Tuning Fork Level Switch

visit
i i our website
b i
PRODUCT INTRODUCTION

WORKING PRINCIPLE APPLICATION


The FineTek tuning fork level switch is suitable 1 Most materials in powder can be measurable,
level control switch for liquids, sludges, petroleums includes the grounded coffee, milk power,
as well solid level detection of almost any granular, chocolate, coal ash, bulk, sugar, salt, wheat,
sandy, chip like, powdery, low bulk density grains, glass debris, plastic pellet, cement
materials.
1 Sludge level detection in waste water
The working principle is based on the changes of
vibration frequency of the tuning fork when it The SC series detects the min. and max of
comes into contact with a liquid or solid material.. level in bins, silos and hoppers, filled with
powdered materials. The following list shows its
The Tuning fork contains piezoelectric crystals built applications.
into the vibration tube that produces
vibrations/resonations at specific frequencies. One
element acts as a transmitter of the signal and the SOLID LEVEL DETECTION
other receives the signal and converts it to * Powdered milk * Peanuts
electrical output. * Frozen potato chips * Tobacco
* Beans * Wood shavings
When the fork comes in contact with material the * Sugar * Chalk
vibration is weakened/dampened and results in * Sweets * Stearin chips
frequency change which triggers the switch. It's * Coffee beans * Powdered cellulose
ideal for applications where: the dielectric constant * Coffee Powder * Glass fine power
is low (where capacitance level switches can't be * Tea * Granular plastics
used) ; when material moisture content changes * Salt * Gravel
easily; low viscosity liquids; there is a combination * Flour (in a flour mill) * Powdered clay
of differing materials in the container/tank. * Foundry sand * Polystyrene powder
* Spices * Styrofoam
The tuning fork level switch provides a reliable & * Animal food * Soda
maintenance-free means of process control for * Pellets * Soot dry
bulk solids. Easy mounting at almost any angle
and calibration procedures will provide reliable
functioning and less required monitoring. This
device can withstand tough lateral loads and static
electricity. Also, it is equipped with a Fail-safe that
FOR LIQUID
prevents malfunctioning caused by power * Water & Solutions * Ink
shortage. * General Purpose Solvent * Corrosive liquid
* Petroleum * Cream
* Oil * Drink & Beverage
* Heavy oil
FEATURE
1 Glass window, to review power supply and output
directly without having to take off enclosure cover
(SC 3 series).
1 Dual insulation can reduce damage on PCB board
caused by temperature, humidity, and condensation
effects.
1 Wide voltage supply range 20~250, 50~60Hz Vac/
Vdc.
1 SPDT Relay output, SSR MOSFET output.
1 No calibration required, easy use, sturdy and durable
design.
1 High / Low failure safe modes.
1 Sensitivity adjustment is abailable for different density
of media. Fine power can be detected.
1 Suitable for liquid, power, solid applications.

1
SPECIFICATION

f38 f38 f38

114 114 114

Dimensions
271 25 273 25 258 25
(Unit:mm) HEX38 HEX38 HEX38
25 f29 25 f29 25 f29
1PT 1PT 1PT
Max. Max. Max.
f27 250mm f27 250mm f27 250mm

105 105 105

f20 f27 f20 f27 f20 f27

Standard Type Extension Type Standard Type Extension Type Standard Type Extension Type

SC2400/2410 SC2400/2410 SC2400/2410


Model No. 【DIN Connector】 【M12 Connector】 【Cable Wire Type】
Supply Voltage SC240 99:20~250Vac / Vdc 2 wire Contactless electronic switch.
& Output SC24199:12~55 Vdc 3 wire PNP/ NPN Output.

Fork Length 100mm

Operating Temp.
-40~60LC
In Ambient Air
Storage Temp. -40~70LC

Operating Temp. SC24999: -40~+100LC


In Bin SC24999T: -40~+150LC
Operation
80% RH non-condensed
Humidity
Operation
Maximum 40 Bar
Pressure
Min. material Solid:density: ³0.07g/cm3
density sensed Liquid:density: ³0.7g/cm3 Viscosity:1~10000 cSt

Magnetic testing Output function test performed by putting magnets near the indicated spot

Green light:indicate power supply


Status indication Red light:indicate operating mode
Housing
SUS 304
material
Fork Material 316L

IP Protection IP65 IP67 IP67

Mounting 1" PT

Conduit Valve plug DIN 43650 M12x1 connector Cable connector

2
MINI TUNING FORK LEVEL SWITH

f38 f38 f38

Dimensions 111 111 111

(Unit:mm) 215 217 201


26 26 26
HEX38 HEX38 HEX38
36 3/4PT 36 3/4PT 36 3/4PT
f21 Max. f29 f21 Max. f29 f21 Max. f29
250mm 250mm 250mm
40 40 40

f17 f17 f17 f17 f17 f17

Standard Type Extension Type Standard Type Extension Type Standard Type Extension Type

SC2800/2810 SC2800/2810 SC2800/2810


Model No. 【DIN Connector】 【M12 Connector】 【Cable Wire Type】
Supply Voltage SC2809:20~250,50/60Hz Vac/Vdc 2 wire Contactless electronic switch.
& Output SC2819:12~55 Vdc 3 wire PNP/ NPN Output

Fork Length 40mm

Operating Temp.
-40BC~70BC
In Ambient Air
Storage Temp. -40BC~85BC

Operating Temp. -40BC~150BC


In Bin
Operation
80% RH non-condensed
Humidity
Operation -1~600PSI (40BAR)
Pressure
Min. material Solid:density: ³0.07g/cm3
density sensed Liquid:density: ³0.7g/cm3 Viscosity:1~10000 cSt

Magnetic testing Output function test performed by putting magnets near the indicated spot

Green light:indicate power supply


Status indication Red light:indicate operating mode
Housing
SUS 304
material
Fork Material 316L

IP Protection IP65 IP67 IP67

Mounting 3/4"PT

Conduit Valve plug DIN 43650 M12x1 connector Cable connector

3
SPECIFICATION

f113
f113
108
f113 1/2"NPT
108
1/2"NPT
20
108 20
1"PT
1/2"NPT
Dimensions 1"PT
20
(Unit:mm) 25 1" PT f29
f27 f27.2 130~250mm
105 250mm~3M
f27
f27
105
105

Model No. SC1400 SC1410【Tuning Fork SC1420【Tuning


【Standard Type】 Ultra Extension Type】 Fork Extension Type】
Level Sensor
Aluminum / IP65
Housing
Probe
316L
Construction
Mounting 1"PT

Conduit 1/2"NPTx2

Max. Vertical 177in.Lbs(20Nm)


load on rod.
Operating -1~600PSI (40BAR)
Pressure.
Power Supply 20~250,50/60Hz Vac/Vdc

Power
10VA
Consumption
Operating Temp.
-40LC~60LC
In Ambient Air
Operating Temp. -40LC~130LC
In Bin
Relay, SPDT, 5A/250Vac/ 28Vdc, 1 set or 2 set
Signal Output
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1 set or 2 set
Min. material
Solid:³0.07g/cm3, Liquid: ³0.7g/cm3
density sensed
Time Delay 0.6 Second / Operate; 1~3 Seconds / Reset

Vibrating 350~370Hz
Frequency.
Selectable
Hi./ Lo.
Fail-safe
Selectable
Hi./ Lo.
Sensitivity

4
SPECIFICATION

f113 f113

108 108
1/2"NPT 1/2"NPT
Dimensions
(Unit:mm)

105 105

SC1540 SC1600
Model No.
【Corrosion Proof Type】 【Sanitary Type】
Level Sensor
Aluminum / IP65
Housing
Probe
316L Coating TEFLON 316L
Construction
Mounting Flange 1"(min.) 2" Sanitary

Conduit 1/2"NPTx2

Max. Vertical 177in.Lbs(20Nm)


load on rod.
Operating -1~600PSI (40BAR)
Pressure.
Power Supply 20~250Vac/dc

Power
10VA
Consumption
Operating Temp.
-40LC~60LC
In Ambient Air
Operating Temp. -40LC~130LC
In Bin
Relay, SPDT, 5A/250Vac/ 28Vdc, 1 set or 2 set
Signal Output
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1 set or 2 set
Min. material
Solid: ³0.07g/cm3, Liquid: ³0.7g/cm3
density sensed
Time Delay 0.6 Second / Operate; 1~3 Seconds / Reset

Vibrating 350~370Hz
Frequency.
Selectable
Hi./ Lo.
Fail-safe
Selectable
Hi./ Lo.
Sensitivity

5
SPECIFICATION (Multi-Function Tuning Fork Level Switch)

f84
f84
105
f84 1/2"PF
105
1/2"PF 20
105 20 1"PT
Dimensions 1/2"PF
1"PT
(Unit:mm) 20
1" PT 25 f29
f27 f27.2
130~250mm
105 250mm~3M

105
105

Model No. SC3400 SC3410【Tuning SC3420【Tuning Fork


【Standard Type】 Fork Extension Type】 Ultra Extension Type】
Level Sensor
Aluminum / IP65
Housing
Probe
316L
Construction
Mounting 1"PT

Conduit 1/2"PFx2

Max. Vertical 177in.Lbs(20Nm)


load on rod.
Operating -1~600PSI (40BAR)
Pressure.
Power Supply 20~250,50/60Hz Vac/Vdc

Power
10VA
Consumption
Operating Temp.
-40LC~60LC
In Ambient Air
Operating Temp. -40LC~130LC
In Bin
Relay, SPDT, 5A/250Vac/ 28Vdc , 1set
Signal Output
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1set
Min. material Solid:density: ³0.07g/cm3
density sensed Liquid:density: ³0.7g/cm3 Viscosity:1~10000 cSt

Time Delay 0.6 Second / Operate; 1~3 Seconds / Reset

Vibrating 350~370Hz
Frequency.
Selectable
Hi./ Lo.
Fail-safe
Selectable
Hi./ Lo.
Sensitivity

6
SPECIFICATION (Mult-Function Tuning Fork Level Switch)

f84 f84 f84

105 105 105


Dimensions 1/2"PF 1/2"PF

(Unit:mm) 20 20 19
3/4" PT 35

41
105 105
16

SC3440 SC3450 SC3800


Model No.
【Corrosion Proof Type】 【Sanitary Type】 【Mult-Function Mini Type】
Level Sensor
Aluminum / IP65
Housing
Probe
316L Coating TEFLON 316L 316L
Construction
Mounting Flange 1"(min.) 2" Sanitary 3/4" PT(Default)

Conduit 1/2"PF X 2

Max. Vertical 177in.Lbs(20Nm)


load on rod.
Operating -1~600PSI (40BAR)
Pressure.
Power Supply 20~250,50/60Hz Vac/Vdc

Power
10VA
Consumption
Operating Temp.
-40BC~60BC
In Ambient Air
Operating Temp. -40BC~130BC -40BC~150BC
In Bin
Relay, SPDT, 5A/250Vac/ 28Vdc, 1set Relay, SPDT, 5A/250Vac
Signal Output NPN/PNP(MosFET):400m/60Vac/Vdc
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1set
Min. material Relay, SPDT, 5A/250Vac/ 28Vdc, 1set
density sensed SSR(MOSFET) 400mA/60 Vac/ Vdc, 1set

Time Delay Solid: density: ³0.07g/cm3


Liquid: density: ³0.7g/cm3 Viscosity:1~10000 cSt
Vibrating 350~370Hz
Frequency.
Selectable Hi./ Lo.
Fail-safe
Selectable Hi./ Lo.
Sensitivity

7
NEPSI PROOF No.GYJ111212 Ex d IIC T3~T6
PTB PROOF No. 09 ATEX 1058 II 2G Ex d IIB T4 Gb
SPECIFICATION II 2D Ex tb IIIC T80BC ~ T130BC Db IP65

f113

108
f113 1/2"NPT

20
108 1-1/4"PT
1/2"NPT
Dimensions
20
(Unit:mm) 1" PT
f27.2
105
250mm~3M

f27

105

SC1740 SC1741【Tuning Fork


Model No. 【Standard Type】 Ultra Extension Type】
Level Sensor
Aluminum / NEPSI Ex d llC T3~T6 / II 2G Ex d IIB T4
Housing
Probe
316L
Construction
Mounting 1"PT 1-1/4"PT

Conduit 1/2"NPTx2

Max. Vertical 177in.Lbs(20Nm)


load on rod.
Operating -1~600PSI (40BAR)
Pressure.
Power Supply 20~250,50/60Hz Vac/Vdc

Power
10VA
Consumption
Operating Temp.
-40LC~60LC
In Ambient Air
Operating Temp. -40LC~130LC
In Bin
Relay, SPDT, 3A/250Vac/ 28Vdc, 1 set or 2 set
Signal Output
SSR(MOSFET) 400mA/60 Vac/ Vdc, 1 set or 2 set
Min. material
Solid: ³0.07g/cm3, Liquid: ³0.7g/cm3
density sensed
Time Delay 0.6 Second / Operate; 1~3 Seconds / Reset

Vibrating 350~370Hz
Frequency.
Selectable
Hi./ Lo.
Fail-safe
Selectable
Hi./ Lo.
Sensitivity

8
TERMINAL / SENSITIVITY ADJUSTMENT (SPDT TYPE)

SC1400X, SC1410X, SC1420X, SC1540X,SC1600X, SC1740X, SC1741X

Relay Output

SENSITIVITY
PWR SIGNAL FSL FSH L H

RT2 RT1 NC COM NO N- L+

SSR(MOSFET) Output

20~250VAC
20~250VDC

RT2 RT1 N- L+

TERMINALl FUNCTION PANEL FUNCTION


L+, N-: Power Supply PWR: Power Supply (Green Light)
SIGNAL: Output Indication (Red Light)
NC, COM, No: Relay Output
FSH: Power On. The signal lamp is on and the
RT1, RT2: Remote-Test relay is conductive. While the tuning fork
switch senses the material, the signal lamp
: Ground Connection
is off and relay is not conductive.
: SSR(MOSFET) Output FSL: Power On. The signal lamp is off and the
relay is not conductive. While the tuning
fork switch senses the material, the signal
FAIL-SAFE HIGH / LOW PROTECTION
lamp is on and relay is conductive.
FSH (Fail-Safe High) Protection: SENSITIVITY L: Low Sensitivity
Switch to FSH mode. SENSITIVITY H: High Sensitivity
Normal Status: The signal lamp is on. It means that
the tuning fork switch does not sense the material
and the relay is conductive. SENSITIVITY ADJUSTMENT
Failure: When the power shuts down, the signal lamp The SENSITIVITY is located on the right side of
is off. It means that the tuning fork switch is voided the panel. The user is able to do the minor
and the relay is not conductive. adjustment by the screw driver. If it turns to H
position clockwise, the sensitivity increases; if it
FSL (Fail-Safe Low) Protection: turns to L position anti-clockwise, the sensitivity
Switch to FSL mode. decreases. The sensitivity is originally set at max.
Normal Status: The signal lamp is on. The tuning value. The switching point is at 15mm from tip of
fork switch senses the material and the relay is tuning fork switch.
conductive.
Failure: When the power shuts down, the signal lamp The switching point position will be changed by the
is off. The tuning fork switch is voided and the relay sensitivity value. If the sensitivity adjusts to lower
is not conductive. value, the switching point position is moving
backward; if the sensitivity adjusts to high value,
FSL FSH the switching point position is moving forward. The
Level changing range of switching point is about 60mm.

For example, if the switching point needs to be


Contact moved backward by 30mm, the user needs to
Form NO COM NC NO COM NC NO COM NC NO COM NC adjust SENSITIVITY anti-clockwise by 10 turns. In
Indication
general case, it is no need for sensitivity
adjustment.
Status Fail Normal Normal Fail

9
TERMINAL / SENSITIVITY ADJUSTMENT (DPDT TYPE)

SC1400X, SC1410X, SC1420X, SC1540X,SC1600X, SC1740X, SC1741X


Relay Output

SENSITIVITY
PWR SIGNAL FSL FSH L H

RT2 RT1 COM2 NC2 NO2 COM1 NC1 NO1 N- L+

SSR(MOSFET) Output

20~250VAC
20~250VDC

RT2 RT1 2 2 1 1 N- L+

TERMINAL FUNCTION PANEL FUNCTION


L+, N-: Power Supply PWR: Power Supply (Green Light)
SIGNAL: Output Indication (Red Light)
NC1, COM1, NO1: Relay Output
FSH: Power On. The signal lamp is on and the
NC2, COM2, NO2: Relay Output relay is conductive. While the tuning fork
switch senses the material, the signal lamp
RT1, RT2: Remote-Test
is off and relay is not conductive.
: Ground Connection FSL: Power On. The signal lamp is off and the
relay is not conductive. While the tuning
: 1st SSR(MOSFET) Output fork switch senses the material, the signal
: 2st SSR(MOSFET) Output lamp is on and relay is conductive.
SENSITIVITY L: Low Sensitivity
FAIL-SAFE HIGH / LOW PROTECTION SENSITIVITY H: High Sensitivity
FSH (Fail-Safe High) Protection:
Switch to FSH mode. SENSITIVITY ADJUSTMENT
Normal Status: The signal lamp is on. It means that The SENSITIVITY is located on the right side of
the tuning fork switch does not sense the material the panel. The user is able to do the minor
and the relay is conductive. adjustment by the screw driver. If it turns to H
Failure: When the power shuts down, the signal lamp position clockwise, the sensitivity increases; if it
is off. It means that the tuning fork switch is voided turns to L position anti-clockwise, the sensitivity
and the relay is not conductive. decreases. The sensitivity is originally set at max.
value. The switching point is at 15mm from tip of
FSL (Fail-Safe Low) Protection: tuning fork switch.
Switch to FSL mode.
Normal Status: The signal lamp is on. The tuning The switching point position will be changed by the
fork switch senses the material and the relay is sensitivity value. If the sensitivity adjusts to lower
conductive. value, the switching point position is moving
Failure: When the power shuts down, the signal lamp backward; if the sensitivity adjusts to high value,
is off. The tuning fork switch is voided and the relay the switching point position is moving forward. The
is not conductive. changing range of switching point is about 60mm.
FSL FSH
For example, if the switching point needs to be
Level moved backward by 30mm, the user needs to
adjust SENSITIVITY anti-clockwise by 10 turns. In
general case, it is no need for sensitivity
Contact adjustment.
Form NO COM NC NO COM NC NO COM NC NO COM NC

Indication

Status Fail Normal Normal Fail

10
TERMINAL / SENSITIVITY ADJUSTMENT (MULTI-FUNCTION TYPE)

SC3400X, SC3410X, SC3420X, SC3450X


Relay Output

SENSITIVITY L+ N- NO COM NC PE RT1 RT2


FSL FSH PWR SIGNAL

OUTPUT MODE L H
SSR(MOSFET) Output

L+ N- NG PE RT1 RT2

TERMINAL FUNCTION PANEL FUNCTION


L+, N-: Power Supply PWR: Power Supply (Green Light)
SIGNAL: Output Indication (Red Light)
NC, COM, No: Relay Output
FSH: Power On. The signal lamp is on and the
RT1, RT2: Remote-Test relay is conductive. While the tuning fork
switch senses the material, the signal lamp
: Ground Connection
is off and relay is not conductive.
: SSR(MOSFET) Output FSL: Power On. The signal lamp is off and the
relay is not conductive. While the tuning
fork switch senses the material, the signal
FAIL-SAFE HIGH / LOW PROTECTION lamp is on and relay is conductive.
FSH (Fail-Safe High) Protection: SENSITIVITY L: Low Sensitivity
Switch to FSH mode. SENSITIVITY H: High Sensitivity
Normal Status: The signal lamp is on. It means that
the tuning fork switch does not sense the material
and the relay is conductive. SENSITIVITY ADJUSTMENT
Failure: When the power shuts down, the signal lamp The SENSITIVITY is located on the right side of
is off. It means that the tuning fork switch is voided the panel. The user is able to do the minor
and the relay is not conductive. adjustment by the screw driver. If it turns to H
position clockwise, the sensitivity increases; if it
FSL (Fail-Safe Low) Protection: turns to L position anti-clockwise, the sensitivity
Switch to FSL mode. decreases. The sensitivity is originally set at max.
Normal Status: The signal lamp is on. The tuning value. The switching point is at 15mm from tip of
fork switch senses the material and the relay is tuning fork switch.
conductive.
Failure: When the power shuts down, the signal lamp The switching point position will be changed by the
is off. The tuning fork switch is voided and the relay sensitivity value. If the sensitivity adjusts to lower
is not conductive. value, the switching point position is moving
backward; if the sensitivity adjusts to high value,
FSL FSH the switching point position is moving forward. The
Level changing range of switching point is about 60mm.

For example, if the switching point needs to be


Contact moved backward by 30mm, the user needs to
Form NO COM NC NO COM NC NO COM NC NO COM NC adjust SENSITIVITY anti-clockwise by 10 turns. In
Indication
general case, it is no need for sensitivity
adjustment.
Status Fail Normal Normal Fail

11
WIRING DIAGRAM DETAILS

SC240X (Two wires) WIRING

Min. Max. Wiring


Power can be AC/DC switching. Two wires are
connected with terminals (L+/N-) as in Figure 1.

Low (Min.) Mode:


1 2 3 4 1 2 3 4
Brown Black Blue Yellow Brown Black Blue Yellow
Pin 1 (Brown) is connected to N-. Pin 2 (Black) is
Green Green
connected to L+ with relay. Pin 4 (Yellow Green)
connects to tank ground.
N- L+ N- L+ High (Max.) mode:
Figure 1 Two wires wiring Pin 1 (Brown) is connected to N-. Pin 3 is
Min. Max.
connected to pin 2 (Black) to L+ with Relay . Pin 4
Min. Max.
Yellow Green Yellow Green
Black Black
(Yellow Green) connects to tank ground.
Brown Black Brown Black Blue Blue
1 2 1 2
3 3 Brown Brown
Yellow Green Yellow Green
Blue Blue

PE N - L+ PE N - L+
PE N- L+ PE N- L+
DIN Wiring Diagram M12x1、Cable Wiring Diagram

SC240X (Two wires) WIRING


PNP NPN Wiring
Max. Min. Max. Min. Power supply is for DC only. Output is PNP / NPN.
Please see Figure 2.
Yellow Yellow Yellow Yellow
Green Green Green Green
Brown 1 2 Black Brown 1 2 Black
3 3
Brown 1 2 Black Brown 1 2 Black
3 3
PNP wiring:
Blue Blue Blue Blue High(Max.) Mode:
R R
R Pin 1(Brown) connects to N-. Pin 3 (Blue)
PE N- L+ PE N- L+ PE L+ N- PE L+ N- connects to L+. To output, it is pin 2. (Black)
DIN Wiring Diagram connects to N- with relay. Pin 4 (Yellow Green)
PNP NPN connects to tank ground.
Max. Min. Max. Min.

Low(Min.)Mode:
Black Black
Pin 1 (Brown) connects to N-. Pin 2 (Black)
Black Black
Blue Blue
Brown
Blue Blue
Brown
connects to L+. To output, Pin 3 (Blue) connects to
Brown Brown
Yellow Green Yellow Green Yellow Green Yellow Green N- with relay. Pin 4 (Yellow Green) should contact
to tank ground.
PE N- L+ PE N- L+ PE L+ N- PE L+ N-
M12x1、Cable Wiring Diagram NPN wiring:
Figure 2 PNP / NPN Output Wiring Diagram High(Max.) Mode:
Pin 1 (Brown) connects to L+. Pin 3 (Blue)
connects to N-. To output, Pin 2 (Black) connects to
L+ with relay. Pin 4(Yellow Green) should contact
to tank ground.

Low(Min.)Mode:
Pin1 (Brown) connects to L+. Pin 2 (Black)
connects to N-. To output Pin 3 (Blue) connects to
L+ with relay. Pin 4 (Yellow Green) should contact
to tank ground.

12
TUNING AND INDICATION DETAILS

FORK TRIGGER POINT MAGNETIC TEST


SC2409 fork trigger point is shown as Figure 3 After the switch has installed and power tested,
3
below. The testing medium is water(S.G.=1 g/cm ), magnetic switch can be performed accordingly.
and its trigger point is about 23mm from the fork tip. Output status will switch from status of NO. to NC.
If testing medium with S.G (specific gravity) lower than or NC to NO. and red LED would indicate the
3
1g/cm (water), the trigger point would increase. vibration status by on / off.
Similarly, the trigger point will downward while the S.G When magnet is pulled away from the housing, red
is large than water. LED would return as default while fork continues to
vibrate. By this verification, user can confirm the
wiring and function are correct or not.

S.G.<1g/cm 3
Trigger Point Testing
point
moves upward Magnet
Trigger
point
S.G.>1g/cm 3 23mm
Trigger Point
moves downward
S.G.<1g/cm 3
Trigger Point
moves upward
Sensing spot

10 mm

S.G.>1g/cm 3
Trigger Point
moves downward

Output Status for Relay Output Status for PNP / NPN Transistor
Low (Min.) Mode: Tuning fork switch will be active Low(Min.) Mode : Tuning fork switch will be  
after 3 seconds while power on. Relay is on active after 3 seconds while power on. Output
NO status and red LED indication is off. When transistor is on NO status and red LED indication
tuning fork is covered by testing medium, the vibration is off. When tuning fork covered by testing medium,  
will stop and relay becomes NC status. vibration will stop and output transistor becomes NC
Red LED indication then is on. status. Red LED indication is on.

High(Max.) Mode: Tuning fork switch will be active High(Max.) Mode: Tuning fork switch will be  
after 3 seconds while the power on. Relay is on active after 3 seconds while power on. Output
NC status and red LED indication is on. When tuning transistor is on NC status and red LED indication
fork covered by testing medium, the vibration stops and is on. When tuning fork covered by testing medium,
relay becomes NO status. Red LED indication is on. vibration will stop and output transistor becomes
NO status. Red LED indication is off.
Min. Mode Max.Mode Min. Mode Max.Mode

Level Level

Contactless PNP/
electronic NPN
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2
switch Output
Switch open Switch closed Switch closed Switch open Switch open Switch closed Switch closed Switch open
Red Red
LED LED

13
INSTALLATION FOR TUNING FORK

Horizontal Installation:
1. Can be applied for high 2. Wiring port faces 3.Consistence of the wiring
viscosity fluid and power downward recommended. port direction and always in
Do not install near around downward direction for
material inlet. multi-tuning fork
installation.
Inlet

Vertical Installation:
1. Depends on the sensitivity 3.Consistence of the wiring 3. Do not install near material
tuning, user should note port direction for multi- inlet.
the switching point is tuning fork installation
triggered around 15mm
from the tip of fork.

15mm

14
ORDER INFORMATION

ORDER NO.
1400: Tuning Fork Standard Type
1410: Tuning Fork Extension Type
1420: Tuning Fork Ultra Extension Type
1540: Tuning Fork Corrosion Proof Type
1600: Tuning Fork Sanitary Type
1740: Explosion Proof Tuning Fork Standard Type
1741: Explosion Proof Tuning Fork Ultra Extension Type
3400: Multi-Function Tuning Fork Standard Type
3410: Multi-Function Tuning Fork Extension Type
3420: Multi-Function Tuning Fork Ultra Extension Type
3440: Multi-Function Tuning Fork Corrosion Proof Type
3450: Multi-Function Tuning Fork Sanitary Type
3800: Multi-Function Mini Type
POWER & OUTPUT MODULE
20~250Vac/ Vdc, 50/60Hz R: Relay O/P-EuroType
N: SSR(MOSFET) EuroType
Q: Relay O/P x 2 -EuroType
M: SSR(MOSFET) x 2 -EuroType
※Multion Funtion version can choose R、N only
MATERIAL (Wetted Part)
0: SUS304 6: SUS316 L: SUS316L
CONNECTION
Dimension Specification
D---1"(25A) M---5kg/cm 2 Y---PN 25
3---1-1/4"(32A) N---10kg/cm 2 Z---PN 40
E---1-1/2"(40A) O---150 Lbs S---others
F---2"(50A) P---300 Lbs 9---Sanitary
G---2-1/2"(65A) Q---PT
H---3"(80A) R---PF(G)
I---4"(100A) T---BSP
J---5"(125A) U---NPT
K---6"(150A) W---PN 10
S---others X---PN 16

LENGTH (L) (UNIT: mm)


0500: below 500mm
1000: 501~1000mm
1500: 1001~1500mm 500mm per Unit
Use English letter as first code for probe length over 10m.
A150 represents 15m, A200 represents 20m.
The Probe Length of SC3800 is Fixed.
BEFORE YOU ORDER
1. Please affirm the voltage.
2. Please affirm the mounting positions.
3. Please affirm the material specific gravity (S.G.) value.
4. Please affirm whether any bridge block or vibrating motor are attached onto the silo wall.
Tolerance of the total product length is±5mm
Characteristics, specifications and dimensions are subject to change without notice.
Please contact your nearest distributing office for further information.
15
ORDER INFORMATION

SC
ORDER NO.
24: 100mm 28: 40mm

POWER & OUTPUT MODULE


0: 20~250Vac / Vdc 2 wire Contactless
electronic switch.
1: 12~55 Vdc 3 wire PNP/ NPN Output.

MATERIAL (Wetted Part)


0: SUS304 6: SUS316 L: SUS316L

MODEL
0: Standard 1: Extended
(High temp. 150BC)
ELECTRICAL CONNECTION
A: M12x1(180B) B: M12x1(90B)
C: CABLE D: Valve plug DIN43650
(M12x1/ CABLE Wire length are 2M,PVC 24AWG)
CONNECTION
Dimension Specification

C---3/4"(20A)SC28 only M---5kg/cm2 X ---PN16


D---1"(25A) N ---10kg/cm2 Y ---PN25
E---1-1/2"(40A) O---150 Lbs Z ---PN40
F---2"(50A) P ---300 Lbs S ---Special
G---2-1/2"(65A) Q---PT
H---3"(80A) R---PF(G)
I ---4"(100A) T ---BSP
J ---5"(125A) U ---NPT
K---6"(150A) W---PN10
S---Special

PROBE LENGTH (UNIT: mm)


Max Length:250mm
EX 0205 :250mm

BEFORE YOU ORDER


1. Please affirm the voltage.
2. Please affirm the mounting positions.
3. Please affirm the material specific gravity (S.G.) value.
4. Please affirm whether any bridge block or vibrating motor are attached onto the silo wall.
Tolerance of the total product length is±5mm
Characteristics, specifications and dimensions are subject to change without notice.
Please contact your nearest distributing office for further information.

16
[FC/FD] Mini Float/Magnetic Float Level Switch
[PB]
[FG] Magnetic Float Level Transmitter
[EA] [LR]
[FF] Side Mounting Float Switch
[EG] [EB] [FG] [JFR]
[FA/FB] Cable Float Level Switch [FC/FD]
[FA/FB] [EC]
[SB]
[SP] Thermal Dispersion Flow Switch [EB]

[SF] Paddle Flow Switch [EF]


[SC]
[SD] Optical Level Switch
[SA]
[SE] Rotary Paddle Level Switch
[SA] Capacitance Level Switch
[FF]
[EC] Pressure Level Transmitter
[SF]
[LR] Loop Power Indicator
[SC] Vibrating Probe Level Switch
[SC] Tuning Fork Level Switch
[SD] [FC/FD] [SP]
[EB] RF-Capacitance Level Transmitter
[SB] RF-Capacitance / Admittance Level Switch [EA] [PB/PM]
[EE]
[EG] Magnetostrictive Level Transmitter
[SB] [SE] [SC] [JFR] [EB]
[EF] By-Pass Level Transmitter
[EB]
[MEF] Mini By-Pass Level Transmitter
[SA]
[EA] Ultrasonic Level Transmitter
[SC]
[JFR] FMCW Radar Level Transmitter
[SC]
[EE] Electromechanical Level Measuring System [SE]
[ED] Speed Monitor
[SB]
[SRT/SRS] Conveyer Belt Misalignment Switch &

Safety Cable Pull Switch


[PB/PM] Microprocessor Based Bargraphic Display Scaling Meter
[BVK/
[BRD/AE] Valve and Controller for Dust Collector System [BAS/ BVR/BVT]
[BAS/BAH/BVP] Air Hammer BAH/BVP]

[BVK/BVR/BVT] Pneumatic Vibrator

FineTek Co., Ltd.


No.16, Tzuchiang St., Tucheng Industrial Park, New Taipei City 236, Taiwan.
TEL: 886 2 2269 6789 FAX: 886 2 2268 6682
Email: info@fine-tek.com http://www.fine-tek.com

Taichung Branch TEL: 886 4 2465 2820 FAX: 886 4 2463 9926
Tainan Branch TEL: 886 6 289 0635 FAX: 886 6 289 4073
Kaohsiung Branch TEL: 886 7 333 6968 FAX: 886 7 536 8758

Fine automation (ShangHai) Co., Ltd.


No.451 DuHui Rd, MinHang District, Shanghai, China 201109
TEL: 86 21 6490 7260 FAX: 86 21 6490 7276
Email: info.sh@fine-tek.com

FineTek Pte Ltd.


No. 60 Kaki Bukit Place, #07-06 Eunos Techpark 2
Distributor:
Lobby B, Singapore 415979
TEL: 65 6452 6340 FAX: 65 6734 1878
Email: info.sg@fine-tek.com

FineTeK GmbH
Frankfurter Str. 62, OG D-65428 Ruesselsehim, Germany
TEL: 49 6142 17608 0 FAX: 49 6142 17608 20
E-Mail: info@fine-tek.de

Aplus Finetek Sensor inc.


355 S. Lemon Ave, Suite D, Walnut, CA 91789
Tel : 1 909 598 2488 Fax : 1 909 598 3188 08-SC02-B1-EP, 12/26/2012
Email: peter.wu@aplusfine.com