Professional Documents
Culture Documents
Ifahe service conditions of a vessel are changed, the maxi 6.6 PRESSURE-RELIEVING DEVICES
When the authorized pressure vessel inspector believes that d. Statement of authority and responsibility.
alterations, the inspector believes that one is necessary (see f. Scope of work.
7 .2.9), the test shall be conducted at a pressure in accordance
g. Drawings and specification controls.
with the construction code used for determining the maxi
h. Material and part control.
mum allowable working pressure. To minimize the risk of
i. Repair and inspection program.
brittle fracture during the test, the metal ten¢erature should
be maintained at least 30°F (17°C) above, the minimum j. Welding, nondestructive examination, and heat treatment
98 design metal temperature for vessels that are more than 2 procedures.
inches (5 centimeters) thick, or 10°F (6°C) above for vessels k. Valve testing, setting, leak testing, and sealing.
that have a thickness of 2 inches (5 centimeters) or less. The l. General example of the valve repair nameplate.
-
�
test temperature need not exceed 120°F (50°C) unless there is
m. Procedures for calibrating measurement and test gauges.
information on the brittle characteristics of the vessel material
n. Controlled copies of the manual.
indicating that a lower test temperature is acceptable or a
5 o. Sample forms.
higher test temperature is needed.
When the pressure test has been completed, pressure relief acceptable. For clean (nonfouling), noncorrosive services,
devices of the proper settings and other appurtenances maximum intervals may be increased to 10 years. When ser
removed or made inoperable during the pressure test shall be vice records indicate that a pressure-relieving device was
reinstalled or reactivated. heavily fouled or stuck in the last inspection or test, the ser