Distribution Substations
The power supply to the city of Baghdad is provided basically from
two main substations of 400/132 kV (Baghdad East and Baghdad west),
which in turn supply many substations of 132/33 kV (or 132/33/11 kV)
distributed geographically throughout the city. A schematic diagram
showing the structure of this system is given in Fig.1. These 132/33 kV
substations in turn provide power supply to a very large number of
33/11 kV substations as shown in Fig.2. Most of these 33/11 kV
substations are equipped with two transformers of 31.5 MVA each (or
2x16 MVA) as shown in Fig.3. To the 11 kV busbars of these
substations (which is divided into two sections) several 11 kV feeders
(up to fourteen) are connected using underground cables and/or
overhead line systems.
Each circuit branch is served by a draw-out circuit breaker mostly
by using one of these types :
SF6 Circuit Breaker ( Sulfur Hexafluoride ) Circuit Breaker
Vacuum Circuit breaker
Minimum-Oil Circuit Breaker
There are about 1150 feeders operating at 11 kV in the city
Baghdad alone with a total length of 6845 km.
Transformer Compartment
~2~
various numbers of consumers. A single line diagram of a typical
such substation is shown in Fig.6.
g) High operation safety for both the operator and the equipment
~3~
BAGHDAD EAST 400/132 kV
132 kV
132/33 kV Substations
Waziriya Gazali Bag. South
Meedan Sarrafiya
132/33 kV Substations
132/33 kV Substations
Kadimiya Maarry Mansoor Jadiriya
132 kV
~4~
132 kV 132 kV 132 kV
11 kV 11 kV
x 33 kV x 33 kV x
33KV 33KV
33/11 kV 33/11 kV
Transformers Transformers
X 11 kV X 11 kV X X 11 kV X 11 kV X
~5~
Fig.3 Single line Diagram of a Typical 33/11 kV Substation
~6~
Fig.4. Equipment Layout of a Typical 33/11 kV Substation
~7~
Fig.5. Equipment Layout and Some Constructional Details
of a Typical 33/11 kV Substation
~8~
Incoming Feeder Outgoing Feeder
11 kV Load break
switches
11 kV Load break
switch fitted with
80 A HRC Fuses
1000 kVA
11/0.4 kV
Transformer
11 Single core cables size 240 mm2 each
(three cables per phase & two for neutral)
1600 A TP MCCB
A A A
1600/5A CT
V Cos
2000A TP&N Copper Busbars
MCCB
Circuit Size (A) 500 630 500 630 100 100 500
~9~
Fig.7 Equipment Layout of a Typical 11/0.4 kV Compact Unit Substation
Showing all Three Compartments
~ 10 ~
Fig.8 External View of a Privately Owned Substation
~ 11 ~
Fig.9 External View of the 11 kV Ring Main Unit
~ 12 ~