TECHNICAL DATA SHEET

FIRE ALARM SYSTEM

Project IL& FS PRIME TANK TERMINALS (IPTT)

Client IL& FS PRIME TERMINALS FUJAIRAH (IPTF), UAE


0 28/01/2012 Issued for Tender A.H A.A M.S
Consultant MUC Oil & Gas Engineering Consultancy,FZC
Rev Date Description Prepared Checked Approved
Document No Sheet No.
Project No 110701
110701-INS-DS-09 1 of 2

Fire Alarm Control Panel (FACP)


1 Manufacturer GENT (U.K) / Equivalent
2 Model No. VTA
3 Maximum no. of Loops 4
4 Loop Capacity 200
5 Battery VTA
6 Battery Stand by 24 hrs Stand by + 30 mins alarm upgradable to 72 hrs.
7 Approx. weight VTA
8 Operating Temperature 0-45 Degree C
9 Relevant Standard EN54 Part 2 & 4
10 Cable Entry Top & rear knockins
11 Fire alarm control panel type Analogue Addressable
12 Type of Alarm Audio & Visual Both
13 Location Central Control Room
Fire Alarm Repeaterl Panel (FARP)
14 Manufacturer GENT (U.K) / Equivalent
15 Model No. VIG-RPT/ Equivalent
16 Maximum no. of Loops 4
17 Loop Capacity NA
18 Battery 12V @ 7Ah
19 Battery Stand by 24 hrs Stand by + 30 mins alarm upgradable to 72 hrs.
20 Approx. weight 9 Kgs
21 Operating Temperature 0-45 Degree C
SYSTEM DATA

22 Relevant Standard EN 54
23 Cable Entry Top & rear knockins
24 Location Security Guard room
Manual Call Point (MCP)
25 Manufacturer GENT (U.K) / Equivalent
26 Model No. VTA
27 Maximum no. of Loops 200
28 Operating Temperature -25 to 70
29 Ingress Protection IP55 (with cover & backbox)
30 Relevant Standard EN54 Part 11
31 Approx. weight VTA
32 Device Load Factor 1
Sounder
33 Manufacturer GENT (U.K) / Equivalent
34 Model No. VTA
35 Ingress Protection IP55
36 Approx. weight VTA
37 Operating Temperature -10 to 55 Deg. C
38 Relevant Standard EN54 - 3
39 IR Control Operating Distance 3m
Loop Powered Interface
40 Manufacturer GENT (U.K) / Equivalent
41 Model No. VTA
42 Type 4 Channel Input / Output
43 Approvals EN54 - 17 (2005) & EN54 - 18 (2005)
44 Approx. weight 100g
45 Operating Temperature -10 to 60

46 Manufacturer IDH KILFLAM 1000/ CAVICEL/Equivalent


FIRE ALARM

47 Type 2 Core x 1.5mm2


CABLES

48 Nominal Cable Dia VTA


49 Max. Conductor resistance (Ohm/Km) 12.1
50 Fire resistance IEC 331, BS 6387
51 Flame retardance BS-EN-50265-2-1

1 Factory test certificates shall be provided.


NOTES

2 VTA: Vendor to Advise.


3 Vendor to confirm selection and materials of Instrument.

110701-INS-DS-09, Rev. 0 Jan. 12 Fire Alarm System Page 1 of 2


TECHNICAL DATA SHEET

GAS DETECTION AND ALARM SYSTEM

Project IL& FS PRIME TANK TERMINALS (IPTT)

Client IL& FS PRIME TERMINALS FUJAIRAH (IPTF), UAE

0 28/01/2012 Issued for Tender A.H O.A M.S


Consultant MUC Oil & Gas Engineering Consultancy,FZC
Rev Date Description Prepared Checked Approved
Document No Sheet No.
Project No 110701
110701-INS-DS-09 2 of 2

GAS DETECTION PANEL


1 Application *
2 Manufacturer Honeywell / Equivalent
3 Model No. VTA
4 Mounting Wall mounting
5 Power supply 230 VAC, 1-Phase, UPS power
6 Location Central Control room
7 Battery Stand by 24 hrs Stand by + 30 mins alarm upgradable to 72 hrs.
8 Ingress Protection IP 44
9 Operating Temperature 0-45 Degree C
10 Model No. VTA
SYSTEM PANEL

11 Cable Entry Top & rear knockins


12 No. of Panel 2 Nos.
Comunication to Terminal Central Control
13 system Yes
14 Applicable Standard IEC 60079-29-3
Front Panel & Controls
15 Indication Backlit Display in Both Numeric and Bar Graph
16 Outputs 2 Nos. of Fault alarm relays (potential free contacts)
17 Power Supply VTA
18 Communications RS-485 channel
Input Channels/ Panel
19 No. of channels 4 Channels
20 Display Bargraph & Alphanumeric
21 Inputs 3 Wire , 4-20 mA Transmitters
22 Outputs Potential free alarm contact relays
23 Sensor Tag No. HGD-001 to HGD-008
24 Manufacturer Honeywell/equivalent
25 Model VTA
HYDROCARBON GAS DETECTORS

26 Function Hydrocarbon Gas Detection/toxic gas detection


27 Qty. 8 Nos.(see note-4)
28 Location (see note-4)
29 Maximum Ambient temperature 50 Deg. C
30 Area Classification/ Certificaton IEC Zone-1/ ATEX, IEC Ex
31 Sensor Type VTA
32 Measurement range 0-100%
33 Sensor Enclosure SS 316
34 Accuracy <=+/- 1.5%
35 Response Time <=25 Sec.
36 Transmitter Output 4-20mA
37 Power supply 24VDC, 3-wire
38 Electrical Connection M20 x 1.5 (2 nos.)
39 Ingress Protection IP 66
40 Display LCD
41 Manufacturer -
DETECTION

42 Type 3 Core x 1.5mm2


CABLES

43 Nominal Cable Dia VTA


GAS

44 Max. Conductor resistance (Ohm/Km) 12.1


45 Fire resistance IEC 331, BS 6387
46 Flame retardance BS-EN-50265-2-1
1 Factory test certificates shall be provided.
NOTES

2 VTA: Vendor to Advise.


3 Vendor to confirm selection and materials of Instrument.
4 Exact Location & Quantities Shall be finalize during detailed engineering

110701-INS-DS-09, Rev. 0 Jan. 12 Gas Dectection and Alarm System Page 2 of 2