
1. General
Rated current (Arabic numerals)
Applicable to the three-phase four-line two-circuit power
supply network with an AC power frequency of 50Hz, Release with nothing as its code: NM1
rated operational voltage of AC400V, and rated operational
current of up to 630A, the NZ7 series automatic transfer Number of poles: 3, 4
switching equipment can automatically connect one or
several loads from one power source to another to ensure Breaking capacity code: S, H, R
the normal power supply of the load circuit.
Frame size rated current (Arabic numerals)
This product is applicable to the important places such as
industrial, commercial, and storied buildings, Design serial number
and residential houses.
Automatic transfer switching equipment
Certificate: KEMA
Execution standard: IEC/EN 60947-6-1 Company code

3. Operation conditions
3.1 Ambient air temperature
The upper limit for the ambient air
temperature is +40℃, lower limit -5℃,
and the mean value of the temperature is Ambient temperature

not greater than +35℃ within 24 hours;


3.2 Altitude
Altitude: not higher than 2,000m for the
installation site.
3.3 Atmospheric conditions:
2000m

When the ambient air temperature is +40℃,


the relative humidity of the air shall not be Altitude

higher than 50%, a higher relative humidity


is allowed at a lower temperature, e.g. 90%
at +20℃, and special measures shall be
taken for the condensation occasionally
produced due to temperature changes.
3.4 Class of pollution:
Class of pollution: 3 No Pollution

44 > >>
N7 Series Products
NZ7
4. Technical data

Product type NZ7-63 NZ7-125 NZ7-250 NZ7-400 NZ7-630


Up to standard IEC/EN 60947-6-1
Actuator circuit breaker NM1-63 NM1-125 NM1-250 NM1-400 NM1-630
Parameters of electrical characteristics
Operating environment temperature -5℃~+40℃
Altitude 2000m
Class of pollution 3
Specification for current 10,16,20,25, 16,20,25,32,40, 100,125,160, 250,315, 400,500,
32,40,50,63A 50,63,80,100A 180,200,225A 350,400A 630A

Rated operational voltage(Ue) 400V 50Hz


Nominal insulation voltage(Ui) AC500V AC800V
Rated impulse withstand voltage 6kV 8kV
Number of poles 3P 4P 3P 4P 3P 4P 3P, 4P 3P, 4P
Short circuit breaking capacity codes S H H S H R H S H R H S H R S H R
Rated short circuit making capacity(Icm) 31.5 73.5 73.5 52.5 105 143 105 52.5 105 143 105 73.5 110 154 73.5 110 154
Rated short circuit breaking capacity(Icn) 15 35 35 25 50 65 50 25 50 65 50 35 50 70 35 50 70
Service life 6000 times 6000 times 6000 times 4000 times 3000 times
Usage category AC-33B
Electric equipment grade CB Class
Protection level IP30(except the main circuit terminal)
Protection Overload protection/short circuit protection
Controller characteristic
Controller Type A(basic type)
Rated control supply voltage Us 230V 50Hz
Installation mode for the controller Integrated/separated (as installed on the surface of the cabinet)
Operating transfer time (no time delay) ≤3.2s ≤3.5s ≤3.6s ≤4s ≤5s
Power consumption ≤10W
Installation and connection
Installation mode Fixed type
Connection mode Front connection

5. Characteristics and functions


The NZ7 series automatic transfer switching equipment
(hereinafter referred to as automatic transfer switch) is the
CB class product of a new generation combined with the
advanced digital electronic control technique. The product
features compactness, energy conservation, convenient
installation, reliable dual-interlock protection, etc., and is
advanced and complete in terms of function.

Single motor structure, compact

AUTO
ON
N

R
OFF

AU TO QU ER Y
SE T
MA NU

N R OF F

Visualized management

> >> 45
N7 Series Products
NZ7
5.1 Compactness
The transfer function is achieved via using the forward and
backward rotation of the only one motor which allows for reducing
the product’s height and room for its installation.
5.2 Energy saving
The driving mechanism works in the mode of motor drive with less
power consumption and noise.

Transmission mechanism (short-term service)


Type A controller (long-term service)
Type 63/Type 100 Type 225 Type 400/Type 630
≤10W 20W 40W 20W

5.3 Advanced and multipurpose functions

Auto
ON
N
R

OFF

Settable transfer parameter Visualized management Multi auxiliary functions


Under voltage transfer value three-phase voltage Off/on indication external-terminal Integrated controller in the
Delay time transfer magnitude display Fire control linkage modes of integrated and
Power network to power network Off/on state display Generator signal separated configurations easy
self-throwing and self-reset/power External power source
network to power network for installation
self-throwing and not self-reset/
power network to power generation
Self-throwing and self-reset

46 > >>
N7 Series Products
NZ7
5.4 Dual-interlock protection
The mechanical-electrical interlock duplex protection is used to
prevent two power sources from being connected simultaneously
to the load, wherein the electrical interlock works in the breaker
contact position mode for directly indicating the automatic transfer
switch to perform the genuine electrical interlock so that the
automatic transfer does not take place automatically in such cases
as contact fusion welding, breaker handle damage, and circuit
fault breaker tripping.
6. Controller

Type and function Type A (basic type)

Modes of manual and automatic transfer ■


Working position of the main contact (actuator circuit breaker)
Prime power turned on ■
Standby power turned on ■
OFF ■
Automatic control
Monitoring the prime power Failures such as loss of phase/voltage, under and over voltage for any of three phases of the power supply
Monitoring the standby power Failures such as loss of phase/voltage, under and over voltage for any of three phases of the power supply
Self-throwing and self-reset ■
Self-throwing and not self-reset ■
Power network to power network ■
Power network to power generation ■
No-voltage transfer ■
Under voltage transfer ■
Over voltage transfer ■
Adjustable delay time ■
Transfer delay a Continuously adjustable in the range of 0s~180s
Return c Continuously adjustable in the range of 0s~180s
Generator control ■
Fire control linkage (inactive contact) ■
Indication
Indication for on, off, and double-break ■
Prime power indication ■(Displaying voltage magnitude)
Standby power indication ■(Displaying voltage magnitude)
Fault tripping indication ■
External indication signal terminal ■
Parameter setting indication ■
Interlock protection
Mechanical interlock ■
Electrical interlock ■(not transfer automatically with faulty tripping)

6.1 The Type A integrated controller works in the modes of integrated or separated configurations,
and is installed in the cabinet or on the panel to allow operation outside the cabinet.
Whether to transfer from one power source to another depends on the state of the operational power supply.
Generating set control
Press-key manually forced transfer operating
6.2 Control voltage
AC230V 50Hz
6.3 Operation: automatic operation, manual operation
6.4 Setting delay
Transfer delay: adjustable in the range of 0s - 180s, prime power failure,
time before off for QN
Return delay: continuously adjustable within the range of 0s - 180s,
prime power recovery, time before off for QR

> >> 47
N7 Series Products
NZ7
6.5 Interface for display and operation
LED digital display

1 2 3

AUTO MANU ERR


4
ON
5 N 9
OFF
6 SET 10

ON
7 R 11
OFF
12
STOP GENERATOR
8 13

19
AUTO QUERY
SET
14 MANU 18

N R OFF
15 17

16

1. Indication of automatic working mode; 15. Button for compulsorily turn off the normal power
2. Indication of manual working mode; Under the manual control mode, if this button is pressed, it can
3. Failure indication compulsorily switch to the normal power; if it is setting condition,
When the breaker is disengaged due to the failure or short-circuit this button is the “scroll up” button of setting programs;
of the switch, this lamp will be on; 16. Button for compulsorily turn off the alternative power
4. Display area of normal power voltage parameters Under the manual control mode, if this button is pressed, it can
It displays normal power voltage parameters and changeover compulsorily switch to the alternative power; if it is setting
delay time under the working condition, and setting items under condition, this button is the “scroll up” button of setting
the setting condition; programs;
5. Indication of the on or off of breaker on the normal power side 17. Off button
6. Indication of setting condition Under the manual control mode, if either line of both power
7. Indication of the on or off of breaker on the alternative power side lines are normal and this button is pressed, it will switch to
8. Indication of the start of stop function; the disengagement position; this button is the minus button
9. Units of voltage, time, and frequency of the normal power; for setting parameters when it is under setting condition;
10. Phases A, B, and C; 18. Failure inquiry button
11. Units of voltage, time, and frequency of the alternative power; When the switch fails and malfunction lamp on the failure
12. Display area of alternative power voltage parameters; screen is on, the detail malfunction code can be inquired if it
It displays alternative power voltage parameters and transfer is pressed; this button is the plus button if it is under the
delay time under the working condition, and setting items under setting condition;
the setting condition; 19. Setting button
13. Indication of the start signal of generator When this button is pressed, it may enter into the parameter
14. Selection button of automatic/manual transfer setting menu of the controller.
When it is regularly used, it can be used for selecting the
automatic or manual mode; it saves and exits the functions
when it is under the setting condition.

48 > >>
N7 Series Products
NZ7
6.6 Operation description on parameter setting

AUTO

N
ON

R
OFF

Setting

AUTO
MANU
Set transfer value of under-voltage ofnormal power, press
SET
to increase and to decrease. 160V to 200V

N R

AUTO
MANU
Set transfer value of over-voltage of normal power, press
SET
to increase and to decrease. 240V to 290V

N R

AUTO
MANU Set transfer delay time, press
SET
to increase and to decrease. 0s to 180s

N R

AUTO
MANU
Set transfer value of under-voltage of alternative power, press
SET
to increase and to decrease. 160V to 200V

N R

AUTO
MANU
Set transfer value of over-voltage of alternative power, press
SET
to increase and to decrease. 240V to 290V

N R

AUTO
MANU
Set return delay time, press
SET
to increase and to decrease. 0s to 180s

N R

AUTO
MANU Set start delay time of generator, press
SET
to increase and to decrease. 0s to 180s

N R

AUTO
MANU Set shut-down delay time of generator,press
SET
to increase and to decrease. 0s to 180s

N R

AUTO
MANU
SET
Set transfer mode, press button to change the mode
(when the last digit is 0, it is grid-grid self-throw and self-reset mode;
when the value is 1, it is mutual alternative mode, when it is 2, it is
grid-generator. self-throw and self-reset mode.)

Note for keys


Button Description:
Press the Setting Button when the controller is working, LED will display
the parameter setting menu interface displayed in Figure ; press “ ”
and “ ” buttons in the setting menu to scroll up the setting options;
if the automatic/ manual button is pressed, it will exit the setting menu;
press “ ” or “ ” to change parameters.

> >> 49
N7 Series Products
NZ7
Working processes of typy A controller

Grid – Grid
Grid – Grid mutual alternative operation
self-throw and self-reset operation

QN QR
QN QR UN is normal
UN is normal
UN fails
UN fails T1 can be adjusted from 0s to 180s
T1 can be adjusted from 0s to 180s
QN QR
QN QR UN is disconnected
UN is disconnected
UR is put into use
UR is put into use
QN QR
QN QR UR supplies
UR supplies
UN resumes to normal
UN resumes to normal
T2 can be adjusted from 0s to 180s
QN QR
QN QR UR supplies
UR is disconnected
UR fails
UN is put into use T2 can be adjusted from 0s to 180s
QN QR
QN QR UR is disconnected
UN supplies

UN is put into use


QN QR
UN supplies
Grid-Power Generation
self-throw and self-reset operation

QN QR
UN is normal

UN fails
T3 can be adjusted from 0s to 180s

Generator starts

Output of generator reaches set value


T1 can be adjusted from 0s to 180s
QN QR
UN is disconnected

UR is put into use

QN QR T1: Transfer delay can be adjusted from 0s to 180s


UR supplies
Failure of UN , time before disconnecting QN
T2: Return delay time can be adjusted from 0s to 180s
UN resumes to normal
Normal of UN , time before disconnecting QR
T2 can be adjusted from 0s to 180s T3: Delay time in starting generator can be adjusted from 0s to 180s
QN QR
UR is disconnected
T4: Delay time in shutting-down generator can be adjusted from 0s to 180s
UN is put into use QN: Operating breaker on the frequently used side
QR: Operating breaker on the stand-by side
QN QR UN : Normal power supply
UN supplies
UR : Alternative power supply
UN is put into use
T4 can be adjusted from 0s to 180s

Generator shuts down

50 > >>
N7 Series Products
NZ7
7. NZ7 external connection diagram
7.1 product connection diagram

N standby power
N Prime power
Prime power UN standby power UR
1 3 5 1 3 5

QN QR
N N

7.2 4P product connection diagram

Prime power UN standby power UR


1 3 5 N 1 3 5 N

QN QR

Note:
QN actuator circuit breaker on the prime (normal) side
QR actuator circuit breaker on the standby (reserve) side

> >> 51
N7 Series Products
NZ7
7.3 Wiring diagram of external terminals of the controller

Indication of UN status Indication of UR status


Auxiliary power Stop signal
101 102 103 104 201 202 203 204
301 302 401 402 403 404 501 502 503

Passive contact point


+ -

Passive contact point

Feedback signal
Tripping signal

Tripping signal
Power signal

Power signal
On signal

On signal
Zero line

Zero line

DC24V/0.5A

Start control of generator

Output is AC230V/0.5A Note: the hidden line is the internal wiring of the controller.

7.4 Application

Terminals 401 and 402 can only connect to


passive signal; otherwise, the controller will
be burnt! Passive signals may be inputted
through relay. Product after receiving the
stop signal off, 403 and 404 will be
connected.
After removing stop signals, this product will
restore to normal working status by pressing
any key of the controller.

UN normal
To control center
401 101
402 102 UN
403 103 QN on
Internal contact
terminal of the

404 104 QN tripped


controller

To the remote port of the generator


501 201
502 202 UR
503 203 QR on
204 QR tripped

301 +
DC24V
302 -
This terminal is used under the
Grid-Power Generation; it must
be connected to the generator
if required; and it does not affect
its use if it is not connected. It is used under the Grid-Power
When the UN fails Generation mode and it is
allowed not to connect it, but
501 the default start delay of the
502 generator is 0 second.
503

52 > >>
N7 Series Products
NZ7
8. Line incoming pattern
8.1 Connecting bus-bar type

Normal power bus-bar Alternative power bus-bar

Line voltage signal sampling

Power bus-bar

Load bus-bar

8.2 Installation mode: vertical installation or horizontal installation

9. Overall and mounting dimensions (mm)


9.1 Outline dimension & Installation dimension

Wiring terminal of zero line


(Only three pole products)

J
H
M K L
H2 H3

① Outline dimension
O
N
B

H1

F G

Dimension A F G K
B E J L M N O H H1 H2 H3
Modle 3P 4P 3P 4P 3P 4P 3P 4P
NZ7-63 355 380 240 200 40 52.5 132.5 145 178 24 11.5 25 40 200 117 150 170 25 18/28
NZ7-125 390 420 240 200 43 58 148 163 194 24 9 30 43 200 136 150 180 25 24
NZ7-250 435 470 240 200 41.5 59 170.5 188 225 36 18.5 35 41.5 200 144 160 190 25 24
NZ7-400 565 615 330 225 43.5 68.5 232.5 257.5 304 61.5 36.5 48 43.5 265 224 200 227 24 40
NZ7-630 680 740 330 225 45.5 74.5 291 320 385 89 60 58 45.5 270 234 200 232 24 42

> >> 53
N7 Series Products
NZ7
9.2 Installation dimension

4×φP

Dimension C
D P
Modle 3P 4P
NZ7-63 322 347 220 φ8
NZ7-100 357 387 220 φ8
D

NZ7-225 402 437 220 φ8


NZ7-400 505 555 300 φ10
NZ7-630 622 680 300 φ10

9.3 Controller Module

nstallation dimension of the controller


when it is installed by split type
84 42 14
144

140

140
50

80

80

10. Ordering information


The user shall indicate such items as the type,
current specification, number of poles.

Example: If you order an auto transfer switch equipment,


shell current 100A, rated current 100A,breaking capacity
of Type H, 4 poles, Type A controller, you can write it as
NZ7-100H/4100YA.

54 > >>
N7 Series Products
NB7
2. Type designation
N B7

Design number
Miniature circuit breaker
Company code

3. Technical data
3.1 Main specifications
3.1.1 Graded according to the rated current In: 1A, 2A, 3A, 4A,
6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;
3.1.2 Classified as follows according to the type of instantaneous
release: type B (3-5)In, type C (5-10)In, type D ((10-16)In;
3.1.3 Categorized as follows according to the number of poles:
a. Single pole
b. Two poles
c. Three poles
d. Four poles
3.2 Technical parameters
NB7 Series 3.2.1 For the rated short circuit breaking capacity, see Table 1
Miniature Circuit Breaker Table 1
Rated current Number of Rated voltage Rated short circuit
1. General In (A) poles Ue (V) capacity Icn (A)
The NB7 series miniature circuit breaker is applicable to the 1 230/400
circuit with an alternating current of 50Hz, rated voltage of B、C type: 1~40 6000
2, 3, 4 400
230/400V, and rated current up to 63A for overload
1 230/400
protection and short circuit protection, and also for not- B、C type: 50 60
frequent operational transformation in the circuit under 2, 3, 4 400
4500
normal condition. 1 230/400
This product can be applied to various places such as D type: 1~63
2, 3, 4 400
industrial, commercial, and tall buildings, and residential
houses. 3.2.2 Mechanical/electrical Life
The product meets the standards of IEC60898-1.
a. Electrical life: not less than 4,000 times
b. Mechanical life: not less than 10,000 times
3.2.3 For the over current protection characteristics, see Table 2

Table 2
Test Initial Time limit for tripping Expected Test environment
Test Type Remarks
current state or not tripping result temperature
a B, C, D Cold state t≤1h Not tripping
b B, C, D Right after test number 1 t<1h Tripping The current is
1s<t<60s (In≤32A) rising within 5s
c B, C, D Cold state Tripping
1s<t<120s (In>32A)
B 3In 30℃~35℃
The power supply is turned on
d C 5In Cold state t≤0.1s Not tripping
by closing the auxiliary switch
D 10In
B 5In
The power supply is turned on
e C 10In Cold state t<0.1s Tripping
by closing the auxiliary switch
D 16In
Note: The terminology “Cold state” means that the test is performed at the base calibration temperature with no load prior to the test.

> >> 55
N7 Series Products
NB7
2
3.2.4 For the tripping performance diagram, see Fig 1 3.2.5 Wiring: good for connection of leads of less than 25mm
(see Table 3); wiring method: screw hold-down with a toque
t(s) B Type
of 2N•m
10000
5000
1h Rated current Nominal cross-sectional area
2000
1000
In (A) of the copper conductor (mm2)
500
200
1~6 1
100
50
10 1.5
20 16, 20 2.5
10
5 25 4
2
1 32 6
0.5
40, 50 10
0.2
0.1
0.05
63 16
0.02
0.01
0.005
4. Overall and mounting dimensions (mm)
0.002
0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 I/In

0
72 -1.2
4P 0 Multi pole 80 -1.2
0
54 -1.2
C Type 3P
0
t(s) 2P
36 -0.62
0
0
Single pole 78 -1.2
10000 18 -0.43 67.3±0.37
5000 1P
1h
2000
1000
500
200

81.5±0.44
34.5±0.5

45±0.31
100

85.5 -1.4
0
50
20 .OFF .OFF .OFF .OFF
10
5
2
1
0.5
0.2 50.3±0.37
0.1
0.05
0.02
0.01
0.005
0.002
0.001
I/In
5. Ordering information
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200
5.1 When ordering the goods, the user shall indicate the following
items:
5.1.1 Types and names of products, for example, NB7 miniature
D Type
t(s) circuit breaker;
10000
5000
1h
5.1.2 Instantaneous tripping type and rated current, for example,
2000
1000 C25;
500
5.1.3 Number of poles: for example, 2P;
200
100 5.1.4 Amount on order, for example, 50 units;
50
20
5.2 Example for ordering: 50 units of the NM7 series miniature
10
5
circuit breakers, 2P, C25.
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.5 1 2 3 4 5 7 10 16 20 30 50 70 100 200 I/In

56 > >>
N7 Series Products
NB7LE
2. Type designation
N B 7 LE - □

Frame size rated current (32A,63A)


Function code (LE: electronic type RCB0)
Design number
Miniature circuit breaker
Company code

3. Technical data
3.1 Main specifications
3.1.1 Graded as follows according to the rated current In:
NB7LE-32: 6A, 10A, 16A, 20A, 25A, 32A;
NB7LE-63: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
3.1.2 Classified as follows according to the type of
instantaneous release: C type (5-10) In, D type (10-16) In;
3.1.3 Categorized as follows according to the number of poles
and current circuit: Single pole and two lines (1P+N), two
poles (2P), three poles(3P), three poles and four lines (3P+N),
NB7LE Series Residual Current four poles (4P) for the NB7LE-32;
Single pole and two lines (1P+N), two poles (2P) for the
Operated Circuit Breaker NB7LE-63;
3.1.4 Graded as follows according to the rated residual
1. General operating current: 0.03A, 0.1A, 0.3A;
The NB7LE series residual current operated circuit breaker is 3.2 Technical parameters
applicable to the circuit with an alternating current of 50Hz, 3.2.1 Rated short circuit breaking capacity (see Table 1)
rated-voltage single pole and two lines/two poles 230V, 3.2.2 Rated residual making and breaking capacity: 2,000A;
three poles/three poles and four lines/four poles 400V, and
3.2.3 Rated residual non-operating current: 0.5IΔn;
a rated current up to 63A; when the human body gets an
electric shock or the network leak current exceeds the 3.2.4 Breaking time of the residual current operating (see Table
specified value, the residual current operated circuit breaker 2)
can rapidly cut off the power supply in trouble within a very 3.2.5 Mechanical/Electrical Life
short time for the safety of the human body and the a. Electrical life: no less than 2,000 times
powered equipment. With the function of overload and
b. Mechanical life: no less than 2,000 times
short circuit protection, the residual current operated circuit
breaker can be used to protect the circuit or motor from 3.2.6 Insulation shock-resistance voltage performance
being damaged by overload and short circuit, and can also a. The impulse voltage with a peak value of 6,000V can be
be used for not-frequent operational transformation in the withstood between the various poles connected together and
circuit under normal condition. the neutral pole;
The product meets the standards of IEC 61009-1.
b. The impulse voltage with a peak value of 8,000V can be
withstood between the various poles connected with the neutral
pole and the metal support;
3.2.7 The residual current operated circuit breaker has the
capability of withstanding the impact of the surge current with a
peak current of 200A (0.5μs/100kHz) and 3,000A (8 /20μs)
without causing misoperation;

Table 1 Rated short circuit capacity Table 1

Rated current Number of Rated voltage Rated short circuit


In (A) poles Ue (V) capacity Icn (A)
C type: 6~40 1P+N,2P 230
C type: 6~40 3P, 3P+N, 4P 400 6000
C type: 50 63 1P+N,2P 230
D type: 6~63 1P+N,2P 230 4500
D type: 6~32 3P, 3P+N, 4P 400

> >> 57
N7 Series Products
NB7LE
Table 2 Maximum breaking time of the residual current operating
Table 2

Breaking time when the residual current assumes the following values (s)
In A I△n A
I△n 2 I△n 5 I△n 5A,10A,20A,50A,100A,200A,500Aa I△tb
6~63A 0.03,0.1,0.3 0.1 0.05 0.04 0.04 0.04

a. The test of 5A,10A,20A,50A,100A,200A,500A is only performed for the verification of operation, and is not performed for the magnitude of
current greater than the lower limit of the over-current instantaneous tripping range.
b. The test is carried out for the current with the IΔn being equal to the lower limit of the over-current instantaneous tripping range for type C or D.

3.2.8 Over current protection characteristic (see Table 3)

Test Initial Time limit for tripping Expected Test environment


Test Type Remarks
current state or not tripping result temperature
a C, D 1.13In Cold state t≥1h No tripping
b C, D 1.45In Right after test a t<1h Tripping The current is
1s<t<60s (In≤32A) rising within 5s
c C, D 2.55In Cold state Tripping
1s<t<120s (In>32A)
30℃~35℃
C 5In The power supply is turned on
d Cold state t≥0.1s No tripping
by closing the auxiliary switch
D 10In

C 10In The power supply is turned on


e Cold state t<0.1s Tripping
by closing the auxiliary switch
D 16In

Note: The terminology “Cold state” means that the test is performed at the base calibration temperature with no load prior to the test.

3.2.9 For the tripping performance diagram, see Fig 1 3.2.10 Wiring: suitable for the connection of leads of less than
25mm2 (see Table 4); wiring method: screw hold-down
C Type
10000 with a toque of:
5000
1h
2000 Not less than 0.8N•m and not greater than 1.2N•m for
1000
500 the M4 screw
200 Not less than 1.5N•m and not greater than 2.0N•m for
100
50 the M5 screw
20
10 Table 4 Nominal cross-sectional area of the copper conductor
t(s)

5
2 Table 4
1
0.5
0.2
Rated current Nominal cross-sectional area
2
0.1 In (A) of the copper conductor (mm )
0.05
0.02 6 1
0.01
0.005 10 1.5
0.002
0.001 16, 20 2.5
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200
25 4
I/ln
32 6
40, 50 10

10000
D Type 63 16
5000
1h
2000
1000
500
200
100
50
20
t(s)

10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200

I/ln

58 > >>
N7 Series Products
NB7LE
4. Overall and mounting dimensions (mm)

H
50.3±0.31

34.5±0.5
L(mm)
87.5 -1.4

45±0.31
Poles H(mm)
0 NB7LE-32 NB7LE-63
0 0 0
1P+N 78 -1.2 45 -0.74 54 -0.74
0 0 0
2P 80 -1.2 63 -0.74 72 -0.74
0 0
3P 80 -1.2 90 -1.4 -
0 0
L 3P+N 80 -1.2 99 -1.4 -
0 0
4P 80 -1.2 117 -1.6 -

5. Ordering information
5.1 When ordering the goods, the user shall indicate the following items:
5.1.1 Types and names of products, for example, NB7LE series residual current operated circuit breaker
5.1.2 Instantaneous tripping type and rated current, for example, C25;
5.1.3 Number of poles: for example, 2P;
5.1.4 Rated residual operating current: for example, 0.03A;
5.1.5 Quantity on order, for example, 50 units;
5.2 Example for ordering: NB7LE-32 residual current operated circuit breaker, 2P,0.03A,C25, 50 units.

> >> 59
N7 Series Products
NC7
2. Operation conditions
2.1 Ambient air temperature:-5℃~+40℃,
its mean value not greater than +35℃
within 24 hours.
2.2 Atmospheric conditions: Ambient temperature

When the maximum temperature is +40℃,


the relative humidity of the air shall not be
higher than 50%; a higher relative humidity
is allowed at a lower temperature, e.g.,
up to 90% at 20℃. Special measures shall
be taken for the condensation occasionally

2000m
produced due to temperature change.
2.3 Altitude: not higher than 2000m. Altitude

2.4 Pollution grade: 3


2.5 Installation classification: III
2.6 Installation condition:
the installing surface shall be inclined
at not greater than ±5°to the vertical.
2.7 Impact vibration:
The product shall be installed in the place
free of remarkable shake, impact and vibration. No Pollution

NC7 Series AC Contactor

1. General
The NC7 series AC contactor (hereinafter referred to as
“contractor”) is mainly used in the circuit with an alternating
current of 50Hz (or 60Hz), rated operational voltage up to
690V, and rated operational current up to 620A under the
usage category of AC-3/400V; this contact is mainly used for
remotely closing and breaking circuits, and can be combined
with an appropriate thermal overload relay to form a
electromagnetic starter so as to protect the circuits likely
to be overloaded in operation; the contact is well suited for
frequently starting and controlling AC motors.

This product meets the standard of IEC60947-4-1

60 > >>
N7 Series Products
NC7
3. Type and meaning
3.1 Product type and meaning

NC7 - 09 01 /N

Main circuit current Number of auxiliary contacts An interlock product


AC Contactor
09 9A 01 1NC /N Reversible product
9A~38A 9A~95A
12 12A 10 1NO omitted Single unit of the product
... ... 40A~95A 11 1NO+1NC 115A~170A In development In development
475 475A 115A~170A omitted 2NO+2NC Reversible product
620 620A 205A~620A omitted 4NO+4NC /Nc
vertical installation

205A~620A Reversible product


/Ns
horizontal installation

omitted Single unit of the product

3.2 Accessory type and meaning

AX-3 / 20 F5 - T 0

Number of auxiliary contacts Time-delay type Time-delay range


Top Air
suspension 20 2NO time-delay T Making time-delay 0 0.1s~3s
auxiliary 11 1NO+1NC head Breaking time-delay 2 0.1s~30s
D
contactor 02 2NC 4 10s~180s
block 40 4NO
31 3NO+1NC
22 2NO+2NC
13 1NO+3NC
04 4NC

NCF1 - 11C NJ1 S-GG

Number of auxiliary contacts Mechanical Installation mode Size code


Side
suspension interlock GG NC7-205 Combination of two units
auxiliary 11C 1NO+1NC module HH NC7-250~300 Combination of two arbitrary units
s Horizontal
contactor KK NC7-410~475 Combination of two arbitrary units
installation
block LL NC7-620 Combination of two units
GG NC7-205 Combination of two units
GH NC7-205 and NC7-250~300
GK NC7-205 and NC7-410~475
GL NC7-205 and NC7-620
Note: For the NC7 product, the 9A-95A mechanical interlock HH NC7-250~300 Combination of two arbitrary units
c Vertical
module can be directly purchased with an indication. HK NC7-250~300 and NC7-410~475
installation
HL NC7-250~300 and NC7-620
KK NC7-410~475 Combination of two arbitrary units
KL NC7-410~475 and NC7-620
LL NC7-620 Combination of two units

> >> 61
N7 Series Products
NC7
4. Quick type selection table

Specified current 9A 12A 18A 25A 32A 38A

Number of 1 NO
the auxiliary auxiliary contact NC7-0910 NC7-1210 NC7-1810 NC7-2510 NC7-3210 NC7-3810

contacts provided 1 NC
with the body itself auxiliary contact NC7-0901 NC7-1201 NC7-1801 NC7-2501 NC7-3201 NC7-3801

IEC/EN 60974-4-1 kW A kW A kW A kW A kW A kW A

Appointed free air heat


20 20 32 40 50 50
generation current (A)
380V/400V(AC-3) 4 9 5.5 12 7.5 18 11 25 15 32 18.5 38
Rated
operational 380V/400V(AC-4) 1.5 3.5 2.2 5 3 7.7 4 8.5 5.5 12 5.5 12
current 660V/690V(AC-3) 5.5 6.6 7.5 8.9 10 12 15 18 18.5 22 18.5 22
and power 660V/690V(AC-4) 1.1 1.5 1.5 2 3.7 3.8 4 4.4 5.5 7.5 5.5 7.5

Accessories which can be further attached

Side suspension Top suspension


Air delay head Mechanical interlock module
auxiliary contact auxiliary contact

Surge suppressor Thermal overload relay Electronic overload relay

62 > >>
N7 Series Products
NC7

Specified current 40A 50A 65A 80A 95A

Number of 1NO+1NC
the auxiliary auxiliary contact NC7-4011 NC7-5011 NC7-6511 NC7-8011 NC7-9511
contacts provided
with the body itself

IEC/EN 60974-4-1 kW A kW A kW A kW A kW A

Appointed free air heat generation current (A) 60 80 80 110 110

380V/400V(AC-3) 18.5 40 22 50 30 65 37 80 45 95
Rated
operational 380V/400V(AC-4) 7.5 18.5 11 24 15 28 18.5 37 22 44
current 660V/690V(AC-3) 30 34 37 39 37 42 45 49 45 49
and power 660V/690V(AC-4) 7.5 9 11 12 11 14 15 17.3 18.5 21.3

Accessories which can be further attached

Side suspension Top suspension


Air delay head Mechanical interlock module
auxiliary contact auxiliary contact

Surge suppressor Thermal overload relay Electronic overload relay

> >> 63
N7 Series Products
NC7

Specified current 115A 150A 170A

Number of
the auxiliary
2 NO+2NC NC7-115 NC7-150 NC7-170
contacts provided
auxiliary contact
with the body itself

IEC/EN 60974-4-1 kW A kW A kW A

Appointed free air heat


200 200 275
generation current (A)
380V/400V(AC-3) 55 115 75 150 90 170
Rated
operational 380V/400V(AC-4) 55 115 75 150 75 150
current 660V/690V(AC-3) 80 86 100 107 110 118
and power 660V/690V(AC-4) 80 86 100 107 100 107

Accessories which can be further attached

Top suspension Side suspension


Air delay head
auxiliary contact auxiliary contact

Mechanical interlock module

64 > >>
N7 Series Products
NC7

Specified current 205A 250A 300A

without auxiliary mount two


contacts, can mount AX-3/22 NC7-205 NC7-250 NC7-300
two Top suspension 4NO+4NC
auxiliary contacts
Other mode Note Note Note

IEC/EN 60974-4-1 kW A kW A kW A

Appointed free air heat


275 315 380
generation current (A)

Rated 380V/400V(AC-3) 110 205 132 250 160 300


operational 380V/400V(AC-4) 110 205 132 250 160 300
current 660V/690V(AC-3) 129 137 160 170 220 235
and power
660V/690V(AC-4) 129 137 160 170 220 235

Accessories which can be further attached

Top suspension
Air delay head Mechanical interlock module
auxiliary contact

Thermal overload relay Electronic overload relay

> >> 65
N7 Series Products
NC7

Specified current 410A 475A 620A

mount two
without auxiliary
AX-3/22 NC7-410 NC7-475 NC7-620
contacts, can mount
two Top suspension 4NO+4NC
auxiliary contacts
Other mode Note Note Note

IEC/EN 60974-4-1 kW A kW A kW A

Appointed free air heat


450 630 800
generation current (A)

Rated 380V/400V(AC-3) 200 410 250 475 335 620


operational 380V/400V(AC-4) 200 410 250 475 335 620
current 660V/690V(AC-3) 280 303 335 353 450 462
and power
660V/690V(AC-4) 280 303 335 353 450 462

Accessories which can be further attached

Top suspension
Air delay head Mechanical interlock module
auxiliary contact

Thermal overload relay Electronic overload relay

66 > >>
N7 Series Products
NC7
Modularized accessories which can be installed additionally

4NO AX-3/40

3NO+1NC AX-3/31

2NO+2NC AX-3/22

1NO+3NC AX-3/13
Number of Able to be used for
auxiliary contacts the whole series products
4NC AX-3/04
AX-3
Auxiliary contact 2NO AX-3/20

1NO+1NC AX-3/11

2NC AX-3/02

0.1~3 F5-T0

On-delay time (s) 0.1~30 F5-T2

10~180 F5-T4
Able to be used for
the whole series products
F5 0.1~3 F5-D0
1N/O+1N/C
Air delay head Off-delay time (s) F5-D2
0.1~30

10~180 F5-D4

Number of 1NO+1NC NCF1-11C Able to be used for


auxiliary contacts the products of
170A or lower
NCF1-11C
Secondary side suspension
auxiliary contact

AC 24V~48V SR1 24V~48V

AC 100V~250V SR1 100V~250V ble to be used for


the products of
9A~38A or lower
SR1
AC 380V~440V SR1 380V~440V
Surge suppressor
Suppression
voltage range
AC 24V~48V SR2-B 24V~48V

AC 100V~250V SR2-B 100V~250V ble to be used for


the products of
40A~95A or lower
SR2-B
AC 380V~440V SR2-B 380V~400V
Surge suppressor

> >> 67
N7 Series Products
NC7

NR2-25 9A~32A

NR2-36 32A, 38A

NR2-93 40A~95A

NR2-150 115A~150A

NR2 NR2-200 115A~205A


Thermal overload relay

NR2-630 205A~620A

NRE8-25 9A~32A

NRE8-40 40A

NRE8-100 40A~95A

NRE8-200 115A~205A
NRE8
Electronic overload relay
NRE8-630 205A~620A

Purchase individually
Purchase it individually,
How to purchase and install it by yourself
How to purchase Reversible product without
connecting wire the products of
the products of Directly purchase the reversible products
205A or higher
95A or lower (specified current for two contactors
Reversible product with
connecting wire to be the same)

NJLs-GG NC7-205 Combination of two units


NJLs-HH NC7-250~ 300 Combination of two arbitrary units
Horizontal
NJLs-KK NC7-410~475 Combination of two arbitrary units
installation
NJLs-LL NC7-620 Combination of two units
NJLc-GG NC7-205 Combination of two units
NJLc-GH NC7-205 and NC7-250~ 300
NJLc-GK NC7-205 and NC7-410~475
NJLc-GL NC7-205 and NC7-620
Over 205A product NJLc-HH NC7-250~ 300 Combination of two units
Mechanical mechanical interlocking Vertical
NJLc-HK NC7-250~ 300 and NC7-410~ 475
interlock module mechanism code installation
NJLc-HL NC7-250~ 300 and NC7-620
NJLc-KK NC7-410~ 475 Combination of two units
NJLc-KL NC7-410~475 and NC7-620
NJLc-LL NC7-620 Combination of two units

68 > >>
N7 Series Products
NC7
5. Main parameters and technical performance
5.1 Main parameters and technical performance criteria for the NC7 product

Type NC7-09 NC7-12 NC7-18 NC7-25 NC7-32 NC7-38 NC7-40 NC7-50 NC7-65 NC7-80 NC7-95
AC-3 9 12 18 25 32 38 40 50 65 80 95
Rated 380V/400V
AC-4 3.5 5 7.7 8.5 12 12 18.5 24 28 37 44
operational
AC-3 6.6 8.9 12 18 22 22 34 39 42 49 49
current (A) 660V/690V
AC-4 1.5 2 3.8 4.4 7.5 7.5 9 12 14 17.3 21.3
Appointed free air heat generation current (A) 20 20 32 40 50 50 60 80 80 110 110
Rated insulation voltage (V) 690 690 690 690 690 690 690 690 690 690 690
Rated impulse withstand voltage (kV)6 6 6 6 6 6 8 8 8 8 8
Rated making capacity Making current: 10xIe(AC-3) or 12xIe(AC-4)
Rated breaking capacity Making/breaking current: 8xIe(AC-3) or 10xIe(AC-4)
Short time withstand current (10s) 72 96 144 200 256 304 320 400 520 640 760
Controllable three-phase 380V/400V 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45
squirrel-cage motor power(AC-3)kW 660V/690V 5.5 7.5 10 15 18.5 18.5 30 37 37 45 45
Intermittent-periodic-duty 380V/400V 1.5 2.2 3 4 5.5 5.5 7.5 11 15 18.5 22
motor power(AC-4)kW 600V/690V 1.1 1.5 3.7 4 5.5 5.5 7.5 11 11 15 18.5
Frequency of AC-3 1200 1200 1200 1200 600 600 600 600 600 600 600
operation Electrical life AC-4 300 300 300 300 300 300 300 300 300 120 120
(times/h)
Mechanical life 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600
Electrical life AC-3 100 100 100 100 80 80 80 60 60 60 60
(ten thousand times) AC-4 20 20 20 20 20 20 15 15 15 10 10
Mechanical life(ten thousand times) 1000 1000 1000 1000 800 800 800 800 800 600 600
Type of the fuse adapted RT36-20 RT36-20 RT36-32 RT36-40 RT36-50 RT36-50 RT36-63 RT36-80 RT36-80 RT36-100 RT36-125
Piece (of string, etc) 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
Cold-pressed Non-prefabricated-tip cord 1/2.5 1/2.5 1/2.5 1/2.5 1.5/4 1.5/4 1.5/4 1.5/4 2.5/6 2.5/6 2.5/6 2.5/6 6/25 4/10 6/25 4/10 6/25 4/10 10/35 6/16 10/35 6/16
terminal Cord with the prefabricated tip mm2 1/4 1/2.5 1/4 1/2.5 1.5/6 1.5/4 1.5/10 1.5/6 2.5/10 2.5/6 2.5/10 2.5/6 6/25 4/10 6/25 4/10 6/25 4/10 10/35 6/16 10/35 6/16
Non-prefabricated-tip hard wire 1/4 1/4 1/4 1/4 1.5/6 1.5/6 1.5/6 1.5/6 2.5/10 2.5/10 2.5/10 2.5/10 6/25 4/10 6/25 4/10 6/25 4/10 10/35 6/16 10/35 6/16
Connection terminal screw size and M3.5 M3.5 M3.5 M4 M4 M4 M4 M4 M4 M4 M8 M8 M8 M8 M8 M8 M10 M10 M10
tightening torque (N·m) 0.8 0.8 0.8 1.2 1.2 1.2 1.2 1.2 1.2 1.2 3.5 3.5 3.5 3.5 3.5 3.5 4.0 4.0 4.0
Attracting(VA) 70 70 70 110 110 110 200 200 200 200 200
AC coil 50Hz
Holding(VA) 9 9 9.5 14 19 19 57 57 57 57 57
power
Power(W) 1.8~2.7 1.8~2.7 3~4 3~4 3~4 3~4 6~10 6~10 6~10 6~10 6~10
Action (actuating)range Pull-in voltage: 85%Us~110%Us; Release voltage: 20%Us~75%Us
Basic parameters of the auxiliary contact AC-15: 360VA DC-13: 33W Ith: 10A

5.2 Rated control source voltage Us and code for the NC7 ac contactor of 95A or lower

Coil voltage Us(V) 24 36 42 48 110 127 220 230 240 380 400 415 440 480 500 600 660
50Hz B5 C5 D5 E5 F5 G5 M5 P5 U5 Q5 V5 N5 R5 T5 S5 X5 Y5
60Hz B6 C6 D6 E6 F6 G6 M6 P6 U6 Q6 V6 N6 R6 T6 S6 X6 Y6
50/60Hz B7 C7 D7 E7 F7 G7 M7 P7 U7 Q7 V7 N7 R7 T7 S7 X7 Y7

> >> 69
N7 Series Products
NC7

Type NC7-115 NC7-150 NC7-170 NC7-205 NC7-250 NC7-300 NC7-410 NC7-475 NC7-620
Rated AC-3 115 150 170 205 250 300 410 475 620
380V/400V
operational AC-4 115 150 150 205 250 300 410 475 620
AC-3 86 107 118 137 170 235 303 353 462
current (A) 660V/690V
AC-4 86 107 107 137 170 235 303 353 462
Appointed free air heat generation current (A) 200 200 275 275 315 380 450 630 800
Rated insulation voltage (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage (kV) 8 8 8 8 8 8 8 8 8
Rated making capacity Making current: 10xIe(AC-3) or 12xIe(AC-4)
Rated breaking capacity Making/breaking current: 8xIe(AC-3) or 10xIe(AC-4)
Short time withstand current (10s) 920 1200 1360 1640 2000 2400 3280 3600 4960
Controllable three-phase 380V/400V 55 75 90 110 132 160 200 250 335
squirrel-cage motor power(AC-3)kW 660V/690V 80 100 110 129 160 220 280 335 450
Intermittent-periodic-duty 380V/400V 55 75 75 110 132 160 200 250 335
motor power(AC-4)kW 600V/690V 80 100 100 129 160 220 280 335 450
Frequency of AC-3 1200 1200 600 600 600 600 600 600 600
operation Electrical life AC-4 120 120 120 60 60 60 60 60 60
(times/h)
Mechanical life 1200 1200 600 600 600 600 600 600 600
Electrical life AC-3 80 80 60 60 60 60 60 60 60
(ten thousand times) AC-4 2 2 1 1 1 1 1 0.6 0.6
Mechanical life(ten thousand times) 600 600 600 600 600 600 600 600 600
Type of the fuse adapted NT3-225 NT3-225 NT3-315 RT36-3 RT36-3 RT36-3 RT36-3 RT36-4 RT36-4
Action (actuating)range Pull-in voltage: 85%Us~110%Us; Release voltage: 20%Us~75%Us; NC7-250~620 Release voltage: 10%Us~75%Us
Basic parameters of the auxiliary contact AC-15: 360VA DC-13: 33W Ith: 10A

Type NC7-115 NC7-150 NC7-170 NC7-205 NC7-250 NC7-300 NC7-410 NC7-475 NC7-620
Piece (of string, etc) 1 1 1 1 1 1 1 2 2
Cable (mm2) 70 70 120 120 185 240 240 185 240
Copper (mm) - - - - - - - 40X5 50X5
Bolt M10 M10 M10 M10 M10 M10 M10 M10 M12
Tightening torque(N·m) 4 4 4 10 10 10 10 10 14

5.3 Rated control source voltage Us and code for the NC7 ac contactor (205A - 620A) product coil

Coil code Control voltage (V) Power VA


110 127 220 380 Schematic drawing
Contactor type Start Hold
NC7-205 FG110 FG127 FG220 FG380 966 91.2
NC7-250 FI110 FI127 FI220 FI380 1500 34.2
NC7-300 FI110 FI127 FI220 FI380 1500 34.2
NC7-410 FJ110 FJ127 FJ220 FJ380 1500 34.2
NC7-475 FK110 FK127 FK220 FK380 1500 34.2
NC7-620 FL110 FL127 FL220 FL380 1700 34.2

Note: Products of NC7-250 or higher are duplex winding ones.

70 > >>
N7 Series Products
NC7
6. Derivative products

Derivative products Contactor Auxiliary module Schematic drawing

Reversing contactor

Mechanical interlocking mechanism

Timing-delay contactor

Air delay head

Star-delta
starter

Air delay head Auxiliary contactor block

Magnetic starter

Thermal relay

AC contactor
for capacitor switching
Current limiting contact block

> >> 71
N7 Series Products
NC7

7. Overall and mounting dimensions

NC7 09~38

D(AX-3)/E(F5) A Φ
C

b
B
a

NC7 40~95

A
D(AX-3)/E(F5) Φ
C

b
B

72 > >>
N7 Series Products
NC7

NC7 115~170

D(AX-3)/E(F5)
C A
Φ

b
a

NC7 205~300

Φ
11.5
B

b
a
C
A

> >> 73
N7 Series Products
NC7

NC7 410~475

13.5
B

b
a
C A

NC7 620

Φ
15.5
B

b
a

C A

74 > >>
N7 Series Products
NC7

mm
Type Amax Bmax Cmax Dmax Emax a b φ
NC7-09~12 47 76 86 124.5 144.5 34/35 50/60 4.5
NC7-18 47 76 91 129.5 149.5 34/35 50/60 4.5
NC7-25 57 86 98 136.5 156.5 40 48 4.5
NC7-32~38 57 86 102 140.5 160.5 40 48 4.5
NC7-40~65 77 129 119 157.5 177.5 64 100~110 6
NC7-80~95 87 129 127 165.5 185.5 64 100~110 6
NC7-115~170 120 156 155 193.5 213.5 96~110 130 7
NC7-205 171 197 186 80 110~120 6.5
NC7-250 202 203 215 96 110~120 6.5
NC7-300 213 206 220 96 110~120 6.5
NC7-410 213 206 221 80 170~180 8.5
NC7-475 233 238 233 80 170~180 8.5
NC7-620 309 304 256 180 180~190 10.5

8. Ordering information
8.5 Amount on order
The following to be indicated when ordering: 8.6 The 95A-or-lower derivative N conventional products triple
8.1 Full name and type of the contactor poles are provided in the mode of reversible wiring, so you
8.2 Rated control source voltage and frequency or size code of the coil must give clear indication for your special wiring mode.
8.3 If you need to order the F4 auxiliary contactor block, F5 air delay 8.7 The 205A-or-higher derivative NS conventional products triple
head or standard rail track for the product, you should further give poles are provided in the mode of reversible wiring, so you must
a clear indication; For products of 205A or higher, the auxiliary give clear indication for your special wiring mode.
contactor blocks will not be attached for lack of indication such as 8.8 Order Sample:
the number of those blocks and how they are combined. 10 units of NC7-0910 ac contacts, coil voltage 220V/50Hz,
8.4 When the NC7 9A-170A products leave the factory, the body with 5 pieces of F4-22
is not provided with the dust cap. It is hoped users will further 10 units of NC7-300 ac contacts, coil voltage 220V/50Hz,
give a clear indication when they need it. with 10 pieces of F4-22 further attached

Mechanical interlocking mechanism to be order Writing format for ordering

NC7-205 combined with NC7-620


NJLc-GL 30 sets
Aertical installation, Mechanical interlocking mechanism, 30 sets

Two NC7-250 combination in a mode of


NJLc-HH 30 sets
Horizontal installation, Mechanical interlocking mechanism, 30 sets

> >> 75
N7 Series Products

ZHEJIANG CHINT ELECTRICS CO.,LTD.


Add: No. 1, CHINT Road, CHINT Industrial Zone, North Baixiang,
Yueqing, Zhejiang, 325603, P.R.China
Tel: +86-577-62877777
Fax: +86-577-62775769 62871811
E-mail: global-sales@chint.com
Website: www.chint.net Oct 2012
EN B22

CHINT Electric All Rights Reserved Recycle Paper Printed Specifications and technical data are subject to change without notice.
Please contact us to confirm relevant information on ordering