Id> 0.3IB
Id>>
Relay Setting Slope-1
Slope-2
Sensitivity Test:
Current Pickup Breaker Signal
Phase Remarks
Injected Current Tripping Relay Panel Control Panel
Side 1 0.599A 0.599A OK 87T Operated
R Element
Side 2 - - OK 87T Operated
Side 1 0.599A 0.599A OK 87T Operated
Y Element
Side 2 - - OK 87T Operated
Side 1 0.599A 0.599A OK 87T Operated
B Element
Side 2 - - OK 87T Operated
Slope Test:
High
Current Slope Actual
Phase I Diff I Rest % Error Set Remarks
Injected Given Slope
Test
Side 1
R Element
Side 2
Side 1
Y Element
Side 2
Side 1
B Element
Side 2
Add additional table if necessary
Tested By Checked By
Phase L1-E:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L2-E:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L3-E:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L1-L2:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L2-L3:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L3-L1:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Phase L1-L2-L3:
Sl No. Testing Imp (Z) Angle Zone T Nominal T Actual % DEV Passed / Failed
Tested By Checked By
Actual Dir
Characterstic Polarizing Pick up Drop off Current Calculated
Phase Duty Is (A) T.M.S RCA Time % Error Signal Operating Remarks
Curve Phase (A) (A) Injected Time (sec)
(sec) Area
3.00 3.009 2.971 -1.27
R
51 1.5 0.30 IEC SI - - 1.57 1.51 4.50 1.891 1.881 -0.51 Okay -
Element
7.50 1.284 1.281 -0.23
Y
51
Element
Tested By Checked By