You are on page 1of 4

Sensepoint XCD

Combustible, Toxic and


Oxygen gas detector for
industrial applications
Sensepoint XCD

One-Stop Shop
•C ombustible (catalytic or infrared), toxic Sensepoint XCD provides comprehensive
and Oxygen versions available
• New and retrofit applications monitoring of combustible, toxic and Oxygen
• Suitable for indoor or outdoor use
• Stainless steel or aluminium
gas hazards in potentially explosive
explosion-proof housing options
• IP66 as standard
atmospheres, both indoors and outdoors.
Proven and Reliable Users can modify detector operation using the
Sensor Technology
• SurecellTM electrochemical sensors LCD and magnetic switches without ever


Reflex® sensor health check
Poison immune infrared sensors
needing to open the unit. This enables one-


Poison resistant catalytic bead sensors
Long life sensors
man, non-intrusive operation and reduces
Global Approvals routine maintenance time and costs.
•U  S and Latin America, European,
Canadian and Asian A tri-color backlit LCD clearly indicates the Sensepoint XCD has an integral mounting plate
• Compliant with UL, INMETRO, ATEX, unit’s status at a glance, even from a distance. for surface mounting or can be mounted to a
IECEx, CSA, KTL, PA, GB, and A steady green backlight indicates normal horizontal or vertical pipe using the optional
CCCF standards operation, flashing yellow indicates fault and pipe mounting bracket. Electrical installation
Easy to Use flashing red indicates an alarm. can be made using either conduit or cable
•U  ser friendly and intuitive tri-colour backlit with suitable mechanical protection. Two M20
All detectors include two programmable alarm
display with digits, bar graph and icons or ¾"NPT entries are provided (depending on
relays, one programmable fault relay and an
• Fully configurable via magnetic switches certification). A weatherproof cap is also included
industry standard 4-20mA output (sink or source
• Selectable sink or source 4-20mA output for use in the harshest outdoor conditions. Other
selectable). Modbus comes optional.
• Auto-inhibit during maintenance optional accessories include a sunshade/deluge
• MODBUS communications Sensepoint XCD’s operation can be modified protection, duct mounting kit and collecting cone.
using the transmitter’s LCD and non-intrusive
Cost Effective Sensepoint XCD ensures easy installation and
magnetic switches. Outputs are automatically
• Common transmitter platform the fastest routine operation by removing the
inhibited during adjustment, thereby reducing
• Minimal training required need for hot work permits in hazardous areas.
the risk of false alarm at the control panel during
• Reduced spares Using easy to replace plug-in sensors, downtime
maintenance.
• Non-intrusive, one-man operation is also reduced and ongoing costs are minimized
• Plug-in sensor replacement through the use of poison resistant flammable
Sensepoint XCD’s remote sensing capabilities
• MODBUS multi-drop option offers sensors, poison immune infrared Hydrocarbon
allow the sensor to be mounted up 100 feet
cabling savings sensors and patented Surecell™ toxic sensors
(30m) away from the transmitter in areas that
and Reflex® sensor health check.
Simple Installation are difficult to access. The transmitter can be
•P  lug-in display module removes to mounted at a suitable location away from this
provide access to terminal area area where it is easy to access, view its display
• Integral mounting bracket and interact with via the user interface.
• 2 x M20 or ¾” NPT cable/conduit entries
(certification dependent)
• Removable plug/socket type terminal
blocks for ease of wiring
• Sink/source switch to suit preferred
wiring topology
Range of Optional Accessories
• Remote sensor gassing kit
• Duct mounting kit
• Calibration gas flow housing
• Collecting cone
Sensepoint XCD Overview

Sensepoint XCD Gases and Ranges Sensepoint combustible, toxic and Oxygen
sensors offer a wide variety of gases and
User Selectable Range Class I, Class I, Remote measuring ranges. The sensor can be
Gas
Full Scale Range Increments Division 1 Division 2 Capability
mounted directly to the transmitter or remotely.
Combustible Sensors Sensepoint XCD can be used as a common
Flammable 1 to 8* 20 to 100%LEL 10%LEL P platform for all toxic and Oxygen gas detection,
Methane 20 to 100%LEL 10%LEL P reducing maintenance. The Sensepoint sensor
design includes an IS portion with a removable
Propane 20 to 100%LEL 10%LEL P
sensor cartridge, eliminating the need for a hot
Carbon Dioxide 2%Vol. 0.1%Vol. P work permit when changing the sensor cartridge.
Toxic Sensors The sensor has an IP66 rating for use in the
10 to 100ppm 0.1ppm P harshest conditions. The maximum distance
Hydrogen Sulfide between the transmitter and the remote sensor
50ppm N/A P P
is 100 ft. (30m).
100 to 1,000ppm 100ppm P
Carbon Monoxide
200ppm N/A P P
1,000ppm N/A P
Hydrogen
1,000ppm N/A P P
10 to 50ppm 5ppm P
Nitrogen Dioxide
10ppm N/A P P
Ammonia 50ppm N/A P P
Chlorine 5ppm N/A P P
Sulphur Dioxide 15ppm N/A P P
Nitric Oxide 100ppm N/A P P
Oxygen Sensors
25%V/ V N/A P
Oxygen
25%V/ V N/A P P

Sensepoint XCD Class I, Division 1 Sensepoint XCD Class I, Division 2 Sensepoint XCD Class I, Division 2
with Remote Sensor

Safety at a Glance!
Sensepoint XCD uses three instantly
recognizable ‘traffic light’ colors to indicate
its status. The large tri-color backlit LCD
is steady green to indicate normal operation,
flashes yellow to indicate a fault/warning
and flashes red to indicate an alarm. This
allows anyone in the area to clearly see at a
glance the status of any detector. This can be
particularly useful to identify detector status if
the detector is located in a difficult to access Normal Fault/Warning Alarm
area or if a number of detectors are located in
the same area.
XCD is the right choice for a variety of demanding industrial applications Honeywell Analytics
Building
Specific Area
Gases Present Serves Every Business
Environment (Detected by XCD)
We offer the industry's most complete
• Raw material storage range of gas detection products and
• Ethylene services to meet all customer needs.
• Process Areas • Hydrogen
Chemical • Laboratories • Hydrogen Sulfide
• Pump rows • Methane
Commercial
Plants Gas detection from standalone units to fully
• Compressor stations • Oxygen
• Loading/unloading areas • Propane engineered, multi-point systems, all offering
cost-effective regulatory compliance
• Carbon Dioxide » Applications: parking structures, chillers,
• Exploration drilling rigs • Carbon Monoxide mechanical rooms, office towers,
• Production platforms • Hydrogen commercial buildings, shopping centers,
Oil & Gas • Onshore oil and • Hydrogen Sulfide swimming pools, golf courses, schools
gas terminals • Methane and universities, laboratories
• Refineries • Oxygen
• Propane
Industrial
Renowned Sieger, Zareba and Manning
gas detection systems with advanced
• Around the boiler
electrochemical, infrared and open path
pipework and burners • Carbon Monoxide sensing technologies
Power • Turbines • Hydrogen » Applications: oil and gas, cold storage,
Stations • Coal silos and conveyor • Methane water/wastewater treatment, chemicals,
belt areas in older • Oxygen engine rooms, plastics and fibers,
coal/oil fired stations
agriculture, printing and light industrial

Portables
• Carbon Monoxide Single or multi-gas BW Technologies,
Waste Water • Digesters
• Hydrogen Sulfide Lumidor and other premium detectors with
• Plants sumps
Treatment • Methane compact, lightweight designs ranging from
• H2S scrubbers
Plants • Nitrogen Dioxide simple alarm only units to advanced, fully
• Pumps
• Oxygen configurable and serviceable instruments
» Applications: underground utility and
electricity ducts, boiler rooms, post-fire
sites, sewers, industrial plants, industrial
• Loading and unloading • Carbon Dioxide
hygiene, first esponder teams,
• Carbon Monoxide
Steel Industry • Pre-treatment remote fleets
• Blast furnace • Methane
• Oxygen High Tech/Government
A complete portfolio of gas and chemical
detection instrumentation including infrared
spectroscopy with no cross interference
• Battery rooms • Carbon Monoxide (MST Technologies), to Chemcassette paper-
General • Loading and • Methane based solutions (MDA Scientific) offering
unloading docks
Industry • Oxygen detection down to parts per billion
• Process areas • Propane » Applications: semiconductor manufacturing
• Machinery rooms
and nanotechnology, aerospace propulsion
and safety, specialty chemicals industry,
research laboratories, emergency response

Technical Services
24/7 global network includes post-sales
service and Systems Integration teams
» Emergency call out, service contracts, on/
off-site repair, training and commissioning
» Complete range of spares, consumables
and accessories

Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions.
Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations,
standards, and guidelines. This publication is not intended to form the basis of a contract.

DS01082_v3 12/11
© 2011 Honeywell Analytics

You might also like