You are on page 1of 1

According to RFP SLD and Tariff Metering Agreement,

there are no specification or requirements for 0.2CL VT


®Êu nèi tíi s©n ph©n phèi 500kV winding. SYMBOL & LEGEND

§­êng d©y trªn kh«ng

2 windings transformer (OLTC) Ampere Meter Distance Relay Neutral Overvoltage Relay
500KV 110V 110V 110V
3 3 3 3
According to Tariff Metering Agreement : 2 windings transformer (OCTC)
Voltage Meter

Active power Meter


Volts per Hertz Relay Voltage Balance Relay

HÖ thèng ®o ®Õm ®iÖn n¨ng chÝnh


HÖ thèng ®o ®Õm ®iÖn n¨ng dù phßng 1
HÖ thèng ®o ®Õm ®iÖn n¨ng chÝnh
+ Number of secondary coils: 02 Circuit Breaker (withdrawable type)
Reactive power Meter
Synchronize checking Relay Buchholz Relay

+ Level each roll accurately: 0.5/3P


CORE-1 Phèi hîp b¶o vÖ
Phèi hîp b¶o vÖ
víi SPP 500kV Active energy Meter Iod Ground Protective Relay
3 Oil Temperature Relay
víi SPP 500kV HÖ thèng ®o ®Õm ®iÖn n¨ng dù phßng 1
CORE-2 Motor

+ Capacity of each roll: 10/50VA


3 Reactive energy Meter Iod 100% Stator Ground Relay
s©n ph©n phèi 500kV tt®l qu¶ng tr¹ch 3 Winding Temperature Relay

3 500KV 110V 110V 110V


FOC-1 nhµ m¸y nhiÖt ®iÖn qu¶ng tr¹ch 1 Ampere Switch Iod 100% Stator Ground Relay
3 3 3 3 Generator Under Voltage Relay
G
I > I> Voltage Switch
I I > I > I> Id>
0.5 10VA Iod 95% Stator Ground Relay
FOC-2 Revese Power Relay
3 I> I > resistance Light
Id> I> I > I > I
Spare 95% Stator Ground Relay
Iod
3 Auto change channel Low Power Relay
Spare Aptomat MCB
Auto Voltage Regulator

According to RFP SLD and Tariff Metering Agreement,


3 Iod Stator winding Relay
Loss Excitation Relay
Spare <
Electro Hydraulic Govenor
Current Transformer (CT)
3 Stator winding Relay
Negative Sequence Current Relay Iod

there are specification or requirements for 0.2CL CT core.


Backup 2A I
Ampere Transfer
TM-5A(6A)
3 CT Bushing
0.5 10VA Wh Rotor Ground Relay
Voltage Transfer Thermal Over Load Relay Iod
VArh
3 Surge Arrester
Active power Transfer Rotor Ground Relay
M¸y biÕn ¸p m¸y ph¸t GT1 Generator Thermal Over Load Relay Iod
HÖ thèng b¶o vÖ m¸y biÕn ¸p m¸y ph¸t sè 2
GENERATOR TRANSFORMER GT1

According to Tariff Metering Agreement : Disconnected Reactive power Transfer


(GT1) NUMERICAL PROTECTION : MAIN-2
BCT-5 I> Instantaneous Overcurrnet Relay I > Ac Directional Overcurrent Relay
Id I > I > HÖ thèng b¶o vÖ m¸y biÕn ¸p m¸y ph¸t sè 1 Frenquency Transfer
3

+ Current transformer ratio : 800-1200-2000/1A


(GT1) NUMERICAL PROTECTION : MAIN-1 Fuse
Power Factory Transfer
BCT-4 I Ground Directional Overcurrent Relay
I > Id I > Neutral Instantaneous Overcurrent
3 I > Connect Point
Bảo vệ so lệch tổng thể
Double Voltage Meter

+ Number of secondary coils : 06


BCT-3
OVERALL DIFF. PROTECTION Liquid Switch
3 Capacitor I > Restart Generator Relay
Double Frequency Meter
I > I > I> I> Id> BCT-2

+ Level each roll accurately: 0.5/0.5/5P20/5P20/5P20


87O Synchronizing Device Alarm Relay
3 Bus duct
BCT-1 Id> I> I> I > I > I> Breaker Failure Relay
3 At relay cubicle in Center Control Room (CCR)
Overhead line Phase Angle Measuring

BCT-7
+ Capacity of each roll : 10/15/30/30/30/30VA withdrawable At Mesurement cubicle in CCR
I> Ac Time Overcurrent Relay

/
Over/Under Frequency Relay

+ Ratio of variables for metering : 1200/1A


1
Voltage Restrained Time Overcurrent
BCT-8 Grounding
1
Pilot-Wire Receiver Relay
Neutral grounding transformer At synchronous table in CCR

+ Accuracy level for backup metering 2: 0.5


BCT-9 Neutral Time Overcurrent
1 I >

BCT-10
1 Differential Protective Relay
At 11kV cubicle in CCR I > Neutral Time Overcurrent for Transformer
Id> a. 87L - Differential Line Protective Relay
a. 87O - Differential Over Protective Relay

Overvoltage Relay
Generator Circuit Breaker
Pressure Protection Switch

Disconnected Neutral Shift of Generator


Oil Flow Protection

Earthing Switch
Winding Temperature Indicator

Timing

Oil Temperature Indicator

Energy Meter
Over fluxing
Wh Tariff Meter for Vietnam Competitive Generator Market (VCGM)
M¸y c¾t ®Çu cùc m¸y ph¸t VArh
Spare TM 13; TM-14; TM-15; TM-16; TM-17; TM-18
GEN. BREAKER CUBICLE core 1 Torsional Stress Relay

3
core 2 0.5 15VA
HÖ thèng r¬le b¶o vÖ sè 1 cho UAT1A HÖ thèng r¬le b¶o vÖ sè 1 cho UAT1B
Wh 22000/1A HÖ thèng r¬le b¶o vÖ sè 2 cho UAT1B
UAT1A NUMERICAL PROTECTION No.1 3 UAT1B NUMERICAL PROTECTION No.1
VArh UAT1B NUMERICAL PROTECTION No.2
core 3
TM-13(16)
core 5 Id> I> I> I > I > 3 core 5 Id> I> I> I > I >
3 I > I > I> I> Id> 3
core 4
3 3
I> I> I > I > TÝn hiÖu ®iÖn ¸p I> I> I > I >
core 4 tõ m¸y biÕn ®iÖn core 4
3 22KV 110V 110V I > I > I> I>
¸p 500kV 3 3 3
HÖ thèng r¬le b¶o vÖ sè 2 cho UAT1A LA
core 1
UAT1A NUMERICAL PROTECTION No.2 I > I > Id I > I > Id
core 3 0.5 50VA core 3
3 3
core 2 Id I > I >
I > I > I> I> Id>
B¶ng hßa ®ång bé
core 2 core 2 3
GEN. SYN. PNL. 57/2
3
I > I > I> I> 0.5 15VA 89 0.5 15VA
core 1 core 1
52G
2000/1A 2000/1A
3 Wh 3 Wh
Id I > I > 57/1
VArh VArh
LA
Tñ biÕn ®iÖn ¸p, CSV
TM-14(17) VT, LA CUBICLE Id> I> I> TM-15(18)

BCT-8 BCT-8
22KV 110V 110V I>
1 Id> I> 1
3 3 3

BCT-9 BCT-9
1 1
BCT-6 22KV 110V 110V BCT-6
3 Tíi hÖ thèng DCS Tíi hÖ thèng DCS 3 3 3 3
22KV 110V
3 3
BCT-7 BCT-7
3 CORE-1 CORE-2 CORE-3 CORE-1 CORE-2 3
M¸y biÕn ¸p
kÝch tõ
BCT-10 EXCITATION BCT-10
3 3
TRANSFORMER

IPBD

1
Tù dïng 11kV tæ m¸y VS V Tù dïng 11kV tæ m¸y
BCT-7
11kV UNIT SWGR. 11kV UNIT SWGR.
1 1 3
1 3 1 3
CORE-1 WT AT AS A VT PROTECTION CORE-1
W Wh BCT-6
MASTER-1 MASTER-2 FOLLOWER
3 3 3

BCT-5
Numerical Multifunction 3 Numerical Multifunction
Relay at 11kV Unit Relay at 11kV Unit
SWGR 1A BCT-4 SWGR 1B
CORE-2 CORE-2
3
3 3
I> I > I> I >
BCT-3
3

CORE-3 BCT-2 Iod


CORE-3
3
3 DC FLASHING 3
BCT-1 MODULE
3
CORE-4 M¸y ph¸t ®iÖn 1 P1 DE-EXCITATION
THYRISTOR CORE-4 3
GENERATOR
3 HÖ thèng kÝch tõ vµ AVR
648MW , 22KV
3phase , 50HZ , 0.85 P.f
G STATIC EXCITATION & AVR

P1
BCT-8
Thanh c¸i 11kV tæ m¸y 1A HÖ thèng b¶o vÖ r¬ le m¸y ph¸t ®iÖn - HÖ thèng A Thanh c¸i 11kV tæ m¸y 1B
3
11kV UNIT 1 SWGR 1A HÖ thèng b¶o vÖ r¬ le m¸y ph¸t ®iÖn - HÖ thèng B GENERATOR NUMERICAL RELAY PROTECTION : MODULE-A 11kV UNIT 1 SWGR 1B
BCT-9
GENERATOR NUMERICAL RELAY PROTECTION : MODULE-B 3

BCT-10
3
I < I > I> Iod
I> I > BCT-11
Iod < I 3 NOTES:
I> Id> 0 FINAL VERSION
BCT-12 This drawing is applied to Unit 1
Id> I> 3 REVISION DESCRIPTION
P2
Iod Lockout relay will be provided to receive signals from digital relays and provide necessary contactor for protection. Lockout relay is manual set up type.

Iod VIETNAM ELECTRICITY


Iod Iod Busing current transformer of generator (BCT-1 to BCT-12) are arrenged at phase and neutral.
U> POWER PROJECTS MANAGEMENT BOARD No.2
Value on CT, Transformer, Meter, Relay... show requirement number.
U> I> I >
POWER ENGINEERING CONSULTING
Generator's charateristic is proposed.
JOINT STOCK COMPANY 3
Voltage value of LV winding GT and HV winding 22kV UAT are proposed. This value will be confirmed with voltage level of generator (by Manufactor).

Charateristics of CT, VT will be confirmed in detail design phase.


QUANG TRACH I THERMAL POWER PLANT PROJECT
Capacity of neutral grouding transformer will be confirmed in detail design phase. ELECTRICAL PART
Considering provide TSR relay to turbine - generator unit to supervising vibration, twist of rotor shaft and emergency stop when low resonator appear.

REQUEST FOR PROPOSAL


DRAWING No. QTI-RFP-EL-005 SCALE -
FOR REFERENCE ONLY
DATE February-2019 SHEET 1/1