EN B22
“CHIN” indicates ”CHINA”,and ”T” represents “TOMORROW”,
proclaiming its signification-”Tomorrow of China”.
Europe
Asia-Pacific
China
West Asia & Africa
Marketing Network
Chint not only has advanced production equipment, strict quality management and innovative research and
development team, but also a worldwide marketing network consisting of 5 international marketing areas,
13 domestic marketing offices, 12 logistics centers, more than 280 specialty stores and more than 1000 sales
companies, which are always ready to provide the users with high-quality professional services.
America
Solar Farm
Public Cable Net KWH Meter
Microcomputer Protection-
Control Device
Main Station Concentrator
Automatic Meter Reading System Prefabricated Substation
Solar Inverter
HV Switchgear
GIS
Outdoor HV AC Switch-Disconnector
Distrivuted Solar Inv
HV Power Factor Compensation
HV Power Factor Compensation
HV Current/Voltage Transformer
Power Transformer Power Capicitor
KWH Meter
HV Capacitor
Power of Dedication has transformed CHINT from a simple electric component manufacturer
into a leading electric system solution provider, enabling all users from power transmission,
distribution and usage sectors to access more reliable, secure, energy-saving, precise,
eco-friendly, and intelligent electric products and services.
CHINT highly values all personalized demands of electric power, machinery, construction,
communications, HVAC, metallurgy, petrochemical, railway, and other industries all the time,
and devote itself to facilitating technical innovations and building a green future by
providing users with world-class tailor-made electric system solutions.
Automatic monitoring
and management power system
Intelligent Measurement-
Control Unit
DP Contactor
LV Capacitor Motor
Soft Starter
Push-button/Indicator Light
Change-over Switch
Motor Starter Motor Protection Device
itch
Sw
LV Current Transformer
vel
Measure
Tra
Panel Meter
NA8G Series
Air Circuit Breaker
Page 01
NM7 Series
Moulded Case Circuit Breaker
Page 34
NZ7 Series
Automatic Transfer
Switching Equipment
Page 44
NB7 Series
Miniature Circuit Breaker
Page 55
NB7LE Series
Residual Current Operated
Circuit Breaker
Page 57
Page 60
N7 Series Products
NA8G
2. Type designation
N A 8G - □/□
No. of poles
(pole 3 may be omitted)
ACB
Company code
3. Operation conditions
> >> 01
N7 Series Products
NA8G
4. Product structure
Body structure
OFF pushbutton
ON/OFF indication
ON pushbutton
Intelligent controller
Data plate
Breaker off and energy storage over Breaker off and no energy storage Breaker off and energy storage over Breaker off and no energy storage
02 > >>
N7 Series Products
NA8G
Drawout structure
Side panel
Safety separator
Guide rail
Rocking handle work hole
Connected Connected
Test Test
Disconnected Disconnected
Connected: both main circuit and secondary circuit are connected Test: the main circuit is disconnected,
the safety separator works well,
and the secondary circuit is connected.
Connected
Test
Disconnected
> >> 03
N7 Series Products
NA8G
(3)Place the breaker body on the guide rail (4)Move the breaker body onto the guide rail with a snap
(5)Push the breaker body in, and turn the break body to the working position
04 > >>
N7 Series Products
NA8G
5.2 Capacity-reducing usage
5.2.1 Capacity-reducing at different temperatures
The following table shows the continual current-loading capacity of the circuit breakers and buses in each wiring mode
at the corresponding ambient environment temperatures and under the conditions of the satisfaction of conventional heating
with a similarity in capacity reducing between the breaker connected in a mixed way and the breaker connected horizontally.
Style wiring Draw-out type
mode ambient Front/rear horizontal wiring mode Rear vertical wiring mode
temperature℃
-5~40 45 50 55 60 -5~40 45 50 55 60
200 200 200 200 200 200 200 200 200 200
400 400 400 400 400 400 400 400 400 400
630 630 630 630 550 630 630 630 630 580
1600 800 800 800 800 700 800 800 800 800 700
1000 1000 1000 950 900 1000 1000 1000 950 900
1250 1250 1250 1150 1050 1250 1250 1250 1200 1100
1600 1550 1500 1450 1350 1600 1600 1550 1500 1450
1600 1600 1600 1600 1600 1600 1600 1600 1600 1600
2000 2000 2000 2000 1900 2000 2000 2000 2000 1950
3200 2500 2500 2500 2450 2350 2500 2500 2500 2500 2400
2900 2900 2900 2800 2700 2900 2900 2900 2900 2800
3200 3200 3100 3000 2900 3200 3200 3200 3050 2900
4000 4000 4000 3900 3800 4000 4000 4000 3900 3800
6300 5000 5000 4700 4600 4400 5000 5000 4800 4650 4500
6300 6100 6000 5500 5200 6300 6100 6000 5500 5200
5.2.2 Capacity-reducing at different altitudes
When the altitude is higher than 2000m, there will appear changes in insulation property, cooling performance, pressure,
and the performance can be modified in reference to the following table.
Altitude(m) 2000 3000 4000 5000
Insulation withstand voltage(V) 3500 3000 2500 2000
Insulation voltage(V) 1000 800 700 600
Rated operational voltage(V) 690 580 500 400
Rated operational current(A) 1×In 0.96×In 0.92×In 0.87×In
Note: The data and parameters in the above technical documentation results from tests and theoretical calculation,
and can only be used as a general type selection guide.They cannot replace industrial practical experience or proof test.
5.4 Recommended bus for the breaker and recommendation for users to install the buses
Inm(A) NA8G-1600 NA8G-3200 NA8G-6300
In(A) 200 400 630 800 1000 1250 1600 1600 2000 2500 2900 3200 4000 5000 6300
Thickness(mm) 5 5 5 5 5 8 10 6 6 5 10 10 10 10 10
Busbar Width(mm) 20 50 40 50 60 60 60 100 100 100 100 100 100 100 100
Number of buses 1 1 2 2 2 2 2 2 3 4 3 4 5 7 8
> >> 05
N7 Series Products
NA8G
6. Dimensions and connection
NA8G-1600 (In=200A ~1250A) Draw-out type
(horizontal connection is the default by the factory, vertical one to be made by users themselves).
210 36
a
275
149
310
7
351
78.5
95 76
345(Connecting position)
391(Separating position)
2-φ6.5
149(3P)
155(4P)
95
2-φ6.5×10
7
35
75.5(4P)
78.5(3P)
95 76
145(3P) 63
215(4P) 345(Connecting position)
4P Central line 391(Separating position)
3P Central line Wires connected vertically
12×φ11(3P) 60
16×φ11(4P)
15
25
N Pole
In(A) a(mm) Note: If users intend to change the
35
275
310
179
7
351
63.5
95 76
435(Connecting position)
481(Separating position)
282(3P)
352(4P)
Wires connected horizontally
2-φ6.5×10
35
149(3P)
155(4P)
145(3P) 63 7
215(4P)
78.5(3P)
75.5(4P)
4P Central line
3P Central line 95 76
24×φ11(3P) 85
15
32×φ11(4P) 35
N pole 435(Connecting position)
481(Separating position)
35
80.5
06 > >>
N7 Series Products
NA8G
210 22
Separator between phases
(to be ordered separately)
a
320
149
281
275
7
48.5
100 92
237(3P) 251
307(4P)
254(3P) Wires connected horizontally
324(4P)
149(3P)
155(4P)
237(3P)
307(4P)
7
48.5(3P)
45.5(4P)
100 92
4P Central line
251
12×φ11(3P) 3P Central line
16×φ11(4P) 60 Wires connected vertically
N Pole 25
15
In(A) a(mm)
horizontal connection into vertical one
76 76 76
200, 400, 630 5 on site, they need to replace the upper
Drawing illustrating the distance between mounting holes 800, 1000 10 and lower buses on both sides with
1250 15 the same one as the central bus.
210 22
275
149(3P)
155(4P)
281
7
48.5(3P)
45.5(4P)
237(3P) 100 92
307(4P) 341
254(3P)
324(4P) Wires connected vertically
4-φ7
100
4P Central line
3P Central line
179
24-φ11(3P)
32-φ11(4P) 85
15
N Pole 35
7
35
80.5
33.5
> >> 07
N7 Series Products
NA8G
NA8G-1600 Draw-out type NA8G-1600 Fixed type
Size of the hole to be drilled on the panel Size of the hole to be drilled on the panel
220 220
10-φ5 8-φ5
118
120
322
285
320
6
78 118.5
From the center of the mounting hole on the right side of the breaker From the center of the mounting hole on the right side of the breaker
258 258
217.5(3P) 217.5
332.5(4P) 52 386 7
385
240
258
Datum line 2
199.5
Datum line 1
308
371
328
155
11×17
φ11
175
Datum line 2
φ14
268
376
φ1 4 7
11×1
18
145
21.5
97
Installation panel
10
47
08 > >>
N7 Series Products
NA8G
52
78 50 φ11
25
14
29
133
Datum line
84
445(Connecting position)
492(Separating position)
Note: If users want to change the horizontal connection into vertical one on site, they only have to turn the bus by 90°
42
25
14
φ11
78
55
Datum line
25
445(Connecting position)
57.5
492(Separating position)
Note: If users want to change the vertical connection into horizontal one on site, they only have to turn the bus by 90°
C 86 25 12-φ13
15
29
In(A) C
1600, 2000, 2500 20
2900, 3200 30
29
16.5
> >> 09
N7 Series Products
NA8G
NA8G-3200(In=2900, 3200A) Draw-out type (horizontal connection is the default by the factory)
C
7
52
C
25
φ11 100 25
29
14
112
Datum line
90
445(Connecting position)
492(Separating position)
C 7
52
14
φ11 C
25
100
57
Datum line
25
35.5
445(Connecting position)
492(Separating position)
Note: If users want to change the horizontal connection into vertical one on site,
it is necessary to replace the upper and lower buses for the N and B phases with the same one as the A and C phases.
308
N
402
258
Datum line 2
163.5
13
10 > >>
N7 Series Products
NA8G
NA8G-3200 Fixed type, size of the hole to be drilled on the panel
4×φ 12 371
328
150
311
268
72.5
29.5
21.5
200(3P) 200
8×φ6
315(4P) Installation
panel
Datum line Datum line
Ferrous materia l
C
32
C
a
86 50 12-φ13
18.5
112
In(A) a(mm)
115 115 115 1600~2500 20
Datum line 2900~3200 30
55
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.
Ferrous materia l
C
32
29
a C
14
φ11
100
57
Datum line
2900~3200 30
45
Note: If users want to change the horizontal connection into vertical one on site, they only have to additionally install a vertical bus.
> >> 11
N7 Series Products
NA8G
NA8G-6300 In=(4000A~5000A) Draw-out type
size of the hole to be drilled on the panel
710.5(4P)
232 617.5(3P) 217.5 391
Datum line 2
199
Datum line 1
371
328
φ14
155
175
268
11×17
376
Datum line 2
145
18
97
162.5
21.5
703(3P)
47
10×φ6
Datum line 1
Datum line 1
818(4P)
Size of the hole to be drilled on the panel
Datum line 2
199
Datum line 1
371
328
φ14
155
175
268
11×17
376
Datum line 2
145
18
97
162.5
21.5
818
47
10×φ6
Datum line 1
Datum line 1
12 > >>
N7 Series Products
NA8G
NA8G-6300(In=4000A~5000A) Draw-out type
(vertical connection to be made by users themselves)
29
115 N pole
φ11 103 129.5 105 142 105 142 105
125 30
25
57
14
10.5
Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.
N pole
28-Φ13
100 155 210
20
40
103
30
112
55
182 247 247 170.5
92
Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.
14
115
φ11 103 130 207 130 207 130
30
125
25
57
29
10.5
Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.
180 260
20
40
103
112 30
24-Φ13
80
320 320 140
92
Note: If users want to change the horizontal connection into vertical one on site,
they only have to additionally install a vertical bus.
> >> 13
N7 Series Products
NA8G
7. Secondary circuit wiring
Connection diagram for the secondary circuit of the NA8G-1600 optional standard type intellectual controller
Fault indication
N A B C
XT 3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55 FU
Breaker body
M L1
QF F DT Q/QY
SAL
Intellectual controller
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12 Control power supply
SA L2(N)
TA
FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
+DC24V -
S
Power
Energy -driven ON OFF
Main circuit Intellectual controller Open Close Under storage
energy indication indication Auxiliary contact available for users AC auxiliary contact for standby application
voltage indication storage
Notes: 1. Four open (contacts) and four close from DF1 to DF8
with a common point available conventionally, two open
and two close from DF9 to DF12 with a common point available
additionally for Inm = 1600 when special order is made
for alternating current, four open and four close from
DF1 to DF8 with a common point available only for
Inm = 1600 in case of direct current,
contact capacity (DC220V 0.5A).
2. Various control voltages of the 1600 has to be put
to #1 and #2 after the power module inputs DC24V.
3. The wiring for the part indicated by dashed lines shall be made by users.
14 > >>
N7 Series Products
NA8G
Connection diagram for the secondary circuit of the NA8G-3200 to 6300 optional standard type intellectual controller
Fault indication
N A B C
XT 3 4 6 8 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
FU
Breaker body
M L1
QF F DT Q/QY
SAL Intellectual controller
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12 Control power supply
SA L2(N)
TA
FU
XT 1 2 5 7 9 10 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
3200 and 6300 shell controller power supply: AC230V and AC400V
+DC24V -
S
3200, 6300 shell controller power supply: DC220V,DC110V; 1600 shell controller power supply
Power
Under Energy -driven ON OFF
Main circuit Intellectual controller Open Close storage
voltage indication energy indication indication
Auxiliary contact available for users AC auxiliary contact for standby application
storage
Notes: 1. Four open (contacts) and four close from DF1 to DF8
with a common point available conventionally, one open and
one close from DF9 to DF10 with a common point available additionally,
contact capacity (DC220V 0.5A)
2. When the controller voltage of the 3200 and 6300 shells
is AC230V/400V, it can be directly put to #1 and #2; if the voltage
is DC220V/110V, it has to be put to #1 and #2 after the power module inputs DC24V.
3. The wiring of the part indicated by dashed lines shall be made by users.
> >> 15
N7 Series Products
NA8G
Connection diagram for the secondary circuit of the NA8G-1600 optional type multifunctional controller
FU
L1
N
PE
L N PE
Profibus-DP
ST-4 power module
- + - + - + - +
ST-DP
Device
12 13 14 15 16 17 18 19
N A B C
Fault indication 1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V
ST201 SB2 SB1
Green Red
XT 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
PE
QF M
D14 F DT Q/QY
Intellectual controller
SAL D13 D15 D16
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12
SA
TA
Breaker body
XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
+DC24V-
S
Power
Under Energy -driven ON OFF
Main circuit Intellectual controller Open Close voltage
storage
energy indication indication
Auxiliary contact available for users AC auxiliary contact for standby application
indication
storage
# #
1 and 2: input (terminals) for intellectual controller auxiliary power supply
#
3:PE
#
4, #5 and #6: faulty tripping contact output ( #5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliary contact output ( #8 is the common terminal, AC250V 5A)
#
10, #11 and #12: auxiliary contact output ( #11 is the common terminal, AC250V 5A)
#
14 and #15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V,5A)
#
20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
#
24 and #25: to be externally connected to the mutual inductor input
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally,
two open and two close from DF9 to DF12 with a common point available additionally for Inm = 1600 when
special order is made for alternating current. Four open (contacts) and four close from DF1 to DF8 with a
common point available only for Inm = 1600 in case of direct current, contact capacity (AC250V 5A).
2. The wiring of the part indicated by dashed lines to be made by users.
16 > >>
N7 Series Products
NA8G
Connection diagram for the secondary circuit of the NA8G-3200 and 6300 optional type multifunctional intellectual controller
FU
L1
N
PE
L N PE
Profibus-DP
ST-4 power module
- + - + - + - +
ST-DP
Device
12 13 14 15 16 17 18 19
N A B C
Fault indication 1 2 3 4 5 6 7 8
+ + COM D11 D12 D13
DC24V
ST201 SB2 SB1
Green Red
XT 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 39 41 42 44 45 47 48 50 51 53 54 55
PE
QF M
D14 F DT Q/QY
Intellectual controller
SAL D13 D15 D16
DF1 DF2 DF3 DF4 DF5 DF6 DF7 DF8 DF9 DF10 DF11 DF12
SA
TA
Breaker body
XT 1 2 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 40 43 46 49 52 56
3200 and 6300 shell controller power supply: AC230V and AC400V
+ DC24V -
S
3200, 6300 shell controller power supply: DC220V,DC110V; 1600 shell controller power supply
Power
Under Energy -driven ON OFF Auxiliary contact
Main circuit Intellectual controller Open Close voltage
storage
energy indication indication available for users
AC auxiliary contact for standby application
indication
storage
# #
1 and 2: input (terminals) for intellectual controller auxiliary power supply
#
3:PE
#
4, #5 and #6: faulty tripping contact output ( #5 is the common terminal, AC250V 5A)
#
7, #8 and #9: auxiliary contact output ( #8 is the common terminal, AC250V 5A)
#
10, #11 and #12: auxiliary contact output ( #11 is the common terminal, AC250V 5A)
#
14 and #15:RS485 communication interfaces (in case of communication type)
#
16, #17, #18, #19, #26 and #27: programmable input/output points (DC110V 0.5A, AC250V,5A)
#
20, #21, #22, and #23: A, B, C, and N voltage signal output (in case of multifunction type) (maximum voltage AC400V)
#
24 and #25: to be externally connected to the mutual inductor input
Notes: 1. Four open (contacts) and four close from DF1 to DF8 with a common point available conventionally,
one open and one close from DF9 to DF10 with a common point available additionally when special order is made
for alternating current. Contact capacity AC250V 5A
2. When the controller voltage of the 3200 and 6300 shells is AC230V/400V, it can be directly put to #1 and #2;
if the voltage is DC220V/110V, it has to be put to #1 and #2 after the power module inputs DC24V.
3. The wiring of the part indicated by the dashed lines shall be made by users.
> >> 17
N7 Series Products
NA8G
8. Intelligent controller and protective characteristics
8.1 User interface of the standard type controller
10
11
12
13
14
15
16
1 LED window LCD window capable of showing the current for each phase, various setting parameters,
rated current, fault current, tripping time, and the like
2 “ Ig ” limp Asymmetric grounding, neutral line fault indication
Over current long time delay fault indication
3 “ IR ” limp
Short-circuit short-time delay fault indication
4 “ Isd ” limp Short-circuit instantaneous fault indication
5 “ Ii ” limp Successively access to submenus at various levels by pressing the MENU key
To inquire the current for each phase at present:
6 “ MENU ” Pushbutton recurrently select the contents in the menus at various levels
Return to previous menu; the intellectual controller software is reset;
7 “ “ Pushbutton
RESET key must be pressed after the encoder switch position is adjusted;
the intellectual controller faulty tripping results in fault memory which
8 “ RESET ” Pushbutton
can be cleared only by pressing the RESET key;
There are (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 0.98, 1.0)In,
nine settings altogether, for the over current long time delay current multiple setting
9 “ IR ” Knob switch There are (1, 2, 4, 8, 12, 16, 20, 24, 30)s, nine settings altogether,
for the over current long time delay time setting in case of 6Ir
10 “ tR ” Knob switch
There are (1.5, 2, 2.5, 3, 4, 5, 6, 8, 10)Ir, nine settings altogether,
11 “ Isd ” Knob switch for the short-circuit short-time delay current multiple setting
For the short-circuit short-time delay time setting, there are nine settings:
12 “ tsd ” Knob switch the inverse time limit, i.e., I2t on(0.1, 0.2, 0.3, 0.4)s, the definite-time limit,
i.e., I2t OFF (0.1 0.2 0.3 0.4)s and X, i.e., closing the short-time delay
13 “ Ig ” Knob switch There are (A, B, C, D, E, F G, H, J), nine settings altogether, for the asymmetric grounding
(neutral line) current multiple setting
For the typical numerical values thereof, see the characteristic parameter table
14 “ test ” Pushbutto n Button for simulating instantaneous tripping test
15 “ tg ” Knob switch For the asymmetric grounding (neutral line) time setting, there are nine settings: the inverse time limit,
i.e., I2t on(0.1, 0.2, 0.3, 0.4)s, and the definite-time limit, i.e., I2t OFF(0.1 0.2 0.3 0.4)s, and X,
i.e., closing the asymmetric grounding (neutral line)
16 “ Ii ” Knob switch Short-circuit instantaneous current multiple setting.
18 > >>
N7 Series Products
NA8G
8.2 Default interface and menu structure for the standard type controller
The default interface for the standard type controller is described as Default interface for the standard type controller
follows (the current for each phase to be selected by pressing “ ”)
Operation method: Press MENU to go to the primary menu,
then press “ ” selection menu, and than press MENU Go to the 158A
secondary menu, press “ ” selection menu or modify the parameter, 150 N A B C
press RESET to return to the previous menu
100
50
Notes: a. The actual menu will very depend on the function selected by a user.
b. The controller starts screensaver automatically 10min after it is energized.
> >> 19
N7 Series Products
NA8G
8.3 User interface of the multifunctional controller
5
3
6
10
11
13 12
Switch to the set default menu (left arrow key, when it is necessary to move leftwards or rightwards
3 SET key
for the set interface).
Move the box select menu under the current menu to change the position of said box upwards,
4 UP key
and perform the setting of the parameter ADD in the parameter setup menu.
5 RETURN key Exit the current menu and go to the previous menu, or cancel the value of the current setup parameter.
Go to the next menu of the currently selected select box (go to the set state under the set interface, a
6 ACK key
nd exit the set state by double pressing the key).
Move the box select menu under the current menu to change the position of said box downwards,
7 DOWN key
and perform the setting of the parameter SUBTRACT in the parameter setup menu.
Switch to the inquiry default menu (right arrow key, when it is necessary to move leftwards
8 INQUIRY key
or rightwards for the set interface).
9 “ IR “ limp Over current long time delay fault indication
10 “ Isd “ limp Short-circuit short-time delay fault indication
11 “ test ” Button for simulating instantaneous tripping test
12 “ Ii “ limp Short-circuit instantaneous fault indication
13 “ Ig “ limp Asymmetric grounding, neutral line fault indication
20 > >>
N7 Series Products
NA8G
8.4 Default interface and menu structure for the multifunctional controller Default interface for the multifunctional controller
The multifunctional controller provides 4 title menus (measurement
menu, parameter setup menu, protection parameter setup menu, 1002A
N A B C
and history record and maintenance menu) and 1 default menu. 150
100
50
Primary menu Secondary menu Third menu Fourth menu Fifth menu
Ia Ia= 1000A
Ib Ib= 1001A
Ic Ic= 998A
In In= 0A
Ig= 0A or I△n=0.00A
Ia= 1300A
Ib= 1400A
Instantaneous value
Ic= 1380A
Maximum
In= 200A
Ig= 0A or I△n=0.00A
Reset(+/-)
Ia= 3%
Magnitude of currentⅠ Ib= 5%
Unbalance rate
Ic= 1%
Current thermal capacitance 100%
15min
Ia= 1000A
Real-time value
Ib= 1000A
Ia,Ib,
Ic= 998A
Ic,In
In= 0A
Required value Ia= 1050A
Ib= 1040A
Maximum
Ic= 1010A
In= 0A
Reset(+/-)
Uab= 380V
Ubc= 380V
Instantaneous value Uca= 380V
Uan= 220V
Voltage U Ubn= 220V
Ucn= 220V
Mean value Uav= 380V
Unbalance rate 0%
Phase sequence A,B,C
FrequencyF 50Hz
EP= 200kWh
Total electric energy EQ= 10kvarh
ES= 200kVAh
EP= 200kWh
Electric energy E Input electric energy
EQ= 200kvarh
EP= 0kWh
Output electric energy
EQ= 0kvarh
Electric energy reset Reset
> >> 21
N7 Series Products
NA8G
Primary menu Secondary menu Third menu Fourth menu Fifth menu
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
-1.00
Perceptual
Power factor
PFa= 1.00
PFb= 1.00
PFc= 1.00
Instantaneous value Pa= 220kW
Pa, Qa, Sa Qa= 0kvar
Sa= 220kVA
Pb= 220kW
Power P
Pb, Qb, Sb Qb= 0kvar
Sb= 220kVA
Pc= 220kW
Pc, Qc, Sc Qc= 0kvar
Sc= 220kVA
P= 660kW
P, Q, S Q= 0kvar
S= 660kVA
Required value P= 661kW
Q= 2kvar
Maximum
S= 662kVA
Reset(+/-)
Ia
Ib
Ia,Ib
Harmonic H Ic,In Ic
In
Waveform
Uan
Uan,Ubn Ubn
Ucn
Ucn
Ia= 1000A
I(A) Ib= 1000A
Ic= 1000A
In= 1000A
Uab= 380V
Base form
Ubc= 380V
U(V) Uca= 380V
Uan= 220V
Ubn= 220V
Ucn= 220V
Ia= 0.0%
Ib= 0.0%
I(%)
Ic= 0.0%
In= 0.0%
Uab= 0.0%
THD
Ubc= 0.0%
Uca= 0.0%
U(%)
Uan= 0.0%
Ubn= 0.0%
Ucn= 0.0%
Ia= 0.0%
Ib= 0.0%
thd I(%)
Ic= 0.0%
In= 0.0%
22 > >>
N7 Series Products
NA8G
Primary menu Secondary menu Third menu Fourth menu Fifth menu
Uab= 0.0%
Ubc= 0.0%
Uca= 0.0%
thd
Uan= 0.0%
U(%)
Ubn= 0.0%
Ucn= 0.0%
Ia FFT THD=0.0%
0.0%
Ia(3, 5, 7...31)
3 5 7 9 11...31)
Ib FFT THD=0.0%
0.0%
Ib(3, 5, 7...31)
3 5 7 9 11...31)
I(3, 5, 7...31)
Ic FFT THD=0.0%
0.0%
Ic(3, 5, 7...31)
3 5 7 9 11...31)
In FFT THD=0.0%
0.0%
In(3, 5, 7...31)
3 5 7 9 11...31)
FFT
Uab FFT THD=0.0%
0.0%
Uab(3, 5, 7...31)
3 5 7 9 11...31)
> >> 23
N7 Series Products
NA8G
Primary menu Secondary menu Third menu Fourth menu Fifth menu
e.g. =5000A=5.0Ir
Definite-time limit Operating current
e.g. =0.1s
Short-time delay
e.g. =2000A=2.0Ir
Inverse-time limit Delay time
e.g. =C1,0.Is@6Ir
Instantaneous Operating current e.g. =10000A=10.0In
Neutral phase protection Neutral phase protection e.g. =200%
Operating current e.g. =800A
Ground protection Delay time e.g. =0.4s
Coefficient of earthing e.g. =6.0
Current protection Starting current e.g. =600A
Starting time e.g. =0.1s
Grounding alarm
Return current e.g. =100A
Return time e.g. =0.1s
Operating current e.g. =8.0A
Leakage protection
Setup delay time e.g. =0.75s
Starting current e.g. =5.0A
Starting time e.g. =0.1s
Electric leakage alarm
Return current e.g. =4.0A
Return time e.g. =0.1s
Executive mode e.g. =I the first method
Unloading value 1 e.g. =800A
Load Monitoring Unloading time 1 e.g. =50%tr
Unloading value 2 e.g. =700A
Unloading time 2 e.g. =25%tr
Executive mode e.g. =Alarm
Startup value e.g. =200V
Under voltage Starting time e.g. =0.2s
Return value e.g. =320V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =480V
Voltage protection Over voltage Starting time e.g. =1s
Return value e.g. =400V
Return time e.g. =60.0s
Executive mode e.g. =Alarm
Startup value e.g. =10%
U unbalanced Starting time e.g. =1s
Return value e.g. =5%
Return time e.g. =60.0s
24 > >>
N7 Series Products
NA8G
Primary menu Secondary menu Third menu Fourth menu Fifth menu
A phase short-circuit definite-time limit
T= 0.4s
I= 4300A
e.g. 15:28:25
8 (for) short-circuit definite-time limit
Tripping record 5/30
2004/05/30
Ia= 4300A
Ib= 4200A
Ic= 4000A
In= 150A
Di input alarm
e.g.
Di1
1 DI (for) DI input alarm 2004/07/16
2004/07/16 20:38:45
Alarm logging ...... ......
e.ge Under voltage alarm
8 Under voltage alarm Umax= 0V
2004/06/20 2004/06/20
Note: Up to 8 times of alarms can be recorded 22:29:40
e.g. local switch on
1 (for) local switch on 2002/06/18
2002/06/18 9:30:56
Position changing record ...... ......
e.g. Test tripping
8 (for) testing tripping
2002/06/15
2002/06/15
10:30:20
Note: Up to 8 times can be recorded
Notes: a. The actual menu will very depend on the function selected by the user.
b. The controller starts screensaver automatically 10min later.
8.5 List of the controller functions
Standard configuration
Standard type (M type) Multifunction type (H type)
1.Quadruple over current protection (for overload, 1.Quadruple over current protection (for overload, short-time delay time,
short-time delay time, instantaneous, grounding); instantaneous, grounding); grounding corresponds to vector sum (T type);
grounding corresponds to vector sum (T type); 2.Parameter setup: fixed value keyboard setting function;
2.Parameter setup: fixed value setting position setting function 3.Current measurement function;
3.Current measurement 4.Current unbalance rate measurement function;
4.Test function; 5.Two test functions:
5.Fault recording function: 8 times of failures can be recorded; (1)Instantaneous tripping test simulated on the panel;
6.Self-diagnostic function; (2)Triple over current, grounding/leakage and operating time tests
7.MCR make/break function; simulated by software;
8.Human-machine interface: 33×22 LCD; 6.Fault recording function: 8 times of failures can be recorded;
9.Heat capacity measurement 7.Self-diagnostic function
8.MCR make/break function
9.Communication function: MODBUS protocol;
10.Alarm logging function;
11.Recording number of operations;
12.Contact wear
13.Position changing record
14.Human-machine interface: 28×43 LCD;
15.Heat capacity measurement
> >> 25
N7 Series Products
NA8G
Heat capacity measurement
Multifunction type (H type)
Standard type (M type)
P Function H Function
5000
IR=(0.4-1)In
1000
500
200
TR=(1~30)s
100
50
20
T(s) 10
I2t ON
5
2 Isd=(1.5~10)IR
Isd=(1.5~10)IR
1
I2t OFF
0.5
0.2
0.1
Ii=(2~15)In
0.05
0.02
0.01
0.2 0.3 0.5 0.6 0.8 1 2 3 4 5 8 10 20 30 40 50 60 80 1.5 2 3 4 5 6 8 10 20 30
X IR
5000
Ig=(0.2-1)In
1000 MAX 1200A
MIN 120A
500
200
100
50
20
T(s) 10
I2 ON
5
1
0.5
0.2
0.1
I2 t OFF
0.05
0.02
0.01
0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20 30
X In
26 > >>
N7 Series Products
NA8G
8.6.1 Over current long time delay characteristic
Rated current range IR Error Line current I Operating time tR(s) Time (delay) error
≤1.05IR No actuation within 2h
>1.30IR <1h and then actuate
(0.4~1)In ±10% 1.5IR 16 32 64 128 192 256 320 384 480
2.0 IR 9 18 36 72 108 144 180 216 270 ±15%
6.0 IR 1 2 4 8 12 16 20 24 30
<0.85Isd No actuation
> 1.15Isd Time-delay action
I 2t OFF 0.1 0.2 0.3 0.4
(1.5~10)IR
±15% I 2t ON ±15%
+OFF(Power off) 0.1 0.2 0.3 0.4
I>10IR
I 2t ON
anti-time-limit delay:I 2Tsd=(10IR) 2tsd
I≤10IR
The short-circuit short-time delay protection operating current adjustable: Isd tsd
3 4 5 (s)
Isd=(1.5-2-2.5-3-4-5-6-8-10)×IR, and there are nine settings for option. .4 .4 .3
2.5 6 .3 .2
There are nine settings for the short-time delay tripping time, wherein 4 2 8 .2 .1
1.5 10 .1 X
settings represent the definite-time limit characteristic (i.e., I2t OFF), ON 2
OFF
×IR It
4 settings the inverse-time limit characteristic, and 1 setting the function
of closing the short-time delay (X).
> >> 27
N7 Series Products
NA8G
8.6.3 Short-circuit instantaneous protection
28 > >>
N7 Series Products
NA8G
8.7 Explanation for auxiliary functions 8.8 Explanation for display function
a. Explanation for test functions When the rated current is greater than or equal to 400A,
When onsite adjustment, periodical inspection or overhaul is the primary current shall not be lower than 0.4In for single phase,
made with the controller supported by the breaker, breaking several and 0.2In for three phases for normal operation of the breaker.
times is necessary by using the test functions of the controller to
check the cooperation of the controller and the breaker. When the rated current is less than 400A, the primary current shall
With the breaker on, press the T key, and the intellectual controller not be lower than 0.8In for single phase,and 0.4In for three
will trip instantaneously to cut off the breaker. phases for normal operation of the breaker.
Note: ① This function can be used only when onsite adjustment
or overhaul for the breaker is made, and shall not be used during Note: When the AC220V ST power module is energized, and the
the normal operation. voltage falls to AC120V, there will be no display on the controller
② Each time before the controller is switched on, it is necessary When the AC380V ST power module is energized, and the
to press the reset button in the upper position of the controller voltage falls to AC200V, there will be no display on the controller
panel so that the breaker can be switched on again for operation. a. Current display
Error range for current display: ±5%
b. Explanation for fault memory b. Voltage display
The controller still has the function of fault memory after reset Error range for voltage display: ±1.5%
or de-energized to keep a latest historical event for post analysis.
Only when there is a new fault again, the original information is
cleared with the current latest faulty data saved.
For the inquiry method, refer to the above explanation about fault
display
9. Accessories
9.1 Under voltage release
When the under voltage release is not energized, neither
power-driven nor manual operation can make the breaker on.
For the under voltage release, there are two varieties:
instantaneous and time delay operations.
The time for the under voltage time delay release is Inm=1600A,
the time can be selected from but not adjusted in the range of 0 – 7s;
Inm=3200A or 6300A, the time can be selected from but not
adjusted among 0.5s, 1s, 3s, and 5s. When, within 1/2 delay time,
the power voltage returns to 85%Ue or above, the breaker will
not get disconnected.
Operating characteristic:
Rated control supply voltage Us(V) AC230 AC400 DC220 DC110
(0.7~1.1)Us Shunt release Shunt release
Operating voltage (V)
(Inm=1600A) (Inm=3200A, 6300A)
Power consumption (W) 200VA 200W
Breaking time 50±10ms
Operating characteristic:
Rated control supply voltage Us(V) AC230 AC400 DC220 DC110 Closing electromagnet Closing electromagne
Operating voltage (V) (0.85~1.1)Us (Inm=1600A) (Inm=3200A, 6300A)
Power consumption (W) 200VA 200W
Closing time 50±10ms
> >> 29
N7 Series Products
NA8G
9.4 Power operating mechanism
The functions of motor energy storage and automatic energy
re-storage after the breaker comes on are available to ensure that
the breaker can come on immediately after it gets disconnected.
Operating characteristic:
Rated control supply voltage Us(V) AC230 AC400 DC220 DC110
Operating voltage (V) (0.85~1.1)Us
Power consumption (W) 75/150VA 75/150W
Energy storage time <4s (Inm=1600A) (Inm=3200A, 6300A )
Frequency of operation At most 3 times in a minute
9.10 Drawer type of air circuit breaker “separation” position locking device
For the “separation” position of the open frame (draw-out) circuit breaker, a lock rod can be
pulled out to lock the matter, and the breaker locked will be unable to be turned towards
the TEST or CONNECTION position. Padlocks have to be provided by users themselves.
9.11 The drawer type of air circuit breaker about any working position locking device
After the breaker body is locked automatically in any working position, it is necessary to turn
the key to unlock the matter so that the break body can be moved to the next working position
by turning the handle. (this function available for 3200 to 6300).
30 > >>
N7 Series Products
NA8G
10. Installation 10.4 Installation of the fixed type breaker
10.1 Following items to be checked before installation Place the breaker into the distribution cabinet, and fasten it by
Check the label plate on the breaker panel to see if it is using 4 pieces of M6(In=1600A) or M10(In=3200A or more)
conform to the specifications of the ordered goods. bolts and washers. The breaker shall be installed stably with no
a.Rated current additional mechanical stress to avoid damage of the breaker or
b.Under voltage release voltage and delay time bad contact of the main bus bar.
c.Shunt release voltage
d.Closing electromagnet voltage 10.5 Installation of the open frame (draw-out) circuit breaker
e.Motor voltage Take the breaker body out of the draw-out socket, and install
the socket in the distribution cabinet, and fasten it by using 4 pieces
10.2 Before installation, operation, maintenance and inspection, of M6(In=1600A) or M10(In=3200A or more) bolts and washers;
you shall read this manual, and consult the manufacturer for the breaker shall be installed stably with no additional mechanical
questions, if any. stress to avoid damage of the breaker or bad contact of the main
bus bar. After the work is completed, mount the body into the
10.3 Preparations before installation draw-out socket.
Before the breaker is installed, check the insulation resistance
of the breaker by using a 1000V megohmmeter according to 10.6 The specifications of the wiring copper bars for the primary
regulations; when the surrounding media temperature is 25℃±5℃ circuit of the breaker shall meet the copper bar specifications used
and the relative humidity 50% - 70%, the insulation resistance under the conditions of conventional heating in IEC/EN 60947-2
shall not be less than 20 megohm.
The place with the insulation resistance to be tested includes: 10.7 The breaker shall be grounded substantially.
the place between various phases and between various phases
and the frame when the breaker is closed; the place between
in- and out- lines of various phases.
1 Check the breaking current and operating time on the intellectual controlle
Breaker tripping Short-circuit fault tripping 2 Promptly find and shoot the trouble if overload is confirmed
(fault indicator on) (short time delay or 3 Check the setting value of the intellectual controller
1
instantaneous indicator on) 4 Check to see whether the breaker is in good condition, and determine whether
it can be closed for operation
5 Press the reset button to close the breaker again
1 Check the breaking current and operating time on the intellectual controller
Grounding fault tripping 2 Promptly find and shoot the trouble if it is confirmed that there is a grounding fault
(grounding fault indicator on) 3 If no grounding fault is detected, please determine whether the grounding
fault current setting is proper, and can be well matched with the actual protection;
if not, the setting shall be modified
4 Press the reset button to close the breaker again
Under voltage release 1 Check to see if the power voltage is lower than 70%Ue
Tripping 2 Check the under voltage release and control unit for fault
Mechanical interlock action Check the working condition of two breakers equipped with mechanical interlock.
1 Whether the under voltage release has been energized
Under voltage release 2 Whether the power voltage is lower than 85%Ue
No attracting 3 Whether the under voltage release or control unit malfunctions,
if so, the release shall be replaced.
Reset button fails to reset Press the reset button to close the breaker again.
Breaker fails Open frame (draw-out) circuit breaker f Check the contract status of the secondary circuit,
2 to close ails to be put to the right position by rocking and shoot the trouble, if any
1 Check the motor control power supply and see if it is well
Open frame (draw-out) circuit breaker
providing power, and the voltage must be ≥85%Us
Bad contact for the secondary circuit 2 Check the status of the motor energy storage mechanism.
Put the open frame (draw-out) circuit breaker to the right position
Breaker fails to pre-store energy
by rocking (with it locked in the connection position)
1 Check the power voltage of the closing electromagnet,
and it must be higher than or equal to 85%Us
Closing electromagnet trouble
2 If there is any trouble in the closing electromagnet to enable the attracting,
it shall be replaced.
> >> 31
N7 Series Products
NA8G
Breaker fails to be pulled out when the Pull out the rock rod
Rock rod fails to be pulled out
6 open frame (draw-out) circuit breaker is Put the breaker completely
Breaker fails to completely reach the SEPERATION position to the SEPERATION position by rocking
in the SEPARATION position
Open frame (draw-out) circuit The "drawer” has seized up for foreign matters fall in it; Check it for foreign matters and for condition
7 breaker fails to be put to the damage in the mechanism for putting in by rocking or the of the rack and gear
CONNECTION position by rocking gear thereof; Position locking device fails to be unlocked Turn the key on the “drawer” to unlock the matter
Intellectual controller fails to be energized by power supply: 1 Check to see if the intellectual controller
power supply is well be connected and works well
Improper input voltage for the auxiliary power supply
No display on the 2 Cut off the intellectual controller control
8 Improper secondary output voltage for the transmitter
intellectual controller screen power supply, and then connect the power supply;
Unreliable connection between the secondary output If the fault is still present, there may be some
terminal of the transmitter and the controller troubles in the controller which has to be replaced
32 > >>
N7 Series Products
NA8G
12. Specifications for ordering
Optional function □Over voltage protection □Under voltage protection □Over frequency protection □Under frequency protection
(this function to □Voltage unbalance measurement □Phase sequence protection □Voltage measurement □Frequency measurement
be added as □Measurement of harmonic current □Power factor measurement □Power measurement □Phase sequence detection
required by the
□Voltage unbalance rate measurement □Electric energy measurement □Contact equivalent
user, and to be
matched with the □Power network history parameter recording function □MCR make/break function □Load monitoring function
controller type) □Signal contact output function □Communication function □ZSI regional interlocking protection
Under voltage □Instantaneous □Time delay______s (1-2-3-4-5-6-7s provided for the 1600 shell, optional but not adjustable;
release 0.5-1-3-5s for the 3200 and 6300 shell, optional and adjustable) □AC400V □AC230V
device □Two breakers is provided with two same locks and one key (the same key/lock not available
for the 1600 and 3200/6300 shell breakers)
□Three breakers is provided with three same locks and two keys (the same key/lock not available
configuration
Note: Extra costs are needed for the optional functions, optional accessories and the like for the breaker.
> >> 33
N7 Series Products
NM7
2. Type designation
N M 7- □ □ /□ / □ □ □□□
Company code
34 > >>
N7 Series Products
NM7
3. Operation conditions
3.1 Ambient air temperature
3.2 The upper limit for the ambient air temperature is+40℃,
lower limit -5℃, and the average temperature is not higher
than+35℃ within 24 hours. Ambient temperature
3.3 Altitude: not higher than 2000m for the installation site.
3.4 Atmospheric conditions:
When the ambient air temperature is +40℃, the relative
2000m
humidity of the air shall not be higher than 50%; a higher
relative humidity is allowed at a lower temperature; Altitude
for the wettest month, the maximum relative humidity
averaged shall be 90% while the lowest temperature
averaged in that month +25℃, and the condensation
produced due to temperature change shall be taken into
consideration.
3.5 Class of pollution: 3 No Pollution
Table 1
Accessory code Accessory installation and mode of wirings
3P 4P 3P 4P 3P 4P 3P 4P
No accessories 300
Shunt release,
340
auxiliary contact
Shunt release,
350
under voltage release
Two groups of
360
auxiliary contacts
Auxiliary contact,
370
under voltage release
Shunt release,
318
alarm contact
Auxiliary contact,
328
alarm contact
Note: a. 200 for the breaker body only with the magnetic release;
300 for thermal release + magnetic release body;
000 for the breaker body with no release and inner accessory.
b. ●alarm contact; ○auxiliary contact; ■shunt release; ▲under voltage release.
> >> 35
N7 Series Products
NM7
4. Technical data
NM7 NM7-125
Rated currentIn(A) 16,20,25,32,40,50,63,80,100,125
Rated insulation voltage Ui(V) 800
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 380/400/415/690
Appearance
36 > >>
N7 Series Products
NM7
NM7-250
100,125,160,180,200,225,250
800
8
380/400/415/690
S
3 4
35 35
- -
17.5 17.5
- -
20000
2500
A
165×105×74
165×140×74
●
▇
▇ *
▇ *
▇ *
▇ *
▇
▇
▇
▇
▇ *
> >> 37
N7 Series Products
NM7
NM7 NM7-400
Rated currentIn(A) 250,315,350,400
Rated insulation voltage Ui(V) 800
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 380/400/415/690
Appearance
38 > >>
N7 Series Products
NM7
NM7-630 NM7-800
400,500,630 500,630,700,800
800 800
8 8
380/400/415/690 380/400/415/690
S H S H
3 4 3 4 3 4 3 4
50 50 65 65 50 50 75 75
- - 15 15 - - 15 15
25 25 32.5 32.5 25 25 37.5 37.5
- - 7.5 7.5 - - 10 10
4000 2500
1000 500
A A
280×182×112 275×210×112
280×240×112 275×280×112
● ●
● ●
▇ * ▇*
▇ * ▇*
▇ *
▇*
▇ ▇
▇ ▇
▇ ▇
▇ ▇
▇ * ▇*
> >> 39
N7 Series Products
NM7
5. Inverse-time overcurrent protection curve for the
breaker for distribution (see Fig. 1 – 10)
Fig.1 NM7-125(16A~32A) operation characteristic curve Fig.2 NM7-125(16A~32A) temperature compensation curve
10000
7200
3600 130
1200
600 120
300
Tripping time(S)
Rated current(%)
120
60 110
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 -5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20
Fig.2 NM7-125(40A~125A) operation characteristic curve Fig.4 NM7-125(40A~125A) temperature compensation curve
10000
7200
3600 130
1200
600 120
300
Tripping time(S)
Rated current(%)
120
60 110
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 -5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20
Rated current times Ambient temperature (℃)
Fig.3 NM7-250 operation characteristic curve Fig.6 NM7-250 temperature compensation curve
10000
7200
3600 130
1200
600 120
300
Tripping time(S)
Rated current(%)
120
60 110
30
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02 -5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20
40 > >>
N7 Series Products
NM7
Fig.7 NM7-400 operation characteristic curve Fig.8 NM7-400 temperature compensation curve
10000 130
7200
3600
1200 120
Rated current(%)
600
300
120
110
Tripping time(S)
60
30
20
100
10
5
2
90
1
0.5
0.2 80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20
Fig.9 NM7-630 operation characteristic curve Fig.10 NM7-630 temperature compensation curve
10000
7200
3600 130
1200
600 120
300
120
Rated current(%)
Tripping time(S)
60 110
30
20
10 100
5
2
90
1
0.5
0.2
80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60
1 2 3 4 5 7 8 12 20
Fig.11 NM7-800 operation characteristic curve Fig.12 NM7-800 temperature compensation curve
10000
7200 130
3600
1200 120
600
Rated current(%)
Tripping time(S)
300
110
120
60
20 100
10
5
2 90
1
0.5
0.2 80
0.1
0.05
0.02
-5 0 10 20 30 40 50 60
1 2 3 4 57 8 12 20
> >> 41
N7 Series Products
NM7
6. Overall and mounting dimensions
NM7-125
96
74
120(4P) 70
90(3P) 61.5
30 30 30 24.5
1 3 5 N
23
102
155
135
132
45
29
2 4 6 N
30(3P)
60(4P)
NM7-250
96
74
140(4P) 70
105(3P) 61.5
35 35 35 24.5
1 3 5 N
21
105
52
126
165
145
31
2 4 6 N
35(3P)
70(4P)
NM7-400
160
198(4P) 107
106
150(3P)
98.5
52.5 48 52.5
48
1 3 5 N
150
90
225
257
194
311
50
2 4 6 N
28 44(3P)
45.5
94(4P)
42 > >>
N7 Series Products
NM7
NM7-630
165
112
240(4P)
182(3P)
110
103
58 58 58
52
1 3 5
160
92
210
280
245
405
50
2 4 6
50 58(3P)
116(4P)
NM7-800
169
112
280(4P) 105.5
210(3P) 95
70 70 70
41.5
1 3 5 N
243
329.5
240.5
221
275
88
67
2 4 6 N
70(3P)
140(4P)
7. Ordering information
Users shall order goods in the following way:
Product type + rated current + code of the inner accessory
(00 for no inner accessories) + application code + operation mode
+ (word description, accessory voltage, type and the like to be
described in detail).
Order Sample: 10 pcs of NM7-250S, 250A, three poles,
shunt release (AC230V), for motor protection, power operating
mechanism (DC220V), plug-in type.
10 pcs of NM7-250S/250/3310 2 D (shunt AC230V,
power operating mechanism DC220V, plug-in type).
> >> 43
N7 Series Products
NZ7
2. Type designation
N Z 7-□□/□□□□□□□
Controller type
A: basic type
Structure
NZ7 Series Y: integrated (type)
Without code: separated (type)
Automatic Transfer
Switching Equipment Actuator circuit breaker type
Without code: NM1
1. General
Rated current (Arabic numerals)
Applicable to the three-phase four-line two-circuit power
supply network with an AC power frequency of 50Hz, Release with nothing as its code: NM1
rated operational voltage of AC400V, and rated operational
current of up to 630A, the NZ7 series automatic transfer Number of poles: 3, 4
switching equipment can automatically connect one or
several loads from one power source to another to ensure Breaking capacity code: S, H, R
the normal power supply of the load circuit.
Frame size rated current (Arabic numerals)
This product is applicable to the important places such as
industrial, commercial, and storied buildings, Design serial number
and residential houses.
Automatic transfer switching equipment
Certificate: KEMA
Execution standard: IEC/EN 60947-6-1 Company code
3. Operation conditions
3.1 Ambient air temperature
The upper limit for the ambient air
temperature is +40℃, lower limit -5℃,
and the mean value of the temperature is Ambient temperature
44 > >>
N7 Series Products
NZ7
4. Technical data
AUTO
ON
N
R
OFF
AU TO QU ER Y
SE T
MA NU
N R OF F
Visualized management
> >> 45
N7 Series Products
NZ7
5.1 Compactness
The transfer function is achieved via using the forward and
backward rotation of the only one motor which allows for reducing
the product’s height and room for its installation.
5.2 Energy saving
The driving mechanism works in the mode of motor drive with less
power consumption and noise.
Auto
ON
N
R
OFF
46 > >>
N7 Series Products
NZ7
5.4 Dual-interlock protection
The mechanical-electrical interlock duplex protection is used to
prevent two power sources from being connected simultaneously
to the load, wherein the electrical interlock works in the breaker
contact position mode for directly indicating the automatic transfer
switch to perform the genuine electrical interlock so that the
automatic transfer does not take place automatically in such cases
as contact fusion welding, breaker handle damage, and circuit
fault breaker tripping.
6. Controller
6.1 The Type A integrated controller works in the modes of integrated or separated configurations,
and is installed in the cabinet or on the panel to allow operation outside the cabinet.
Whether to transfer from one power source to another depends on the state of the operational power supply.
Generating set control
Press-key manually forced transfer operating
6.2 Control voltage
AC230V 50Hz
6.3 Operation: automatic operation, manual operation
6.4 Setting delay
Transfer delay: adjustable in the range of 0s - 180s, prime power failure,
time before off for QN
Return delay: continuously adjustable within the range of 0s - 180s,
prime power recovery, time before off for QR
> >> 47
N7 Series Products
NZ7
6.5 Interface for display and operation
LED digital display
1 2 3
ON
7 R 11
OFF
12
STOP GENERATOR
8 13
19
AUTO QUERY
SET
14 MANU 18
N R OFF
15 17
16
1. Indication of automatic working mode; 15. Button for compulsorily turn off the normal power
2. Indication of manual working mode; Under the manual control mode, if this button is pressed, it can
3. Failure indication compulsorily switch to the normal power; if it is setting condition,
When the breaker is disengaged due to the failure or short-circuit this button is the “scroll up” button of setting programs;
of the switch, this lamp will be on; 16. Button for compulsorily turn off the alternative power
4. Display area of normal power voltage parameters Under the manual control mode, if this button is pressed, it can
It displays normal power voltage parameters and changeover compulsorily switch to the alternative power; if it is setting
delay time under the working condition, and setting items under condition, this button is the “scroll up” button of setting
the setting condition; programs;
5. Indication of the on or off of breaker on the normal power side 17. Off button
6. Indication of setting condition Under the manual control mode, if either line of both power
7. Indication of the on or off of breaker on the alternative power side lines are normal and this button is pressed, it will switch to
8. Indication of the start of stop function; the disengagement position; this button is the minus button
9. Units of voltage, time, and frequency of the normal power; for setting parameters when it is under setting condition;
10. Phases A, B, and C; 18. Failure inquiry button
11. Units of voltage, time, and frequency of the alternative power; When the switch fails and malfunction lamp on the failure
12. Display area of alternative power voltage parameters; screen is on, the detail malfunction code can be inquired if it
It displays alternative power voltage parameters and transfer is pressed; this button is the plus button if it is under the
delay time under the working condition, and setting items under setting condition;
the setting condition; 19. Setting button
13. Indication of the start signal of generator When this button is pressed, it may enter into the parameter
14. Selection button of automatic/manual transfer setting menu of the controller.
When it is regularly used, it can be used for selecting the
automatic or manual mode; it saves and exits the functions
when it is under the setting condition.
48 > >>
N7 Series Products
NZ7
6.6 Operation description on parameter setting
AUTO
N
ON
R
OFF
Setting
AUTO
MANU
Set transfer value of under-voltage ofnormal power, press
SET
to increase and to decrease. 160V to 200V
N R
AUTO
MANU
Set transfer value of over-voltage of normal power, press
SET
to increase and to decrease. 240V to 290V
N R
AUTO
MANU Set transfer delay time, press
SET
to increase and to decrease. 0s to 180s
N R
AUTO
MANU
Set transfer value of under-voltage of alternative power, press
SET
to increase and to decrease. 160V to 200V
N R
AUTO
MANU
Set transfer value of over-voltage of alternative power, press
SET
to increase and to decrease. 240V to 290V
N R
AUTO
MANU
Set return delay time, press
SET
to increase and to decrease. 0s to 180s
N R
AUTO
MANU Set start delay time of generator, press
SET
to increase and to decrease. 0s to 180s
N R
AUTO
MANU Set shut-down delay time of generator,press
SET
to increase and to decrease. 0s to 180s
N R
AUTO
MANU
SET
Set transfer mode, press button to change the mode
(when the last digit is 0, it is grid-grid self-throw and self-reset mode;
when the value is 1, it is mutual alternative mode, when it is 2, it is
grid-generator. self-throw and self-reset mode.)
> >> 49
N7 Series Products
NZ7
Working processes of typy A controller
Grid – Grid
Grid – Grid mutual alternative operation
self-throw and self-reset operation
QN QR
QN QR UN is normal
UN is normal
UN fails
UN fails T1 can be adjusted from 0s to 180s
T1 can be adjusted from 0s to 180s
QN QR
QN QR UN is disconnected
UN is disconnected
UR is put into use
UR is put into use
QN QR
QN QR UR supplies
UR supplies
UN resumes to normal
UN resumes to normal
T2 can be adjusted from 0s to 180s
QN QR
QN QR UR supplies
UR is disconnected
UR fails
UN is put into use T2 can be adjusted from 0s to 180s
QN QR
QN QR UR is disconnected
UN supplies
QN QR
UN is normal
UN fails
T3 can be adjusted from 0s to 180s
Generator starts
50 > >>
N7 Series Products
NZ7
7. NZ7 external connection diagram
7.1 product connection diagram
N standby power
N Prime power
Prime power UN standby power UR
1 3 5 1 3 5
QN QR
N N
QN QR
Note:
QN actuator circuit breaker on the prime (normal) side
QR actuator circuit breaker on the standby (reserve) side
> >> 51
N7 Series Products
NZ7
7.3 Wiring diagram of external terminals of the controller
Feedback signal
Tripping signal
Tripping signal
Power signal
Power signal
On signal
On signal
Zero line
Zero line
DC24V/0.5A
Output is AC230V/0.5A Note: the hidden line is the internal wiring of the controller.
7.4 Application
UN normal
To control center
401 101
402 102 UN
403 103 QN on
Internal contact
terminal of the
301 +
DC24V
302 -
This terminal is used under the
Grid-Power Generation; it must
be connected to the generator
if required; and it does not affect
its use if it is not connected. It is used under the Grid-Power
When the UN fails Generation mode and it is
allowed not to connect it, but
501 the default start delay of the
502 generator is 0 second.
503
52 > >>
N7 Series Products
NZ7
8. Line incoming pattern
8.1 Connecting bus-bar type
Power bus-bar
Load bus-bar
J
H
M K L
H2 H3
① Outline dimension
O
N
B
H1
F G
Dimension A F G K
B E J L M N O H H1 H2 H3
Modle 3P 4P 3P 4P 3P 4P 3P 4P
NZ7-63 355 380 240 200 40 52.5 132.5 145 178 24 11.5 25 40 200 117 150 170 25 18/28
NZ7-125 390 420 240 200 43 58 148 163 194 24 9 30 43 200 136 150 180 25 24
NZ7-250 435 470 240 200 41.5 59 170.5 188 225 36 18.5 35 41.5 200 144 160 190 25 24
NZ7-400 565 615 330 225 43.5 68.5 232.5 257.5 304 61.5 36.5 48 43.5 265 224 200 227 24 40
NZ7-630 680 740 330 225 45.5 74.5 291 320 385 89 60 58 45.5 270 234 200 232 24 42
> >> 53
N7 Series Products
NZ7
9.2 Installation dimension
4×φP
Dimension C
D P
Modle 3P 4P
NZ7-63 322 347 220 φ8
NZ7-100 357 387 220 φ8
D
140
140
50
80
80
54 > >>
N7 Series Products
NB7
2. Type designation
N B7
Design number
Miniature circuit breaker
Company code
3. Technical data
3.1 Main specifications
3.1.1 Graded according to the rated current In: 1A, 2A, 3A, 4A,
6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;
3.1.2 Classified as follows according to the type of instantaneous
release: type B (3-5)In, type C (5-10)In, type D ((10-16)In;
3.1.3 Categorized as follows according to the number of poles:
a. Single pole
b. Two poles
c. Three poles
d. Four poles
3.2 Technical parameters
NB7 Series 3.2.1 For the rated short circuit breaking capacity, see Table 1
Miniature Circuit Breaker Table 1
Rated current Number of Rated voltage Rated short circuit
1. General In (A) poles Ue (V) capacity Icn (A)
The NB7 series miniature circuit breaker is applicable to the 1 230/400
circuit with an alternating current of 50Hz, rated voltage of B、C type: 1~40 6000
2, 3, 4 400
230/400V, and rated current up to 63A for overload
1 230/400
protection and short circuit protection, and also for not- B、C type: 50 60
frequent operational transformation in the circuit under 2, 3, 4 400
4500
normal condition. 1 230/400
This product can be applied to various places such as D type: 1~63
2, 3, 4 400
industrial, commercial, and tall buildings, and residential
houses. 3.2.2 Mechanical/electrical Life
The product meets the standards of IEC60898-1.
a. Electrical life: not less than 4,000 times
b. Mechanical life: not less than 10,000 times
3.2.3 For the over current protection characteristics, see Table 2
Table 2
Test Initial Time limit for tripping Expected Test environment
Test Type Remarks
current state or not tripping result temperature
a B, C, D Cold state t≤1h Not tripping
b B, C, D Right after test number 1 t<1h Tripping The current is
1s<t<60s (In≤32A) rising within 5s
c B, C, D Cold state Tripping
1s<t<120s (In>32A)
B 3In 30℃~35℃
The power supply is turned on
d C 5In Cold state t≤0.1s Not tripping
by closing the auxiliary switch
D 10In
B 5In
The power supply is turned on
e C 10In Cold state t<0.1s Tripping
by closing the auxiliary switch
D 16In
Note: The terminology “Cold state” means that the test is performed at the base calibration temperature with no load prior to the test.
> >> 55
N7 Series Products
NB7
2
3.2.4 For the tripping performance diagram, see Fig 1 3.2.5 Wiring: good for connection of leads of less than 25mm
(see Table 3); wiring method: screw hold-down with a toque
t(s) B Type
of 2N•m
10000
5000
1h Rated current Nominal cross-sectional area
2000
1000
In (A) of the copper conductor (mm2)
500
200
1~6 1
100
50
10 1.5
20 16, 20 2.5
10
5 25 4
2
1 32 6
0.5
40, 50 10
0.2
0.1
0.05
63 16
0.02
0.01
0.005
4. Overall and mounting dimensions (mm)
0.002
0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 I/In
0
72 -1.2
4P 0 Multi pole 80 -1.2
0
54 -1.2
C Type 3P
0
t(s) 2P
36 -0.62
0
0
Single pole 78 -1.2
10000 18 -0.43 67.3±0.37
5000 1P
1h
2000
1000
500
200
81.5±0.44
34.5±0.5
45±0.31
100
85.5 -1.4
0
50
20 .OFF .OFF .OFF .OFF
10
5
2
1
0.5
0.2 50.3±0.37
0.1
0.05
0.02
0.01
0.005
0.002
0.001
I/In
5. Ordering information
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200
5.1 When ordering the goods, the user shall indicate the following
items:
5.1.1 Types and names of products, for example, NB7 miniature
D Type
t(s) circuit breaker;
10000
5000
1h
5.1.2 Instantaneous tripping type and rated current, for example,
2000
1000 C25;
500
5.1.3 Number of poles: for example, 2P;
200
100 5.1.4 Amount on order, for example, 50 units;
50
20
5.2 Example for ordering: 50 units of the NM7 series miniature
10
5
circuit breakers, 2P, C25.
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.5 1 2 3 4 5 7 10 16 20 30 50 70 100 200 I/In
56 > >>
N7 Series Products
NB7LE
2. Type designation
N B 7 LE - □
3. Technical data
3.1 Main specifications
3.1.1 Graded as follows according to the rated current In:
NB7LE-32: 6A, 10A, 16A, 20A, 25A, 32A;
NB7LE-63: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
3.1.2 Classified as follows according to the type of
instantaneous release: C type (5-10) In, D type (10-16) In;
3.1.3 Categorized as follows according to the number of poles
and current circuit: Single pole and two lines (1P+N), two
poles (2P), three poles(3P), three poles and four lines (3P+N),
NB7LE Series Residual Current four poles (4P) for the NB7LE-32;
Single pole and two lines (1P+N), two poles (2P) for the
Operated Circuit Breaker NB7LE-63;
3.1.4 Graded as follows according to the rated residual
1. General operating current: 0.03A, 0.1A, 0.3A;
The NB7LE series residual current operated circuit breaker is 3.2 Technical parameters
applicable to the circuit with an alternating current of 50Hz, 3.2.1 Rated short circuit breaking capacity (see Table 1)
rated-voltage single pole and two lines/two poles 230V, 3.2.2 Rated residual making and breaking capacity: 2,000A;
three poles/three poles and four lines/four poles 400V, and
3.2.3 Rated residual non-operating current: 0.5IΔn;
a rated current up to 63A; when the human body gets an
electric shock or the network leak current exceeds the 3.2.4 Breaking time of the residual current operating (see Table
specified value, the residual current operated circuit breaker 2)
can rapidly cut off the power supply in trouble within a very 3.2.5 Mechanical/Electrical Life
short time for the safety of the human body and the a. Electrical life: no less than 2,000 times
powered equipment. With the function of overload and
b. Mechanical life: no less than 2,000 times
short circuit protection, the residual current operated circuit
breaker can be used to protect the circuit or motor from 3.2.6 Insulation shock-resistance voltage performance
being damaged by overload and short circuit, and can also a. The impulse voltage with a peak value of 6,000V can be
be used for not-frequent operational transformation in the withstood between the various poles connected together and
circuit under normal condition. the neutral pole;
The product meets the standards of IEC 61009-1.
b. The impulse voltage with a peak value of 8,000V can be
withstood between the various poles connected with the neutral
pole and the metal support;
3.2.7 The residual current operated circuit breaker has the
capability of withstanding the impact of the surge current with a
peak current of 200A (0.5μs/100kHz) and 3,000A (8 /20μs)
without causing misoperation;
> >> 57
N7 Series Products
NB7LE
Table 2 Maximum breaking time of the residual current operating
Table 2
Breaking time when the residual current assumes the following values (s)
In A I△n A
I△n 2 I△n 5 I△n 5A,10A,20A,50A,100A,200A,500Aa I△tb
6~63A 0.03,0.1,0.3 0.1 0.05 0.04 0.04 0.04
a. The test of 5A,10A,20A,50A,100A,200A,500A is only performed for the verification of operation, and is not performed for the magnitude of
current greater than the lower limit of the over-current instantaneous tripping range.
b. The test is carried out for the current with the IΔn being equal to the lower limit of the over-current instantaneous tripping range for type C or D.
Note: The terminology “Cold state” means that the test is performed at the base calibration temperature with no load prior to the test.
3.2.9 For the tripping performance diagram, see Fig 1 3.2.10 Wiring: suitable for the connection of leads of less than
25mm2 (see Table 4); wiring method: screw hold-down
C Type
10000 with a toque of:
5000
1h
2000 Not less than 0.8N•m and not greater than 1.2N•m for
1000
500 the M4 screw
200 Not less than 1.5N•m and not greater than 2.0N•m for
100
50 the M5 screw
20
10 Table 4 Nominal cross-sectional area of the copper conductor
t(s)
5
2 Table 4
1
0.5
0.2
Rated current Nominal cross-sectional area
2
0.1 In (A) of the copper conductor (mm )
0.05
0.02 6 1
0.01
0.005 10 1.5
0.002
0.001 16, 20 2.5
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200
25 4
I/ln
32 6
40, 50 10
10000
D Type 63 16
5000
1h
2000
1000
500
200
100
50
20
t(s)
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200
I/ln
58 > >>
N7 Series Products
NB7LE
4. Overall and mounting dimensions (mm)
H
50.3±0.31
34.5±0.5
L(mm)
87.5 -1.4
45±0.31
Poles H(mm)
0 NB7LE-32 NB7LE-63
0 0 0
1P+N 78 -1.2 45 -0.74 54 -0.74
0 0 0
2P 80 -1.2 63 -0.74 72 -0.74
0 0
3P 80 -1.2 90 -1.4 -
0 0
L 3P+N 80 -1.2 99 -1.4 -
0 0
4P 80 -1.2 117 -1.6 -
5. Ordering information
5.1 When ordering the goods, the user shall indicate the following items:
5.1.1 Types and names of products, for example, NB7LE series residual current operated circuit breaker
5.1.2 Instantaneous tripping type and rated current, for example, C25;
5.1.3 Number of poles: for example, 2P;
5.1.4 Rated residual operating current: for example, 0.03A;
5.1.5 Quantity on order, for example, 50 units;
5.2 Example for ordering: NB7LE-32 residual current operated circuit breaker, 2P,0.03A,C25, 50 units.
> >> 59
N7 Series Products
NC7
2. Operation conditions
2.1 Ambient air temperature:-5℃~+40℃,
its mean value not greater than +35℃
within 24 hours.
2.2 Atmospheric conditions: Ambient temperature
2000m
produced due to temperature change.
2.3 Altitude: not higher than 2000m. Altitude
1. General
The NC7 series AC contactor (hereinafter referred to as
“contractor”) is mainly used in the circuit with an alternating
current of 50Hz (or 60Hz), rated operational voltage up to
690V, and rated operational current up to 620A under the
usage category of AC-3/400V; this contact is mainly used for
remotely closing and breaking circuits, and can be combined
with an appropriate thermal overload relay to form a
electromagnetic starter so as to protect the circuits likely
to be overloaded in operation; the contact is well suited for
frequently starting and controlling AC motors.
60 > >>
N7 Series Products
NC7
3. Type and meaning
3.1 Product type and meaning
NC7 - 09 01 /N
AX-3 / 20 F5 - T 0
> >> 61
N7 Series Products
NC7
4. Quick type selection table
Number of 1 NO
the auxiliary auxiliary contact NC7-0910 NC7-1210 NC7-1810 NC7-2510 NC7-3210 NC7-3810
contacts provided 1 NC
with the body itself auxiliary contact NC7-0901 NC7-1201 NC7-1801 NC7-2501 NC7-3201 NC7-3801
IEC/EN 60974-4-1 kW A kW A kW A kW A kW A kW A
62 > >>
N7 Series Products
NC7
Number of 1NO+1NC
the auxiliary auxiliary contact NC7-4011 NC7-5011 NC7-6511 NC7-8011 NC7-9511
contacts provided
with the body itself
IEC/EN 60974-4-1 kW A kW A kW A kW A kW A
380V/400V(AC-3) 18.5 40 22 50 30 65 37 80 45 95
Rated
operational 380V/400V(AC-4) 7.5 18.5 11 24 15 28 18.5 37 22 44
current 660V/690V(AC-3) 30 34 37 39 37 42 45 49 45 49
and power 660V/690V(AC-4) 7.5 9 11 12 11 14 15 17.3 18.5 21.3
> >> 63
N7 Series Products
NC7
Number of
the auxiliary
2 NO+2NC NC7-115 NC7-150 NC7-170
contacts provided
auxiliary contact
with the body itself
IEC/EN 60974-4-1 kW A kW A kW A
64 > >>
N7 Series Products
NC7
IEC/EN 60974-4-1 kW A kW A kW A
Top suspension
Air delay head Mechanical interlock module
auxiliary contact
> >> 65
N7 Series Products
NC7
mount two
without auxiliary
AX-3/22 NC7-410 NC7-475 NC7-620
contacts, can mount
two Top suspension 4NO+4NC
auxiliary contacts
Other mode Note Note Note
IEC/EN 60974-4-1 kW A kW A kW A
Top suspension
Air delay head Mechanical interlock module
auxiliary contact
66 > >>
N7 Series Products
NC7
Modularized accessories which can be installed additionally
4NO AX-3/40
3NO+1NC AX-3/31
2NO+2NC AX-3/22
1NO+3NC AX-3/13
Number of Able to be used for
auxiliary contacts the whole series products
4NC AX-3/04
AX-3
Auxiliary contact 2NO AX-3/20
1NO+1NC AX-3/11
2NC AX-3/02
0.1~3 F5-T0
10~180 F5-T4
Able to be used for
the whole series products
F5 0.1~3 F5-D0
1N/O+1N/C
Air delay head Off-delay time (s) F5-D2
0.1~30
10~180 F5-D4
> >> 67
N7 Series Products
NC7
NR2-25 9A~32A
NR2-93 40A~95A
NR2-150 115A~150A
NR2-630 205A~620A
NRE8-25 9A~32A
NRE8-40 40A
NRE8-100 40A~95A
NRE8-200 115A~205A
NRE8
Electronic overload relay
NRE8-630 205A~620A
Purchase individually
Purchase it individually,
How to purchase and install it by yourself
How to purchase Reversible product without
connecting wire the products of
the products of Directly purchase the reversible products
205A or higher
95A or lower (specified current for two contactors
Reversible product with
connecting wire to be the same)
68 > >>
N7 Series Products
NC7
5. Main parameters and technical performance
5.1 Main parameters and technical performance criteria for the NC7 product
Type NC7-09 NC7-12 NC7-18 NC7-25 NC7-32 NC7-38 NC7-40 NC7-50 NC7-65 NC7-80 NC7-95
AC-3 9 12 18 25 32 38 40 50 65 80 95
Rated 380V/400V
AC-4 3.5 5 7.7 8.5 12 12 18.5 24 28 37 44
operational
AC-3 6.6 8.9 12 18 22 22 34 39 42 49 49
current (A) 660V/690V
AC-4 1.5 2 3.8 4.4 7.5 7.5 9 12 14 17.3 21.3
Appointed free air heat generation current (A) 20 20 32 40 50 50 60 80 80 110 110
Rated insulation voltage (V) 690 690 690 690 690 690 690 690 690 690 690
Rated impulse withstand voltage (kV)6 6 6 6 6 6 8 8 8 8 8
Rated making capacity Making current: 10xIe(AC-3) or 12xIe(AC-4)
Rated breaking capacity Making/breaking current: 8xIe(AC-3) or 10xIe(AC-4)
Short time withstand current (10s) 72 96 144 200 256 304 320 400 520 640 760
Controllable three-phase 380V/400V 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45
squirrel-cage motor power(AC-3)kW 660V/690V 5.5 7.5 10 15 18.5 18.5 30 37 37 45 45
Intermittent-periodic-duty 380V/400V 1.5 2.2 3 4 5.5 5.5 7.5 11 15 18.5 22
motor power(AC-4)kW 600V/690V 1.1 1.5 3.7 4 5.5 5.5 7.5 11 11 15 18.5
Frequency of AC-3 1200 1200 1200 1200 600 600 600 600 600 600 600
operation Electrical life AC-4 300 300 300 300 300 300 300 300 300 120 120
(times/h)
Mechanical life 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600
Electrical life AC-3 100 100 100 100 80 80 80 60 60 60 60
(ten thousand times) AC-4 20 20 20 20 20 20 15 15 15 10 10
Mechanical life(ten thousand times) 1000 1000 1000 1000 800 800 800 800 800 600 600
Type of the fuse adapted RT36-20 RT36-20 RT36-32 RT36-40 RT36-50 RT36-50 RT36-63 RT36-80 RT36-80 RT36-100 RT36-125
Piece (of string, etc) 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
Cold-pressed Non-prefabricated-tip cord 1/2.5 1/2.5 1/2.5 1/2.5 1.5/4 1.5/4 1.5/4 1.5/4 2.5/6 2.5/6 2.5/6 2.5/6 6/25 4/10 6/25 4/10 6/25 4/10 10/35 6/16 10/35 6/16
terminal Cord with the prefabricated tip mm2 1/4 1/2.5 1/4 1/2.5 1.5/6 1.5/4 1.5/10 1.5/6 2.5/10 2.5/6 2.5/10 2.5/6 6/25 4/10 6/25 4/10 6/25 4/10 10/35 6/16 10/35 6/16
Non-prefabricated-tip hard wire 1/4 1/4 1/4 1/4 1.5/6 1.5/6 1.5/6 1.5/6 2.5/10 2.5/10 2.5/10 2.5/10 6/25 4/10 6/25 4/10 6/25 4/10 10/35 6/16 10/35 6/16
Connection terminal screw size and M3.5 M3.5 M3.5 M4 M4 M4 M4 M4 M4 M4 M8 M8 M8 M8 M8 M8 M10 M10 M10
tightening torque (N·m) 0.8 0.8 0.8 1.2 1.2 1.2 1.2 1.2 1.2 1.2 3.5 3.5 3.5 3.5 3.5 3.5 4.0 4.0 4.0
Attracting(VA) 70 70 70 110 110 110 200 200 200 200 200
AC coil 50Hz
Holding(VA) 9 9 9.5 14 19 19 57 57 57 57 57
power
Power(W) 1.8~2.7 1.8~2.7 3~4 3~4 3~4 3~4 6~10 6~10 6~10 6~10 6~10
Action (actuating)range Pull-in voltage: 85%Us~110%Us; Release voltage: 20%Us~75%Us
Basic parameters of the auxiliary contact AC-15: 360VA DC-13: 33W Ith: 10A
5.2 Rated control source voltage Us and code for the NC7 ac contactor of 95A or lower
Coil voltage Us(V) 24 36 42 48 110 127 220 230 240 380 400 415 440 480 500 600 660
50Hz B5 C5 D5 E5 F5 G5 M5 P5 U5 Q5 V5 N5 R5 T5 S5 X5 Y5
60Hz B6 C6 D6 E6 F6 G6 M6 P6 U6 Q6 V6 N6 R6 T6 S6 X6 Y6
50/60Hz B7 C7 D7 E7 F7 G7 M7 P7 U7 Q7 V7 N7 R7 T7 S7 X7 Y7
> >> 69
N7 Series Products
NC7
Type NC7-115 NC7-150 NC7-170 NC7-205 NC7-250 NC7-300 NC7-410 NC7-475 NC7-620
Rated AC-3 115 150 170 205 250 300 410 475 620
380V/400V
operational AC-4 115 150 150 205 250 300 410 475 620
AC-3 86 107 118 137 170 235 303 353 462
current (A) 660V/690V
AC-4 86 107 107 137 170 235 303 353 462
Appointed free air heat generation current (A) 200 200 275 275 315 380 450 630 800
Rated insulation voltage (V) 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage (kV) 8 8 8 8 8 8 8 8 8
Rated making capacity Making current: 10xIe(AC-3) or 12xIe(AC-4)
Rated breaking capacity Making/breaking current: 8xIe(AC-3) or 10xIe(AC-4)
Short time withstand current (10s) 920 1200 1360 1640 2000 2400 3280 3600 4960
Controllable three-phase 380V/400V 55 75 90 110 132 160 200 250 335
squirrel-cage motor power(AC-3)kW 660V/690V 80 100 110 129 160 220 280 335 450
Intermittent-periodic-duty 380V/400V 55 75 75 110 132 160 200 250 335
motor power(AC-4)kW 600V/690V 80 100 100 129 160 220 280 335 450
Frequency of AC-3 1200 1200 600 600 600 600 600 600 600
operation Electrical life AC-4 120 120 120 60 60 60 60 60 60
(times/h)
Mechanical life 1200 1200 600 600 600 600 600 600 600
Electrical life AC-3 80 80 60 60 60 60 60 60 60
(ten thousand times) AC-4 2 2 1 1 1 1 1 0.6 0.6
Mechanical life(ten thousand times) 600 600 600 600 600 600 600 600 600
Type of the fuse adapted NT3-225 NT3-225 NT3-315 RT36-3 RT36-3 RT36-3 RT36-3 RT36-4 RT36-4
Action (actuating)range Pull-in voltage: 85%Us~110%Us; Release voltage: 20%Us~75%Us; NC7-250~620 Release voltage: 10%Us~75%Us
Basic parameters of the auxiliary contact AC-15: 360VA DC-13: 33W Ith: 10A
Type NC7-115 NC7-150 NC7-170 NC7-205 NC7-250 NC7-300 NC7-410 NC7-475 NC7-620
Piece (of string, etc) 1 1 1 1 1 1 1 2 2
Cable (mm2) 70 70 120 120 185 240 240 185 240
Copper (mm) - - - - - - - 40X5 50X5
Bolt M10 M10 M10 M10 M10 M10 M10 M10 M12
Tightening torque(N·m) 4 4 4 10 10 10 10 10 14
5.3 Rated control source voltage Us and code for the NC7 ac contactor (205A - 620A) product coil
70 > >>
N7 Series Products
NC7
6. Derivative products
Reversing contactor
Timing-delay contactor
Star-delta
starter
Magnetic starter
Thermal relay
AC contactor
for capacitor switching
Current limiting contact block
> >> 71
N7 Series Products
NC7
NC7 09~38
D(AX-3)/E(F5) A Φ
C
b
B
a
NC7 40~95
A
D(AX-3)/E(F5) Φ
C
b
B
72 > >>
N7 Series Products
NC7
NC7 115~170
D(AX-3)/E(F5)
C A
Φ
b
a
NC7 205~300
Φ
11.5
B
b
a
C
A
> >> 73
N7 Series Products
NC7
NC7 410~475
13.5
B
b
a
C A
NC7 620
Φ
15.5
B
b
a
C A
74 > >>
N7 Series Products
NC7
mm
Type Amax Bmax Cmax Dmax Emax a b φ
NC7-09~12 47 76 86 124.5 144.5 34/35 50/60 4.5
NC7-18 47 76 91 129.5 149.5 34/35 50/60 4.5
NC7-25 57 86 98 136.5 156.5 40 48 4.5
NC7-32~38 57 86 102 140.5 160.5 40 48 4.5
NC7-40~65 77 129 119 157.5 177.5 64 100~110 6
NC7-80~95 87 129 127 165.5 185.5 64 100~110 6
NC7-115~170 120 156 155 193.5 213.5 96~110 130 7
NC7-205 171 197 186 80 110~120 6.5
NC7-250 202 203 215 96 110~120 6.5
NC7-300 213 206 220 96 110~120 6.5
NC7-410 213 206 221 80 170~180 8.5
NC7-475 233 238 233 80 170~180 8.5
NC7-620 309 304 256 180 180~190 10.5
8. Ordering information
8.5 Amount on order
The following to be indicated when ordering: 8.6 The 95A-or-lower derivative N conventional products triple
8.1 Full name and type of the contactor poles are provided in the mode of reversible wiring, so you
8.2 Rated control source voltage and frequency or size code of the coil must give clear indication for your special wiring mode.
8.3 If you need to order the F4 auxiliary contactor block, F5 air delay 8.7 The 205A-or-higher derivative NS conventional products triple
head or standard rail track for the product, you should further give poles are provided in the mode of reversible wiring, so you must
a clear indication; For products of 205A or higher, the auxiliary give clear indication for your special wiring mode.
contactor blocks will not be attached for lack of indication such as 8.8 Order Sample:
the number of those blocks and how they are combined. 10 units of NC7-0910 ac contacts, coil voltage 220V/50Hz,
8.4 When the NC7 9A-170A products leave the factory, the body with 5 pieces of F4-22
is not provided with the dust cap. It is hoped users will further 10 units of NC7-300 ac contacts, coil voltage 220V/50Hz,
give a clear indication when they need it. with 10 pieces of F4-22 further attached
> >> 75
N7 Series Products
CHINT Electric All Rights Reserved Recycle Paper Printed Specifications and technical data are subject to change without notice.
Please contact us to confirm relevant information on ordering