Professional Documents
Culture Documents
25 Steam system
Document ID WDAAA116787b
Status Approved
Classification Confidential
INSTRUCTIONS
Installation Manual
Table of Contents
WDAAA116787b Confidential i
Installation Manual 25. Steam system
The resultant water hammer can cause severe damage to pipework and fittings. The likelihood
of water hammer occurring increases if the pipework is allowed to sag. This can occur when
pipe hangers fail or when the support is inadequate. There is the same sort of danger when
water is allowed to collect at low points in the pipework.
Fig 25-2 shows an example where the pipework is half flooded. This doubles the steam
velocity in the remaining free area of the pipe. The chance of slugs of water being picked up
to create water hammer conditions is thereby increased. At the same time, the restricted free
area will cause high pressure drops despite correct sizing of the pipework.
● Pipework should be arranged to avoid pockets where water can collect. Fig 25-5 shows
the incorrect use of a concentric reducer that allows condensate to collect. The correctly
installed eccentric reducer ensures that condensate can flow to the next drain point. Similar
problems can occur with some valves and fittings. All steam lines should be connected to
the upper side of the main pipe.
● The strainer shown in Fig 25-6 is a potential cause of water hammer, or of wire drawing of
control valves; also much of the screening area is ineffective because it is out of the steam
flow. Strainers above 25 mm (1") should be fitted on their side to avoid these problems.
Globe valves of under and over construction can also form a weir and prevent condensate
from flowing to the next drain point if they are fitted in the “normal” position in a horizontal
line. Again, this can be avoided by fitting the valves on their side.
NOTE
When installing L-bend and U-bend pipe supports, pay attention to the pipe
movement in the side to side direction.
NOTE
For more details, see the installation instructions WDAAA116756 (Piping/ducting
supports).
NOTE
For information about the expansion allowance for boilers and other equipment,
see the manufacturer’s installation instructions.
NOTE
Refer to chapter 10 “Piping/ducting supports” for more information on Wärtsilä
standard supports for steam piping.