GEN-SPC-ELC-6320 REV. B
SPECIFICATION FOR ELECTRIC
LOW VOLTAGE CABLES Petro-Energy
AND CABLE GLANDS
DOCUMENT NO : GEN-SPC-ELC-6320 REV. : B PAGE 2 of 7
GEN-SPC-ELC-6320 REV. B
SPECIFICATION FOR ELECTRIC
LOW VOLTAGE CABLES Petro-Energy
AND CABLE GLANDS
DOCUMENT NO : GEN-SPC-ELC-6320 REV. : B PAGE 3 of 7
TABLE OF CONTENTS
1.0 SCOPE..............................................................................................................................4
4.0 GENERAL.........................................................................................................................5
5.0 CONSTRUCTION..............................................................................................................5
GEN-SPC-ELC-6320 REV. B
SPECIFICATION FOR ELECTRIC
LOW VOLTAGE CABLES Petro-Energy
AND CABLE GLANDS
DOCUMENT NO : GEN-SPC-ELC-6320 REV. : B PAGE 4 of 7
1.0 SCOPE
This Specification covers the minimum requirements for the design, manufacturing,
testing and supply of Electric Low Voltage Power Cables, Control Cables and Cable
Glands.
Vendor shall meet or exceed the requirements of the latest edition of the following
codes, regulations and standards, except as superseded herein. In cases where more
than one code, regulation or standard apply to the same condition, the most stringent
shall be followed. In the event of a conflict between this specification and other
specifications or correspondence, the OWNER shall be consulted and a ruling, in writing,
shall be obtained before any work is started.
• IEC 60502 Extruded solid dielectric insulated power cables for rated
voltage from 1kV up to 30kV
• IEC 60811 Common test method for insulating and sheathing materials of
electric and power cables
Any deviation from this specification must be approved, in writing, by OWNER. Such
written approval must be obtained prior to the commencement of any work which would
constitute such a deviation.
GEN-SPC-ELC-6320 REV. B
SPECIFICATION FOR ELECTRIC
LOW VOLTAGE CABLES Petro-Energy
AND CABLE GLANDS
DOCUMENT NO : GEN-SPC-ELC-6320 REV. : B PAGE 5 of 7
For details of environmental data, please refer to the Data Sheet for LV Cables and
Cable Glands.
4.0 GENERAL
All cables shall generally be IEC approved and bear an IEC approved label for the
particular application.
5.0 CONSTRUCTION
Conductor :
Annealed, stranded high conductivity copper, preferably circular in shape with maximum
conductor temperature limited to 900C
Core identification:
GEN-SPC-ELC-6320 REV. B
SPECIFICATION FOR ELECTRIC
LOW VOLTAGE CABLES Petro-Energy
AND CABLE GLANDS
DOCUMENT NO : GEN-SPC-ELC-6320 REV. : B PAGE 6 of 7
Note:
All cables shall confirm to the data sheet for electric low voltage cables. All missing
details and parameters in the data sheet shall be filled by the vendor. The cables shall
be supplied and installed in such a way that:
2) No less than four pieces of tight fitting PVC/Rubber end caps per drum length shall
be provided with each drum for use during the cable cutting / installation.
a) Be of wood or steel provided with wooden batons to protect the cable from
damage.
b) Have either ends of the cable wound on it properly plumbed / sealed with water
proof sealing caps, immediately after the factory tests.
c) Be arranged to take round spindle.
d) Have clear markings on outside faces of both the flanges as follows:
• Ultimate user’s name.
• Project name.
• Purchase order number.
• Year of manufacture.
• Voltage rating.
• Type of cable.
• Number of cores and size.
• Drum length.
• Drum number.
• Drum weight.
• Direction of rotation.
Inspection and testing of the material shall meet the requirements as per the Standards
listed under Item 2.0 of this specification.
GEN-SPC-ELC-6320 REV. B
SPECIFICATION FOR ELECTRIC
LOW VOLTAGE CABLES Petro-Energy
AND CABLE GLANDS
DOCUMENT NO : GEN-SPC-ELC-6320 REV. : B PAGE 7 of 7
This section describes the Vendor Data Requirements applicable to a Vendor's scope.
The Vendor Data Requirements Form is provided as a separate document.
Buyer : CNPCIS
Vendor : Manufacturer/Supplier of the material items.
Contractor : The persons selected by Buyer and Buyer’s Agent to perform
Vendor shall submit, as a condition of this Purchase Order or Contract, all data
requirements specified as following at least:
Each document submitted for review must be clear, legible, complete and properly
identified. Failure to provide adequate documents may result in them being returned
without review at Vendor’s expense. In that event, Vendor will be considered not to
have formerly submitted the documents so returned.
Drawings and data approval does not relieve Vendor of his responsibility to meet
Purchase Order or Contract conditions relating to specifications, material and delivery
requirements, nor relieve Vendor of responsibility for compliance with laws, codes and
regulations.
Vendor shall be responsible for preparing the materials for shipment in accordance with
item 2 above.
Adoption of suitable packing methods and materials is at the sole discretion of the
Vendor, and should any loss, damage and/or deterioration be caused due to improper
packing, the consequences shall be responsibility of the Vendor.
The maximum dimensions of any package should not exceed 4 meters in width, 5
meters in height, and 20 meters in length, and total weight should not exceed 30 tonnes.
The preferred size is 2.74 meters high x 3 meters width x 12 meters long with maximum
weight of 20 tonnes. Packages larger or heavier than this will require approval of the
Purchaser.
GEN-SPC-ELC-6320 REV. B