Professional Documents
Culture Documents
FAULT RELAY
User Manual
Version 1.0
CHAPTER 1
INTRODUCTION
1. INTRODUCTION
CHAPTER 2
SWITCHGEAR
AND
PROTECTION SYSTEM
Switchgear
Refers to various equipment associated with switching of electrical plants and circuits during
normal and abnormal conditions.
Protective Relay
Refers to various subsystems associated with sensing the abnormal operating condition in
an electrical plant and consequent alarm, indication and tripping commands to circuit breaker.
Principle of operation
Fig - 2
The Protective Relays are connected in the secondary circuits of current transformers and/or
potential transformers. The Relay senses the abnormal condition and closes the trip circuit of
associated circuit breaker.
Abnormal Conditions
* Over loads
* Loss of synchronism
* Under voltage, Over voltage
* Under frequency
* Reversal of direction of power flow
The graph is plotted between Operating quantity ( X axis) and Operating time ( Y axis).
Fig - 3
The Relay picks up in certain shortest time without any intentional time delay. The
operating time is less than 0.2 seconds.
Operating time varies inversely with respect to operating quantity. e.g. Over current
protection.
IDMT Characteristic
Over current protection - Feeders, Lines, Motors, Generators, Transformer, Load circuit,
Individual loads.
Over current protection - Feeders, Lines, Large Motors, Generators, Transformer, Load
circuit.
Differential protection - Large Transformer, Motor, Generator.
Carrier current protection (Phase comparison of carrier signals) - Feeders, Long over head
lines.
CHAPTER 3
- Selecting increment
- Selecting decrement
- Cursor movement
- Enter
LED (Indication)
RELAY CONTACTS
NO - Normally open
NC - Normally Closed
COM - Common
CHAPTER 4
EXPERIMENTAL SECTION
Experiment No. – 1
STATIC TYPE EARTH FAULT RELAY (DMT TYPE)
1.1 AIM
To study the operation of STATIC TYPE EARTH FAULT RELAY in DMT Type Using
STATIC TYPE EARTH FAULT RELAY module.
1.2 CONNECTION DIAGRAM
The connection diagram of STATIC TYPE EARTH FAULT RELAY in DMT Type is
shown in fig-1.1.
1.3 RESOURCES
1. Module - 1 no
1.4 PROCEDURE
1.4.1 Connection
4. Now switch on the power supply of variable AC current source and Over current Relay.
Now the auxiliary supply LED glows.
1. Before you going to do Controller mode you should know about key functions.
- Selecting increment
- Selecting decrement
- Cursor movement
- Enter
2. Initially keep the current source pot at minimum position. Now press RESET button and
START button of Current Source.
3. The display of STATIC TYPE EARTH FAULT RELAY shows
NUMERICAL RELAY
ACT CURRENT:
To set current value, use the for curser movement and & for increasing
8. For example if you set the current value as 10A, now the display shows,
SET CURRRENT 10.00A
ACTUAL CURRENT 00.00A
9. After setting the current value, press now the display shows
1.DMT
2IDMT
3.INSTANTANUOUS
10. For example if you set the time value as 5sec, now the display shows,
11. After setting the time value, press . Now increase the supply current given to the over
current Relay by increasing the knob of Current source. When 80% of set current is reached
the Alarm LED glows.
12. Gradually increase the current value above the set value. The display of over current Relay
module shows,
13. At the instant the relay time is started to trip relay. After the set time (here, 5sec) relay
will trip and the Trip LED glows.
14. After the tripping of relay the display of over current Relay module shows,
Actual relay
Set Current
S. No Fault Current (A) Set Time (Sec) tripping Time
(A)
(sec)
STATIC TYPE EARTH FAULT RELAY
Experiment No. – 2
STATIC TYPE EARTH FAULT RELAY (IDMT TYPE)
2.1 AIM
To study the operation of STATIC TYPE EATH FAULT RELAY in IDMT Type Using
STATIC TYPE EARTH FAULT RELAY module.
2.2 FORMULA
Where,
The connection diagram of STATIC TYPE EARTH FAULT RELAY in IDMT Type
is shown in fig-2.1
2.5 PROCEDURE
2.5.1 Connection
- Selecting increment
- Selecting decrement
- Cursor movement
- Enter
11. Initially keep the current source pot at minimum position. Now press RESET button and
START button of Current Source.
12. The display of STATIC
13. TYPE EARTH FAULT RELAY shows
NUMERICAL RELAY
ACT CURRENT:00
Set current:10.00
Act current:00.00
Then enter
15. To select IDMT press .,then display shows set time :0.1,then enter
16. The display shows,
Normal very
Extremely
Very long
g
SET CURRRENT 10.00A
ACTUAL CURRENT 00.00A
20. After setting the time value, press . Now increase the supply current given to the Earth Fault
Relay by increasing the knob of Current source. When 80% of set current is reached the
Alarm LED glows.
21. Gradually increase the current value above the set value. The display of Earth Fault Relay
module shows,
SET CURRRENT 10.00A
ACTUAL CURRENT 12.50A
22. When the actual current is increased above the set current then the trip time will be calculated
by the processor and after the t seconds the relay trips and the Trip LED glows.
23. The calculated time for relay tripping is obtained from the formula.
The IDMT used is of normal inverse type. So the values of k, α, C are constant and are K
= 0.14, α = 0.02 and C = 0. I is the Fault Current and Is is the Set Current of the relay unit.
Do the procedure for various set voltage value & noted down the readings in tabulation. Press
the reset button to get normal position.
24. After the tripping of relay the display of Earth Fault Relay module shows,
(sec)
STATIC TYPE EARTH FAULT RELAY
2.7 RESULT: