Professional Documents
Culture Documents
ii
CONTENTS
2.1 PVC (Heavy Duty) & XLPE Insulated Electric Cables ........................................................ 3
3.2.2 Take the rating of incoming MCCB of the system duly considering requirement of overload
protection factor. ............................................................................................................ 8
3.2.4 Applying reduction factor due to Thermal resistivity of soil (applicable only for
underground cables). .................................................................................................... 10
3.2.5 Applying reduction factor due to ambient temperature ................................................... 10
3.2.7 Selection of Suitable size of cable after applying all reduction factor. .............................. 11
3.2.8 Check size of cable is suitable for short circuit fault conditions ...................................... 14
3.2.9 Check the voltage drop based on size & length of cable ................................................. 14
4.5 Storage......................................................................................................................... 23
5.3.2 Cable Laid Across Roads, Railway Tracks and Water Pipe Lines. ................................... 26
5.4 Reinstatement............................................................................................................... 27
5.5.3 One example is given below for making straight joint for better understanding ................ 28
5.8.1 Insulation Resistance Test on Newly Installed Cables Before Jointing. ............................ 32
ANNEXURE – I: THICKNESS OF INSULATION FOR PVC & XLPE INSULATED CABLE ........................ 38
ANNEXURE - II : THICKNESS OF INNER SHEATH FOR PVC & XLPE INSULATED CABLE ................... 39
ANNEXURE – III : DIMENSIONS OF ARMOUR – ROUND WIRES AND STRIPS FOR PVC & XLPE
INSULATED CABLE ...................................................................................................... 40
ANNEXURE – IV: THICKNESS OF OUTER SHEATH FOR PVC & XLPE INSULATED CABLE .................. 41
ANNEXURE – VI: RELATIVE MERITS/ DEMERITS OF DIFFERENT METHODS OF CABLE LAYING ....... 43
ANNEXURE - IX: CURRENT CARRYING CAPACITY (IN AMPERES) IN DIFFERENT INSTALLATION .... 62
REFERENCES ...................................................................................................................................... 65
LIST OF FIGURES
LIST OF TABLES
Table 3: Classification of XLPE & PVC insulated cable with improved fire performance ................ 3
Table 9: Application where improved fire performance for XLPE/PVC cable is required. ............... 7
Table 10: 1st Method for accessing the current carrying capacity of the particular cross-section of
the cable .................................................................................................................... 12
Table 11: 2nd Method for accessing the current carrying capacity of the particular cross-section of
the cable .................................................................................................................... 13
Table 13: List of Type Test for XLPE & PVC Cable ...................................................................... 16
Table 14: Additional Type Test for XLPE & PVC Cable with improved fire performance ................ 17
Table 16: Number of Drums to Be Selected For Sampling and Permissible Number of Defectives 19
vi
Table 17: List of Acceptance Test for XLPE & PVC Cable............................................................ 19
Table 18: Additional Acceptance Test for XLPE & PVC Cable with improved fire performance ...... 19
Table 22: Minimum depth of laying from ground surface to the top of the cable .......................... 25
TABLE 24: Correction Factor for Ambient Air Temperatures Other Than 30 °C to be Applied to the
Current-Carrying Capacities for Cables In The Air ........................................................ 52
Table 25: Correction Factors for Ambient Ground Temperatures Other Than 20 °C to be applied to
the Current-Carrying Capacities for Cables in Ducts in the Ground ............................... 53
Table 26: Correction Factors for Cables Buried Direct in the Ground or in Buried Ducts for Soil
Thermal Resistivity Other Than 2.5 K·m/W to be Applied to the Current-Carrying
Capacities for Reference Method D ............................................................................. 53
Table 27: Reduction Factors for One Circuit or One Multi-core Cable or for a Group of more than
One Circuit, or more than one multi-core cable ........................................................... 54
TABLE 28: Reduction Factors for More Than One Circuit, Cables Laid Directly in the Ground –
Installation Method D2 .............................................................................................. 55
TABLE 29: Reduction Factors for More Than One Circuit, Cables Laid in Ducts in the Ground -
Installation Method D1 ................................................................................................ 56
TABLE 30: Reduction Factors for Group of More Than One Multi-Core in Free Air - Method of
Installation E............................................................................................................... 58
TABLE 31: Reduction Factors for Groups of One or More Circuits of Single-Core Cables in Free Air -
Method of Installation F .............................................................................................. 60
The correction slips to be issued in future for this handbook will be numbered as follows:
CAMTECH/EL/2022-23/Vol.5/1.0/Conductor and Cables. # XX date---
Where “XX” is the serial number of the concerned correction slip (starting from 01 onwards).
Sr. No. Date of Issue Page no. & Item no. modified Remarks
viii
DISCLAIMER
It is clarified that the information given in this booklet does not supersede any
existing provisions of Indian Standards (IS) on the subject, related matters,
and other existing provisions laid down by the Railway Board, RDSO. This is
not a statuary document and instructions given are for the purpose of
guidance only. If at any point contradiction is observed, then Indian Standards,
regulations issued by Government bodies, Railway Board/RDSO guidelines
shall be referred.
OBJECTIVE OF PUBLICATION
To prepare guidelines which can educate the Indian Railway (IR) engineers and
technicians dealing with low voltage electrical installations and other IR officials about
various provisions given in IS standards pertaining to IS-1554 (Part-I) – 1988, IS-7098
(Part-I) – 1988, IS-1255 – 1983 & IS-14255 – 1995
जितेंद्र ज िंह आई आर ए एम ई
Jitendra Singh IRSME
प्रधान कार्यकारी जनदे शक
Principal Executive Director
FOREWORD
Our motto of preparing these documents under the series “Safety in Electrical Low
Voltage Installations” is to reduce damaging of equipment /fire cases due to electrical
faults and electrocution on Indian Railways. These publications are based on Indian
standards and codes in simplified and practically implementable manner.
Four volumes i.e. Vol-1: “Basics of LV Earthing System”, Vol-2: “Selection and application
of LV Protective Devices, Vol-3: “Inspection of Electrical LV Installations” and volume-4
on “Testing of Electrical LV Installations” have already been published under this
series.
I am sure that this volume-5 along with earlier volumes will be useful for electrical design
and maintenance engineers and technicians for updating their knowledge, improving the
reliability and safety of electrical LV installations as well as precious human lives. This will
be also helpful in reducing the accidents on account of electrical failures.
x
PREFACE
As per instructions of Railway Board, CAMTECH, Gwalior has done detail study on safety
in low voltage electrical installations by referring various Indian Standards on the subject
and with the help of experts in this domain.
On the basis of various Indian standards, CAMTECH, Gwalior has already prepared &
published four volumes under the series “Safety in Electrical Low Voltage Installations”.
These volumes give basic information about protective earthing, selection and application
of protective devices including inspection & testing of LV installations before being put
into service.
This booklet covers various topics on power cable like classification of power cables, basic
information of PVC & XLPE cable, Selection, Inspection, testing & laying of cables
including faults in cables etc. Basic information of Aerial Bunched (AB) cables & end
termination kit/straight through jointing kit are also cover in this booklet.
Selection of the type and size of cable with factors, which affects the size of the cable,
has been explained properly with suitable examples for better understanding of field staff.
All topics have been explained with photos/tables for better understanding of field staff.
This will help electrical engineers & technicians to understand the basic need & complete
procedure of testing for safe and reliable electrical LV installations.
Technological up-gradation & learning is a continuous process. Please feel free to write
to us for any addition/ modification in this booklet. We shall highly appreciate your
contribution in this direction.
1.1 Introduction
Cables are used for transmission of electrical power. They are mostly used for low voltage distribution
in thickly populated area, in substations from transformers to main distribution panels and from main
distribution panels to different distribution panels. Low voltage cables are also used in industries,
workshops and maintenance shops/ sheds. Medium & high voltage transmission cables are also
used for crossing the roads, railway lines and in densely populated areas in big cities. Cables as
compared to overhead lines have the following advantages.
i. The cable transmission and distribution are not subjected to supply interruptions caused by
lightening or thunderstorms, birds and other severe weather conditions.
ii. It reduces accidents caused by the breaking of the conductors.
iii. Its use does not spoil the beauty of place, cities. But if a fault occurs due to any reason, it is
not easily located.
1.2 Classification of Electrical Cables
Electrical cables may be classified according to their application as follows:
Wiring cables
These cables are used for internal wiring of the buildings and other protected installations and have
two components viz. conductor and insulation. PVC as insulation material and annealed copper
(solid or stranded) as conductor are commonly used for wiring cables. Voltage grade of these cables
is upto 1100 Volts.
Control cables
These are designed for control purposes or measuring circuits for carrying signals of direct current
upto 220 Volts and alternating currents up to 440 volts. These cables are available with armour and
without armour. In these cables PVC, XLPE, EPR, Neoprene etc. are used as insulation. Control cables
are available in 0.5/0.75/1.00/ 1.5/2.5 mm2 size copper conductor (solid/stranded) from 2 cores to
61 cores.
Power Cables
Electrical power cables are used for distribution and transmission of electrical energy. These cables
either single core or multicore are particularly useful in power stations, substations, house service
connections, street lighting, etc. They can be installed indoors or outdoors, in air, in cable ducts or
under ground.
Special Application Cables
Cables are also classified based on special applications such as –
i. Fire performance and heat resistant cables.
ii. Pilot cables.
iii. Instrumentation cables.
iv. Submarine cables & ship board cables.
v. Airport lighting cables.
vi. Mining cables.
vii. Cables for lifts and hoisting gears.
viii. Welding cables.
ix. Cables for hazardous areas such as petro- chemical industries etc.
Medium voltage electrical power cables are usually available in following voltage ratings
Where,
UO = Rated power frequency voltage between conductor and earth or metallic screen.
U = Rated power frequency voltage between phase conductors.
UM = Maximum permissible continuous 3 phase system voltage.
1.3.2 Classification as Per Type of Insulation Used
Electrical power cables are generally classified according to the type of insulation used as given
below:
i. PVC (Poly Vinyl Chloride) cables.
iii. XLPE (Cross Linked Poly Ethylene) cables.
Special category of cables with improved fire performance also comes in PVC & XLPE insulated
cable. Classification of these cables are as below
Table 3: Classification of XLPE & PVC insulated cable with improved fire performance
(Ref: Para 2.2 of IS 7098 (Part-I) – 1988 & IS 1554 (Part-I) – 1988)
C1 FR Flame retardant. Does not propagate fire even when installed in groups in
vertical ducts
C2 FR-LSH Flame retardant cables with reduced Halogen evolution and smoke
2.2.3 Materials
Table 7: Detail of Materials of AB Cables
(Ref: Para 4 & 5 of IS 14255 – 1995)
S.N. Type of Conductor/ Insulation Material
1 Phase/Street Lighting H2 or H4 grade Aluminium conductors conform to
conductor IS:8130(Class-II)
2 Messenger (Neutral Conductor The conductor shall be of heat treated Aluminium -
or Otherwise) magnesium -silicon alloy wires containing approximate
0.5% magnesium and approximately 0.5% silicon
confirming to IS 398 (Part 4) : 1979).
3 Insulation XLPE and HDPE insulation of power conductors specify
IS:7098 (Part – I & II) and IS:6474 respectively
2.2.4 Construction
(Ref: Para 6 of IS 14255 – 1995)
I. The power/outer insulated neutral/street lighting conductors shall conform to flexibility class 2
of IS 8130 : 1984.
II. The messenger (Neutral conductor) or otherwise shall be either stranded circular or compacted
circular type and shall have minimum 7 strands. The surface of the conductor shall be smooth.
III. A protective barrier may be applied between the conductor and insulation, if required. Such
barrier, when used, shall be compatible with insulating material and suitable for the operating
temperature of the cable.
V. There shall be no joints in any wire of the messenger conductor except those made in the base
rod or wires before final drawing. The direction of outer layer of wires in messenger conductor
shall be right hand.
VI. The size of messenger conductor and its breaking load shall be as per Annexure-5
2.2.5 Code Identification
(Ref: Para 8 of IS 14255 – 1995)
The single phase conductor shall be provided with 'One Ridge' and if neutral insulated conductor is
provided shall have 'Four Ridges' as shown in below Figure for quick identification. The Street Light
Conductor & Messenger Conductor (if insulated) shall not have any identification mark
There are two important criteria for selection of power cable in LV installation i.e type & size of power cable.
1 PVC unarmoured single Mainly suitable for indoor conditions where chances of
core and multicore cables external damage is less ex House/Building wiring etc.
2 PVC armoured single core Mainly suitable for installations where rough operation
and multicore cables conditions and tensile stresses are required Generating
stations, substations, distribution systems, street lighting,
industrial installations, etc
Table 9:Application where improved fire performance for XLPE/PVC cable is required.
(Ref: Para 2.2 of IS 7098 (Part-I) – 1988 & IS 1554 (Part-I) – 1988)
a. Normal continuous load – It means that the given load current will be flowing continuously
through cable. Annexures may be referred for current ratings for PVC cables which are based
on the normal conditions of installation. If the actual conditions are not the same as the normal
conditions, the values for the normal current ratings should be multiplied by the relevant rating
factors given in the IS-3961.
b. Intermittent load – If the cable is switched on and off periodically, so that the time between
switching ‘off’ and then ‘on’ is not sufficient to cool the conductor to the ambient temperature
during the rest period, then such load is called intermittent load. A proper cross-section of
cable conductors for such load conditions may be decided in consultation with the cable
manufacturers.
c. Short time load – Under these load conditions, the conductor is allowed to cool down to
ambient temperature after the load period. Here again, the conductor cross-section may be
decided in consultation with the cable manufacturers.
d. Cyclic load – If the load is cycle, the maximum permissible current may be increased by an
amount depending on the shape of the load curve, type of cable, its heat capacity and
method of installation
3.2.1 Procedure for selection of size of cable are as below:-
Take the rating of incoming MCCB of the system duly considering requirement of overload
protection factor.
Identify the Method of Installation of cable
Applying reduction factor due to Thermal resistivity of soil (applicable only for underground
cables).
Applying reduction factor due to ambient temperature
Applying reduction factor due to grouping
Select the suitable size of cable after applying all reduction factor.
Check size of cable is suitable for short circuit fault conditions.
Check the voltage drop based on size & length of cable.
Finally select the optimum size of cable for the installation.
3.2.2 Take the rating of incoming MCCB of the system duly considering requirement of overload
protection factor.
(Ref: Para 4.1.3.6 & 5.2.7 of IS 732:2019)
After deriving the capacity of incoming MCCB (rating of MCCB is selected based on load requirement
of installations). Now apply the overload factor to that rating current which is 1.3 times for normal
MCCB/ACB or as specified by manufacturers. The operating characteristics of a device protecting a
cable against overload shall satisfy the two following conditions:
IB ≤ I n ≤ I Z (Equation 1),
I2 ≤ 1.30x IZ (Equation 2)
Where;
IB The design current for that circuit
IZ The continuous current-carrying capacity of the cable/wire
In The rated current of Protective device
(NOTE: For adjustable protective devices, the rated current In is the current setting selected.
I2 The current ensuring effective operation in the conventional time of the protective device i.e.
1.30x In (As per table 6 of IS 60947 part-2)
Conventional time: -The conventional time is 1 h for circuit-breakers of rated current up to
and including 63 A, and 2 h for circuit-breakers of rated current above 63 A.
A1 A2 B1 B2 C D1 D2
E F G
3.2.4 Applying reduction factor due to Thermal resistivity of soil (applicable only for underground
cables).
The current-carrying capacities tabulated in Table 32 & 33 of ANNEX IX for cables in the ground
relate to a soil thermal resistivity of 2.5 K.m/W. This value is considered necessary as a precaution
for worldwide use when the soil type and geographical location are not specified.
In locations where the effective soil thermal resistivity is higher than 2.5 K.m/W, an appropriate
reduction in current-carrying capacity should be made. Such cases can usually be recognized by
very dry ground conditions. Correction factors for soil thermal resistivity other than 2.5 K.m/W are
given in table 26 of ANNEXURE VIII.
The ambient temperature is the temperature of the surrounding medium when the cable(s) or
insulated conductor(s) under consideration are not loaded. Current carrying capacity of conductor
also depends on the ambient temperature.
While selecting the type of insulation of the conductor for a particular location, it should be ensured
that the ambient temperature in that area under normal operation and fault conditions should not
exceed the limiting temperature of the insulation, which is given Table 8 of IS 732:2019
Where the ambient temperature in the intended location of the insulated conductors or cables differs
from the reference ambient temperature (30 °C for Air & 20 °C for buried in ground), the appropriate
correction factor given in table-24 & 25 of ANNEXURE VIII shall be applied to the values of current-
carrying capacity set out in Table 32 & 33 of ANNEX IX
Ambient temperature for cables should be taken for particular location of the installation not the
ambient temperature of the environment.
The current-carrying capacities given in Table 32 & 33 of ANNEX IX related to single circuits for
single phase/three phase PVC/XLPE conductor in different installation (A1, A2, B1, B2, C, D1, D2, E
& F). Where more insulated conductors or cables, other than bare mineral insulated cables not
exposed to touch, are installed in the same group, the group reduction factors specified in tables 27
to table 31 of ANNEX VIII shall be applied.
For groups containing cables or insulated conductors having different maximum operating
temperatures, the current-carrying capacity of all the cables or insulated conductors in the group
shall be based on the lowest maximum operating temperature of any cable in the group, together with
the appropriate group reduction factor.
If, due to known operating conditions, a cable or insulated conductor is expected to carry a current
not greater than 30 percent of its grouped current-carrying capacity, it may be ignored for the
purpose of obtaining the reduction factor for the rest of the group.
Perforated cable tray Vertical perforated Perforated cable tray Vertical perforated
systems (vertical cable tray systems systems (for vertical cable tray systems
spacing between cable (for horizontal spacing between cable (for horizontal
trays of 300 mm and at spacing between trays of 300 mm and at spacing between
least 20 mm between cable trays of 225 least 20 mm between cable trays of 225
cable trays) mm) cable trays) mm)
3.2.7 Selection of Suitable size of cable after applying all reduction factor.
All above factors (para 3.2.2 to 3.2.6) affect the current carrying capacity of cabling system.
Following two methods are applicable for accessing the current carrying capacity of the particular
cross-section of the cable are as below. Above methods can be explain by taking an example as
given below:
Example: 125 A MCCB is installed for an installation. The outgoing XLPE insulated aluminium cable
is to be installed in underground with soil thermal resistivity of 2.5 K.m/m. Ambient temperature 40°C
is considered and two another cable is also to be installed along at a distance of 0.125m ( cable to
cable clearance) with this cable for other installation. What will be optimum size of cable for the
installation?
Table 10: 1st Method for accessing the current carrying capacity of the particular cross-section of
the cable
12 Checking of size of cable for particular 4 core 240 4 core 240 Sq.mm XLPE
size/core/insulation/installation from Sq.mm XLPE insulated aluminium cable
ANNEXURE IX which has minimum insulated is suitable for D-2
Current carrying capacity given in aluminium Installation as current
S.N.11 (final current after applying all cable carrying capacity is 272
reduction factor) Amp table 33 of
ANNEXURE-IX),which is
more than 254.90 Amp.
Table 11: 2nd Method for accessing the current carrying capacity of the particular cross-section of
the cable
S.N. Procedure/Step Example Remarks
1 Decide type of cabling underground/ duct, Underground Cabling direct in the
shafts, voids, (where cable is to be laying ground
installed)
2 Based on the above installation method D-2 Installation S.N.73 of ANNEXURE VII
identify type of Installation from
ANNEXURE VII
3 Decide type of Insulation of conductor XLPE Type of insulation
PVC / XLPE/ EPR / Mineral as per table 8
4 Decide type of Core 4 Core Type of core
5 Check the rating of MCCB 125 Amp. Capacity of MCCB
6 Deriving the tripping current of MCCB 162.5 Amp. 125x1.3= 162.5
due to overload (Multiply overload factor
of MCCB (1.3) to this rated current)
7 Selecting the size of cable for particular 272 Amp. 4 core 240 Sq.mm XLPE
size/core/insulation/installation from insulated aluminium cable
ANNEXURE IX , which has higher for D-2 Installation is being
(approx. 50 to 70%) Current carrying selected. Current carrying
capacity given above S.N.6 (tripping capacity is 272 Amp (table
current of MCCB due to overload ),as 33 of ANNEXURE-IX),
current carrying capacity will be reduced which is more tha 67.90%
due to reduction factor (as given below) from 162.5 Amp.
8 Applying reduction factor (by current 272x1= 272 Reduction factor=1 for
carrying capacity multiplied by reduction Thermal Resistivity 2.5
factor) for soil thermal resistivity from Km/W from table 26 of
tables 26 of ANNEXURE VIII ANNEXURE VIII
9 Apply ambient temperature reduction 272x1x0.85 Ambient temperature 40°C
factor(by current carrying capacity to be considered.,
multiplied by reduction factor) from Reduction factor 0.85 from
table-24 & 25 of ANNEXURE VIII table 25 of ANNEXURE VIII
10 Apply reduction factor (by current 272x1x0.85x0.75 2 No. circuits with 4 core
carrying capacity multiplied by reduction cable are also laid direct in
factor) depending on the number of the ground (D-2
circuits (grouping) from table-27 to 31 installation). Reduction
of ANNEXURE VIII factor 0.75 (cable to cable
clearance 0.125) from
from table 28 of
ANNEXURE VIII
11 Deriving the final current (calculating 173.40 Amp. 272x1x0.85x0.75=173.40
from S.N.9)
12 Check that Current carrying capacity 4 core 240 173.40 Amp. Is nearest
given in S.N.11 (final current capacity Sq.mm XLPE higher than 162.5 Amp.
after applying all reduction factor) is insulated
nearest higher than S.N.6 (tripping aluminium cable
current of MCCB due to overload ).If not is suitable
than upper size cable to be select
3.2.8 Check size of cable is suitable for short circuit fault conditions
(Ref: Para 4.4.5.5.2 of IS 732:2019)
The selected size of cable should be checked for short circuit withstand capability, the max short
circuit withstand current can be calculated by the formula given below or as given in manufacturers
manual. This current cable should hold without any thermal damage to it until such time the fault can
be removed by the protective device (circuit breaker or fuse).
Any cable’s short circuit withstand current can be calculated using the following formula:
𝑆×𝐾
𝐼=
√𝑡
Where,
I= Short Circuit Current, in Amperes,
t= Duration of Short Circuit, in seconds (This formula is applicable for short circuit duration up
to 5 Sec)
K = Adiabatic Constant (K = 115 for PVC /Copper, K = 143 for XLPE / Copper, K = 76 for
PVC / Aluminium and K = 94 for XLPE / Aluminium)
S= Size of cable in Sq mm.
3.2.9 Check the voltage drop based on size & length of cable
Voltage in an installation should be as per the standard supply voltage with permissible tolerance. To
ensure this, it is important to check that the cumulative voltage drop from the source up to any point
in the installation does not exceed the tolerance permitted. Due to increase length of wire, If value of
Voltage drop exceeds the specified value in the wiring system, then cross-section of the conductors
must be increased.
The percentage voltage drop with respect to the value of the nominal voltage from the source up to
any point in the installation shall not exceed the value given in below table.
Table 12: Voltage Drop
(Para 5.2.8 of IS 732:2019)
Type of Installation Lighting % Other Uses %
1 Low voltage installations supplied directly from a public low 3 5
voltage distribution system
2 Low voltage installation supplied from private LV supply 1 6 8
1
As far as possible, it is recommended that voltage drop within the final circuits do not exceed
those indicated in installation type 1.
When the main wiring systems of the installations are longer than 100 m, these voltage drops may
be increased by 0.005 percent per metre of wiring system beyond 100 m, without this supplement
being greater than 0.5 percent.
Voltage drop is determined from the demand by the current-using equipment, applying diversity
factors where applicable, or from the values of the design current of the circuits.
NOTES
1. A higher voltage drop may be acceptable in the following case:-
– for motor during starting periods,
– for other equipment with high inrush current,
It is also ensured that the voltage variations remain within the limits specified in the relevant
equipment standard.
2. The following temporary conditions are excluded:
– voltage transients;
–voltage variation due to abnormal operation.
3.2.9.2 Calculation of voltage drop
(Ref: Annex Y of IS 732:2019)
After selecting the size of cable voltage drop to be checked for particular length. It shall not
exceed the value given in table-12. Voltage drop chart are generally given by a manufactures in
their manuals further this can also be calculated using the following formula:
Where
u = Voltage drop in V
b = Coefficient equal to 1 for three phase circuit, and to 2 for single phase circuits.
= Resistivity of conductors in normal service, 0.0225 mm2/m for copper and
1
0.036 mm2/m for aluminium
L = The straight length of the wiring systems, in m
S = The cross-sectional area of conductors, in mm2
= The power factor, in the absence of precise details, the power factor is taken as
Cos
equal to 0.8 (sin =0.6)
= The reactance per unit length of conductors
IB = Design current (in amps)
u
The relevant voltage drop in % is equal to : ∆𝑢 = 100 U , Where U0 = Voltage between line &
0
neutral, in V.
After giving order of cable by purchaser the supplier submits the test reports with Material. There are different
classification of Test i.e Type Test, Acceptance Test and Routine test which are done on cables that are
based on Indian Standard IS 7098:1988, IS1540:1988 and 15250 with amendments for XLPE, PVC & AB
Cable respectively.
A. Tests required to be made before supply on a general commercial basis a type of cable in
order to demonstrate satisfactory performance characteristics to meet the intended
application.
B. These tests are of such a nature that after they have been made, they need not be repeated
unless changes are made in the cable materials or design which might change the
performance characteristics.
C. When type tests have been successfully performed on a particular type of cable with a
specific conductor cross-sectional area and rated voltage, type approval shall be accepted
as valid for cables of the same type with other conductor cross sectional areas and/or rated
voltages provided the following two conditions are satisfied:
a. The same material of insulation and manufacturing process are used.
b. The conductor cross-sectional area is not larger than that of the tested cable. Approval
shall be independent of the conductor material.’
Table 13: List of Type Test for XLPE & PVC Cable
(Ref: Para 15.1 of IS 7098 (Part-I) – 1988 & IS 1554 (Part-I) – 1988)
S.N. Name of Test For Test Method Refer Part
Number of IS : 10810
a) Tests on conductor
i) Annealing Test (for Copper) 1
ii) Tensile Test (for Aluminium) 2
iii) Wrapping Test (for Aluminium) 3
iv) Resistance Test 5
b) Test for Armouring Wires/Strips 36 to 42
c) Test for thickness of Insulation & Sheath 6
d) Physical tests for insulation
i) Tensile Strength and elongation at break. 7
The following shall constitute additional type tests for cables with improved fire performance as
per the categories given below:
Table 14: Additional Type Test for XLPE & PVC Cable with improved fire performance
(Ref: Para 15.1 of IS 7098 (Part-I) – 1988 & IS 1554 (Part-I) – 1988)
Category Name of Test For Test Method Refer Part
Number of IS : 10810
01 No additional tests
C1 Oxygen index test 58 (under preparation)
Flame retardance test on single cable 61
Flame retardance test bunched cables 62
Temperature index Under Consideration
C2 Oxygen index test 58 (under preparation)
Flame retardance test on single cable 61
Flame retardance test bunched cables 62
Test for specific optical Under Consideration
density of smoke 63
Smoke density 59
Temperature index Under Consideration
4.1.1.3 Type Test List for AB Cable
Table 15: List of Type Test for AB Cable
4.1.2.1 Definition
These tests are done for the purpose of acceptance of the lot and carried out on samples taken
from that lot. Details of size of sample is given in below table.
Table 16: Number of Drums to Be Selected For Sampling and Permissible Number of Defectives
(Ref: Appendix B of IS 7098 (Part-I) – 1988 & IS 1554 (Part-I) – 1988 & Annex A of 14255 – 1995)
Table 17: List of Acceptance Test for XLPE & PVC Cable
(Ref: Para 15.2 of IS 7098 (Part-I) – 1988 & IS 1554 (Part-I) – 1988)
II. In order to distinguish these electric cables from telephone cables the word ‘electric' shall be
indented, printed or embossed throughout the length of the table
III. The code shall be used for designating the cable as per below table
NOTE - No code letter for conductor is required when the conductor material is copper.
III. A crane should be used for unloading cable drums. When lifting drums with the crane, it is
recommended that the lagging should be kept in place to prevent the flanges from crushing on
to the cable.
IV. If the crane is not available, a ramp should be prepared with approximate inclination of 1:3 or 1:4.
The cable drum should be rolled over the ramp by means of ropes and winches. Additionally a
sand bed at the foot of the ramp may be prepared to brake the rolling the cable drum.
V. Cable should not be dragged along the earth surface.
VI. Cable ends should always be sealed by means of suitable end sealing materials to prevent
moisturisation of cores and armour.
VII. Drums should be rolled in direction of arrow marked on the drum.
4.5 Storage
(Ref: Para 7 of IS: 1255 – 1983)
I. Cables should be stored in a dry covered place to prevent exposure to climatic conditions and
wear and tear of wooden drums
II. It should preferably stored on a concrete surface/firm surface which will not cause the drums to
sink and thus lead to flange rot and extreme difficulty in moving the drums.
III. Whenever the storage time is very long then rotate the drum at 90 degree after every 3 months.
The direction of drum rotation should match the direction of arrow marked on the flat side.
IV. All drums should be stored in such a manner as to leave sufficient space between them for air
circulation.
V. It is desirable for drums to stand on battens placed directly under the flanges.
VI. In no case should the drums be stored, “On the Flat”, i.e., with flange horizontal as shown below.
Note: D is outer diameter of cable. At joints and terminations bending radius for the individual cores
should be above 12 times the diameter over the insulation.
5.3 Methods of Cable Laying & Installation
(Ref: Para 6.1 of IS: 1255 – 1983)
The conventional methods of cable laying and installation are:
Laying direct in ground.
Drawing in ducts.
Laying on racks in air.
Laying on racks inside a cable tunnel.
Laying along buildings or structures.
5.3.1.1 Depth
The desired minimum depth of laying from ground surface to the top of the cable should be as
below
Table 22: Minimum depth of laying from ground surface to the top of the cable
(Ref: Para 6.3.2 of IS: 1255 – 1983)
3.3 KV to 11 kV Voltage rating 0.9m
22 kV, 33 kV Voltage rating 1.05 m
Low voltage and control cables 0.75 m
Cables at road crossings 1.00 m
Cables at railway level crossings 1.0m
(Measured from bottom of sleepers to the top of pipe) 2.0m
5.3.1.2 Clearances
Table 23: Desired Minimum Clearances
(Ref: Para 6.3.3 of IS: 1255 – 1983)
Power cable to power cable Clearance not necessary. However larger the
clearance, better would be current carrying capacity.
Power cable to control cables 0.2m
Power cable to communication cable 0.3m
Power cable to gas/ water main 0.3m
5.3.1.3 Trenching
Following are the known methods of trenching.
i. Manual excavation
ii. Excavation with mechanical force.
iii. Thrust bore
iv. Trench ploughing
Manual excavation method is generally in practice. Trenches shall be excavated according to the
line and level shown on the cable route plan. It possible the cable trench shall be of straight lines.
All curves must be smooth and suitable for laying the cable. The excavated trench sides and trench
floor should be trimmed to remove the sharp projections, if any, which might damage cables.
During excavation take adequate measures to protect all existing structures and existing services
such as electrical cables, telecom cables, gas line, water pipe etc.
There should be sufficient overlap of cables to allow for the removal of cable ends which may have
been damaged. This point is extremely important as otherwise it may result in a short piece of the
cable having to be included. The joint should not be near pipe end or at the bend.
5.3.2 Cable Laid Across Roads, Railway Tracks and Water Pipe Lines.
(Ref: Para 6.3.4 of IS: 1255 – 1983)
Hume pipe/ ‘B’ grade GI pipe of suitable size shall be used where cable cross roads, railway
tracks. Spare ducts for future extensions shall also be provided.
The duct/ pipe joints shall be covered by collars to prevent settlement in between pipes.
The diameter of the cable conduit or pipe/duct shall be at least 1.5 times the outer diameter of
cable. The ducts/pipes shall be mechanically strong to withstand forces due to heavy traffic
when they are laid across the road/ railway tracks.
The cable entry and exit shall be through bell mouth or padding.
The bending radii of steel or plastics ducts shall not be less then 1.5m.
Single core cables shall not be laid individually in steel ducts but instead, all three cables of the
same system shall be laid in one duct.
On bridges, the cables are generally supported on steel cable hooks or clamped on steel supports
at regular intervals. It is advisable that cables laid in bridges are provided with sun shields to protect
the cable from direct heating by sun’s rays.
5.4 Reinstatement
(Ref: Para 11 of IS: 1255 – 1983)
After laying the cable it should be checked again for ensuring that the all cable ends are
undamaged and sealed.
If trench is partially filled with water, cable ends should kept clear off water as far as possible.
If cable has to be cut, reseal both the cable ends immediately. Lead cap for paper cable and
plastic cap for PVC/XLPE cable should be used. As a temporary measure, end can be sealed by
inserting them in an empty tin which is filled with hot bitumen based compound.
Each cable length should be aligned immediately after it is laid starting from one end. When
aligning the cable, it should be ensured that there is no external damage.
If the joints are not to be made immediately after laying the cable, the cable ends should be
covered. The position of cable joint should be marked with markers.
The trench at the duct mouth at road or railway crossing should be deepened to prevent the
stone or the gravel from being drawn into duct and clogging it.
Before the trench is filled in, all joints and cable positions should be carefully plotted.
The requisite protective covering should then be provided, the excavated soil replaced after
removing large stones and well rammed in successive layers of not more than 0.3m in depth.
Where necessary, the trenches should be watered to improve consolidation.
It is advisable to leave a crown of earth not less than 50mm in the center and tapering towards
the sides of the trench to allow for settlement.
After the subsidence has ceased, the trench may be permanently reinstated and the surface
restored to its original conditions.
Cable route markers are to be installed on either sides of the cable trench at every 200m interval
on straight runs, and turning points. Joint markers should be installed at all the four corners of
the joint pit.
5.5 Cable Jointing
(Ref: Para 12 of IS: 1255 – 1983)
Cable joint is a device used to join two or more cables together for extension of lengths or to branch.
These joints are made to perform at the same voltage class and ratings of the intended cables and are
able to withstand the normal and emergency loading conditions. Selection of proper cable accessories,
proper jointing techniques, skill and workmanship is important. The quality of joint should be such that
it does not add any resistance to the circuit. All underground cable joints must be mechanically and
electrically sound and it is protected against moisture and mechanical damage. The joint should further
be resistant to corrosion and chemical effects.
Before jointing is commenced, it is advisable that the insulation resistance of both sections of the
cable to be jointed, be checked by insulation resistance testing instruments like megger.
5.5.3 One example is given below for making straight joint for better understanding
(M-seal tapex type joint for 12 kV to 36 kV XLPE cables)
Cable jointing is basically a technique of rebuilding the cable construction in the same formation as
the original cables to be jointed. Jointing of XLPE power cables is based on following components.
i. Crimping type jointing ferrule.
ii. Self amalgamating insulating tapes.
iii. Self amalgamating semiconducting tapes.
5.6.1 One example is given below for making end termination for better understanding
(M-seal push-on type pre moulded terminations for XLPE/ EPR/ PVC cables upto 36 kV)
M-seal push on type termination kit comprises of intricately engineered and moulded EPDM (Ethylene
Propylene Diene Monomer) rubber components and these are available up to 1000 sq. mm for cables
from 3.3 kV to 22 kV and up to 630sq. mm for cables of 33kV grade.
Now if the termination is to be used for indoor use, provide the cable lug and crimp it using
suitable crimping tool. This completed termination is ready for indoor use as shown in figure
no. 4.
For out door termination, provide rain sheds and top cap. Number of rain sheds vary with
voltage rating of the cables as shown in figure no. 5.
Crimp the cable lug by using suitable crimping tool and provide lug seal. This completed
termination is ready for outdoor use as shown in figure no. 6.
Note : For long feeders, motorized insulation resistance tester should be used.
5.8.2 Tests on Completed Cable Installation
(Ref: Para 14.2 of IS: 1255 – 1983)
The test of completed installation may be measured and entered into record book for comparison
purposes during service life of cable installation and during fault location.
5.8.2.1 Insulation Resistance
Insulation resistance is measured by a suitable bridge. In non-screened cables, the insulation
resistance of each core is measured against all the other cores and armour/metal sheath connected
to earth. With screened construction the insulation resistance of each core is measured against all
the other core and the metal screen connected to earth.
5.8.2.2 Conductor Resistance (dc)
(a) The resistance of conductor is measured by a suitable bridge. For this purpose conductors at
other end are looped together with connecting bond of at least same effective electrical cross-
section as conductor. The contact resistance is kept to a minimum by proper clamped or bolted
connections. With properly installed and jointed cables, values thus measured and corrected
to 20°C, are in general agreement with values given in test certificates.
(b) The measured loop resistance is converted to ohms per km per conductor as:
Rt = R / 2L
Where
R = measured loop resistance in ohms at temperature, t°c;
Rt = measured resistance per conductor at t°C in ohms per km.
L = length of cable (not the loop) in km.
The ambient temperature at the time of measurement to be recorded and the conductor
resistance to be corrected to 20°C by the following formula:
Where
R20 = conductor dc resistance at 20°C in ohm/km,
t = ambient temperature during measurement in °C, and
= temperature coefficient of resistance (3.93 x 10-3 ohms/°C for aluminium).
5.8.2.3 Capacitance
For unscreened cables, capacitance is measured for one conductor against others and metal
sheath/armour connected to earth. In case of screened cable it is measured between conductor and
screen. Capacitance bridge is used for this purpose. This measurement may be carried in case of
cables above 11kV; alternatively values given in test certificate are considered sufficient.
5.8.2.4 High voltage test
Cables after jointing and terminating are subjected to dc high voltage test. The recommended
values of test voltages are given in table. The leakage current shall also be measured and
recorded for future reference.
Generally dc test should be preferred as test equipment required is compact, easily portable
and power requirements are low.
The cable cores must be discharged on completion of dc high voltage test and cable should
be kept earthed until it is put into service.
DC test voltage for old cables is 1.5 times rated voltage or less depending on the age of cables,
repair work or nature of jointing work carried out etc. In any case, the test voltage should not
be less than the rated voltage. Test voltage in these cases should be determined by the
engineer-in-charge of the work.
It may be noted that frequent high voltage tests on cable installations should not be carried out.
This test should be carried only when essential. During the high voltage test, all other electrical
equipment related to the cable installation, such as switches, instrument transformers, bus
bars, etc. must be earthed and adequate clearance should be maintained from the other
equipment and framework to prevent flashovers.
*****
Before starting the testing procedure it may be ensured that the far end of the cable is open and free
from earth connection. In case of testing earth fault the ‘L’ terminal of the meggar is touched with
each conductor(core) of the cable and the ‘E’ terminal is permanently connected with a earth lead.
Meggar indicates zero reading it means the respective conductor(core) is earthed.
6.1.4 Low insulation fault
Sometimes when the cable core insulation material is deteriorated by ageing, moisture, excessive
heating or dirt the insulation resistance is dropped to very low value (several hundred to several kilo
ohms) it is called as low insulation fault.
If the resistance between any two conductors is low, the megger may show reading between several
hundred ohms to Kilo Ohms.
ANNEXURE - II : THICKNESS OF INNER SHEATH FOR PVC & XLPE INSULATED CABLE
All dimensions in millimeters
(Ref:Table-4 of IS 1554 (Part-I) – 1988 & Table 5 of IS 7098 (Part-I) -1988)
Calculated diameter over laid up cores (Ref: IS:10462(Part-I) - 1983 Thickness of inner sheath
(Minimum)
Over Upto and Including
-- 25 0.3
25 35 0.4
35 45 0.5
45 55 0.6
55 -- 0.7
Fictitious calculation method for determination of dimensions of protective coverings of cables: Part I
Elastomeric and thermoplastic insulated cables.
b)-- 13 -- 1.40
13 25 0.8 1.60
25 40 0.8 2.00
40 55 1.4 2.50
55 70 1.4 3.15
70 -- 1.4 4.00
Note: (a) and (b) indicate the methods of practice in the application of armouring.
Fictitious calculation method for determination of dimensions of protective coverings of cables: Part
I Elastomeric and thermoplastic insulated cables.
ANNEXURE – IV: THICKNESS OF OUTER SHEATH FOR PVC & XLPE INSULATED CABLE
[Clauses 14.4.1, 14.4.2 and 15.1 (c)]
(Ref: Table-7 of IS 1554 (Part-I) – 1988 & Table 8 of IS 7098 (Part-I) -1988)
i) 16 25 1.38 7
ii) 25 25 1.38 7
iii) 35 25 1.38 7
v) 70 50 0.689 14
Sr. Subject Direct in Ground Laid in duct Laid on Racks Laid inside
No. in Air Tunnel
1. Application General application Normally for short- In factories, In power
for all site conditions runs across power stations, stations,
and types of railway carriages sub-stations, switching yards,
distribution way, etc. but etc. usually control rooms
extensively used in joints are where a large
American cabling eliminated on number of
practice racks. cables run in
parallel.
2. Preferred type of Armoured having Unarmoured with Armoured or Armoured or
cable finish ordinary/ special or without ordinary unarmoured unarmoured
servings serving
3. Conductor Very good Poor God if Fair if well
economy or sunshields are ventilated
current carrying provided
capacity
4. Initial preparatory Nominal Most significant Significant Most significant
work before laying
5. Initial cost of Comparatively low Higher High Highest
laying
6. Cost of repair and Higher High Fair Low
maintenance
7. Time requirement Significant Most significant Little Little
for locating a fault
8. Cost of cable High Low Lower loest
replacement for
load growth
9. Cost of cable for Least Highest High Low
repairing following
a fault
10. Susceptibility to Considerable Infrequent Little Little
electrolytic/
galvanic corrosion
11. Susceptibility to Little Little Considerable Considerable
cable sheath
failure by inter-
crystaline fatigue
Sr. Subject Direct in Ground Laid in duct Laid on Racks Laid inside
No. in Air Tunnel
12. Susceptibility to Considerable Infrequent Little Negligible
mechanical
damage
13. Damage to Rare Huge Considerable Considerable
adjacent cables
following a fault in
a cable
14. Special Nominal but special a. Care against a. Protection a. Protection to
precautions care may be abrasion during to cable at cable at
necessary required in pulling clamp clamp
b. Proper position position
aggressive site
alignment of b. Insulating b. Insulating the
conditions. duct the cable at cable at
c. Precautions metallic metallic
against clamp clamp
damage to positions positions
cable at duct c. Provision to c. Provision to
entry positions. reduce reduce thrust
d. Provision for thrust at at joints
pumping water joints, if position
from any. d. Provision for
manholes. drafting of
accumulate
water
ventilation
and lighting.
- Run vertically
V 20 De B1
- In a raised floor 5 De V 50 De B1
1. The inner skin of the wall has a thermal conductance of not less than 10 W/m2·K.
2. Values given for installation methods B1 and B2 in Annex S are for a single circuit. Where there is
more than one circuit in the trunking the group reduction factor given in Table 36 is applicable,
irrespective of the presence of an internal barrier or partition.
3. Care shall be taken where the cable runs vertically and ventilation is restricted. The ambient
temperature at the top of the vertical section can be increased considerably. The matter is under
consideration.
4. Values for reference method B2 may be used.
5. The thermal resistivity of the enclosure is assumed to be poor because of the material of
construction and possible air spaces. Where the construction is thermally equivalent to methods
of installation 6 or 7, reference method B1 may be used.
6. The thermal resistivity of the enclosure is assumed to be poor because of the material of
construction and possible air spaces. Where the construction is thermally equivalent to methods
of installation 6, 7, 8, or 9, reference methods B1 or B2 may be used.
7. The factors in Table 36 may also be used.
8. De is the external diameter of a multi-core cable:
— 2.2 x the cable diameter when three single core cables are bound in trefoil, or
—3 x the cable diameter when three single core cables are laid in flat formation.
9. V is the smaller dimension or diameter of a masonry duct or void, or the vertical depth of a
rectangular duct, floor or ceiling void or channel. The depth of the channel is more important than
the width.
10. De is the external diameter of conduit or vertical depth of cable ducting.
11. De is the external diameter of the conduit.
12. For multi-core cable installed in method 55, use current-carrying capacity for reference method
B2.
13. It is recommended that these methods of installation are used only in areas where access is
restricted to authorized persons so that the reduction in current-carrying capacity and the fire
hazard due to the accumulation of debris can be prevented.
14. For cables having conductors not greater than 16 mm2, the current-carrying capacity may be
higher.
15. Thermal resistivity of masonry is not greater than 2 K·m/W, the term “masonry” is taken to include
brickwork, concrete, plaster and the like (other than thermally insulating materials).
16. The inclusion of directly buried cables in this item is satisfactory when the soil thermal resistivity
is of the order of 2.5 K·m/W. For lower soil resistivity, the current-carrying capacity for directly
buried cables is appreciably higher than for cables in ducts.
TABLE 24: Correction Factor for Ambient Air Temperatures Other Than 30 °C to be Applied to the Current-
Carrying Capacities for Cables In The Air
(Ref: Table 33 of IS 732:2019)
Insulation
Ambient (Mineral1)
Temperature PVC XLPE and EPR PVC Covered or Bare not Exposed
°C Bare and Exposed to Touch
to Touch 70 °C 105 °C
(1) (2) (3) (4) (5)
10 1.22 1.15 1.26 1.14
15 1.17 1.12 1.20 1.11
20 1.12 1.08 1.14 1.07
25 1.06 1.04 1.07 1.04
30 1.00 1.00 1.00 1.00
35 0.94 0.96 0.93 0.96
40 0.87 0.91 0.85 0.92
45 0.79 0.87 0.78 0.88
50 0.71 0.82 0.67 0.84
55 0.61 0.76 0.57 0.80
60 0.50 0.71 0.45 0.75
65 – 0.65 – 0.70
70 – 0.58 – 0.65
75 – 0.50 – 0.60
80 – 0.41 – 0.54
85 – – – 0.47
90 – – – 0.40
95 – – – 0.32
1) For higher ambient temperatures, consult the manufacturer
Table 25: Correction Factors for Ambient Ground Temperatures Other Than 20 °C to be applied to the
Current-Carrying Capacities for Cables in Ducts in the Ground
(Ref: Table 34 of IS 732:2019)
Ground Temperature Insulation
°C PVC XLPE and EPR
(1) (2) (3)
10 1.10 1.07
15 1.05 1.04
20 1.00 1.00
25 0.95 0.96
30 0.89 0.93
35 0.84 0.89
40 0.77 0.85
45 0.71 0.80
50 0.63 0.76
55 0.55 0.71
60 0.45 0.65
65 – 0.60
70 – 0.53
75 – 0.46
80 – 0.38
Table 26: Correction Factors for Cables Buried Direct in the Ground or in Buried Ducts for Soil Thermal
Resistivity Other Than 2.5 K·m/W to be Applied to the Current-Carrying Capacities for Reference Method D
(Ref: Table 35 of IS 732:2019)
4 It is assumed that the soil properties are uniform. No allowance had been made for the possibility of
moisture migration which can lead to a region of high thermal resistivity around the cable. If partial
drying out of the soil is foreseen, the permissible current rating should be derived by the methods
specified in IEC 60287 series.
Table 27: Reduction Factors for One Circuit or One Multi-core Cable or for a Group of more than One
Circuit, or more than one multi-core cable
(Ref: Table 36 of IS 732:2019)
Below table to be used with Current-Carrying Capacities of table -32 of annexure-IX
To be Used
Arrangement Number of Circuits or Multi-core Cables with Current-
Item (Cables Carrying
Touching) Capacities,
Reference
1 2 3 4 5 6 7 8 9 12 16 20
1 Bunched in air, on a 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.45 0.41 0.38 Tables 21 to
surface, embedded 32 Methods
or enclosed A to F
2 Single layer on 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
wall, floor or
Tables 21
unperforated cable
to 26
tray systems
No further reduction Method
3 Single layer 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61 factor for more than C
fixed directly nine circuits or
under a wooden multicore cables
ceiling
4 Single layer on a 1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72
perforated
Tables 27 to
horizontal or 32 Methods E
vertical cable tray and F
systems
5 Single layer on 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78
cable ladder
systems or cleats
etc.,
NOTES
1. These factors are applicable to uniform groups of cables, equally loaded.
2. Where horizontal clearances between adjacent cables exceeds twice their overall diameter, no reduction factor need be
applied.
3. The same factors are applied to:
a. groups of two or three single-core cables;
b. multi-core cables.
4. If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits,
and the corresponding factor is applied to the tables for two loaded conductors for the two-core cables, and to the
tables for three loaded conductors for the three-core cables.
5. If a group consists of n single-core cables it may either be considered as n/2 circuits of two loaded conductors or n/3
circuits of three loaded conductors.
6. The values given have been averaged over the range of conductor sizes and types of installation included in Tables 21 to
Table 32 the overall accuracy of tabulated values is within 5 percent.
7. For some installations and for other methods not provided for in the above table, it may be appropriate to use factors
calculated for specific cases, see for example, Table 39 and Table 40.
TABLE 28: Reduction Factors for More Than One Circuit, Cables Laid Directly in the Ground –
Installation Method D2
(Ref: Table 37 of IS 732:2019)
Below table to be used with Current-Carrying Capacities of table-33 of Annexure-IX for Single-Core
or Multi-Core Cables
NOTES
1. Values given apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 Km/W. They
are average values for the range of cable sizes and types quoted for Tables 21 to Table 24. The
process of averaging, together with rounding off, can result in some cases in errors up to 10 %.
(Where more precise values are required they may be calculated by methods given in IEC 60287-2-
1).
2. In case of a thermal resistivity lower than 2.5 Km/W the corrections factors can, in general, be
increased and can be calculated by the methods given in IEC 60287-2-1.
3. If a circuit consists of m parallel conductors per phase, then for determining the reduction factor, this
circuit should be considered as m circuits.
TABLE 29: Reduction Factors for More Than One Circuit, Cables Laid in Ducts in the Ground - Installation
Method D1
(Ref: Table 38 of IS 732:2019)
Below table to be used with Current-Carrying Capacities of table-33 of Annexure-IX for Single-Core
or Multi-Core Cables
b Single-core cables
NOTES
1. Values given apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 K·m/W. They are
average values for the range of cable sizes and types quoted for Table 20 to Table 24. The process of
averaging, together with rounding off, can result in some cases in errors up to 10 percent. Where more
precise values are required they may be calculated by methods given in the IEC 60287series.
2. In case of a thermal resistivity lower than 2.5 K·m/W the corrections factors can, in general, be increased
and can be calculated by the methods given in IEC 60287-2-1.
3. If a circuit consists of n parallel conductors per phase, then for determining the reduction factor this circuit
shall be considered as n circuits.
TABLE 30: Reduction Factors for Group of More Than One Multi-Core in Free Air - Method of Installation E
(Ref: Table 39 of IS 732:2019)
Below reduction factor to be applied to reference Current-Carrying Capacity for multi-core cables in table-
table-32 of Annexure-IX & table 27 to 28 of IS732:2019
Method of Installation as per Number Number of Cables Per Tray or Ladder
Table 19 of IS 732:2019 of Trays
or 1 2 3 4 6 9
Ladders
Vertic
al
perfor 31 1 1.00 0.88 0.82 0.78 0.73 0.72
ated
cable 2 1.00 0.88 0.81 0.76 0.71 0.70
tray
1 1.00 0.91 0.89 0.88 0.87 –
syste
ms
1 2 3 4 6 9
NOTES
1. Values given are averages for the cable types and range of conductor sizes considered in Tables
27 to Table 32. The spread of values is generally less than 5 percent.
2. Factors apply to single layer groups of cables as shown above and do not apply when cables are
installed in more than one layer touching each other. Values for such installations may be
significantly lower and has to be determined by an appropriate method.
3. Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between
cable trays and wall. For closer spacing the factors should be reduced.
4. Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted
back to back. For closer spacing the factors should be reduced.
TABLE 31: Reduction Factors for Groups of One or More Circuits of Single-Core Cables in Free Air - Method
of Installation F
(Ref: Table 40 of IS732:2019)
Below reduction factor to be applied to reference Current-Carrying Capacity for One or More Circuits of
Single-Core Cables in table-32 of Annexure-IX & table 27 to 28 of IS732:2019
Vertical 31
perforated 1 0.96 0.86 – Three cables in
cable tray 2 0.95 0.84 – vertical formation
systems
(Note 4)
Cable ladder 32
systems, 33 1 1.00 0.97 0.96 Three cables in
cleats, etc 34 2 0.98 0.93 0.89 horizontal
(Note 3) 3 0.97 0.90 0.86 formation
Vertical
perforated 31
cable tray 1 1.00 0.91 0.89
systems 2 1.00 0.90 0.86
(Note 4)
Cable ladder
systems, 32
cleats, etc. 33
(Note 3) 34 1 1.00 1.00 1.00
2 0.97 0.95 0.93
3 0.96 0.94 0.90
NOTES
1. Values given are averages for the cable types and range of conductor sizes considered in
Table 27 to Table 32. The spread of values is generally less than 5 percent.
2. Factors are given for single layers of cables (or trefoil groups) as shown in the table and
do not apply when cables are installed in more than one layer touching each other. Values
for such installations may be significantly lower and should be determined by an
appropriate method.
3. Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm
between cable trays and wall. For closer spacing the factors should be reduced.
4. Values are given for horizontal spacing between cable trays of 225 mm with cable trays
mounted back to back. For closer spacing the factors should be reduced.
5. For circuits having more than one cable in parallel per phase, each three phase set of
conductors should be considered as a circuit for the purpose of this table.
6. If a circuit consists of m parallel conductors per phase, then for determining the reduction
factor this circuit should be considered as m circuits.
REFERENCES
1. IS 1554 (Part-I) – 1988 Specification for PVC Insulated (Heavy duty) Electrical cables for working
voltages upto and including 1100 V.
2. IS 7098 (Part-I) – 1988 Specification for Cross Linked Polyethylene Insulated PVC Sheathed Cables
for working voltages upto and including 1100 V
3. IS 1255 – 1983 Code of practice for Installation and Maintenance of Power cables upto and
including 33 kV rating.
4. IS 14255 – 1995 Aerial Bunched Cables-For Working Voltages Upto And Including 1100 Volts –
Specification.
5. IS 8130 : 2013 Conductors For Insulated Electric Cables and Flexible Cords — Specification.
NOTE
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
CONTACT US
CAMTECH is continuing its efforts in the documentation and up-gradation of information on maintenance
practices of electrical assets. Over the years a large number of publications on electrical assets have been
prepared in the form of handbooks, pockets books, pamphlets and video films, etc. These publications have
been uploaded on the internet as well as rail net.
E-mail : direlcamtech@gmail.com