CERBO GX Multi RS Solar Array Optional MPPT RS Solar Array

VE.Can to/from MPPT RS

GX TOUCH 50 VE.Can to/from Multi RS

ETHERNET

GX TOUCH 50 HDMI

AC Input Inverting AC Loads


IMPORTANT INFORMATION ! IMPORTANT INFORMATION ! IMPORTANT INFORMATION ! victron energy
VRM
WORLD
0W 425W
Solar array configuration setup info-1 Solar array configuration setup info-2 Solar array configuration setup info-3
The Multi RS Solar contains multiple PV When the RS MPPT switches to float stage it reduces the battery charge current by The Multi RS Solar has a built in AC PV inverter detection system. When feedback is
input connectors. However these are increasing the PV Power Point voltage. The maximum open circuit voltage of the PV detected of AC PV power on the AC-output side, frequency shift will automatically be
internally connected to one single array must be less than 8 times the minimum battery voltage when at float. enabled. While no further configuration is required, it is important that the AC PV inverter
PV-Charger
Maximum Power Point Tracker. For example, where a battery has a float voltage of 54.0 volts as with the batteries is configured correctly to respond to a rising frequency adjustment by reducing its -

75%
+ victron energy

It is recommended that the connected used in this drawing, the maximum open circuit voltage of the connected array cannot output. Be aware of the 1:1 rule of any AC PV inverter size to the Multi RS size, and 1250W

strings are made with the same number exceed 432 volts. Where the array voltage exceeds this parameter the system will give minimum battery sizing applies. More information about these limitations are available in 870W
DC Power
and type of panels. The max operational a "Over-charge Protection" error and shuts down. To correct this, simply reduce the the Victron AC Coupling manual, and this document is required reading if using any AC 51.2V 17A -....W

input current for the MPPT is 18A. PV voltage by removing a panel from the Array string. PV inverter. More info is available in the Multi RS manual and on the website. victron energy

CERBO Power -

The smallBMS is enlarged visible CERBO Power +


VE.Can to/from Multi RS
MPTT RS remote-H/6
POWER + From terminal fuse MPPT RS remote-L/5
smallBMS Bat + MPTT remote-H/6
LOAD DISCONNECT
Load Multi RS remote-H/6
PRE-ALARM +

Multi RS Solar 48/6000


Load ON Pre-alarm
MPPT remote-L/5 VE.Can to/from MPPT RS
These BMS M8 circular connectors are enlarged visible Temp or OVP
Charger CHARGE DISCONNECT Multi RS remote-L/5
MPTT RS remote-H/6
Bat - POWER -

victron energy
BLUE POWER
Remote L
Remote H
ON/OFF SWITCH
ON/OFF SWITCH
60 Volt/16mA
PRE-ALARM BUZZER
From central negative MPPT RS remote-L/5
Opional SmartSolar MPPT RS
All BMS M8 Circular connectors are
daisy chained connected to the BMS !

4 x Lithium 25.6V-200Ah BMS On/Off Switch WARNING !


AC Power from Grid
230V Volt AC GRID Power
Smart LiFePO4
victron energy IMPORTANT INFORMATION !
BLUE POWER
Victron LiFePO4 Smart batteries
When using Victron lithium batteries, the system will need to be
Lithium wired using the allow to charge ATC, and allow to discharge ATD
AC Power from: AC Power from:
25.6V-200Ah contacts from the Victron smallBMS to the I/O connection port of
Output-1 Output-2
Smart LiFePO4 both RS devices. This will also need to be configured to BMS
mode when commissioning the product with VictronConnect.

WARNING ! WARNING !
1 N 1 N
High Voltage DC High Voltage DC
name name
PV PV
name
ADxxxxx xxA/I n0.03A
:hager :hager :hager name
ADxxxxx xxA/I n0.03A
:hager :hager :hager name 0 OFF 0 OFF
BREAKER 0 OFF 0 OFF
BREAKER
Bx
T Bx
T ISOLATOR ISOLATOR
Li-DISTRIBUTION
test regularly test regularly

0 0 OFF 0 OFF 0 OFF 0 0 OFF 0 OFF 0 OFF 0 OFF 0 OFF


MCB MCB
MAIN SWITCH earth fault indicator earth fault indicator

MCB/RCD MCB/RCD MCB


ON
D
TE PV PV

EC
2 N 2 N power power

OT
PR
N
OF F I G N I T I O

I/O-6 Remote-H
I/O-5 Remote-L
OFF

Multi RS Multi RS
HOUSE
AC Out-1 AC Out-2 AC in
G TO

VE.Can
HIN
ve
mo

I TC
Re

SW

R
E

E FO
E B
GIN

I/O-6 Remote-H
S T OP E N

I/O-5 Remote-L
Single Circuit

VE.Can
Drawing BJE-303A
Smart LiFePO4 Switched load-3
BMS 1A fuse
Cerbo 1A fuse
25.6V-200Ah Switched load-2
Lithium Switched load-1
No Break load-3
No Break load-2
BLUE POWER
victron energy No Break load-1
Battery Pre Main Fuses

BF2|58V

BF2|58V
150A

150A
200A

200A
ANL

ANL

5x20

5x20
DIN END STOP

DIN END STOP

FUSE FUSE

WARNING !
230V Volt AC

Multi RS AC IN
victron energy
Main Fuse

BLUE POWER
To/From Cerbo
Terminal
Multi RS

Multi RS AC OUT-2
Din Rail

VE.Can to/from Cerbo

Lithium from smallBMS


fuses

Multi RS remote-H Multi RS AC OUT-1 To/From Cerbo


25.6V-200Ah VE.Can to/from Cerbo
Smart LiFePO4 Multi RS remote-L
from smallBMS FROM PV
Multi RS remote-H
FROM PV BREAKER/ISOLATOR BREAKER/ISOLATOR
Multi RS remote-L

IMPORTANT INFORMATION ! IMPORTANT INFORMATION !


When operating in inverter mode, the Neutral output of a The primary Case ground connection from a inverter
inverter/charger must be connected to ground to guarantee charger like the Multi RS Solar, must be connected to the
proper functioning of a GFCI or RCD device. In case of a Central Negative Busbar of the DC system. Size of this cable
split phase supply the Neutral also must be grounded. must be identical to connected DC negative.

Negative Busbar Multi RS Solar enlarged Multi RS Solar enlarged


Smart LiFePO4
25.6V-200Ah smallBMS-
I/O & Data connections User I/O User I/O functions Multi RS and MPPT RS I/O & Data connections
CERBO-
Lithium I/O Number Connection Description
1 Relay_NO Programmable relay Normally Open connection

7
2 AUX_IN- Common negative for programmable auxiliary inputs
3 AUX_IN1+ Programmable auxiliary input 1 positive connection

8
BLUE POWER
victron energy 4 AUX_IN2+ Programmable auxiliary input 2 positive connection
5 REMOTE_L Remote On/Off connector Low or ATC connection with SmallBMS
VE.Direct VE.Direct

9
6 REMOTE_H Remote On/Off connector High or ATD connection with SmallBMS

10
4
7 RELAY_NC Programmable relay Normally Closed connection
8 RELAY_COM Programmable relay Common negative

11
5
9 TSENSE- Temperature Sensor negative

KEEP NEGATIVE BATTERY CABLES ALL AS SHORT KEEP POSITIVE BATTERY CABLES ALL AS SHORT VE.Can TERMINATOR VE.Can 10 TSENSE+ Temperature Sensor Positive VE.Can TERMINATOR VE.Can

12
6
11 VSENSE- Voltage Sensor negative
AS POSSIBLE AND ALL AT THE SAME LENGTH ! AS POSSIBLE AND ALL AT THE SAME LENGTH ! 12 VSENSE+ Voltage Sensor Positive

To/From Cerbo To/From Cerbo


IMPORTANT INFORMATION ! IMPORTANT INFORMATION ! IMPORTANT INFORMATION ! IMPORTANT INFORMATION ! VE.CAN to/from Cerbo VE.Can VE.CAN to/from Cerbo VE.Can
Recommended AC Out-1 cable/breaker size Multi RS Recommended AC Out-2 cable/breaker size Multi RS Recommended DC cable/fuse size Multi RS Solar Recommended AC IN
cable/breaker size Multi RS Solar
With Power assist the Multi RS Solar can AC Out-2 only is available when power is 0-2 m cable length: 35SQmm, 2-5 m cable length:
add 6KVA to the output load when needed. present on AC IN and AC Out-2 supports up 70SQmm. When used in closed conduits, cable AC IN must be protected by a circuit
Together with the adjustable 32A input this to 32A similar to the maximum connected size should double. Cable length stands for the breaker rated at 32A max or less. This
1

7
all adds up to the max sum of input and AC IN power source as they are internally distance between the batteries and the Multi RS depends heavily on the size of the
output current of 32+26=58A. An Earth connected. An Earth leakage device with connections !!! Recommendations are without connected power source.The input current
2

8
leakage device with breaker or a breaker or a combination MCB/RCD must other loads in the system and these also should be must be adjusted to fit the size of the
3

9
combination MCB/RCD must be installed be installed on the output. Cable size must taken into account for proper main battery, main connected power source. User I/O User I/O
on the output. Cable size must be adjusted be adjusted accordingly. fuse & main switch cables !!! The breaker and cable size for AC IN From SmallBMS From SmallBMS
10

10
4

4
accordingly. Fuse size should be 125-150A. should be adjusted accordingly.
ATC or CHARGE DISCONNECT-L/5 ATC or CHARGE DISCONNECT-L/5
11

11
5

5
ATD or LOAD DISCONNECT-H/6 location: ATD or LOAD DISCONNECT-H/6 location:
12

12
6

6
Bottom left hand side Bottom left hand side