Professional Documents
Culture Documents
Lecture –III
Pinch Analysis and Process Integration
▄ Conventional Approach
─ Role of Thermodynamics
▪ Targets can be set for the heat exchanger network to assess the performance of the
complete process design without actually having to carry out the network design.
▪ These targets allow both energy and capital cost for the heat exchanger network to be
assessed.
▪ The targets allow the designer to suggest process changes for the reactor and
separation and recycle systems to improve the targets for energy and capital cost of the
heat exchanger network
• .
• The savings received over the life of the plant by using heat integration are (–
471,000 + 1,636,000) = $1,165,000!
The heat integration saves money in two ways:
(1) The cooling water utility is reduced and the high-pressure steam is eliminated,
(2) Heat exchanger E-203 is smaller because the duty is reduced, and E-202 is also
smaller due to the fact that hps condenses at 254°C
❑ Chemical Process/Plant
❑ Heat Exchanger Network
▪ Steam (Hot Utility) = 1652 + 70 = 1722 kW
▪ Cooling Water (Cold Utility) = 654 kW
▪ Number of Units = 6
Stream information
Heat stream
2. If the hot utility load is increased by any value α, the cold utility is increased by α as well. As
the stream heat loads are constant, this also means that the heat exchanged falls by α.
Add up
Where:
▪ The resulting T/H plot is a single
∆H1 = CPA(T1-T2); ∆H2 = (CPA +CPB+ CPC)(T2-T3); curve representing all the hot
streams, known as the hot
∆H3 = (CPA+CPC)(T3-T4); ∆H4 = (CPA(T4-T5)
composite curve
➢ A similar procedure gives a cold composite curve of all the cold streams in a problem
ΔH=27 MW
ΔH=-30 MW
Feed 2 230ºC
Product 2
Reactor 2
140ºC
200ºC 80ºC
ΔH=32 MW
Off Gas
Feed 1 Reactor 1 40ºC
20ºC 180ºC 250ºC
ΔH=-31.5 MW
composite curve?
Product 1
200 200
PINCH
PINCH
150 150
Cold composite curve Hot composite curve Cold composite curve
Hot composite curve
T, C
T, C
o
o
o
Tmin=10 C Tmin=20 C
o
100 100
50 50
0 0
0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70 80
H, MW H, MW
MW 10= QCmin QRecovery=51.5 QHmin =7.5 MW MW 14= Q QRecovery=47.5 QHmin =11.5 MW
Cmin
o Overlap between the composite curves represents the maximum amount of heat recovery possible
o Overshoot at the bottom represents the minimum amount of external cooling required
o Overshoot at the top represents the minimum amount of external heating required
3. Use the shifted temperatures, which are a mean value; all hot stream
temperatures are reduced by ΔTmin/2 and all cold stream temperatures are
increased by ΔTmin/2.
➢ Approach 3 has been the most commonly adopted, we will follow for
designing of the heat exchanger network
The use of the interval temperature rather than the actual temperatures allows the
minimum temperature difference to be taken into account. ∆Tmin = 10oC for the
problem being considered;
24/02/2022 Lecture on Integrated process Design by Nigus Gabbiyev(PhD) 24
Basic concepts of pinch analysis : The Problem Table
Algorithm
(a) Driving forces not feasible within each interval. (b) Heat transfer within temperature intervals now feasible.
➢ The amount that can be recovered depends on the relative slopes of the
two curves in the temperature interval.
➢ This problem can be overcome if, purely for the purposes of construction, the
hot composite is shifted to be ∆Tmin /2 colder than it is in practice and that the
cold composite is shifted to be ∆ Tmin /2 hotter than it is in practice as shown
in Figure b. The shifted composite curves now touch at the pinch.
3. Carry out a heat balance for the streams falling within each temperature
interval: For the nth interval:
Where:-
137.5 kW
▪ The presence of a negative value in the column indicates that the temperature gradient is in the wrong
direction and that the exchange is not thermodynamically possible.
5. Introduce just enough heat to the top of the cascade to eliminate all the
negative values; see Figure 1b.
QCmin = 10 MW.
▪ Some of the heat flows in Figure(a) are negative, which is infeasible. Heat cannot be
transferred up the temperature scale.
▪ To make the cascade feasible, sufficient heat must be added from hot utility to make the
heat flows to be at least zero. The smallest amount of heat needed from hot utility is the
largest negative heat flow from Figure (a), that is 7.5 MW.
There is an imbalance which must be supplied by utilities – external heating and cooling.
▪ Above the pinch, ΔQC > ΔQH and the difference must be supplied by hot utility.
▪ Below the pinch ΔQH < ΔQC and the excess heat is removed by cold utility.
120 0 85
82.5 140
100
80 145
Pinch T(s) = 850C 20 165
80
60
▪ The Problem Table and its graphical
representation, the GCC, give the same
40
results (including the pinch location) more
20
Cooling duty 60 kW easily.
0
▪ Energy targeting is a powerful design and
0 20 40 60 80 100