QF-SPM-14

POWER GRID COMPANY OF BANGLADESH LTD.


Differential Relay Test Report

Name of The Substation : TONGI CTR 1 : 400/1


Name of The Feeder : 132/33kV T2 CTR-2 : 1600/1
Relay Type : MBCH13 Matching CTR-1 : Not Required
Relay Serial No : 598439C,40C,44C Matching CTR-2 : Not Required
Duty : 87T Testing Date : 13.12.2021
Manufacturer : GEC :

Id> 0.20 In
Id>>
Relay Setting Slope-1

Slope-2

Sensitivity Test:
Current Pickup Breaker Signal
Phase Remarks
Injected Current Tripping Relay Panel Control Panel
Side 1 0.210A 0.210A OK 87T Operated
R Element
Side 2 0.210A 0.210A OK 87T Operated
Side 1 0.210A 0.210A OK 87T Operated
Y Element
Side 2 0.210A 0.210A OK 87T Operated
Side 1 0.210A 0.210A OK 87T Operated
B Element
Side 2 0.210A 0.210A OK 87T Operated

Slope Test:
High
Current Slope Actual
Phase I Diff I Rest % Error Set Remarks
Injected Given Slope
Test
Side 1
R Element
Side 2
Side 1
Y Element
Side 2
Side 1
B Element
Side 2
Add additional table if necessary

Tested By Checked By

Sub Divisional Engineer Executive Engineer


SPMD, Dhaka-2, PGCB SPMD, Dhaka-2, PGCB
QF-SPM-03

POWER GRID COMPANY OF BANGLADESH LTD.


Over Current Relay Test Report

Name Of The Substation: TONGI CTR: 400/1


Name Of The Feeder: T2 HV Date: 13.12.2021
Relay Type: MCGG62 Manufacturer: GEC
Relay Amps: 1A Relay Serial No: 598446C

Characterstic Polarizing Drop off Current Calculated Actual Time Dir


Phase Duty Is (A) T.M.S RCA Pick up (A) % Error Signal Operating Remarks
Curve Phase (A) Injected Time (sec) (sec)
Area
1.90 2.507 2.462 -1.84
R
51 0.95 0.25 IEC SI - - 2.85 1.575 1.562 -0.86 Okay -
Element
4.75 1.070 1.062 -0.75
1.90 2.507 2.462 -1.84
Y
51 0.95 0.25 IEC SI - - 2.85 1.575 1.562 -0.86 Okay -
Element
4.75 1.070 1.062 -0.75
1.90 2.507 2.462 -1.84
B
51 0.95 0.25 IEC SI - - 2.85 1.575 1.562 -0.86 Okay -
Element
4.75 1.070 1.062 -0.75

N
51N
Element

Tested By Checked By

Sub Divisional Engineer Executive Engineer


SPMD, Dhaka - 2, PGCB SPMD, Dhaka - 2, PGCB