Technical data Technical data of the analog inputs
Rated protection fuse on UP 10 A fast Indication of the input signals one LED per channel
- Electrical isolation yes, per module Resolution Range 0...10 V: 12 bits
- Current consumption from UP 0.15 A Range -10...+10 V: 12 bits + sign
at normal operation
Range 0...20 mA: 12 bits
- Inrush current from UP 0.050 A²s
(at power up) Range 4...20 mA: 12 bits
Temperature: 0.1 °C / 0.18 °F
- Connections Terminals 1.8 - 4.8 for +24 V (UP)
and 1.9 - 4.9 for 0 V (ZP) Unused voltage inputs are configured as „unused“
Max. length of analog cables, 100 m / 328 ft. Unused current inputs have a low resistance, can be left
conductor cross section open-circuited
> 0.14 mm² (~26 AWG)
Overvoltage protection yes
Conversion error of the ana- typ. 0.5 %, max. 1 %
log values caused by non-
linearity, adjustment error at Technical data of the analog inputs, if they are
factory and resolution within used as digital inputs
the normal range
Number of channels per max. 16
Width x height x depth 67.5 x 76 x 54 mm / module
(without the Terminal Unit) 2.66 x 2.99 x 2.13 inches
Distribution of channels into 2 groups of 8 channels each
Weight 300 g / 10.52 oz groups
Mounting position horizontal or Connections of the channels Terminals 2.0 to 2.7
vertical with derating (output load I0+ to I7+
reduced to 50 % at 40°C/ 104°F per Connections of the channels Terminals 4.0 to 4.7
group) I8+ to I15+
Cooling The natural convection cooling must Reference potential for the Terminals 1.8 to 4.8 (ZP)
not be hindered by cable ducts or inputs
other parts in the mounting cabinet.
Input signal delay typ. 8 ms
Indication of the input signals one LED per channel
Technical data of the analog inputs
Input signal voltage 24 V DC
Number of channels per 16
module Signal 0 -30 V...+5 V
Distribution of channels into 2 groups of 8 channels each Signal 1 +13 V...+30 V
groups
Connections of the channels Terminals 1.0 to 1.7
I0- to I7-
Connections of the channels Terminals 2.0 to 2.7
I0+ to I7+
3
Analog Input/Output Module AX 722F
Functionality Technical data
AX 722F: unused (default setting) LED displays 19 LEDs for signals and error messages
8 analog inputs,
individually 0...10 V Internal power supply through the expansion bus interface
configurable for (I/O-Bus)
-10 V...+10 V
External power supply via the terminals ZP and UP
0...20 mA (process voltage 24 V DC)
4...20 mA Process voltage
Pt100, -50 °C (-58 °F)...+400 °C (+752 °F) - Rated value 24 V DC
2-wire
- max. ripple 5%
Pt100, -50 °C (-58 °F)...+400 °C (+752 °F)
3-wire, requires 2 channels - Protection against reversed yes
voltage
Pt100, -50 °C (-58 °F)...+70 °C (+158°F)
2-wire - Rated protection fuse on UP 10 A fast
Pt100, -50 °C (-58 °F)...+70 °C (+158°F) - Electrical isolation yes, per module
3-wire, requires 2 channels - Current consumption from UP 0.10 A output loads
Pt1000, -50 °C (-58 °F)...+400 °C (+752 °F) at normal operation
2-wire - Inrush current from UP 0.020 A²s
Pt1000, -50 °C (-58 °F)...+400 °C (+752 °F) (at power up)
3-wire, requires 2 channels - Connections Terminals 1.8 - 4.8 for +24 V (UP)
Ni1000, -50 °C (-58 °F)...+150 °C (+302°F) and 1.9 - 4.9 for 0 V (ZP)
2-wire Max. length of analog cables, 100 m / 328 ft.
Ni1000, -50 °C (-58 °F)...+150 °C (+302°F) conductor cross section
3-wire, requires 2 channels > 0.14 mm² (~26 AWG)
Conversion error of the typ. 0.5 %, max. 1 %
0...10 V with differential inputs, requires 2
analog values caused by
channels
non-linearity, adjustment
-10 V...+10 V with differential inputs, requires error at factory and resolution
2 channels within the normal range
4 analog outputs, unused (default setting) Cooling The natural convection cooling must
individually not be hindered by cable ducts or
configurable for -10 V...+10 V other parts in the mounting cabinet.
4
Technical data of the analog inputs Technical data of the analog outputs
Number of channels per 8 Number of channels 8, all channels for voltage, the first
module per module 4 channels also for current
Distribution of the channels 1 group of 8 channels Distribution of channels 1 group of 8 channels
into groups into groups
Connections of the channels Terminals 1.0 to 1.7 - Channels O0-...O7- Terminals 3.0...3.7
I0- to I7-
- Channels O0+...O7+ Terminals 4.0...4.7
Connections of the channels Terminals 2.0 to 2.7
I0+ to I7+ Output type bipolar with voltage, unipolar with current
Electrical isolation against internal supply and other modules
Electrical isolation against internal supply and other modules
Configurability -10...+10 V, 0...20 mA, 4...20 mA (each
Configurability 0...10 V, -10...+10 V, 0/4...20 mA,
output can be configured individually),
Pt100/1000, Ni1000 (each input can be
current outputs only channels 0...3
configured individually)
Output resistance 0...500 Ω
Channel input resistance Voltage: > 100 kΩ, current: ca. 330 Ω
(load), as current output
Time constant of the input Voltage: 100 µs, current: 100 µs
filter Output loadability, max. ±10 mA
as voltage output
Indication of the input signals one LED per channel
Indication of the output one LED per channel
Conversion cycle 2 ms (for 8 inputs + 8 outputs), with signals
Pt/Ni... 1 s
Resolution 12 bits (+ sign)
Resolution Range 0...10 V: 12 bits
Unused outputs can be left open-circuited
Range -10...+10 V: 12 bits + sign
Range 0...20 mA: 12 bits
Range 4...20 mA: 12 bits
Temperature : 0.1 °C / 0.18 °F
Unused voltage inputs are configured as „unused“
Unused current inputs have a low resistance, can be left
open-circuited
Overvoltage protection yes
5
Digital Input/Output Module DC 732F
Functionality Technical data of the digital inputs
Digital inputs 16 (24 V DC) Number of channels per module 16
Digital inputs/outputs 16 (24 V DC) Distribution of the channels into 1 group of 16 channels
(Configurable) groups
High-speed counter Not Available Terminals of the channels 1.0 to 1.7
I0 to I7
LED displays for signal statuses, errors and
supply voltage Terminals of the channels 2.0 to 2.7
I8 to I15
Internal power supply through the expansion bus interface
(I/O-Bus) Reference potential for all inputs terminals 1.9...4.9 (minus pole of
the process supply voltage, signal
External power supply via the terminals ZP and UP name ZP)
(process voltage 24 V DC)
Electrical isolation from the rest of the module
Technical data (I/O-Bus)
Process supply voltage UP Indication of the input signals one yellow LED per channel, the
LED is ON when the input signal
- Connections Terminals 1.8 - 4.8 for +24 V (UP) is high (signal 1)
and 1.9 - 4.9 for 0 V (ZP)
Input type acc. to EN 61131-2 Type 1
- Rated value 24 V DC
Input delay (0->1 or 1->0) typ. 8 ms, configurable
- max. ripple 5% from 0.1 to 32 ms
- Protection against reversed yes Input signal voltage 24 V DC
voltage
signal 0 -3 V...+5 V
- Rated protection fuse on UP 10 A fast
undefined signal > +5 V...< +15 V
- Electrical isolation yes, per module
signal 1 +15 V...+30 V
Current consumption
Ripple with signal 0 within -3 V...+5 V
- internal (via I/O-Bus) ca. 5 mA at 3.3 V DC
Ripple with signal 1 within +15 V...+30 V
- current consumption from UP 0.05 A + max. 0.008 A per input
at normal operation / with + max. 0.5 A per output Input current per channel
outputs
input voltage +24 V typ. 5 mA
- inrush current from UP 0.007 A²s
(at power up) input voltage +5 V > 1 mA
Max. power dissipation within 6 W (outputs unloaded) input voltage +15 V > 5 mA
the module input voltage +30 V < 8 mA
Width x height x depth 67.5 x 76 x 54 mm / Max. cable length
(without the Terminal Unit) 2.66 x 2.99 x 2.13 inches
shielded 1000 m / 3280 ft.
Weight (without Terminal Unit) Approx. 125 g / 4.41 Oz.
unshielded 600 m / 1968 ft.
Mounting position horizontal
or vertical with derating (output load Technical data of the configurable
reduced to 50 % at 40°C/ 104°F per digital inputs/outputs
group)
Each of the configurable I/O channels can be wired as input or output
Cooling The natural convection cooling must by the user.
not be hindered by cable ducts or
other parts in the mounting cabinet. Number of channels per module 16 inputs/outputs (with transistors)
Distribution of the channels into 1 group of 16 channels
groups
if the channels are used as inputs
- channels I16...I23 terminals 3.0...3.7
- channels I24...I31 terminals 4.0...4.7
6
Technical data of the configurable Technical data of the digital inputs/outputs if used
digital inputs/outputs as outputs
if the channels are used as outputs Overload message (I > 0.7 A) yes, after ca. 100 ms
- channels Q16...Q23 terminals 3.0...3.7 Output current limitation yes, automatic reactivation after
short-circuit/overload
- channels Q24...Q31 terminals 4.0...4.7
Resistance to feedback against yes
Indication of the input/output one yellow LED per channel, the
24V signals
signals LED is ON when the input/output
signal is high (signal 1) Max. cable length
Electrical isolation from the rest of the module shielded 1000 m / 3280 ft.
Technical data of the digital inputs/outputs if used unshielded 600 m / 1968 ft.
as outputs
Number of channels per module max. 16 transistor outputs Technical data of the digital inputs/outputs if used
as inputs
Reference potential for all outputs terminals 1.9...4.9 (minus pole of
the process supply voltage, signal Number of channels per max. 16 digital inputs
name ZP) module
Common power supply for all outputs: terminals 1.8...4.8 Reference potential for all terminals 1.9...4.9 (minus pole of the
voltage (plus pole of the process supply inputs process supply voltage, signal name ZP)
voltage, signal name UP)
Input current, per channel see „Technical Data of Digital inputs“
Output voltage for signal 1 UP -0.8 V
Input type acc. to EN 61131-2 Type 1
Output delay (0->1 or 1->0) on request
Input delay (0->1 or 1->0) typ. 8 ms, configurable from 0.1 to 32 ms
Output current
Input signal voltage 24 V DC
rated value, per channel 500 mA at UP = 24 V
Signal 0 -3 V...+5 V *
maximum value 8A
(all channels together) undefined signal > +5 V...< +15 V
Signal 1 +15 V...+30 V
Leakage current with signal 0 < 0.5 mA
Ripple with signal 0 within -3 V...+5 V *
Rated protection fuse on UP 10 A fast
Ripple with signal 1 within +15 V...+30 V
De-magnitization when inductive with varistors integrated in the
loads are switched off module Max. cable length
Switching frequency shielded 1000 m / 3280 ft.
with resistive load on request unshielded 600 m / 1968 ft.
with inductive loads max. 0.5 Hz * Due to the direct connection to the output, the demagnetizing varistor is also effective at
the input. This is why the difference between UPx and the input signal may not exceed the
with lamp loads max. 11 Hz with max. 5 W clamp voltage of the varistor. The varistor limits the voltage to approx. 36 V. Following this,
the input voltage must range from - 12 V to + 30 V when UPx = 24 V and from - 6 V to + 30 V
Short-circuit proof / overload proof yes when UPx = 30 V.
7
Dummy Coupler Module
TA 724F
Technical data
Use to protect the unused coupler slot from dust and touch
Mounting On CPU Terminal Base TB 711F
Weight 50 g / 1.76 oz.
Dimensions 135 mm x 28 mm x 62 mm / 5.31 x 1.1 x 2.44 inches
Distribution of the channels into 4 groups of 8 channels each - solid 0.08 mm² to 2.5 mm² (28 AWG to 13 AWG)
groups (1.0...1.7, 2.0...2.7, 3.0...3.7,
- flexible 0.08 mm² to 2.5 mm² (28 AWG to 13 AWG)
4.0...4.7), the allocation of the
channels is given by the inserted - with wire-end ferrule 0.25 mm² to 1.5 mm² (23 AWG to 15 AWG)
I/O expansion module
Stripped conductor end 8 mm (0.31 inches)
Rated voltage 24 V DC
Width of the screwdriver 3.5 mm (0.14 inches)
Max. permitted total current 10 A (between the terminals
1.8...4.8 and 1.9...4.9) Fastening torque 0.6 Nm (5.3 Pound Inch)
ABB ABB
Process Automation Division Process Automation Division
Mannheim, Germany Västerås, Sweden
Phone: +49 (0) 1805 266776 Phone: +46 (0) 21 34 20 00
Fax: +49 (0) 1805 776329 Fax: +46 (0) 21 13 78 45
www.abb.de/controlsystems www.abb.com/controlsystems
e-mail: Marketing.Control-Products@de.abb.com e-mail: processautomation@se.abb.com
ABB ABB
Process Automation Division Process Automation Division
Wickliffe, Ohio, USA Singapore
Phone: +1 440 585 8500 Phone: +65 6776 5711
Fax: +1 440 585 8756 Fax: +65 6778 0222
www.abb.com/controlsystems www.abb.com/controlsystems
e-mail: industrialitsolutions@us.abb.com e-mail: processautomation@sg.abb.com
3BDD015167 en 07.2008
© Copyright 2008 ABB. All rights reserved.
The term IndustrialIT and all product names mentioned above in the form xxxxxxIT are registered or requested trademarks of ABB.
Microsoft and Windows are registered trademarks of Microsoft Corp.
Pictures, schematics, and other graphics contained herein are published for illustration purposes only and do not represent product configurations or functionality.
User documentation accompanying the product is the exclusive source for functionality descriptions.