INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
TITLE CONTENT
TABLE OF CONTENTS
1. SCOPE
2. APPLIED STANDARDS
3. MATERIAL INSPECTION
4. STRUCTURE
5 ELECTRICAL CHARACTERISTICS
6 MARKING AND PACKING INSPECTION
7 FORM REPORT
Rev.B 03
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
1. SCOPE
This procedure shows the manufacturing standard for the manufacturing of power and
control cable for 500kV AIS.
Cable Types:
Cu/XLPE/PVC/Fr-PVC 0,6/1kV 2X2.5 Sqmm
Cu/XLPE/PVC/Fr-PVC 0,6/1kV (2X2.5+1X2.5) Sqmm
Cu/XLPE/PVC/Fr-PVC 0,6/1kV 2X4 Sqmm
Cu/XLPE/PVC/Fr-PVC 0,6/1kV (2X4+1X4) Sqmm
Cu/XLPE/PVC/Fr-PVC 0,6/1kV 4X2.5 Sqmm
Cu/XLPE/PVC/Fr-PVC 0,6/1kV (4X2.5+1x2.5) Sqmm
Cu/XLPE/PVC/Fr-PVC 0,6/1kV (4X4+1x4) Sqmm
Cu/XLPE/PVC/Fr-PVC-S 0,6/1kV 4X2.5 Sqmm
Cu/XLPE/PVC/Fr-PVC-S 0,6/1kV 4X4 Sqmm
Cu/XLPE/PVC/Fr-PVC-S 0,6/1kV 7X1.5 Sqmm
Cu/XLPE/PVC/Fr-PVC-S 0,6/1kV 19X1.5 Sqmm
Cu/Mica/XLPE/PVC/Fr-PVC-S 0,6/1kV 19X1.5 Sqmm
2. APPLIED STANDARDS
Followings are the applicable codes and standards for the manufacturing works
- Power and Control Cable according to IEC 60228, IEC 60229, IEC 60502-1
or other with similar technical parameters.
Rev.B 04
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Rev.B 05
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
4. STRUCTURE
4.1 Conductor examination
* Test Specitification
- IEC 60228, IEC 60502-1
* Requirements
- According to Spec
* Test Procedure
- Check material conductor
- Measure the diameter of conductor , Number wires
* Test equipment
- Vernier calipers
4.2 Check of dimensions
* Test Specitification
- IEC 60502-1
* Requirements
- According to Spec
* Test Procedure
- Strip the test piece of all layers from completed cable
- Measure the thickness or diameter of belows :
+ Measurement of thickness of inner sheath
+ Measurement of thickness of over sheath
+ Overall dia. Of cable (Approx.)
+ Check cable marking
- Check core identification
* Test equipment
- Micrometer, Vernier calipers, Measuring tape
Rev.B 06
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Rev.B 07
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
5. ELECTRICAL CHARACTERISTICS
5.1 Electrical resistance of conductor
* Test Specitification
- IEC 60228, IEC 60502-1
* Requirements
- According to Spec
* Test Procedure
- Put cable drum in test room
- Measure the conductor resistance at ambient temperature
- Convert the measured value to 20 /km length in accordance with formula given in IEC
60228
* Test equipment
- DC. resistance tester
5.2 Voltage test
* Test Specitification
- IEC 60502-1
* Requirements
- Shall be no breakdown
* Test Procedure
- For single - core cables:
+ Single - core unscreended cables shall be immersed in water at room temperature for 1h
and the test voltage then applied for 5 min between the conductor and the water.
- For multicore cables:
+ For multicore cables with individual screened cores, the test voltage shall be applied for
5 min between each conductor and the metallic layer
+ For multicore cables, without individual screened cores, the test voltage shall be applied
for 5 min in succession between each insulated conductor and all the other conductors and
collective metallic layers, if any.
* Test equipment
- AC. High voltage tester
Rev.B 08
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Rev.B 09
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Rev.B 10
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Project Name: Vung Ang II Thermal Power Plant Project Unit No. :
Results
No Test item Unit Requirement
1-ONE 2-TWO 3-THREE 4-FOUR
Material - Annealed Copper wire
Form - Circular stranded
1 Conductor
Number of wires - 7
Approx. Diameter mm 2.01
Material - XPLE XPLE
Measurements mm -
2 Insulation Thickness Ave. mm 0.7 Ave.: Ave.: Ave.: Ave.:
Min. mm 0.53 Min.: Min.: Min.: Min.:
Color - White
3 Filler and Binder tape - Yes
Material - PVC PVC
Measurements mm -
4 Innersheath Thickness
Min. Ave mm 0.6 Ave.:
Color - Black
Material 1 - Copper tape
5 Metallic screen
Thickness mm Nom. : 0.05
Measurements mm -
6 Outersheath Thickness
Min. mm 1.24 Min.:
Color - Black
□ Satisfactory Prepared by: Reviewed by & Approved by: Witness Review Witness Review
□ Unsatisfactory
Rev.B 11
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Project Name: Vung Ang II Thermal Power Plant Project Unit No. :
2. Customer :
3. Contract No. :
7. Drum no. :
8. Test result :
Test result
No Thickness Width Cross- section Mark length (Lo) Load E/L under load (L1) E/L under load (%) E/L after cooling (L2) E/L after cooling (%)
Sample
(mm) (mm) (mm²) (mm) (g) (mm) (HOT) (mm) (SET)
1 #1
2 #2
9. Verdict :
□ Satisfactory Prepared by: Reviewed by & Approved by: Witness Review Witness Review
□ Unsatisfactory
Rev.B 12
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Rev.B 13
INSPECTION AND TEST PROCEDURE FOR MANUFACTURING OF POWER AND CONTROL CABLE FOR 500kV AIS
VA2-DN04-P0AB-140028
Customer: VAPCO (Vung Ang II Thermal Power Plant LLC) Packing Procedure No.:
PJT Name: VUNG ANG II THERMAL POWER PROJECT Packing list No.:
Description of Goods
PKG Weight (kg) PKG Size (cm) Measure
Package
Package No.: Total Q'ty DESCRIPTION Gross Net
Type Length Width Height -ment (m3)
Weight Weight
Photo 1 Photo 2
Photo 3 Photo 4
Rev.B 14