RTU500 series

Environmental data
Data sheet

Environmental conditions:
– Temperature and humidity
General – Mechanical influences
– Safety
The RTU500 series telecontrol equipment family has been de-
signed to meet the requirements for environmental conditions Performance requirements:
and performance of network control, substation automation sys- – Reliability, availability, maintenance
tems and process industries. – Time quality for process signals

The telecontrol systems RTU560, RTU540, RTU520 and


RTU511 and its products manufactured by ABB are type tested. Electrical interfaces
They fulfill the requirements specified and described. The RTUs
meet and achieve the requirements listed in the following tables. The immunity and emission tests are made according to the re-
quested IEC standards. The list of tests needed for the RTU500
The requirements can be put into the following categories: series is taken from the IEC 60870-2-1 standard. The RTU fulfills
the requested level, specified in IEC 60870-2-1.
Electrical interfaces:
– Power supply and insulation The rules for cable routing and grounding have strictly to be ful-
– Electro-magnetic compatibility (EMC) filled, to reach the requested level. This has to be taken into con-
– Immunity sideration for engineering and commissioning.
– Emission

Power supply and insulation applying to IEC 60255-5, IEC 60870-2-1 and IEEE C37.90-1989

Environmental phenomena Required and verified data / values Verified according to test standard

AC voltage tolerances of power supply -20 % … +15 % IEC 60870-2-1

Frequency tolerances of power supply ±5% IEC 60870-2-1

DC voltage tolerances of power supply -20 % … +15 % IEC 60870-2-1

Immunity to voltage interruption -100 %: 50 ms IEC 61000-4-29

AC power frequency withstand 2,5 kV AC, 50 Hz, 1 min EN 60255-5

Impulse voltage withstand 5 kV DC, 1,2 µs / 50 µs EN 60255-5

Insulation resistance > 100 MΩ at 500 V DC EN 60255-5

EMC Emission applying to IEC 61000-6-4

Environmental phenomena Required and verified data / values Verified according to test standard

Enclosure radio interference field strength 30 dB (30 – 230 MHz) IEC/CISPR 11 / EN 50011
37 dB (230 – 1000 MHz)

Power supply radio interference voltage 79 dB (0,15 – 0,5 MHz) IEC/CISPR 11 / EN 50011
73 dB (0,5 – 30 MHz)
EMC Immunity applying to IEC 60255, IEC 60870-2-1, IEC 61000-6-2, IEC 61000-6-5, IEC 61850-3 and IEEE C37.90.1-2002

Environmental phenomena Required and verified data / values Verified according to test standard

Electrostatic discharge (ESD) Cubicle 15/8 kV IEC 61000-4-2 level 4


Modules 8/6 kV

Radiated electromagnetic field 10 V/m IEC 61000-4-3 level 3

Electrical fast transient / Burst 4 kV IEC 61000-4-4 level 4

Surge 2 kV IEC 61000-4-5 level 3


4 kV (23BE40, 23BA40) IEC 61000-4-5 level 4

Conducted disturbance included by radio-frequency fields 10 V IEC 61000-4-6 level 3

Power frequency magnetic field 30 A/m IEC 61000-4-8 level 4

Damped oscillatory wave 2,5 kV / 1 kV IEC 61000-4-12 level 3

Mains frequency interference 50 Hz 30 / 300 V EN 61000-4-16 level 4

AC ripple on DC power supply 12 % EN 61000-4-17 level 3

Voltage dips on DC power supply -30 %, 100 ms IEC 61000-4-29


-60 %, 100 ms

Voltage short interruptions on DC power supply -100 %, 50 ms IEC 61000-4-29

Environmental conditions The shock values express a shock strain, which may occur dur-
ing transportation.
The tests were made with a typical RTU560 telecontrol station
in a standard cubicle (IP 55 / DIN 40050). RTU540, RTU520 and The results of the vibration and shock tests are mainly influenced
RTU511 are tested without cubicle. The functionality was per- by the used cubicle and mounting methods. The test results are
manently verified during and after the tests, with typical 60 % valid for the RTU560 standard cubicles and mounting methods.
active input signals.

Temperature and humidity applying to IEC 60870-2-2 and IEEE C37.90-1989

Parameter Required and verified data / values Verified according to test standard

Operating temperature -25 °C ... 55 °C IEC 60068-2-1 / 2


-13 °F … 131 °F

Storage temperature -25 °C ... 55 °C IEC 60068-2-1 / 2


-13 °F … 131 °F

Temperature-Humidity (cyclic test) 5 … 95% (non condensing) IEC 60068-2-30

Rate of change of temperature 0,5 °C / min IEC 60870-2-2 class C1


32,9 °F / min

Atmospheric pressure 70 … 106 kPa IEC 60870-2-2 class C1

Altitude (operation) <= 3000 m IEC 60870-2-2 class C1

Mechanical influences applying to IEC 60255-21 and IEC 60870-2-2

Influence Required and verified data / values Verified according to test standard

Vibration (sinusoidal) response test 0,5 g (10 Hz … 150 Hz) IEC 60068-2-6

Vibration (sinusoidal) seismic test 3,5 mm (3 Hz … 9 Hz) IEC 60068-2-6

2 | 1KGT 150 400 V009 1 - Environmental data


Influence Required and verified data / values Verified according to test standard

Vibration (sinusoidal) enduration test 1 g (9 Hz … 200 Hz) IEC 60068-2-6

Vibration (sinusoidal) high frequency test 1,5 g (200 Hz … 500 Hz) IEC 60068-2-6

Shock (half sine) 15 g / 11 ms, IEC 60068-2-27


25 g / 10 ms

Bump (half sine) 10 g / 16 ms / 1000 pulses IEC 60068-2-29

Safety The differences to Australian / New Zealand, Canadian, Chinese,


Israeli, Japanese, Korean, Singapore and US national require-
The safety of the RTU560, RTU540, RTU520 and RTU511 as ments to safety are also verified.
described before is verified according to IEC 60950-1 and cer-
tificated based on the IECEE CB scheme.

Performance requirements
Performance Classes according IEC 60870-4

Performance characteristic Required data / value Class IEC 60870-4

Reliability MTBF MTBF ≥ 8.760 h R3

Availability A A ≥ 99.95 % A3

Maintainability MTTR MTTR ≤ 12 h M3

Mean repair time MRT MRT ≤ 1 h RT4


(depends on strategy)

Data integrity classes IE IE ≤ 10-10 I2

Time separation capability SP SP ≤ 10 ms (between stations) SP2


SP ≤ 5 ms (within a station) SP3

Time resolution TR TR ≤ 1 ms TR4

Analogue overall accuracy E E ≤ 0.5 % A4

Reliability even if the other boards are operating well. The calculation is
shown in Fig. 2. This sheet may also be used for calculation of
The reliability of a RTU500 series is calculated on the base of a any other RTU560 configuration.
typical RTU station. The size is the experience of several hundred
supplied substations. For RTU540, RTU520 and RTU511 also typical configurations
are selected (see Fig. 3 to see "Fig. 5: RTU511 Reliability Val-
The calculation for RTU560 is based on the following data: ues").

– 48 analogue measured information (AMI) The mean repair time (MRT) of a RTU500 series will be typically
– 100 single point information (SPI) 1 hour. The RTU500 series concept has several supervision and
– 64 double point information (DPI) diagnostic capabilities, which assist the debugging and mainte-
– 8 integrated total information (ITI) nance activities, when needed:
– 80 double command output (DCO)
– 1 command supervision board (1 out of n) – Permanent online diagnostic of all I/O boards
– 3 sub-racks with power supply – LEDs on all boards indicating internal/external errors
– 1 FSK modem – None or only a few configuration settings onboard neces-
sary
The typical reliability for such a substation is approximately – PC based diagnostic tools
33.000 hours. The reliability is defined by a serial structure. This
means a failure of one board/unit is defined as a system failure,

Environmental data - 1KGT 150 400 V009 1 | 3


The main telecontrol transmission protocols are based on format
class FT1.2 (IEC 60870-5-1). In addition, the transmission pro-
tocol allows for commands the ‘Select and Execute Command’
strategy, which essentially decreases the residual information er- NCC
ror possibility in command direction.

The performance of time separating is given by the time syn-


chronization quality of the network control system. The RTU500
series has the possibility to be synchronized via communication
lines from the Network Control Centre (NCC), by sntp or by a
DCF77 or GPS clock. The scan cycle for binary input signals is
1 ms, executed by the microcontroller on each input board. The
Communication
boards are synchronized by the communication unit (CMU) of Sub-rack
the RTU560. This allows a time resolution within a station of 1
ms for binary inputs.

The overall accuracy for analogue signals is given by the total


error of the 23AE23 analogue input board. For the real overall
error of the analogue output board 23AA21 see the hardware
Extension
data sheet. Sub-rack

Extension
Sub-rack

Figure 1: Typical RTU560 telecontrol station

4 | 1KGT 150 400 V009 1 - Environmental data


Figure 2: RTU560 Reliability Values

Environmental data - 1KGT 150 400 V009 1 | 5


Figure 3: RTU540 Reliability Values

Figure 4: RTU520 Reliability Values

6 | 1KGT 150 400 V009 1 - Environmental data


Figure 5: RTU511 Reliability Values

Environmental data - 1KGT 150 400 V009 1 | 7


ABB AG Note:
Power Systems Division The specifications, data, design or other information contained in this document
P.O. Box 10 03 51 (the “Brochure”) - together: the “Information” - shall only be for information pur-

68128 Mannheim, Germany poses and shall in no respect be binding. The Brochure does not claim to be ex-
haustive. Technical data in the Information are only approximate figures. We re-

www.abb.com/substationautomation serve the right at any time to make technical changes or modify the contents of
this document without prior notice. The user shall be solely responsible for the
use of any application example or information described within this document.
The described examples and solutions are examples only and do not represent
any comprehensive or complete solution. The user shall determine at its sole
discretion, or as the case may be, customize, program or add value to the ABB
products including software by creating solutions for the end customer and to
assess whether and to what extent the products are suitable and need to be ad-
justed or customized.

This product is designed to be connected to and to communicate information


and data via a network interface. It is the users sole responsibility to provide and
continuously ensure a secure connection between the product and users or end
customers network or any other network (as the case may be). The user shall es-
tablish and maintain any appropriate measures (such as but not limited to the in-
stallation of firewalls, application of authentication measures, encryption of da-
ta, installation of anti-virus programs, etc) to protect the product, the network,
its system and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information. ABB
AG is not liable for any damages and/or losses related to such security breaches,
any unauthorized access, interference, intrusion, leakage and/or theft of data or
information.

ABB AG shall be under no warranty whatsoever whether express or implied and


assumes no responsibility for the information contained in this document or for
any errors that may appear in this document. ABB AG's liability under or in con-
nection with this Brochure or the files included within the Brochure, irrespective
of the legal ground towards any person or entity, to which the Brochure has been
made available, in view of any damages including costs or losses shall be exclud-
ed. In particular ABB AG shall in no event be liable for any indirect, consequen-
tial or special damages, such as – but not limited to – loss of profit, loss of pro-
duction, loss of revenue, loss of data, loss of use, loss of earnings, cost of cap-
ital or cost connected with an interruption of business or operation, third party
claims. The exclusion of liability shall not apply in the case of intention or gross
negligence. The present declaration shall be governed by and construed in ac-
cordance with the laws of Switzerland under exclusion of its conflict of laws rules
and of the Vienna Convention on the International Sale of Goods (CISG).

ABB AG reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents -
in whole or in part - is not permitted without the prior written consent of ABB AG.

© Copyright ABB 2014


All rights reserved

8 | 1KGT 150 400 V009 1 - Environmental data