10, March
24, 2021
Electranix Corporation
Warning: Reading .seq Generator Sequence data: Bus number=101, ID=1 - negative
sequence machine impedance not supported and is ignored...
Warning: Reading .seq Generator Sequence data: Bus number=102, ID=1 - negative
sequence machine impedance not supported and is ignored...
Warning: Reading .seq Generator Sequence data: Bus number=206, ID=1 - negative
sequence machine impedance not supported and is ignored...
Warning: Reading .seq Generator Sequence data: Bus number=211, ID=1 - negative
sequence machine impedance not supported and is ignored...
Warning: Reading .seq Generator Sequence data: Bus number=3011, ID=1 - negative
sequence machine impedance not supported and is ignored...
Warning: Reading .seq Generator Sequence data: Bus number=3018, ID=1 - negative
sequence machine impedance not supported and is ignored...
Warning: Reading .seq Mutual Impedance data: FR1=151, TO1=152, CKT1=1, FR2=151,
TO2=152, CKT2=2 - data not supported and is ignored...
Warning: Reading .seq Mutual Impedance data: FR1=153, TO1=154, CKT1=1, FR2=153,
TO2=154, CKT2=2 - data not supported and is ignored...
Warning: Reading .seq Mutual Impedance data: FR1=203, TO1=205, CKT1=1, FR2=203,
TO2=205, CKT2=2 - data not supported and is ignored...
Warning: Reading .seq Mutual Impedance data: FR1=3003, TO1=3005, CKT1=1, FR2=3003,
TO2=3005, CKT2=2 - data not supported and is ignored...
Warning: Reading .seq Mutual Impedance data: FR1=154, TO1=203, CKT1=1, FR2=203,
TO2=205, CKT2=1 - data not supported and is ignored...
Warning: Reading .seq Mutual Impedance data: FR1=154, TO1=203, CKT1=1, FR2=203,
TO2=205, CKT2=2 - data not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=151, TO=101, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=151, TO=102, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=152, TO=153, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=201, TO=211, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=202, TO=203, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=204, TO=205, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=205, TO=206, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=3001, TO=3002, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=3001, TO=3011, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=3004, TO=3005, TERT=0, CKT=1 - data
not supported and is ignored...
Warning: Reading .seq Transformer Zero data: FR=3008, TO=3018, TERT=0, CKT=1 - data
not supported and is ignored...
Initializing Y Matrix...
Compute P,Q...
Checking V, I, PQ values...
The 23 busses with the largest PQ mis-match (p.u. on base MVA = 100) are:
Bus: 152, (P,Q) = (0.000157274,-0.00195578)
Bus: 205, (P,Q) = (-8.71229e-005,0.00185162)
Bus: 3001, (P,Q) = (-7.35888e-005,-0.00177126)
Bus: 154, (P,Q) = (0.00013702,-0.00169445)
Bus: 153, (P,Q) = (2.17681e-005,0.00157604)
Bus: 3003, (P,Q) = (2.66434e-005,0.00117463)
Bus: 202, (P,Q) = (-4.29031e-005,0.00103113)
Bus: 3005, (P,Q) = (8.88689e-005,0.000811709)
Bus: 151, (P,Q) = (-6.57192e-005,0.000648106)
Bus: 203, (P,Q) = (-8.1721e-005,-0.000558322)
Bus: 211, (P,Q) = (2.73229e-005,-0.000506852)
Bus: 3011, (P,Q) = (7.04901e-005,0.000437153)
Bus: 3006, (P,Q) = (-8.68253e-005,-0.000415474)
Bus: 3008, (P,Q) = (3.83638e-006,-0.000306338)
Bus: 3007, (P,Q) = (2.81125e-006,-0.000276732)
Bus: 201, (P,Q) = (-7.59622e-005,0.00019913)
Bus: 3004, (P,Q) = (-0.000121051,-0.000170679)
Bus: 206, (P,Q) = (0.00010176,0.000159878)
Bus: 3002, (P,Q) = (2.78579e-006,0.000177194)
Bus: 102, (P,Q) = (4.02572e-005,-0.000145044)
Bus: 101, (P,Q) = (4.02572e-005,-0.000145044)
Bus: 204, (P,Q) = (-5.91337e-005,-8.583e-005)
Bus: 3018, (P,Q) = (-1.45001e-005,6.38084e-005)
- If you see PQ which is greater than the load flow tolerance (usually 0.001 pu),
then this loadflow may not be not solved!
Notes:
- You may see a large +ve mismatch and an equally large -ve mismatch
at each end of a branch which has very small impedances (but is not ideal).
- This is because bus angles are usually only available to 6 decimal points in the
.raw file,
so branches entered with very small impedances (but not ideal) can have large
PQ mismatches at each end of the branch (the sum should be within tolerance
however).
- Consider converting these small impedances branches to ideal branches...
Calling Reduce_Y.
Negative R were set to 0 (as per the advanced circuit options specified)...
Calling Generate_Circuit_From_Equivalent.
Calling Reduce_Ykept.
Summary of all Machines read from .dyr transient stability database and
translated into PSCAD:
BusName BasekV Bus # Ckt Machine Exciter
Governor Stabilizer Other
MINE_G 13.8 3011 1 GENROU SEXS
- -
CATDOG_G 13.8 3018 1 GENROU SEXS
- -
The following data was replaced using the Substitution Library: C:\Program Files
(x86)\PSCAD46\master.pslx