THRUST BLOCKING

TABLE A TABLE C

CONCRETE THRUST CONCRETE BLOCKING FOR


BLOCKING (HORIZONTAL) CONVEX VERTICAL BENDS

Thrust (T) at fittings in Pounds DIMENSION TABLE

A B C D E
PIPE Table Bend Concrete Cube Stirrup Stirrup Stirrup
DIA. Pressure Angle Volume Size Dia. Embmt. Bar
Table Tee & 22.5 11.25
PIPE 90 deg 45 deg in. PSI (deg) (cy) (ft) (in) (in) #
Pressure Dead deg deg
DIA. Bend Bend
PSI Ends Bend Bend
11.25 0.21 1.8
4" 250 3035 4320 2315 1215 610 4" 250 5
22.5 0.43 2.3 8 17 5
TEE CROSS STRADDLE
6" 250 6860 9735 5215 2720 1375
45 0.77 2.8
8" 250 12185 17310 9265 4835 2430 11.25 0.48 2.4

10" 250 19045 27045 14480 7560 3800 6" 250 22.5 0.95 3.0 5
17 5
8
UL-2020

12" 250 27405 38940 20840 10880 5465 45 1.79 3.6

14" 250 37320 53010 28370 14815 7445 11.25 0.86 2.9
20-J

16" 250 48740 69245 37050 19360 9735 8" 250 22.5 1.65 3.5 5
8
17 5

45 3.22 4.4

TABLE B 11.25 1.39 3.3


dgn

10" 250 22.5 2.62 4.1 5


8
17 5
Soil Bearing Capacity
rd250.

Soil Type
(B) in PSF 45 4.97 4.1

11.25 1.94 3.7


Muck, peat, etc. 0 5
17 5
8
12" 250 22.5 3.91 4.7
Soft Clay 1000 45
7
24 7
6.89 5.7 8

11.25 2.62 4.1


5
8 17 5 BEND CROSS TEE
Sand 2000
3
14" 250 22.5 5.26 5.2 4 20 6
Sand and gravel 3000 1 27 8
45 9.70 6.4
5
11.25 3.44 4.5 8 17 5
Sand and gravel cemented with clay 4000
7
16" 250 22.5 6.89 5.7 8 24 7
Hard shale 10,000 45 12.63 7.0 118 30 9

Stirrup (Typ.)
THRUST BLOCK BEARING AREA EQUATION

NOTE: WHEN THRUST BLOCK BEARING AREA IS NOT SPECIFIED ON THE PLANS OR
CONVEX WYE
DETERMINED BY THE ENGINEER, USE THE FOLLOWING PROCEDURE TO
DETERMINE REQUIRED BEARING AREA. VERTICAL BEND
(See Table C)
1. Determine thrust (T) for type of fitting or joint and size of pipe from Table A.

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET: CALC. BOOK NO. N/A SDR DATE 25-JUL-2017
2. Determine Design (Test) Pressure from Standard Specifications or Special Provisions.

NOTE: All material and workmanship shall be in accordance with


1. Contractor to provide blocking adequate to withstand full test pressure.
3. Determine Table Pressure from Table A. the current Oregon Standard Specifications

2. Pour concrete blocking against undisturbed earth. The selection and use of this
4. Determine Soil Bearing Capacity (B) of soil from Table B.
OREGON STANDARD DRAWINGS
Standard Drawing, while de-
3. All concrete shall be commercial grade concrete.
5. Determine required bearing area (A) in sq. ft. as follows: signed in accordance with
T Design (Test) Pressure 4. Wrap pipe and/or fittings with 2 layers of polyethylene film where in generally accepted engineer-
Thrust Block
Bearing Area
= A =
(B )
( Table Pressure ) contact with concrete ing principles and practices,
THRUST BLOCKING
RD250

is the sole responsibility of


5. Keep concrete clear of all joints and accessories.
Example: Design (Test) Pressure = 150 PSI From Table A, T = 37320
the user and should not be 2021
Pipe = 14" From Table B, B = 2000
6. Stirrups shall be deformed galvanized cold rolled steel AASHTO M31 used without consulting a DATE REVISION DESCRIPTION
Fitting = Tee
37320 150 (ASTM A615), Grade 60. Coat with coal tar epoxy after installation.
Soil = Sand (
A =
2000 )
( )250
11.2 sq.ft. Registered Professional En-

7. See project plans for details not shown. gineer.

RD250
Effective Date: June 1, 2021 - November 30, 2021
6"
min.

36"x36"x6" Breakaway flange


concrete pad
(optional)
Wrap hydrant barrel with 2
layers of polyethylene film
where in contact with concrete
Sidewalk

Valve box (Install valve box extension 2"-8" above


& operator extension, as reqd.) concrete pad or
surrounding datum

Depth ofbury as reqd.


UL-2020
20-J

6" gate valve mechanical


joint to flange
dgn
rd254.

Concrete
6" ductile iron pipe thrust block

Concrete thrust block


Mechanical joint
retainer gland 1
Min. 3 cubic yard drain
rock to 6" above drain hole.
Mechanical joint x flange hydrant tee
Optional: wrap drain rock in
or tapping sleeve
geotextile fabric

HYDRANT ASSEMBLY

CALC. BOOK NO. N/A SDR DATE 25-JUL-2017


GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
NOTE: All material and workmanship shall be in accordance with

1. When pipe is shorter than 18', no joints allowed. Use mechanical joint retainer glands. 6. Extensions required for hydrant systems shall be installed to the manufacturer's specifications. the current Oregon Standard Specifications

3
Two 4" galvanized tie rods may be used in lieu of thrust blocks for installations The selection and use of this
less than 18' long. Coat tie rods with two coats of coal tar epoxy. 7. Hydrants shall be placed to provide a minimum of 5' clearance from driveways, poles, and other OREGON STANDARD DRAWINGS
obstructions. Standard Drawing, while de-

2. When pipe is longer that 18' retainer glands not required. signed in accordance with
8. Hydrant pumper port shall face direction of access.
generally accepted engineer-
3. There shall be a minimum of 18" horizontal clearance around hydrant.
HYDRANT INSTALLATION
ing principles and practices,
RD254

9. Set hydrant plumb in all directions.

4. When placed adjacent to curb, hydrant port shall be 24" from face of curb.
is the sole responsibility of
10. See project plans for details not shown. the user and should not be 2021
5. Concrete thrust blocks shall be constructed as per thrust blocking Std. Dwg. RD250. used without consulting a DATE REVISION DESCRIPTION
Do not block drain holes.
Registered Professional En-
gineer.

RD254
Effective Date: June 1, 2021 - November 30, 2021
1
4" cap

4"
2"
1
12" 2"

1
1
4" rad.

n.
4"
mi
3
16" (Typ.)

2"

2"
Bollard Weld vertical

8"

8"
1 (4" dia. steel pipe, sides to
2" reflective tape

1
60" long, Sch. 40) collar

8"

8"
(Color as required)

1
4

4
1
4"

2"

2"
2"

4"
Weld vertical
Collar

1
sides to sleeve
44"

Bollard Lock tabs


(5" dia. steel pipe,
(See detail)
48"

(4" dia. steel pipe,


2" long, Sch. 80)
60" long, Sch. 40)
1
4" rad.
(Typ.)
60"
UL-2020

66"

Collar
1
(5" dia. steel pipe, 12"
Sleeve
2" long, Sch. 80) 3
20-J

(5" dia. steel pipe, 4"


Lock tabs
(See detail) 22" long, Sch. 80)
Sleeve
(5" dia. steel pipe, 3
16" 1
1 2" dia. hole
2"
dgn

22" long, Sch. 80)


2"

Typical both

2"
for lock (Typ.)
rd255.

sides of (See general note 6)


Finish grade
m ax.

1"
both tabs
4"

Finish grade

1
2" rad.
(Typ.)
12"

22"
18"

Concrete
LOCK TABS
Concrete (2"x2"x
1
4" steel angle)
30"
6"

3"

1 GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:


4"

Bollard 1. Grind all edges smooth.


1 (4" dia. steel pipe,
3 2"x10" round
16" 2. Prime and paint bollard safety yellow after fabrication.
12"

anchor bar 60" long, Sch. 40)


Typical
3. Hot-dip galvanize sleeve after fabrication.
both sides Gravel drain
of anchor material 4. All concrete shall be commercial grade concrete.
bar
5. Orient lock assembly parallel with pedestrian traffic.

6. Provide lock, if required.


18"
7. See project plans for details not shown.

ELEVATION

CALC. BOOK NO. N/A SDR DATE 25-JUL-2017

Collar NOTE: All material and workmanship shall be in accordance with


Concrete
the current Oregon Standard Specifications
Bollard assembly (5" dia. steel pipe,
18" dia.
2" long, Sch. 80)
Lock tabs The selection and use of this
OREGON STANDARD DRAWINGS
(See detail) Standard Drawing, while de-
signed in accordance with
3
16"
generally accepted engineer-
1 Typical both HYDRANT BOLLARD
2" dia. hole ing principles and practices,
RD255

sides of
for lock (Typ.)
both tabs is the sole responsibility of
(See general note 6)
the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.
PLAN COLLAR & LOCK TABS

RD255
Effective Date: June 1, 2021 - November 30, 2021
Sliding type cast iron
Wrought
valve box and cover
iron rod

Finish grade Pavement or ground

W ATER
PVC valve box extension

Operator extension
(See detail this sheet)

COVER PLAN 3
4"-0 compacted
aggregate base (4" thick)
or conc. block,
UL-2020

(See general note 4)

Raised lettering
Cast iron cover
20-J

Finish grade

VALVE BOX
dgn

ASSEMBLY DETAIL

n.
rd258.

4"m i
From 12"m ax.

36"m ax.
*

n.
ustabl

to 6"m i
Adj
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

Cast iron valve box


1. Valve box not to rest on operating assembly.
(6" dia. min.)

2. Operator extension required when valve nut is deeper than 4' from finish grade.
PVC valve box extension

3. Center valve box on axis of operator nut.

2" square operator nut 4. Valves 12" and smaller shall be provided with compacted aggr. base on undisturbed ground.
welded to pipe shaft 6"
Valves greater than 12" shall be installed on precast concrete block, (4" thick).
*See general note 8
1
5. Welds shall be minimum 4" all around.
Operator extension
1
1 2" Schedule 80
6. Hot dip galvanize operator extension after fabrication.
pipe shaft

7. Casting shall meet H20 load requirement.


1
Rock guard, 8" steel plate:
welded to pipe shaft 8. Provide concrete or asphalt pad (24" square, 4" thick), when required.
diameter = valve box extension
1
inside diameter minus 2" 9. See project plans for details not shown.
Flat bar
1 1 3
2 2"x2 2"x 8"

CALC. BOOK NO. N/A SDR DATE 25-JUL-2017


3 3
8"x 4"square head
cupped capscrews NOTE: All material and workmanship shall be in accordance with
the current Oregon Standard Specifications

The selection and use of this


3"x3"x
3 Gravel bedding OREGON STANDARD DRAWINGS
8"x2" Standard Drawing, while de-
long steel square
signed in accordance with
tube welded all
around to flat bar generally accepted engineer- VALVE BOX AND OPERATOR
ing principles and practices, EXTENSION ASSEMBLY
RD258

is the sole responsibility of


the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

VALVE BOX EXTENSION SECTION Registered Professional En-


gineer.

RD258
Effective Date: June 1, 2021 - November 30, 2021
24"

8"
2" coupling with
UL-2020

plug. assemble with


anti-seize compound
(hand tight)
20-J

Valve box Gravel


(Typical) bedding

24"
dgn

(Typical)
rd262.

2" galvanized
2" iron body screwed steel riser
gate valve with 2"
standard operating nut
Notch PVC
riser

2" galvanized
steel pipe

Gravel bedding
(Typ.)

2" malleable 90 deg.


es
1
elbow with two 4"
Vari
Brass piping and fittings
between tapped plug and dia. drain holes and
gate valve (Typical) 1 cubic ft. of
drain rock GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

1. Wrap main and fittings in thrust block zone with two layers of polyethylene film to facilitate
future removal.

2. In lieu of concrete thrust block, restrain pipe or pour concrete straddle block.

3. See project plans for details not shown.


Thrust block
Water main

CALC. BOOK NO. N/A SDR DATE 25-JUL-2017

NOTE: All material and workmanship shall be in accordance with


Plug or cap with 2" the current Oregon Standard Specifications
I.P.T. tap. for eccentric
tapped plugs, locate tap The selection and use of this
OREGON STANDARD DRAWINGS
at lowest point of pipe. Standard Drawing, while de-
signed in accordance with
generally accepted engineer- TYPICAL MAIN DEAD-END
ing principles and practices, BLOWOFF ASSEMBLY
RD262

is the sole responsibility of


the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.

RD262
Effective Date: June 1, 2021 - November 30, 2021
Match existing 2'x2' meter
grade box & cover Brass nipple & cap
(See general note 4)

6" min. dia.


PVC pipe

n.
12"m i
UL-2020

Burry depth

8"nom .
4"-6"
m um depth
20-J

n
ofwaterm ai
dgn

ni
ed m i
rd266.

Slope Gravel bedding


(6" min. depth)
fi
Speci

3 3
4" Type K 4" curb stop
copper pipe Brass pipe & fittings
(Typ.)

3
4" corporation
stop

Pipe saddle
~

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:


Water main
1. Locate at high point of main.

2. Tap top of main.


Varies

3. Provide insulation and additional depth when specified for freeze protection.

4. Provide minimum 6" side clearance.

5. See project plans for details not shown.

CALC. BOOK NO. N/A SDR DATE 25-JUL-2017

NOTE: All material and workmanship shall be in accordance with


the current Oregon Standard Specifications

The selection and use of this


OREGON STANDARD DRAWINGS
Standard Drawing, while de-
signed in accordance with
generally accepted engineer- MANUAL AIR-RELEASE
ing principles and practices, ASSEMBLY 3
( 4")
RD266

is the sole responsibility of


the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.

RD266
Effective Date: June 1, 2021 - November 30, 2021
4"x4"x80" pressure
Galvanized outlet and pipe to be treated wood post
same size as inlet pipe with
beehive strainer and outlet

Metal strap

2'x2' meter box & cover

n.
Match existing grade

18"m i
n.
Union
UL-2020

6"m i
20-J

Slope

n.
dgn

3'm i
rd270.

Gravel bedding
m um depth

(6" min. depth)


n
ofwaterm ai

PVC valve box


extension
ni

(6" dia. min.)


ed m i

Slope Air release/air vacuum valve


fi
Speci

Type K
Brass pipe & fittings
copper pipe
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

Curb stop or gate valve


Corporation stop 1. Air release/air vacuum valve shall be size specified in Contract.
with operating nut
Piping and valves to be same size as combination air release/air vacuum valve.

Pipe saddle 2. Locate at high point of main.

3. Tap top of main.


~

4. Provide insulation and additional depth when specified for freeze protection.

Water main 5. See project plans for details not shown.

Varies CALC. BOOK NO. N/A SDR DATE 25-JUL-2017

NOTE: All material and workmanship shall be in accordance with


the current Oregon Standard Specifications

The selection and use of this


OREGON STANDARD DRAWINGS
Standard Drawing, while de-
signed in accordance with
COMBINATION AIR RELEASE
generally accepted engineer-
AIR VACUUM VALVE ASSEMBLY
ing principles and practices,
RD270

(2" AND SMALLER)


is the sole responsibility of
the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.

RD270
Effective Date: June 1, 2021 - November 30, 2021
Use felt strip or 10 mil.
poly. isolation joint if meter
box is set in concrete

Service Main
UL-2020
20-J dgn
rd274.

PLAN

Concrete meter box


with cast iron reader lid

4" min.

Isolation joint

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

3" to 6" 1. Meter to be centered and set plumb inside meter box.

3
2. Manufactured meter setter may be used for 4" to 2" services.
Customer
service line
3. Set meter box 4" minimum behind curb or sidewalk.

Corporation 4. Meter boxes set in driveways shall have traffic lids.


3 stop
6" of 4" to 0"
Customer 5. See project plans for meter box size.
Angle meter crushed rock
service valve
valve Water main
6. See project plans for details not shown.

45° N/A 25-JUL-2017


CALC. BOOK NO. SDR DATE
Seamless, soft
annealed copper NOTE: All material and workmanship shall be in accordance with
the current Oregon Standard Specifications
service line,
size as required The selection and use of this
SECTION OREGON STANDARD DRAWINGS
Standard Drawing, while de-
signed in accordance with
3
generally accepted engineer- 4" TO 2"
ing principles and practices, WATER SERVICE CONNECTION
RD274

is the sole responsibility of


the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.

RD274
Effective Date: June 1, 2021 - November 30, 2021
12" clear from all
fittings & valves 15
(See general note 11)

REFERENCE DRAWING ONLY

(NOT FOR CONSTRUCTION)


9 SEE SPECIAL PROVISIONS FOR
M
SPECIFIC PROJECT REQUIREMENTS.

10 5 11
11
7
6
4 14
1 3 3
2
UL-2020

6
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
20-J

6 12 13 8 7
7 1. Vaults shall be sized per specifications and minimum clearances.
When required, vaults shall be designed for site specific conditions by a resistered
9 9
professonal engineer.
dgn

2. All vaults shall be supported with adequate concrete floor and shall be designed
rd278.

to prevent bouyancy from groundwater if groundwater exists at any time during


the year. Vaults shall be water-tight.

3. Precast concrete utility vaults may be used in lieu of cast-in-place when sizes are
12" clear from all
available.
fittings & valves
(See general note 11)
4. Backflow devices to be installed on service and irrigation lines as required.

5. Standard bypass size is 2".

6. Service and irrigation line sizes will vary according to need.


1 Mechanical joint x flange adapter
7. Tees and valves shall be supported with conc. blocks, jacks or adjustable pipe
2 All-flange cross supports.

8. Vault depth shall be such that there is a minimum clearance to the vault lid of 6"
3 Flange gate valve
when the valves are fully open.

4 Meter (Domestic)
9. Provide flexible connections on piping within 18" of vault wall.

5 Meter (Irrigation) 10. Provide opening and ladder locations, vault drainage and pipe penetrations in
accordance with special provisions and contract drawings.
6 Companion flange
11. Provide 12" clear from all fittings & valves to floor.
7 Brass nipples
12. See project plans for details not shown.

8 Mechanical coupling

9 I.P. x I.P. brass elbow


CALC. BOOK NO. N/A SDR DATE 25-JUL-2017

10 I.P. x I.P. gate valve (Optional) NOTE: All material and workmanship shall be in accordance with
the current Oregon Standard Specifications

11 I.P. x meter flange gate valve The selection and use of this
OREGON STANDARD DRAWINGS
Standard Drawing, while de-
12 I.P. x I.P. gate valve
signed in accordance with

13 Brass pipe generally accepted engineer- WATER METER ASSEMBLY


ing principles and practices, (LARGER THAN 2")
RD278

14 All-flange tee is the sole responsibility of


the user and should not be 2021
15 Concrete valult
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.

RD278
Effective Date: June 1, 2021 - November 30, 2021
Sampling station 12"

Padlock
provision

1
With optional 4" ball
1
valve in place of 4" Hinge (2)
petcock on vent pipe Use 2 layers of polyethylene film
UL-2020

between station and concrete pad

Standard valve box


20-J

n.
Concrete pad

4"m i
dgn
rd282.

-0"
-0"To 3'
2'
Curbstop

Elbow
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
Gravel bedding

3
1. Provide insulation and additional depth when specified for freeze protection.
4" service line
45°
2. See project plans for details not shown.
3
4" corporation stop

CALC. BOOK NO. N/A SDR DATE 25-JUL-2017

NOTE: All material and workmanship shall be in accordance with


the current Oregon Standard Specifications

The selection and use of this


OREGON STANDARD DRAWINGS
Standard Drawing, while de-
signed in accordance with
generally accepted engineer-
WATER SAMPLING STATION
ing principles and practices,
RD282

is the sole responsibility of


the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.

RD282
Effective Date: June 1, 2021 - November 30, 2021
5' 5'

Root barrier

ess
10' long x 4' high x 10 GA,
Curb
galv. steel or HDPE

10'orl
Water pipe

1'
UL-2020
20-J

PLAN
dgn
rd286.

TREE

GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:

1. Where existing parkway trees have been root pruned, install continuous,
lineal root barrier adjacent to the pipe.

2. Root sealer shall be applied to all cut root areas which are larger that 2" in
10' or less
diameter. The sealer shall be applied as soon as practical after the cuts have
1'

Curb been made. Root sealer shall be approved by the engineer at least 48 hours
in advance of the pruning operation.

3. Root barriers shall be fabricated from a high density, high impact plastic or hot
dipped galvanized steel.

4. See project plans for details not shown.

Water pipe

CALC. BOOK NO. N/A SDR DATE 25-JUL-2017

NOTE: All material and workmanship shall be in accordance with


Root barrier the current Oregon Standard Specifications

10' long x 4' high x 10 GA,


The selection and use of this
galv. steel or HDPE OREGON STANDARD DRAWINGS
Standard Drawing, while de-
signed in accordance with
generally accepted engineer-
ROOT BARRIER
ing principles and practices,
RD286

SECTION
is the sole responsibility of
the user and should not be 2021
used without consulting a DATE REVISION DESCRIPTION

Registered Professional En-


gineer.

RD286
Effective Date: June 1, 2021 - November 30, 2021