You are on page 1of 55

ENGINEERING

DATA

CONTROLLER &
REMOTE MONITORING SYSTEM
CONTENTS

Sections Page
General Characteristics 2
Hardware Structures 2
General Information for Display 7
LCD Screen Features 8
Touch Screen Features 9
Alarms 10
CGD1: Software Level 1 11
CGD1: Software Level 2 13
PGD TOUCH: Basic Setting 19
PGD TOUCH: Advance Setting 21
Temperature Control 26
Humidity Control 27
Cooling Operation 28
Heating Operation 29
Dehumidification Operation 29
Humidification Operation 30
Combicool Operation 30
Ambicool Operation 30
Heater / Humidifier Interlocks 31
EC Fan 31
Auto Sequencing Management 32
Remote Monitoring System 33
Hardwired Connection 33
Remote Terminal 34
PlantVisor Pro 36
BMS / BAS Connection 38
BMS - Modbus 39
pCOnet 40
LonWorks 40
WebGate 41
pCOWeb 44
BMS ± Variable List 46

1
Genius 5+ is the most advanced Citec programmable controller designed for multiple application in
the fields of precision air-conditioning. It power by a 32bit microprocessor made the processing faster
and smoother ever. The program and the parameters are saved to Flash Memory and EEPROM,
ensuring they are stored even in the event of power failures (without requiring a back up battery). It
UXQV WKH FRQWURO SURJUDP DQG LV ¿WWHG ZLWK D VHW RI WHUPLQDOV UHTXLUHG IRU FRQQHFWLon to devices
(compressor, fans, etc.). This controller allows connection to a network up to 8 units for running in auto
sequencing mode. And it comes with built-in BMS serial ports which allow the controller to
communicate with BMS via Modbus communication protocol over RS485. It also has tKHÀH[LELOLW\LQ
communication with other monitoring systems by additional serial card (Optional).

A. General Descriptions for Genius 5+ Controller:


1 - Power supply 24 V AC
2 - pLAN address button and display, power on LED
3 - pLAN connector
4 - BMS 2 connector (Carel/Modbus RS485)
5 - Fieldbus 2 connector for CYP and other slave device
6 - Connector for uploading software / downloading log and display CGD1
7 - Optional fieldbus card
8 - Optional BMS card

2
B. I/O List for Genius 5+ Controller - Small

(For standard application of Air-cooled, Water-Cooled, Chilled Water, and Dual Chilled Water
Unit)

ANALOGUE INPUTS
Designation Description Type
U1 Control Air Humidity 4-20mA
U2 Pressure 1 0-5 V
U3 Pressure 2 / Water out temperature 0-5 V / NTC
U4 Water In Temperature NTC
U5 Control Air Temperature NTC

DIGITAL INPUTS
Designation Description Type
ID1 Compressor 1 High Pressure Trip 24V AC
ID2 Compressor 2 High Pressure Trip 24V AC
ID3 Water On Floor 24V AC
ID4 Drip Tray Full 24V AC
ID5 Filter Blocked 24V AC
ID6 Heater Overheat 24V AC
ID7 Air Flow Failed 24V AC
ID8 Remote On/Off 24V AC

DIGITAL OUTPUTS
Designation Description Type
NO1 Unit Run N.O.
NO2 Cooling 1 N.O.
NO3 Cooling 2 N.O.
NO4 Damper N.O.
NO5 Heating 1 N.O.
NO6 Heating 2 N.O.
NO7 Maintenance Alarm N.O.
NO8 Critical Alarm Free Contact
Note:
N.O. : Relay Output Normally Open Contact

ANALOGUE OUTPUTS
Designation Description Type
Y1 EC Fan 0-10 V DC
Y2 Cooling 1 / FSC 1 0-10 V DC
Y3 Cooling 2 / FSC 2 0-10 V DC
Y4 Buzzer (DC) 0-10 V DC

3
C. I/O List for Genius 5+ Controller ± Medium

(For standard application of Dual Coil DX+CW Unit)

ANALOGUE INPUTS
Designation Description Type
U1 Control Air Humidity 4-20mA
U2 Pressure 1 0-5 V
U3 Pressure 2 0-5 V
U4 Water In Temperature NTC
U5 Control Air Temperature NTC
U6 Coil Temperature 1 NTC
U7 Coil Temperature 2 NTC
U8 Water Out Temperature NTC

DIGITAL INPUTS
Designation Description Type
ID1 Compressor 1 High Pressure Trip 24V AC
ID2 Compressor 2 High Pressure Trip 24V AC
ID3 Water On Floor 24V AC
ID4 Drip Tray Full 24V AC
ID5 Filter Blocked 24V AC
ID6 Heater Overload 24V AC
ID7 Air Flow Failed 24V AC
ID8 Remote On/Off 24V AC
ID9 Spare 24V AC
ID10 Spare 24V AC
ID11 Spare 24V AC
ID12 Auxiliary Alarm 1 24V AC
ID13 Auxiliary Alarm 2 24V AC
ID14 Auxiliary Alarm 3 24V AC

DIGITAL OUTPUTS
Designation Description Type
NO1 Unit Run N.O.
NO2 Cooling 1 N.O.
NO3 Cooling 2 N.O.
NO4 Damper N.O.
NO5 Heating 1 N.O.
NO6 Heating 2 N.O.
NO7 Maintenance Alarm N.O.
NO8 Critical Alarm Free Contact
NO9 Spare N.O.
NO10 Spare N.O.
NO11 Spare N.O.
NO12 Spare N.O.
NO13 Spare N.O.
Note:
N.O. : Relay Output Normally Open Contact

4
ANALOGUE OUTPUTS
Designation Description Type
Y1 EC Fan 0-10 V DC
Y2 FSC 1 0-10 V DC
Y3 FSC 2 0-10 V DC
Y4 Cooling 1 0-10 V DC

D. I/O List for Genius 5+ Controller ± Medium

(For standard application of Trio Circuit DX System Unit)

ANALOGUE INPUTS
Designation Description Type
U1 Control Air Humidity 4-20mA
U2 Pressure 1 0-5 V
U3 Pressure 2 0-5 V
U4 Spare NTC
U5 Control Air Temperature NTC
U6 Pressure 3 0-5V
U7 Spare NTC
U8 Spare NTC

DIGITAL INPUTS
Designation Description Type
ID1 Compressor 1 High Pressure Trip 24V AC
ID2 Compressor 2 High Pressure Trip 24V AC
ID3 Water On Floor 24V AC
ID4 Drip Tray Full 24V AC
ID5 Filter Blocked 24V AC
ID6 Heater Overload 24V AC
ID7 Air Flow Failed 24V AC
ID8 Remote On/Off 24V AC
ID9 Compressor 3 High Pressure Trip 24V AC
ID10 Spare 24V AC
ID11 Spare 24V AC
ID12 Auxiliary Alarm 1 24V AC
ID13 Auxiliary Alarm 2 24V AC
ID14 Auxiliary Alarm 3 24V AC

5
DIGITAL OUTPUTS
Designation Description Type
NO1 Unit Run N.O.
NO2 Cooling 1 N.O.
NO3 Cooling 2 N.O.
NO4 Damper N.O.
NO5 Heating 1 N.O.
NO6 Heating 2 N.O.
NO7 Maintenance Alarm N.O.
NO8 Critical Alarm Free Contact
NO9 Cooling 3 N.O.
NO10 Spare N.O.
NO11 Spare N.O.
NO12 Spare N.O.
NO13 Spare N.O.

Note:
N.O. : Relay Output Normally Open Contact

ANALOGUE OUTPUTS
Designation Description Type
Y1 EC Fan 0-10 V DC
Y2 FSC 1 0-10 V DC
Y3 FSC 2 0-10 V DC
Y4 FSC 3 0-10 V DC

ADDITIONAL FEATURE OF GENIUS 5+ OVER GENIUS 3


- Display and setting the controller address easier through a segment display and button.(No
software addressing procedure)

6
Description Legend

LCD Display
Alarm Key

PRG key

ESC key

UP key

ENTER key

LCD Display (pGD1) Access Key DOWN key

ON/OFF key

Menu Page

Prev Page

Next Page

Alarm Page

Info Page
Touch Screen Display (pGDTouch)

7
LCD Display comprises:

x Access key with LED backlight.


x Large liquid crystal display, providing icon status of the unit functions, parameter menus,
alarm buffer and access to other controllers via the network system.
x Six access keys, providing access to controller/local network features.
x Mute key for silencing the local audible alarm and resetting the alarm.

LCD Display Icons and Functions

Unit functions are indicated via icons. There are:

UNIT RUN ± shown when unit fan(s) are running.

COOL ± shown when cooling demand is greater than 0%.

HEAT ± shown when heating demand is greater than 0%.

HUMIDIFY ± VKRZQZKHQKXPLGL¿FDWLRQLVLQSURFHVV

DEHUMIDIFY ± VKRZQZKHQGHKXPLGL¿FDWLRQLVLQSURFHVV

ALARM ± shown when an alarm condition is present

The access keys (UP, DOWN, ESC, ENTER, PRG, ALARM) have to be pressed in a coded sequence
in order to enter or change the function currently being accessed.

To turn ON the unit, press ESC key first, then press DOWN key at the main page of display (this
action has to be finished within 2 seconds but not press both keys at the same time)
The ³PRG´NH\ LED shall light up when the unit is turned ON.

The ³$ODUP´NH\ is used for accessing the alarm information. The ³$ODUP´/('VKDOOOLJKWXSDQGalarm
icon will remain on permanently to indicate that an alarm is present. However any subsequent alarms
will re-initiate the alarm.

Current Alarm status caQEHUHYLHZHGE\XVLQJWKH³$ODUP´NH\WRDFFHVVWKH$ODUP%XIIHUIURPWKH


display.

8
Touch Screen Display (pGDTouch) comprises:

x High Resolution Graphical Display, providing icon status of the unit functions, parameter
menus, alarm buffer and access to other controllers via the network system.
x Multi User Level Password protection.
x Featuring animated graphical, multi-language, pop up alarm event, on screen keyboard, etc.
x Trend graph for return air temperature and humidity (standard), water in and water out (option).
Trend graph data can be stored in controller up to 3 months at 5 minutes interval.
x Info page enable you to access to distributor¶V information and emergency call number.

Touch Screen Display (pGDTouch) Icons and Functions

Unit Functions are indicated via icons. There are:

UNIT RUN ± shown when Unit fan(s) are running.

COOL ± shown when cooling demand is greater than 0%.

HEAT ± shown when heating demand is greater than 0%.

HUMIDIFY ± VKRZQZKHQKXPLGL¿FDWLRQLVLQSURFHVV

DEHUMIDIFY ± VKRZQZKHQGHKXPLGL¿FDWLRQLVLQSURFHVV

ALARM ± shown when an alarm condition is present.

7KH ³212))´ icon of the local unit control is located at the left bottom of the touch screen display.
7KHJUDSKLFDOLFRQRIWKH³212))´VKDOOFKDQJHWKHFRORUWRJUHHQZKHQWKHXQLWWXUQHG21DQGLW
shall change to orange when unit suspended and it shall be black when unit turned OFF.

1H[WWRWKLVLVWKH³0(18´icon for accessing configuration, setting, user login, check history alarm of
the unit. The up and down icon is to scroll between the pages for more information of the unit for
example unit status, compressor status, humidifier status, EEV status, CW valve status, trend graph
and etc.

7KH³DODUP´icon is for accessing the alarm page when there are alarms occurring. The alarm icon will
remain on permanently to indicate that an alarm condition is not yet reset. In order to reset the alarm, it
must be acknowledged before it can be reset.

7KH ³LQIR´ LFRQ DW WKH ULJKW ERWWRP RI WKH WRXFK VFUHHQ GLVSOD\ LV XVHG WR DFFHVV WKH LQIR SDJH IRU
GLVWULEXWRU¶VLQIRUPDWLRQDQGHPHUJHQF\FDOOQXPEHU

9
Alarms at LCD Display:

Occurrence of alarms shall energize red LED indicator on dispOD\3UHVVWKH³$ODUP´NH\VKDOOGLVSOD\


any active alarms. To reset an alarm when viewinJDFWLYHDODUPVSUHVVWKH³$ODUP´NH\ $ODUPWH[W
messages are held within an alarm buffer, which is capable of holding 100 possible alarms complete
with time and date of the alarm generated in sequence they occurred. The 101st alarm shall replace
the 1st alarm data.

Alarm at Touch Screen Display:

Occurrence of alarms shall energize a pop up alarm page RQ GLVSOD\ 3UHVV WKH ³Alarm´ icon shall
display any active alarms. To reset an alarm when viewing active alarms, select the alarm you want to
reset and press the ³5(6(7´ LFRQ WR UHVHW EXW EHIRUH WKH DODUP WR EH UHVHW ³ACK´ icon have to be
press to acknowledge the alarm. 7KH ³6HOHFW $OO´ LFRQ FDQ EH XVHG WR VHOHFW DOO WKH DFWLYH DODUP
instead of selecting it one by one. Alarm text messages are held within an alarm buffer, which is
capable of displaying all the alarms happened in 4 weeks complete with time and date of the alarm
generated and acknowledge and reset in sequence.

Alarms List:

High Return Air Temperature


High Return Air Humidity
Low Return Air Temperature
Low Return Air Humidity
Air Flow Failure
Heater Overheat
Compressor 1 LP
Compressor 2 HP
Compressor 1 LP
Compressor 2 HP
Filter Blocked
Water on Floor
Drip Tray Full
LAN Disconnected (when auto sequence is enabled)
Water in High Temperature (when water in temp. enabled)
Unit Run Expired
Unit Health Check
+XPLGL¿HU$ODUPV+LJK&XUUHQW$ODUP F\OLQGHURII 
Low Current Alarm (cylinder off)
Lack Water Alarm (cylinder off)
+LJK&RQGXFWLYLW\$ODUP RIIKXPLGL¿HU 
High Conductivity Warning
Low Production Alarm (cylinder off)
Drain Alarm (cylinder off)
Warning Pre-exhaustion Cylinder
Warning Foam Presence
Warning Cylinder Exhaustion

Remark:
The above table shows the available alarms that can be displayed provided the applicable function is
selected and the hardware is installed.

10
CGD1: SOFTWARE LEVEL 1

Function Application Min. Inc./Dec. Max. Default


Set Point
o o o o
Temperature Set Point All Units 5.0 C 0.1 C 40.0 C 21.0 C
Humidity Set Point All Units 10.0% 0.1% 90.0% 50.0%
o o o o
Water In Temperature Water cooled & Chilled 0C 0.1 C 40.0 C 9.0 C
Alarm Limit Water Unit Only
Time Control
On Time / Off Time:
Monday All Units 00:00 1 23:59 00:00
Tuesday (when weekly time zone 00:00 1 23:59 00:00
Wednesday with on/off unity enabled) 00:00 1 23:59 00:00
Thursday - two time zones per day 00:00 1 23:59 00:00
Friday 00:00 1 23:59 00:00
Saturday 00:00 1 23:59 00:00
Sunday 00:00 1 23:59 00:00
Set Clock
Enter Hour All Units 0 1 23
Enter Minutes (when clock board 0 1 59
Enter Day enable) 1 1 31
Enter Month 1 1 12
Enter Year 0 1 99
Select Language
Select Language All Units Option: English English
Chinese
Software Version
Software Version All Units Displayed Installed Software Version
Remote On Off
Remote On Off Enabled All Units Yes / No No
BMS Setup
BMS 1 Setup BMS Card Option Option: Citec Citec
Modbus
LonWorks
Baud rate Option: 1200 9600 19200
2400 19200
4800
Unit Idendity 1 1 200 1
BMS 2 Setup Built in All Units Option: Citec Citec
Modbus
Baud rate Option: 1200 9600 19200
2400 19200
4800
Unit Idendity 1 1 200 1

11
CGD1: SOFTWARE LEVEL 1

Function Application Min. Inc./Dec. Max. Default


Set New Password
Enter New Password All Units (4 digits p/w) 0 1 9999 0000
Manual Drain
Manual Drain With Humidifier Option Yes / No No
Rotation Configuration
Rotation Type (when pLAN is setup) Option: Automatic Rotation Automatic
Timezones Rotation Rotation
Manual Rotation
Standby units auto. rotation/timezones 0 1 7 0
Rotation Hour (for automatic rotation) 0h 1h 240h 0h
Rotaion Time (for timezones rotation) 00:00 1 23:59 00:00
Days 1 1 7 1
Weekly Monday Mon - Sun Sunday Monday

12
CGD1: SOFTWARE LEVEL 2

Function Application Min. Inc./Dec. Max. Default


EEV Control - EVD Parameters
Refrigerant DX System Only Option: R22 R22
R134a
R404a
R407c
R410a
R507c
Super Heat Set Point:
o o o o
- Cooling Mode 2.0 C 0.1 C 50.0 C 6.0 C
o o o o
- Dehum. Mode 2.0 C 0.1 C 50.0 C 12.0 C
Enable EEV Display Yes / No No
Proportional Gain 0 0.1 99.9 10.0
Integral Time 0s 1s 999s 100s
Derivative Time 0 0.1 99.9 2.0s
o o o o
Dead Zone 0C 0.1 C 9.9 C 0C
Circuit / EEV Ratio 0% 1% 100% 60%
EEV Control - Manual Management
EEV Mode DX System Only Auto / Manual. Auto.
Requested Steps 0 1 480 0
EEV Control - Calibration
S1 DX System Only -140psig 1psig 140psig 1psig
o o o o
S3 -9.9 C 0.1 C 9.9 C 0C
Cool Control
o o o o
Proportional Band Cooling 0C 0.1 C 9.9 C 2.0 C
o o o o
Dead Zone 0C 0.1 C 9.9 C 0C
Valve Open Interval Combi Cool with 2-way
0s 1s 9999s 600s
(DX Mode) Valve fitted
Valve Open Duration
0s 1s 9999s 60s
(DX Mode)
Valve Open Setting
0% 0.1% 100.0% 50.0%
(DX Mode)
Water In High Temp. Enabled
0% 0.1% 100.0% 30.0%
(Valve Open) (CW Mode)
Alarm Delay Time (CW Mode) 0s 1s 9999s 15s
Combi Cool Change Over By
Combi Cool Disabled / Enabled Disabled
Aux. Alarm 1 (Option)
Heat Control
o o o o
Proportional Band Electric Heating 0C 0.1 C 9.9 C 2.0 C
o o o o
Dead Zone 0C 0.1 C 9.9 C 1.0 C

13
CGD1: SOFTWARE LEVEL 2

Function Application Min. Inc./Dec. Max. Default


Dehum Control
Proportional Band Dehumidifying 0% 0.1% 10.0% 2.0%
Dead Zone 0% 0.1% 10.0% 2.0%
% of Cooling to Enable CW System Only
Dehum 0% 0.1% 80.0% 50.0%
% of Valve Opening
When Dehum 10.0% 0.1% 100.0% 70.0%
Humidity Control
Proportional Band Humidification 0% 0.1% 15.0% 2.0%
Dead Zone 0% 0.1% 15.0% 2.0%
Manual Drain Yes / No No
Periodic Flushing Yes / No No
Flush Period 1h 1h 120h 24h
Inactivity Drain Yes / No No
Inactivity Drain 1d 1d 199d 3d (days)
Maximum Production 0% 1% 100% 100%
Hum./Heat Interlock Humidification and Option: Hum and Heat Hum. and
Heating Hum. prevents Heat Heat
Heat prevents Hum.
Alarm Band
o o o o
High Temperature All Units 1.0 C 0.1 C 10.0 C 4.0 C
o o o o
Low Temperature 1.0 C 0.1 C 10.0 C 4.0 C
High Humidity 1.0% 0.1% 30.0% 10.0%
Low Humidity 1.0% 0.1% 30.0% 10.0%
Alarm Sensitivity 1.0% 0.1% 100.0% 100.0%
Control Type
Control Type All Units P / P+I / P+I+D P+I
Stage Delay 0s 1s 99s 20s
Integral Time 0s 1s 999s 600s
Derivative Time 0s 1s 999s 300s
Start Mode After Power
Auto / Manual Auto
Restore:
Unit Configuration
U1 All Units Option: Present/Rotation P/No Rot.
U2 (for pLAN setup) Present/ No Rotation Absent
U3 Absent Absent
U4 Absent
U5 Absent
U6 Absent
U7 Absent
U8 Absent

14
CGD1: SOFTWARE LEVEL 2

Function Application Min. Inc./Dec. Max. Default


Water Temperature
Water In Enabled 'W' & 'CW' option Yes / No No
Water Out Enabled If sensors fitted Yes / No No
FSC
Pressure Probe Type 'A' with FSC option 4-20mA / 0-5V 0-5V
FSC Low Speed Mode Cut Off / Min. Speed Cut Off
Discharge Press. 1 Offset -20psi 0.1psi 20psi 0
Discharge Press. 2 Offset -20psi 0.1psi 20psi 0
Discharge Press. 3 Offset -20psi 0.1psi 20psi 0
Pre Alarm Setpoint 200psi 1psi 400psi 320psi
Alarm Setpoint 200psi 1psi 400psi 350psi
Minimum Pressure 0psi 1psi 999psi 200psi
Average Pressure 0psi 1psi 999psi 230psi
Proportional Band 0psi 1psi 999psi 75psi
Integral Time 0s 1s 999s 600s
Derivative Time 0s 1s 999s 5s
Stage Delay 0s 1s 99s 10s
Min. Speed Vdc 0V 0.1V 10.0V 3.0V
Max. Vdc 0V 0.1V 10.0V 10.0V
Dehum On Off
Dehum Enabled All Units Yes / No Yes
Dehum Intlk With RAT Yes / No Yes
Alarm Setup
Stop Unit When Water On
Floor Alarm If sensor tape is fitted Yes / No No
Stop Unit When Drip
Tray Full If tray sensor is fitted Yes / No No
Unit Off Alarm Enabled All Units Yes / No No
Sensor Fail Enabled All Units Yes / No Yes
Comp. LP Cut Out DX System Only 0psig 1psig 99psig 25psig
Comp. LP Cut In 0psig 1psig 99psig 60psig

15
CGD1: SOFTWARE LEVEL 2

Function Application Min. Inc./Dec. Max. Default


Alarm Setup
Aux. Alarm Setting
All Units Contact: N.O. / N.C. N.O.
Aux. Alarm 1
Aux. Alarm 2
Action: Indication / Off Unit Indication
Aux. Alarm 3
Alarm Log Setting All Units
Unit Start Disabled / Enabled Disabled
Unit Stop Disabled / Enabled Disabled
Power Failure Disabled / Enabled Disabled
Power Restore Disabled / Enabled Disabled
Alarm Acknowledge Disabled / Enabled Disabled
Calibration
o o o o
Temperature All Units -10.0 C 0.1 C 10.0 C 0C
Humidity -20.0% 0.1% 20.0% 0%
Water Temperature o o o o
Water In -10.0 C 0.1 C 10.0 C 0C
option
o o o o
Water Out -10.0 C 0.1 C 10.0 C 0C
o o o o
Coil Temperature 1 Combi Cool option -10.0 C 0.1 C 10.0 C 0C
o o o o
Coil Temperature 2 -10.0 C 0.1 C 10.0 C 0C
Delay Time
Function Delay All Units 0s 1s 999s 20s
Unit Start Delay 0s 1s 999s 0s
Fan Off Delay 0s 1s 999s 0s
Air Flow Failed Delay 0s 1s 300s 30s
LP Start Delay for DX only 0s 1s 999s 60s
LP Run Delay 0s 1s 999s 5s
Compressor Start Delay For water-cooled unit 0s 1s 60s 0s
Reset Alarm History
Erase Alarm History All Units Yes / No No
Forced Outputs
Cooling 1 All Units Auto / Manual Auto
Cooling 2 Auto / Manual Auto
Cooling 3 Auto / Manual Auto
Dehum. Auto / Manual Auto
Heating 1 Auto / Manual Auto
Heating 2 Auto / Manual Auto
Humidify Auto / Manual Auto
Maintenance Alarm Auto / Manual Auto
Critical Alarm Auto / Manual Auto

16
CGD1: SOFTWARE LEVEL 2

Function Application Min. Inc./Dec. Max. Default


Forced Outputs
Analogue Output All Units
Cooling Auto / Manual Auto
Heating Auto / Manual Auto
FSC 1 Auto / Manual Auto
FSC 2 Auto / Manual Auto
FSC 3 Auto / Manual Auto
EC Fan Auto / Manual Auto
Cooling 2 Auto / Manual Auto
Run Hours
Base Unit All Units 0h 1h 99,999h 0
Cooling 1 0h 1h 99,999h 0
Cooling 2 0h 1h 99,999h 0
Cooling 3 0h 1h 99,999h 0
Heating 1 0h 1h 99,999h 0
Heating 2 0h 1h 99,999h 0
Humidifier 0h 1h 99,999h 0
Reset Run Hours
Base Unit All Units Yes / No No
Cooling 1 Yes / No No
Cooling 2 Yes / No No
Cooling 3 Yes / No No
Heating 1 Yes / No No
Heating 2 Yes / No No
Humidifier Yes / No No
Differential Temperature
o o o o
Differential Temperature for Ambicool only 0C 0.1 C 20.0 C 3.0 C
Set New Password
Enter New Password All Units 0 1 9999 0000
Unit Expired
Enter New Date All Units Day/Month/Year 31/12/99
Reset Unit Stop Alarm Yes / No No
Health Check
Enter New Date All Units Day/Month/Year 31/12/99
Reset Health Check Alarm Yes / No No
Aux. Alarm Text
Aux. Alarm 1 Text Message All Units Input text message
Aux. Alarm 2 Text Message (max. 20 characters)
Aux. Alarm 3 Text Message

17
CGD1: SOFTWARE LEVEL 2

Function Application Min. Inc./Dec. Max. Default


EC Fan
EC Fan Output Range EC Fan option
Minimum (speed) 12.0% 0.1% 100.0% 60.0%
Maximum (speed) 12.0% 0.1% 100.0% 80.0%
Temperature Band 0.0% 0.1% 10.0% 3.0%

18
PGD TOUCH: BASIC SETTING

Function Application Min. Inc./Dec. Max. Default


Set Point
o o o o
Temperature Set Point All Units 5.0 C 0.1 C 40.0 C 21.0 C
Humidity Set Point All Units 10.0% 0.1% 90.0% 50.0%
o o o o
Water In Temperature Water cooled & Chilled 0C 0.1 C 40.0 C 9.0 C
Alarm Limit Water Unit Only
Scheduler
On Time / Off Time:
Monday All Units 00:00 1 23:59 00:00
Tuesday (when weekly time zone 00:00 1 23:59 00:00
Wednesday with on/off unity enabled) 00:00 1 23:59 00:00
Thursday - two time zones per day 00:00 1 23:59 00:00
Friday 00:00 1 23:59 00:00
Saturday 00:00 1 23:59 00:00
Sunday 00:00 1 23:59 00:00
Set Clock
Enter Hour All Units 0 1 23
Enter Minutes (when clock board 0 1 59
Enter Day enable) 1 1 31
Enter Month 1 1 12
Enter Year 0 1 99
Select Language
Select Language All Units Option: English English
Chinese
Thai
Japanese
Software Version
Software Version All Units Displayed Installed Software Version
Remote On Off
Remote On Off Enabled All Units Yes / No No
Unit On Off Protection
Enable Unit On Off
All Units Yes / No No
Protection
Turn Off Screen After X min All Units Option: Disable
5
10 30
15
30
pLAN Address Setting
Address of Attached
All Units 1 1 32 1
Controller
Option: Present/Rotation Pre/ No
U1 All Units
Present/ No Rotation Rotation
U2 to U8 Absent Absent

19
PGD TOUCH: BASIC SETTING

Function Application Min. Inc./Dec. Max. Default


Run Hours Counter
Base Unit All Units 0h 1h 99,999h 0
Cooling 1 0h 1h 99,999h 0
Cooling 2 0h 1h 99,999h 0
Heating 1 0h 1h 99,999h 0
Heating 2 0h 1h 99,999h 0
Humidifier 0h 1h 99,999h 0
Rotation Configuration
Rotation Type Option: Automatic Rotation Automatic
Timezone Rotation
Manual Rotation
Standby Unit 0 1 7 0
Switch Standby Yes / No No
Rotation Hour (for automatic rotation) 0h 1h 240h 0h
Rotation Time (for timezones rotation) 00:00 1 23:59 00:00
Reset Sequence Yes / No No
BMS Setup
BMS Enabled Yes / No No
Protocol Type BMS1 Option: Citec Citec
(BMS Card Option) Modbus
LonWorks
Baud Rate Option: 1200 9600 19200
2400 19200
4800
Unit Identity 1 1 200 1
Protocol Type BMS2 Option: Citec Citec
(Built in All Units) Modbus
Baud Rate Option: 1200 9600 19200
2400 19200
4800
Unit Identity 1 1 200 1

20
PGD TOUCH: ADVANCE SETTING

Function Application Min. Inc./Dec. Max. Default


EEV Control - EVD Parameters
Refrigerant Type DX System Only Option: R22 R22
R134a
R404a
R407c
R410a
R507c
Super Heat Set Point
o o o o
- Cooling Mode 2.0 C 0.1 C 50.0 C 6.0 C
o o o o
- Dehum. Mode 2.0 C 0.1 C 50.0 C 12.0 C
Enable EEV Display Yes / No No
Proportional Gain 0 0.1 99.9 10.0
Integral Time 0s 1s 999s 100s
Derivative Time 0 0.1 99.9 2.0s
o o o o
Dead Zone 0C 0.1 C 9.9 C 0C
Circuit / EEV Ratio 0% 1% 100% 60%
EEV Control - Manual Management
EEV Mode DX System Only Auto / Manual. Auto.
Requested Steps 0 1 480 0
EEV Control - Calibration
S1 DX System Only -140psig 1psig 140psig 1psig
o o o o
S3 -9.9 C 0.1 C 9.9 C 0C
Cool Control
o o o o
Proportional Band Cooling 0C 0.1 C 9.9 C 2.0 C
o o o o
Dead Zone 0C 0.1 C 9.9 C 0C
Valve Open Interval Combi Cool with 2-way
0s 1s 9999s 600s
(DX Mode) Valve fitted
Valve Open Duration
0s 1s 9999s 60s
(DX Mode)
Valve Open Setting
0% 0.1% 100.0% 50.0%
(DX Mode)
Water In High Temp. Enabled
0% 0.1% 100.0% 30.0%
(Valve Open) (CW Mode)
Alarm Delay Time (CW Mode) 0s 1s 9999s 15s
Combi Cool Change Over By
Combi Cool Disabled / Enabled Disabled
Aux. Alarm 1 (Option)
Heat Control
o o o o
Proportional Band Electric Heating 0C 0.1 C 9.9 C 2.0 C
o o o o
Dead Zone 0C 0.1 C 9.9 C 1.0 C

21
PGD TOUCH: ADVANCE SETTING

Function Application Min. Inc./Dec. Max. Default


Dehum Control
Enable Dehum Yes / No No
Dehum Interlock with RAT Yes / No No
Proportional Band Dehumidifying 0% 0.1% 10.0% 2.0%
Dead Zone 0% 0.1% 10.0% 2.0%
% of Cooling to Enable CW System Only
Dehum 0% 0.1% 80.0% 50.0%
% of Valve Opening
When Dehum 10.0% 0.1% 100.0% 70.0%
Humidity Control
Enable Humidifier Yes / No No
Proportional Band Humidification 0% 0.1% 15.0% 2.0%
Dead Zone 0% 0.1% 15.0% 2.0%
Manual Drain Yes / No No
Periodic Flushing Yes / No No
Flush Period 1h 1h 120h 24h
Inactivity Drain Yes / No No
Inactivity Drain Period 1d 1d 199d 3d (days)
Maximum Production 0% 1% 100% 100%
Hum./Heat Interlock Humidification and Option: Hum and Heat Hum. and
Heating Hum. prevents Heat Heat
Heat prevents Hum.
Alarm Setup
o o o o
High Temperature Alarm Band 1.0 C 0.1 C 10.0 C 4.0 C
o o o o
Low Temperature 1.0 C 0.1 C 10.0 C 4.0 C
High Humidity 1.0% 0.1% 30.0% 10.0%
Low Humidity 1.0% 0.1% 30.0% 10.0%
Alarm Sensitivity 0% 1% 100% 100%
Stop Unit When Water On
If sensor tape is fitted Yes / No No
Floor Alarm
Stop Unit When Drip Tray Full If tray sensor is fitted Yes / No No
Unit Off Alarm Enabled All Units Yes / No No
Sensor Fail Enabled All Units Yes / No Yes
Alarm Log Setting All Units
Unit Start Log Enable Yes / No No
Unit Stop Log Enable Yes / No No
Power Failure Log Enable Yes / No No
Power Restore Log Enable Yes / No No
Alarm Acknowledge Yes / No No
Aux. Alarm Setting
All Units Contact: N.O. / N.C. N.O.
Aux. Alarm 1
Aux. Alarm 2
Action: Indication / Off Unit Indication
Aux. Alarm 3

22
PGD TOUCH: ADVANCE SETTING

Function Application Min. Inc./Dec. Max. Default


Control Type
Control Type All Units P / P+I / P+I+D P+I
Stage Delay 0s 1s 99s 20s
Integral Time 0s 1s 999s 600s
Derivative Time 0s 1s 999s 300s
Option: Relative Humidity Mode
Humidity Control Mode RH Mode
Dew Point Mode
Humidifier/Heater Interlock Option: Humidity and heating Humidity
Humidity Over Heating and
Heating Over Humidity Heating
Audible Alarm Yes / No No
Start Mode After Power
Auto / Manual Auto
Restore:
Defrost Cycle Control:
o o o o
Saturation Temp. Threshold -10.0 C 0.1 C 10.0 C -1.5 C
Threshold Delay Time 0s 1s 999s 300s
Defrost Cycle 0s 1s 999s 300s
Compressor Status:
Compressor 1 Defrost On / Off Off
Compressor 2 Defrost On / Off Off
Time Delay
Function Delay All Units 0s 1s 999s 20s
Unit Start Delay 0s 1s 999s 0s
Fan Off Delay 0s 1s 999s 0s
Air Flow Failed Delay 0s 1s 300s 30s
LP Start Delay for DX only 0s 1s 999s 60s
LP Run Delay 0s 1s 999s 5s
Compressor Start Delay For water-cooled unit 0s 1s 60s 0s
Damper Open Delay If damper is fitted 0s 1s 999s 0s
Duty Unit Off Delay Time 0s 1s 999s 0s
Reset Run Hours & History Alarm
Base Unit All Units Yes / No No
Cooling 1 Yes / No No
Cooling 2 Yes / No No
Heating 1 Yes / No No
Heating 2 Yes / No No
Humidifier Yes / No No
Reset History Alarm Yes / No No
Unit Expired & Maintenance Schedule
Unit Expired Date All Units Day/Month/Year 31/12/99
Reset Unit Stop Alarm Yes / No No
Unit Health Check Date All Units Day/Month/Year 31/12/99
Reset Unit Health Check Alm Yes / No No

23
PGD TOUCH: ADVANCE SETTING

Function Application Min. Inc./Dec. Max. Default


DX Setup
Compressor Low Pressure:
Cut Out Limit -140psig 1psig 140psig 25psig
Cut In Limit -140psig 1psig 140psig 60psig
Compressor High Pressure: 'A' with FSC option
Pre-alarm Limit 200psig 1psig 400psig 320psig
Alarm Limit 200psig 1psig 400psig 350psig
Fan Speed Controller Config.:
Pressure Probe Type 4-20mA / 0-5V 0-5V
FSC Low Speed Mode Cut Off / Min. Speed Cut Off
Discharge Press. 1 Offset -20psi 0.1psi 20psi 0
Discharge Press. 2 Offset -20psi 0.1psi 20psi 0
FSC Control Parameters:
Minimum Pressure 0psi 1psi 999psi 200psi
Average Pressure 0psi 1psi 999psi 250psi
Proportional Band 0psi 1psi 999psi 300psi
Integral Time 0s 1s 999s 600s
Derivative Time 0s 1s 999s 5s
Stage Delay 0s 1s 99s 5s
FSC Speed Band:
Min. Speed 0% 1% 100% 20%
Max. Speed 0% 1% 100% 100%
Force Output
Cooling 1 All Units Auto / Manual Auto
Cooling 2 Auto / Manual Auto
Heating 1 Auto / Manual Auto
Heating 2 Auto / Manual Auto
Maintenance Alarm Auto / Manual Auto
Critical Alarm Auto / Manual Auto
Dehum. Auto / Manual Auto
Humidify Auto / Manual Auto
Analogue Output: All Units
EC Fan Auto / Manual Auto
Cooling 1 Auto / Manual Auto
Cooling 2 Auto / Manual Auto
Heating Auto / Manual Auto
FSC 1 Auto / Manual Auto
FSC 2 Auto / Manual Auto

24
PGD TOUCH: ADVANCE SETTING

Function Application Min. Inc./Dec. Max. Default


Sensor Calibration
o o o o
Temperature All Units -10.0 C 0.1 C 10.0 C 0C
Humidity -20.0% 0.1% 20.0% 0%
Water Temperature o o o o
Water In -10.0 C 0.1 C 10.0 C 0C
option
o o o o
Water Out -10.0 C 0.1 C 10.0 C 0C
o o o o
Coil Temperature 1 Combi Cool option -10.0 C 0.1 C 10.0 C 0C
o o o o
Coil Temperature 2 -10.0 C 0.1 C 10.0 C 0C
EC Fan Setup
EC Fan Output Range EC Fan option
Minimum (speed) 12.0% 0.1% 100.0% 60.0%
Maximum (speed) 12.0% 0.1% 100.0% 80.0%
EC Fan Speed Control
Temperature Band 0.0% 0.1% 10.0% 3.0%
CW Setup
Water In Temp. Sensor Yes / No No
Water Out Temp. Sensor Yes / No No

25
The controller uses proportional (P) or proportional plus integral (P+I) or proportional plus
integral plus derivative (P+I+D) control actions to maintain the temperature set point. The
integral (I) and derivative (D) time constants can be adjustable with software.
Proportional Control

Proportional Control is the relationship between the setpoint, proportional band and the actual control
air temperature. For a setpoint of 21°C, a proportional band of 2°C and one stage of cooling, to enable
the cooling, the control air temperature has to rise to setpoint plus proportional band, i.e. 23°C (21 + 2).
If the number of cooling stages LVLQFUHDVHGWRWZRWKHQWKH¿UVWVWDJHZRXOGEHHQDEOHGDWVHWSRLQW
plus (prop. Band/2), i.e. 22°C (21 + 2/2). Both stages will be enabled at 23°C.

The same theory applies to chilled water outputs. For the valve to be fully open, the control air
temperature has to be at setpoint plus the full proportional band.

Adjusting the proportional band shall have the following effects:

x A large proportional band will mean a slow system response, i.e. the control air temperature
would have to rise to a high level before full cooling is enabled, and subsequent shutting off
the cooling would also be slower. A small or tight proportional band will bring on cooling
TXLFNHUEXWZRXOGUHVXOWLQV\VWHPLQVWDELOLW\RU³KXQWLQJ´

x An optimum proportional band will be set for the room conditions but due to inherent heat
JHQHUDWLRQWKHUHZLOOJHQHUDOO\EHDVWHDG\VWDWHHUURURU³RIIVHW´IURPWKHVHWSRLQWDWZKLFKWKH
room conditions are maintained.

Proportional plus Integral Control

7R RYHUFRPH WKH ³RIIVHW´ DERYH WKe controller can be set to operate using proportional plus integral
(P+I) control to achieve and maintain the control temperature at setpoint. The addition of the integral
term has the effect of gradually increasing the output to reduce the offset so that the steady state
condition, i.e. heat generation equals cooling input, now occurs at setpoint. The integral action is in
effect resetting the proportional band to reduce the steady state error.

Proportional plus Integral plus Derivative

P + I + D actiRQ LV VXLWDEOH IRU FRQWURO ORRSV ZLWK VLJQL¿FDQW WLPH GHOD\ IDFWRUV ZKHUH QR VXVWDLQHG
deviation from setpoint is acceptable. Furthermore on start up or when there are changes to the load,
over shoot must be kept to a minimum (the bigger the derivative time the bigger the effect).

P + I + D control should not be used with DX cooling or Electric Heating.

26
The controller featuring two types of humidity control mode (selectable through setting).
1. RH Control Mode (Relative Humidity Control)
2. Dew Point Control Mode (Absolute Humidity Control).

Control mode

RH Control mode is the conventional way to control the RH proportional to the RH sensing probe
regardless of the environmental temperature. The Dew Point Control mode is to control the absolute
humidity to prevent unnecessary of humidifying or de-humidifying due to change of temperature. It is
compliance to ASHRAE T9.9 2008 Humidity Specification.

%
40
20 %
30
C
-° ASHRAE 2004 Recommendation
re

Humidity Ratio - kg/kg


tu
era
mp
Te 15
Bulb 20%
t
We
10

5
10%

ASHRAE 2008 Recommendation

Dry Bulb Temperature - °C

Recommended Humidity: 5.5oC DP - 60%RH & 15oC DP

Humidifier Controller

The humidifier to be controlled and managed by an electronic board which features all the input and
output required to completely and independently control the humidifier. This controller capable of show
the following parameters:

x Current (A)
x Supply Water Conductivity (µS/cm)
x Cylinder hour counter (h)
x Steam production control
x Humidifier Status
x Humidifier Alarms

The humidifier controller is communicated with pCO5 controller through Modbus RTU protocol, if there
is a loss in network communication, the humidifier controller shall stop the humidifier by opening the
contactor and goes into standby mode until the communication is restored.

27
Cooling is achieved by one of two methods, Direct Expansion or Chilled Water in response to a
cooling demand from the microprocessor controller. Factors that affect the cooling demand are the
relationship of the control air temperature to the temperature setpoint, cooling proportional band and
cooling dead zone.

In the case of DIRECT EXPANSION (DX), one, two or three stages can be selected (Software Level 3
for CGD1 or Factory Setting page for pGDTouch) to achieve the full (100%) cooling demand. Switch
RQSRLQWVIRUHDFKVWDJHLVGHWHUPLQHGDVIROORZV³GLYLGHE\1XPEHURI6WDJHV´7KHVWDJHVFDQ
be set for automatic sequencing such that the ¿UVW VWDJH VWDUWHG LV WKH ¿UVW VWDJH WR EH VWRSSHG WR
balance running hours and minimize the number of starts. Automatic sequencing of compressors can
be disabled via the software to ensure that CRROLQJ6WDJHLVDOZD\VHQHUJL]HG¿UVW

For CHILLED WATER (CW), the controller drives a valve actuator to position a two-way or three-way
valve to meet the cooling demand. There are two types of actuator: open-close control or modulating
control.

For open-close control, a XQLWWKDWLVFRQ¿JXUHG for Chilled Water operation will use Cooling outputs 1
and 2 to run the valve actuator, output number 1 will be used to drive the actuator open and output
number 2 to drive it close. For a valve actuator with a full running time of 110 seconds (example) the
valve will be opened 100%. The valve opened or valve closed is directly proportional to the variation in
the cooling demand and the maximum time for complete opening.

An interlock prevents the simultaneous activation of the outputs, with closing having the priority.

To enable the controller to determine the position of the actuator on start-up (or at any time the AHU is
stopped and started) it will initially energize the drive close output for 110% of the valve running time.
This ensures the valve is at the fully closed position and any subsequent movement is from a set
position. Thus at switch on the valve may initially be seen to close even though conditions may be
calling for a cooling demand.

The valve is activated only upon variations in cooling demand greater than 5%. If the request is equal
to 0%, the valve closing time equal to half of the valve running time every hour. If the request is
between 0% and 10%, the valve closed for a time that is proportional to the variations plus 20% of
valve running time and then the valve opened for the time necessary to reach the desired value. This
operation is performed only once, and the condition ends when the request exceeds 14%. After having
performed the complete closing operation once, control continues normally by activating the valve
opened or valve closed, for a time that is proportional to the variation of the cooling demand.

If the request is between 10% and 90%, the valve opened or valve closed is activated for a time that is
proportional to valve running time and the variation of the cooling demand.

If the request is between 90% and 100%, the valve opened is proportional to the variation, plus 20% of
valve running time, and then the valve closed takes the necessary time to reach the desired value.
This operation is performed only once, and the condition ends when the request falls below 86%. After
having performed the complete opening operation once, control continues normally by activating the
valve opened or valve closed, for a time that is proportional to the variation of the cooling demand.

If the request is equal to 100%, the valve opened takes time equal to 50% of valve running time every
hour.

For modulating control, the valve actuator is driven by 0-10V signal from controller, which is
proportionally to cooling demand.

28
Heating is achieved in one of two ways, either with Electric Heaters or Low Pressure Hot Water
(LPHW).

In the case of Electric Heating, XSWRWKUHHVWDJHVRIKHDWLQJFDQEHFRQ¿JXUHGLQVRIWZDUH /HYHO for


CGD1 or Factory Setting page for pGDTouch) even though there are only two heating outputs. For this
arrangement, the electric heaters must be of unequal size (in the ratio of 2:1, output No. 1 heater
being the smaller). Operation of the outputs is in a binary manner as shown in the table below.

Heating Step Heater Stage ON OFF


1 1 O
2 O
2 1 O
2 O
3 1 O
2 O

The LPHW output operates a Drive Open or Drive Close valve actuator via the digital outputs in
response to heating demands. The operation of the outputs is similar to that for CW control.

The heating demand is generated in the same way as the cooling demand, i.e. deviations below
setpoint will generate a heating demand relevant to the dead zone and proportional bands set and
operate the heating outputs accordingly. Integral action has the same effect on the heating demand,
thus with no change in the Return Air Temperature and an initial heating demand is present the
demand is gradually increased so that the output increases to raise thH5HWXUQ$LU7HPSHUDWXUHWRLWV¶
setpoint.

The controller can also provide a 0 - 10V DC output to a LPHW valve actuator if required.

7KH'HKXPLGL¿FDWLRQGHPDQGLVFDOFXODWHGLQDVLPLODUZD\WRWKDWRIWKHLQLWLDOFRROLQJGHPDQG)RU
chilled water &: FRROLQJWKHRI&:FRROLQJGHPDQGWRHQDEOHGHKXPLGL¿FDWLRQFDQEHVHWDW
software (Level 2 for CGD1 or Advance Setting page for pGDTouch). Also, the valve opening when
GHKXPLGL¿FDWLRQFDQEHVHWDWVRIWZDUH /HYHO for CGD1 or Advance Setting page for pGDTouch).

'HKXPLGL¿FDWLRQZLWK';FRROLQJenergized when the dehumidify demand reaches 100% and cooling


GHPDQGPHHWWKHSUHVHWYDOXH'HKXPLGL¿FDWLRQLVDFKLHYHGLQRQHRIWhree ways, with split coil, with
low speed blower fan or higher superheat setting.

7KH'HKXPLGL¿FDWLRQRXWSXWFDQEHGLVDEOHGLQVHYHUDOZD\VHYHQWKRXJKWKHUHWXUQDLU5+PD\
LQGLFDWHWKDWGHKXPLGL¿FDWLRQLVUHTXLUHG7KHGLVDEOHIXQFWLRQVDUHDVEHORZ

‡ 'LVDEOH'HKXPLGL¿FDWLRQDW6RIWZDUH/HYHO for CGD1 or Advance Setting page for


pGDTouch.
‡ 'LVDEOHGHKXPLGL¿FDWLRQGXHWR5HWXUQ$LU7HPSHUDWXUH:KHQWKH5HWXUQ$LU7emperature
falls to EHORZ³&RQWURO$LU7HPSHUDWXUH6HW3RLQW- (1.5 x (Heating Prop. Band + Heating Dead
=RQH ´GHKXPLGL¿FDWLRQLVGLVDEOHG5H-enabled when Return Air Temperature rises to
³&RQWURO$LU7HPSHUDWXUH6HW3RLQW- +HDWLQJ'HDG=RQH´
‡ )RU';V\VWHPLIFRROLQJGHPDQGLVJUHDWHUWKDQWKHSUHVHWYDOXHGHKXPLGL¿FDWLRQLV
disabled.
‡ )RU&:V\VWHPGHKXPLGL¿FDWLRQGLVDEOHGZKHQFRROLQJGHPDQGH[FHHGVDSrescribed level
can be set in Software Level 2 for CGD1 or Advance Setting page for pGDTouch (% of
cooling to enable dehum).

29
+XPLGL¿FDWLRQLVDFKLHYHGZLWKHOHFWURGHERLOHUW\SHKXPLGL¿HU,QWKLVW\SHRIKXPLGL¿HUWKHVWHDPLV
produced by boiling thHZDWHUFRQWDLQHGLQVLGHWKHF\OLQGHU7KLVRFFXUVE\VLPSO\¿OOLQJWKHF\OLQGHU
with water and applying voltage to the electrodes. According to the Joule effect, the current will tend to
heat the water until boils. The aim of the algorithm is to maintain the current that runs through the
electrodes at a reference value so as to ensure the percentage of steam production required
according to the readings of the humidity probes and the parameters set by the user. To maintain the
current within a certain rangH DURXQG WKH UHIHUHQFH YDOXH ZDWHU ¿OO DQG HYDSRUDWLRQ F\FOHV DUH
repeated. The other factor that determines the current level is the conductivity of the water inside the
cylinder.

Another element, installed at the top of the cylinder, is the high level sensor, used to detect any water
or foam. The high level electrodes may be activated for one of the following reasons:

x RYHU¿OOLQJRIZDWHULQWKHF\OLQGHU
x KLJKZDWHUOHYHOZKHQ¿UVW¿OOLQJWKHF\OLQGHU
x high water level following the depletion of the cylinder due to fouling on the plates
x formation of foam

In many buildings, central chilled water systems are installed to provide comfort air conditioning.
These systems are usually unsuitable for computer rooms and similar applications because the chilled
water may be unavailable at weekends, at night or during the winter months when general cooling is
not required.

Conditioning unit uses such a source of chilled water when it is available, but also have a back up
direct expansion system to take over when it is not. Low cost chilled water can therefore be used for
much of the cooling season, so saving energy costs, whilst the direct expansion system shall ensure
continuity and security when the chilled water system is unavailable, mulfunction or shut down for
maintenance.

A combicool unit consists of two separate cooling circuits. Normally, the primary circuit will be a chilled
water system and the secondary circuit could be a DX system or chilled water system. The Citec
control system shall provide automatic change over from primary system to secondary system when
³ZDWHULQ KLJKWHPSHUDWXUH´DODUPHQHUJL]HG7KUHVKROGRIWKLVDODUPLVGHWHUPLQHGE\³ZDWHULQDODUP
OLPLW´ LH ž& ZKLFK FDQ EH VHW DW 6RIWZDUH /HYHO  ± Setpoint for CGD1 or Basic Setting menu ±
Setpoint for pGDTouch.

Ambicool is the use of low ambient temperatures cooling a freecooling liquid (typically glycol / water
solution) to effect heat extraction from an air conditioned space. Should the ambient temperature rise
to a level at which no duty can be achieved by freecooling then DX stages will cool the room air in
order to do the cooling duty.

7R HQDEOH IUHHFRROLQJ WZR UHTXLUHPHQWV KDYH WR EH IXO¿OOHG )LUVW WKH $LU +DQGOLQJ 8QLW KDV WR EH
FRQ¿JXUHG IRU $PELFRRO DQG VHFond, the freecooling liquid has to be at a certain temperature. The
OHYHORIWKLVWHPSHUDWXUHLVGHWHUPLQHGDVWKH³5HWXUQ$LU7HPSHUDWXUHPLQXVWKH)UHHFRROLQJ/LTXLG
7HPSHUDWXUH´LVHTXDOWRRUJUHDWHUWKDQWKH)UHHFRROLQJ'LIIHUHQWLDO7HPSerature.

Examples:
x If Return Air Temperature is 22ºC, Freecooling Liquid Temperature is 8ºC and differential
temperature is set to 3ºC, then Ambicool is enabled.

30
x If Return Air Temperature is 22ºC, Freecooling Liquid Temperature is 20ºC and differential
x temperature is set to 3ºC, then Ambicool is NOT enabled.

,QWHJUDODFWLRQDVGHVFULEHGLQ³&RROLQJ2SHUDWLRQ´LVDOVRDSSOLFDEOHWR$PELFRRORSHUDWLRQ7KH
Ambicool valve position is determined by the cooling demand multiplied by four.

e.g. 15% cooling demand = 60% valve position


20% cooling demand = 80% valve position
25% cooling demand = 100% valve position

The DX stages of cooling are enabled when the cooling demand is 100% and disabled when the
demand falls below 25%.

The controller software has facility to select one of a series of interlocks, which affect operation of
HOHFWULFKHDWHUVDQGKXPLGL¿HU

In the majority of cases, electrical supply to an Air Handling Unit is sufficient to enable both heaters
DQG KXPLGL¿HU WR UXQ DW WKH VDPH WLPH VKRXOG RSerating conditions require so. However, there are
cases when only one function or the other can be run at any one time, thus the software can be set so
that one function has priority over the other.

There are three options available as below:

1. Heat and Hum -This option allows both functions to operate simultaneously.

2. Heat prevents Hum -This option shall give priority to the heating function. Should heating be called
for, the KXPLGL¿HUVKDOOEHGLVDEOHGHYHQWKRXJKWKHUHPD\EHGHPDQGIRU
KXPLGL¿FDWLRQ

3. Hum prevents Heat -This option is the opposite of (2) where the heating is disabled when the
KXPLGL¿HULV enabled by demand.

The options are selected in Software Level 2 - Humidity Control for CGD1 or Advance Setting page for
pGDTouch, with option (1) as the default setting. With option (2) or (3) selected, the interlock remains
active even if the software output forcing routines are applied.

EC FAN
Electronic commutated (EC) fan is an option to be fitted in a unit. In auto mode, it shall perform
according to figure shown below.

31
Fig. 1.1 : Wiring connection for auto-sequencing network.

Auto sequencing management is able to manage a group of air-conditioning, maximum eight units in a
network. When the units in a network operate in auto sequencing mode, they shall perform duty and
standby task according to setting at software Level 1 - 5RWDWLRQ &RQ¿JXUDWLRQ DQG /HYHO  ± Unit
Configuration IRU &*' RU 5RWDWLRQ &RQ¿JXUDWLRQ DQG 8QLW &RQILJXUDWLRQ SDJH IURP %DVLF 6HWWLQJ
menu for pGDTouch.

There are two modes of auto sequencing management: automatic rotation or time zone rotation.
Automatic rotation allows the units rotate by a sequence and at an interval time while time zone
rotation allows the units rotate according to preset time and interval day schedule. The quantity of
standby units in a network can be determined at 5RWDWLRQ&RQ¿JXUDWLRQ setting page.

Figure 1.1 shows typical connection for Citec air conditioning units running in auto sequencing mode.
Connection between controller boards in a network is carried out using an AWG20/22 shielded cable,
twisted pair plus shield.
The max cable length for pLAN network is 200m. Connection between terminal G0 of controllers to
2
earth line in a network has to use cable with minimum size of 1.5 mm .
Terminal G0 of all controllers in an auto sequencing network must be connected to same earth
point.

When the controllers connected in a network and operate in auto sequencing mode, the standby unit
shall operate during emergency cases as below:

(a) High temperature


(b) Low temperature
(c) High humidity
(d) Low humidity
(e) $LUÀRZIDLOXUH
(f) Heater Overheat
(g) Filter blocked
(h) Compressor 1 high pressure
(i) Compressor 2 high pressure
(j) Compressor 1 low pressure
(k) Compressor 2 low pressure
(l) Off by Alarms
(m) Compressor stops due to alarm

32
Categories of Remote Monitoring System:

‡ Hard Wired / Dry Contact


‡ Remote Terminal
‡ PC Monitoring
- TeleMon
- PlantVisorPro
‡ BMS/BAS Connection
- Modbus
- LonWorks
- BACnet
‡ TCP/IP Network Connection
- WebGate
- pCOWeb
- PlantVisorPro

&LWHF¶V controller has two numbers of dry contact outputs. There are mains for maintenance alarm and
critical alarm. These outputs are volt free contact.

Any alarms activated in the controller shall energizHFULWLFDODODUPRXWSXW:DWHURQÀRRUGULSWUD\IXOO


DQG¿OWHUEORFNHGDODUPVDUHLQWHJUDWHGLQWKHPDLQWHQDQFHDODUPRXWSXW

These outputs can be linked to external lamp or buzzer to indicate an alarm condition.

33
Remote terminal is a terminal where locates at a place further from the air-conditioning unit, such as
FRQWURO URRP ,W FDQ PRQLWRU DQG FRQWURO DOO WKH XQLWV¶ SDUDPHWHUV E\ DFFHVV WR D SDUWicular unit. At
UHPRWHWHUPLQDOWKHXQLW¶VSDUDPHWHUVFDQEHREVHUYHGDQGFKDQJHG2QO\RQHXQLWFDQEHDFFHVVHG
for every assessment.

The menu main screen shows the controller address on the lower right corner of the displayed board.
IWLVD¿[HGQXPEHUFRUUHVSRQGLQJWRWKHS/$1DGGUHVVRIWKHERDUG -8). Remote terminal is allowed
to select which ERDUG WR EH GLVSOD\HG E\ SXVKLQJ EXWWRQ ³(6&´ DQG ³83´ VLPXOWDQHRXVO\ :KHQ WKH
two buttons are push, the address displayed in the lower right corner increases by 1 and the display
shows the parameters of the board selected among the connected ones.

To perform the remote terminal application, hardware connection and address setting have to be
carried out.

For CGD1 remote terminal connection, T-device is required depend on the connection type. Refer to
Figure 2.3 to Figure 2.5

Example of Remote Terminal Wiring Connection

34
Example of Remote Terminal Wiring Connection

T-Device

35
Web Server Functions

PlantVisor is the web-server based monitoring and telemaintenance system server that features
ÀH[LELOLW\RIXVHDQGHDV\DFFHVVWRLQIRUPDWLRQDQG alarm management functions. The information can
be displayed as graphs, tables of parameters or alarms, device status indicators and so on.

Features

PlantVisorPro allows:

‡ centralised management on the PC of the controller parameters, for display anGPRGL¿FDWLRQ


‡ alarm management by scheduling the actions to be performed according to the time band (fax,
SMS message, activation of a relay, call to the remote PC);
‡ sampling and recording of the temperature, humidity and pressure values and any active
alarms, in compliance with the EU directive, for display or printing;
‡ Different levels of password protect access to the data.
‡ PlantVisor allows the connection of up to 200 controllers in a RS485 serial network.
‡ PlantVisor manages traditional and GSM modems for sending faxes, SMS messages and for
remote access using PlantVisor Remote or Internet Explorer.

36
PlantVisorPro Enhanced Local summary page:
all the utilities and their operating conditions are shown

37
The BMS (Building Management System) is required to develop a balanced function between
economics, operating
costs, safety and comfort with human considerations being most important.

The BMS shall operate on a management by exception concept and essentially be able to operate by
itself on the basis of programmable schedules, events, etc., and requiring only a small degree of
manual intervention and supervision.

The connection with the BMS supervisory systems is executed in different ways.
LonWorks: LQVHUWWKHDGGLWLRQDO/RQ:RUNVLQWHUIDFHFDUGLQWRWKH³6HULDOFDUG´SRUW
Modbus: pCO5 controller has in-built with this interface and protocol.
BACnet: LQVHUWWKH%$&QHWLQWHUIDFHFDUGLQWRWKH³6HULDOFDUG´SRUW
2ZQHUV¶%0S: Many other Gateways have been developed for interfacing with less spread
BMS, i.e. OTE.

38
Fig. 2.8 : Detailed Wiring Connection for the BMS with Modbus protocol.

Hardware Setup

The wiring connection for the BMS with Modbus protocol is shown in Figure 2.8. Connection between
controller BMS2 serial port (J25) in a network is carried out using an AWG20/22, 3-core shielded cable.
The boards are connected in parallel. Maximum cable length in one network is 1000 meters. Pay
ATTENTION to the network polarity: Rx/Tx+ on one board must be connected to Rx/Tx+ on the other
boards; the same is true for Rx/Tx- and GND. Resistor 120 ohm shall be installed at first and last of
the RS485 serial port in the network at terminal + and ± if the network exceeds 100m.

Software Setup
The parameter setup is at Level 2 - BMS Setup for CGD1 or Advance Setting menu ± BMS setup for
pGDTouch. The parameters are as below:

i. BMS2 Enable - set to Yes


ii. Protocol Type - set to Modbus
iii. Baud Rate - VHWDFFRUGLQJWRWKHXVHU¶VV\VWHPEDXGUDWH  
iv. Identity - set accordingly

Variable Database
$VSHFL¿FFRPPXQLFDWLRQGDWDEDVHLVIHDWXUHGWKDWLQFOXGHVDOOWKHPRUHLPSRUWDQWSURJUDPYDULDEOHV
from the values read by the probes to the parameters set on the screens. The following table
describes the database, divided into digital, integer and analogue variables, indicating for each its
GHVFULSWLRQDGGUHVVDQGW\SHWKDWLVUHDGRQO\ 5 RUPRGL¿DEOHIURPWKHVXSHUYLVRU 5: $OVRWKH
equivalent address and type of parameters for Modbus protocol shown in the table.

‡ Modbus protocol has been developed using as reference the following documentation:
GOULD Electronics: PI-MBUS-300 Rev A
Gould Modicon - Gould Inc. Programmable Control Division
Date: November 1983
‡ Modbus uses RTU mode.
‡ Communication parameters: 8 data bit
2 stop bit
no parity
baud rate from 1200 to 19200

39
The optional pCOnet board which is inserted to pCO5
controller allows the controller to be connected to a
BACnet MS/TP (Master/Slave Token Pass) network.

The optional LonWorks serial card is used to


interface to a LonWorks network. The type of
interface on the LonWorks network side is interface
to FTT-10A 78 Kbs (TP/FT-10).

Controller parameters setting:

i. BMS1 Enable - set to Yes

ii. Protocol Type - set to LonWorks

iii. Baud Rate ± 4800

iv. Identity - 1 (not important)

40
WebGate is an innovative electronic device that measures the same size as a normal desktop modem.
It can FRQQHFWDOOFRQWUROOHUVWRWKHORFDOQHWZRUNEDVHGRQWKHVWDQGDUG(WKHUQHWŒDQG7&3,3
(WKHUQHWŒLVD widespread, fast, economical and reliable communication standard, and is the physical
support for the TCP/IP SURWRFRO(WKHUQHWŒQHWZRUNVDUHQRZXVHGLQQXPHURXVGLIIHUHQWW\SHVRI
systems, and can thus be exploited as the backbone for the transmission of data, without needing to
add further wiring in the supervision of the instruments

(WKHUQHWŒDQG7&3,3DUHWKHWHFKQRORJLHVWKDWXQGHUOLHWKH,QWHUQHWDQGDVDUHVXOW:HE*DWHDOORZV
the use of tools, such as web browsers, for performing diagnostic functions and the local and remote
monitoring of the systems.

WebGate is easy to configure either via the web or using an RS232 serial connection : as a matter of
fact, only a minimum configuration is sufficient for setting its individual IP address.
WebGate assessment is protected by multi level password.

Web Server Functions

One of the main functions performed by WebGate is the WebServer function : using the HTTP (Hyper
Text Transfer 3URWRFRO VWDQGDUG:HE*DWHFDQ³VHUYH´ZHESDJHVWRFOLHQt computers connected in a
local network or WAN. The user can thus display and modify the installation parameters using an
Internet browser, such as Microsoft® Internet ([SORUHUŒRU1HW6FDSH1DYLJDWRUŠDVWKHLQWHUIDFH
and typing in the IP address of the WebGate.

FTP Protocol

7KHZHESDJHVUHODWLQJWRWKHVSHFLILFLQVWDOODWLRQDUHVDYHGWRWKH³IODVK´PHPRU\LQVLGHWKH:HE*DWH
(400KB available) via FTP (File Transfer Protocol), the protocol used to transfer files on TCP/IP
networks. An FTP software client, such as SmartFTP, is used to connect to the WebGate on the
TCP/IP network and consequently access its )LOH6\VWHPLQWKHVDPHZD\DVXVLQJWKH³([SORUHU´
utility in the Windows operating system. Then, using simple ³GUDJDQGGURS´RSHUDWLRQZLWKWKHPRuse,
WKHZHESDJH+70/ILOHVFDQEHFRSLHGIURPWKHXVHU¶VFRPSXWHUWRWKH WebGate.

41
SNMP Protocol

WebGate is also an SNMP gateway.

SNMP is a protocol developed specifically for the management of TCP/IP networks, founded in 1988
based on the specifications of the IAB (Internet Administration Board), the body that supervises the
Internet protocol. This is thus a protocol developed specifically for the management of data on TCP/IP
networks, and is consequently very widespread and suitable for the specific application.

The SNMP functions are complementary to the HTTP functions: as a result, an Internet browser,
which uses HTTP, can be used to access the installation data for modification or monitoring.
Nonetheless, it is not possible to perform the other typical supervisor functions, such as logging the
data, managing alarms, etc. These functions in fact require a supervisor that is continuously
connected to the WebGate, and which receives the data from the controllers via the TCP/IP network.
These are then sent to the WebGate via the SNMP protocol and can be managed by a supervisor with
SNMP management functions.

Sample monitoring pages on WebGate

42
Wiring Connection for WebGate

Basically, each controller is connected in a network using additional serial card RS 485 on each unit.
Maximum units that able to be connected in a network is sixteen units. One of the controller in a
network is connected to the WebGate. Then the WebGate is connected to the internet via Ethernet
port and need a fix IP address for it.

Parameter Setup

The parameter setup is at Level 2 - BMS Setup for CGD1 or Advance Setting menu ± BMS setup for
pGDTouch. The parameters required to set are as below:

i. BMS2 Enable - set to Yes


ii. Protocol Type - set to Citec
iii. Baud Rate - set to 19200
iv. Identity - set accordingly (1-16)

43
General Characteristics

Ethernet Interface: RJ45 connector for Ethernet 10 Base T


use a shielded cable class 5, max 100 mt
Available function: Web Server
FTP PUSH
FTP Server
Logger
Graph
Email
SNMP v1 & v2c
DHCP
DNS
MODBUS Over TCP/IP
BACnet Ethernet ISO8802-2/8802-3
BACnet/IP (Addenda A/Annex J)
Memory: 16 MB RAM, 8 MB Flash (3 MB available for web pages and user data)
CPU: ARM7 TDMI@74MHz clock
Operating System: LINUX 2.4.21

SNMP

pCOWeb is able to communicate using the SNMP protocol (v1 & v2c). In this situation, pCOWeb act
as a gateway between the Citec proprietary protocol of the controller and the SNMP network.
pCOWeb manages standard trap conditions and it is possible to define a trap condition for each digital
variable of the application loaded in the controller.

The SNMP parameters setup is done through the Administrator pages.

Wiring Connection for pCOWeb

To access pCOWeb monitoring

44
BACnet Ethernet/IP

pCOWeb is capable to communicate over Ethernet using the BACnet protocol over the following
media:
- BACnet/IP
- ISO8802-2 over 8802-3

In this situation, pCOWeb acts like a gateway between the Citec proprietary protocol of the controller
and the BACnet network. The BACnet parameters setup is done through the Administrator pages.

Configuration of pCOWeb

For configuration of pCOWeb card, please refer to Installation and Operational Manual of pCOWeb
card.

45
BMS ± VARIABLE LIST
A. Digital Variable

CITEC MODBUS BACnet


Address Description Type Address Type Obj._Inst. Obj_Name Remark
1 BMS on off R/W 1 Coil 1 D001 0=off / 1=on
2 Compressor 1 status R 2 Coil 2 D002 0=off / 1=on
3 Compressor 2 status R 3 Coil 3 D003 0=off / 1=on
4 Compressor 3 status R 4 Coil 4 D004 0=off / 1=on
5 Cooling on R 5 Coil 5 D005 0=off / 1=on
6 Dehumidify on R 6 Coil 6 D006 0=off / 1=on
7 Critical alarm R 7 Coil 7 D007 0=no alarm / 1=alarm
8 Heating on R 8 Coil 8 D008 0=off / 1=on
9 Heater 1 status R 9 Coil 9 D009 0=off / 1=on
10 Heater 2 status R 10 Coil 10 D010 0=off / 1=on
11 Humidify on R 11 Coil 11 D011 0=off / 1=on
12 Alarm Humidifier high current R 12 Coil 12 D012 0=no alarm / 1=alarm
13 Fan on / Unit on R 13 Coil 13 D013 0=off / 1=on
14 Alarm air flow fail R 14 Coil 14 D014 0=no alarm / 1=alarm
15 Alarm filter block R 15 Coil 15 D015 0=no alarm / 1=alarm
16 Alarm high humidity R 16 Coil 16 D016 0=no alarm / 1=alarm
17 Alarm high temperature R 17 Coil 17 D017 0=no alarm / 1=alarm
18 Alarm comp. 1 high pressure R 18 Coil 18 D018 0=no alarm / 1=alarm
19 Alarm comp. 2 high pressure R 19 Coil 19 D019 0=no alarm / 1=alarm
20 Alarm Heater Over Heat R 20 Coil 20 D020 0=no alarm / 1=alarm
21 Alarm low humidity R 21 Coil 21 D021 0=no alarm / 1=alarm
22 Alarm low temperature R 22 Coil 22 D022 0=no alarm / 1=alarm
23 Alarm comp. 1 low pressure R 23 Coil 23 D023 0=no alarm / 1=alarm
24 Alarm comp. 2 low pressure R 24 Coil 24 D024 0=no alarm / 1=alarm
25 Alarm Unit Health Check R 25 Coil 25 D025 0=no alarm / 1=alarm
26 Alarm LAN disconnected R 26 Coil 26 D026 0=no alarm / 1=alarm
27 Alarm unit run expired R 27 Coil 27 D027 0=no alarm / 1=alarm
28 Alarm water on floor R 28 Coil 28 D028 0=no alarm / 1=alarm
29 Alarm drip tray full R 29 Coil 29 D029 0=no alarm / 1=alarm
30 Alarm high conductivity R 30 Coil 30 D030 0=no alarm / 1=alarm
31 Alarm low production R 31 Coil 31 D031 0=no alarm / 1=alarm
32 Drain alarm R 32 Coil 32 D032 0=no alarm / 1=alarm
33 Alarm cylinder full R 33 Coil 33 D033 0=no alarm / 1=alarm
34 Warning Clean cylinder R 34 Coil 34 D034 0=no alarm / 1=alarm
35 Alarm CPY Offline R 35 Coil 35 D035 0=no alarm / 1=alarm
36 Alarm Replace Humidifier Cylinder R 36 Coil 36 D036 0=no alarm / 1=alarm
37 Warning high conductivity R 37 Coil 37 D037 0=no alarm / 1=alarm
38 Auxiliary alarm 1 R 38 Coil 38 D038 0=no alarm / 1=alarm
39 Auxiliary alarm 2 R 39 Coil 39 D039 0=no alarm / 1=alarm
40 Auxiliary alarm 3 R 40 Coil 40 D040 0=no alarm / 1=alarm
41 Alarm CPY serial disconnected R 41 Coil 41 D041 0=no alarm / 1=alarm
42 Unit 1 present in LAN R 42 Coil 42 D042 0=absent / 1=present
43 Unit 2 present in LAN R 43 Coil 43 D043 0=absent / 1=present
44 Unit 3 present in LAN R 44 Coil 44 D044 0=absent / 1=present
45 Unit 4 present in LAN R 45 Coil 45 D045 0=absent / 1=present
46 Unit 5 present in LAN R 46 Coil 46 D046 0=absent / 1=present
47 Unit 6 present in LAN R 47 Coil 47 D047 0=absent / 1=present
48 Unit 7 present in LAN R 48 Coil 48 D048 0=absent / 1=present
49 Unit 8 present in LAN R 49 Coil 49 D049 0=absent / 1=present
50 Alarm water in high temperature R 50 Coil 50 D050 0=no alarm / 1=alarm
51 Alarm Humidifier lack water R 51 Coil 51 D051 0=no alarm / 1=alarm
52 Reset alarm R/W 52 Coil 52 D052 0=no / 1=yes
53 Reset sirence R/W 53 Coil 53 D053 0=no / 1=yes

46
BMS ± VARIABLE LIST

CITEC MODBUS BACnet


Address Description Type Address Type Obj._Inst. Obj_Name Remark
54 Enable BMS on off R/W 54 Coil 54 D054 0=no / 1=yes
55 Cylinder maintenance mandatory R 55 Coil 55 D055 0=no / 1=yes
56 Cylinder maintenance recommended R 56 Coil 56 D056 0=no / 1=yes
57 Previous alarm event (webgate) R/W 57 Coil 57 D057 0=no / 1=yes
58 Next alarm event (webgate) R/W 58 Coil 58 D058 0=no / 1=yes
59 Last alarm event (webgate) R/W 59 Coil 59 D059 0=no / 1=yes
60 Alarm high discharge pressure 1 R 60 Coil 60 D060 0=no alarm / 1=alarm
61 Alarm high discharge pressure 2 R 61 Coil 61 D061 0=no alarm / 1=alarm
62 Warning high discharge pressure 1 R 62 Coil 62 D062 0=no alarm / 1=alarm
63 Warning high discharge pressure 2 R 63 Coil 63 D063 0=no alarm / 1=alarm
64 Alarm return air temperature sensor failed R 64 Coil 64 D064 0=no alarm / 1=alarm
65 Alarm return air humidity sensor failed R 65 Coil 65 D065 0=no alarm / 1=alarm
66 Alarm pressure probe 1 failed R 66 Coil 66 D066 0=no alarm / 1=alarm
67 Alarm pressure probe 2 failed R 67 Coil 67 D067 0=no alarm / 1=alarm
68 Unit off alarm R 68 Coil 68 D068 0=no alarm / 1=alarm
69 Clock board error R 69 Coil 69 D069 0=no alarm / 1=alarm
70 Supervisory system online status (Citec) R 70 Coil 70 D070 0=offline / 1=online
71 Alarm anti freeze 1 tripped R 71 Coil 71 D071 0=no alarm / 1=alarm
72 Alarm anti freeze 2 tripped R 72 Coil 72 D072 0=no alarm / 1=alarm
73 Water in sensor failed R 73 Coil 73 D073 0=no alarm / 1=alarm
74 Water out sensor failed R 74 Coil 74 D074 0=no alarm / 1=alarm
75 Anti freeze 1 sensor failed R 75 Coil 75 D075 0=no alarm / 1=alarm
76 Anti freeze 2 sensor failed R 76 Coil 76 D076 0=no alarm / 1=alarm
77 Return air humidity sensor out of range R 77 Coil 77 D077 0=no alarm / 1=alarm
78 Eeprom Error (EEV D1) R 78 Coil 78 D078 0=no alarm / 1=alarm
79 Eeprom Error (EEV D2) R 79 Coil 79 D079 0=no alarm / 1=alarm
80 Eeprom Error (EEV D3) R 80 Coil 80 D080 0=no alarm / 1=alarm
81 MOP Time Out (EEV D1) R 81 Coil 81 D081 0=no alarm / 1=alarm
82 MOP Time Out (EEV D2) R 82 Coil 82 D082 0=no alarm / 1=alarm
83 MOP Time Out (EEV D3) R 83 Coil 83 D083 0=no alarm / 1=alarm
84 LOP Time Out (EEV D1) R 84 Coil 84 D084 0=no alarm / 1=alarm
85 LOP Time Out (EEV D2) R 85 Coil 85 D085 0=no alarm / 1=alarm
86 LOP Time Out (EEV D3) R 86 Coil 86 D086 0=no alarm / 1=alarm
87 Low Super Heat (EEV D1) R 87 Coil 87 D087 0=no alarm / 1=alarm
88 Low Super Heat (EEV D2) R 88 Coil 88 D088 0=no alarm / 1=alarm
89 Low Super Heat (EEV D3) R 89 Coil 89 D089 0=no alarm / 1=alarm
90 High Super Heat (EEV D1) R 90 Coil 90 D090 0=no alarm / 1=alarm
91 High Super Heat (EEV D2) R 91 Coil 91 D091 0=no alarm / 1=alarm
92 High Super Heat (EEV D3) R 92 Coil 92 D092 0=no alarm / 1=alarm
93 EEV Not Closed During Power Off (D1) R 93 Coil 93 D093 0=no alarm / 1=alarm
94 EEV Not Closed During Power Off (D2) R 94 Coil 94 D094 0=no alarm / 1=alarm
95 EEV Not Closed During Power Off (D3) R 95 Coil 95 D095 0=no alarm / 1=alarm
96 Probe S1 (evap. pressure) Error (EEV D1) R 96 Coil 96 D096 0=no alarm / 1=alarm
97 Probe S1 (evap. pressure) Error (EEV D2) R 97 Coil 97 D097 0=no alarm / 1=alarm
98 Probe S1 (evap. pressure) Error (EEV D3) R 98 Coil 98 D098 0=no alarm / 1=alarm
99 Probe S3 (suction temp.) Error (EEV D1) R 99 Coil 99 D099 0=no alarm / 1=alarm
100 Probe S3 (suction temp.) Error (EEV D2) R 100 Coil 100 D100 0=no alarm / 1=alarm
101 Probe S3 (suction temp.) Error (EEV D3) R 101 Coil 101 D101 0=no alarm / 1=alarm
102 LAN Disconnected (EEV D1) R 102 Coil 102 D102 0=no alarm / 1=alarm
103 LAN Disconnected (EEV D2) R 103 Coil 103 D103 0=no alarm / 1=alarm
104 LAN Disconnected (EEV D3) R 104 Coil 104 D104 0=no alarm / 1=alarm
105 Comp.3 HP Tripped R 105 Coil 105 D105 0=no alarm / 1=alarm
106 Comp.3 LP Tripped R 106 Coil 106 D106 0=no alarm / 1=alarm

47
BMS ± VARIABLE LIST

CITEC MODBUS BACnet


Address Description Type Address Type Obj._Inst. Obj_Name Remark
107 Alarm Pressure Probe 3 Failed R 107 Coil 107 D107 0=no alarm / 1=alarm
108 Alarm High Discharge Pressure 3 R 108 Coil 108 D108 0=no alarm / 1=alarm
109 Warning High Discharge Pressure 3 R 109 Coil 109 D109 0=no alarm / 1=alarm
110 Alarm CPY internal error Alarm R 110 Coil 110 D110 0=no alarm / 1=alarm
111 Alarm CPY parameters corrupted R 111 Coil 111 D111 0=no alarm / 1=alarm
113 Dew point Temp Control Status R 113 Coil 113 D113 0=Disable / 1=Enable

48
BMS ± VARIABLE LIST
B. INTEGER VARIABLE

CITEC MODBUS BACnet


Address Description Type Address Type Obj._Inst. Obj_Name Remark
1 Day R 129 Register 1001 I001
2 Day week R 130 Register 1002 I002
3 Hour R 131 Register 1003 I003
4 Last history alarm event read R 132 Register 1004 I004
5 History alarm event R 133 Register 1005 I005 refer Note Integer Var.
6 History day R 134 Register 1006 I006
7 History hour R 135 Register 1007 I007
8 History minute R 136 Register 1008 I008
9 History month R 137 Register 1009 I009
10 History year R 138 Register 1010 I010
11 Minute R 139 Register 1011 I011
12 Month R 140 Register 1012 I012
13 Unit address in LAN R 141 Register 1013 I013
14 Year R 142 Register 1014 I014
15 Unit status R 143 Register 1015 I015 refer Note Integer Var.
16 Fan run hours ( x 1000) R 144 Register 1016 1016
17 Conductivity (uS/cm) R 145 Register 1017 I017
18 Fan run hours R 146 Register 1018 1018
19 Compressor 1 run hours ( x 1000) R 147 Register 1019 1019
20 Compressor 1 run hours R 148 Register 1020 1020
21 Compressor 2 run hours ( x 1000) R 149 Register 1021 1021
22 Compressor 2 run hours R 150 Register 1022 1022
23 Rotation day (time zone rotation) R/W 151 Register 1023 I023
24 Delay time off fan R/W 152 Register 1024 I024
25 Delay time on fan R/W 153 Register 1025 I025
26 Derivative time R/W 154 Register 1026 I026
27 Function delay time R/W 155 Register 1027 I027
28 Compressor 3 run hours ( x 1000) R 156 Register 1028 1028
29 Compressor 3 run hours R 157 Register 1029 1029
30 Rotation time hour change (time zone) R/W 158 Register 1030 I030
31 Flushing interval time (hours) R/W 159 Register 1031 I031
32 Inactivity drain interval time (days) R/W 160 Register 1032 I032
33 Heater 1 run hours ( x 1000) R 161 Register 1033 1033
34 Integral time R/W 162 Register 1034 I034
35 Low pressure run delay time R/W 163 Register 1035 I035
36 Low pressure start delay time R/W 164 Register 1036 I036
37 Humidifier run hours ( x 1000) R 165 Register 1037 1037
38 Humidifier run hours R 166 Register 1038 1038
39 Heater 1 run hours R 167 Register 1039 1039
40 Heater 2 run hours ( x 1000) R 168 Register 1040 1040
41 Heater 2 run hours R 169 Register 1041 1041
42 Rotation time minute change (time zone) R/W 170 Register 1042 I042
43 Enable schedule on/off R/W 171 Register 1043 I043
44 Rotation type R/W 172 Register 1044 I044 refer Note Integer Var.
45 Monday off hour (A) (Sch. On Off) R/W 173 Register 1045 I045
46 Monday off minute (A) (Sch. On Off) R/W 174 Register 1046 I046
47 Tuesday off hour (A) (Sch. On Off) R/W 175 Register 1047 I047
48 Tuesday off minute (A) (Sch. On Off) R/W 176 Register 1048 I048
49 Wednesday off hour (A) (Sch. On Off) R/W 177 Register 1049 I049
50 Wednesday off minute (A) (Sch. On Off) R/W 178 Register 1050 I050
51 Thursday off hour (A) (Sch. On Off) R/W 179 Register 1051 I051
52 Thursday off minute (A) (Sch. On Off) R/W 180 Register 1052 I052

49
BMS ± VARIABLE LIST
CITEC MODBUS BACnet
Address Description Type Address Type Obj._Inst. Obj_Name Remark
53 Friday off hour (A) (Sch. On Off) R/W 181 Register 1053 I053
54 Friday off minute (A) (Sch. On Off) R/W 182 Register 1054 I054
55 Saturday off hour (A) (Sch. On Off) R/W 183 Register 1055 I055
56 Saturday off minute (A) (Sch. On Off) R/W 184 Register 1056 I056
57 Sunday off hour (A) (Sch. On Off) R/W 185 Register 1057 I057
58 Sunday off minute (A) (Sch. On Off) R/W 186 Register 1058 I058
59 Monday on hour (A) (Sch. On Off) R/W 187 Register 1059 I059
60 Monday on minute (A) (Sch. On Off) R/W 188 Register 1060 I060
61 Tuesday on hour (A) (Sch. On Off) R/W 189 Register 1061 I061
62 Tuesday on minute (A) (Sch. On Off) R/W 190 Register 1062 I062
63 Wednesday on hour (A) (Sch. On Off) R/W 191 Register 1063 I063
64 Wednesday on minute (A) (Sch. On Off) R/W 192 Register 1064 I064
65 Thursday on hour (A) (Sch. On Off) R/W 193 Register 1065 I065
66 Thursday on minute (A) (Sch. On Off) R/W 194 Register 1066 I066
67 Friday on hour (A) (Sch. On Off) R/W 195 Register 1067 I067
68 Friday on minute (A) (Sch. On Off) R/W 196 Register 1068 I068
69 Saturday on hour (A) (Sch. On Off) R/W 197 Register 1069 I069
70 Saturday on minute (A) (Sch. On Off) R/W 198 Register 1070 I070
71 Sunday on hour (A) (Sch. On Off) R/W 199 Register 1071 I071
72 Sunday on minute (A) (Sch. On Off) R/W 200 Register 1072 I072
73 Rotation hour (automatic rotation) R/W 201 Register 1073 I073
74 Discharge pressure 3 R 202 Register 1074 I074
75 Unit 1 rotation configuration R/W 203 Register 1075 I075 refer Note Integer Var.
76 Unit 2 rotation configuration R/W 204 Register 1076 I076 refer Note Integer Var.
77 Unit 3 rotation configuration R/W 205 Register 1077 I077 refer Note Integer Var.
78 Unit 4 rotation configuration R/W 206 Register 1078 I078 refer Note Integer Var.
79 Unit 5 rotation configuration R/W 207 Register 1079 I079 refer Note Integer Var.
80 Unit 6 rotation configuration R/W 208 Register 1080 I080 refer Note Integer Var.
81 Unit 7 rotation configuration R/W 209 Register 1081 I081 refer Note Integer Var.
82 Unit 8 rotation configuration R/W 210 Register 1082 I082 refer Note Integer Var.
83 No. of stand-by units R/W 211 Register 1083 I083
84 Stage delay for PID control (s) R/W 212 Register 1084 I084
85 Monday off hour (B) (Sch. On Off) R/W 213 Register 1085 I085
86 Monday off minute (B) (Sch. On Off) R/W 214 Register 1086 I086
87 Tuesday off hour (B) (Sch. On Off) R/W 215 Register 1087 I087
88 Tuesday off minute (B) (Sch. On Off) R/W 216 Register 1088 I088
89 Wednesday off hour (B) (Sch. On Off) R/W 217 Register 1089 I089
90 Wednesday off minute (B) (Sch. On Off) R/W 218 Register 1090 I090
91 Thursday off hour (B) (Sch. On Off) R/W 219 Register 1091 I091
92 Thursday off minute (B) (Sch. On Off) R/W 220 Register 1092 I092
93 Friday off hour (B) (Sch. On Off) R/W 221 Register 1093 I093
94 Friday off minute (B) (Sch. On Off) R/W 222 Register 1094 I094
95 Saturday off hour (B) (Sch. On Off) R/W 223 Register 1095 I095
96 Saturday off minute (B) (Sch. On Off) R/W 224 Register 1096 I096
97 Sunday off hour (B) (Sch. On Off) R/W 225 Register 1097 I097
98 Sunday off minute (B) (Sch. On Off) R/W 226 Register 1098 I098
99 Monday on hour (B) (Sch. On Off) R/W 227 Register 1099 I099
100 Monday on minute (B) (Sch. On Off) R/W 228 Register 1100 I100
101 Tuesday on hour (B) (Sch. On Off) R/W 229 Register 1101 I101
102 Tuesday on minute (B) (Sch. On Off) R/W 230 Register 1102 I102
103 Wednesday on hour (B) (Sch. On Off) R/W 231 Register 1103 I103
104 Wednesday on minute (B) (Sch. On Off) R/W 232 Register 1104 I104
105 Thursday on hour (B) (Sch. On Off) R/W 233 Register 1105 I105
106 Thursday on minute (B) (Sch. On Off) R/W 234 Register 1106 I106
107 Friday on hour (B) (Sch. On Off) R/W 235 Register 1107 I107

50
BMS ± VARIABLE LIST

CITEC MODBUS BACnet


Address Description Type Address Type Obj._Inst. Obj_Name Remark
108 Friday on minute (B) (Sch. On Off) R/W 236 Register 1108 I108
109 Saturday on hour (B) (Sch. On Off) R/W 237 Register 1109 I109
110 Saturday on minute (B) (Sch. On Off) R/W 238 Register 1110 I110
111 Sunday on hour (B) (Sch. On Off) R/W 239 Register 1111 I111
112 Sunday on minute (B) (Sch. On Off) R/W 240 Register 1112 I112
113 Air flow failed alarm delay time (s) R/W 241 Register 1113 I113
114 Discharge pressure 1 R 242 Register 1114 I114
115 Discharge pressure 2 R 243 Register 1115 I115
116 Enable remote on/off R/W 244 Register 1116 I116
118 Enable Dew Point Temp. Control R/W 242 Register 1114 I114
119 Dew Point Temp. Setpoint R/W 243 Register 1115 I115
121 D.P. Temp. Dehum proportional band R/W 243 Register 1115 I115
122 D.P. Temp. Humidify proportional band R/W 244 Register 1116 I116

51
BMS ± VARIABLE LIST

C. ANALOGUE VARIABLE
CITEC MODBUS BACnet
Address Description Type Address Type Obj._Inst. Obj_Name Remark
1 Dehum. Demand (%) R 1 Register 1 A001
2 Return air humidity (%) R 2 Register 2 A002
3 Return air temperature (oC) R 3 Register 3 A003
4 Cooling demand (%) R 4 Register 4 A004
5 Heating demand (%) R 5 Register 5 A005
6 Humidify demand (%) R 6 Register 6 A006
7 Cooling dead zone R/W 7 Register 7 A007
8 % of cooling to enable dehum R/W 8 Register 8 A008
9 Cooling proportional band R/W 9 Register 9 A009
10 Dehum dead zone R/W 10 Register 10 A010
11 Valve opening when dehum (%) R/W 11 Register 11 A011
12 Dehum proportional band R/W 12 Register 12 A012
13 Heating dead zone R/W 13 Register 13 A013
14 Heating proportional band R/W 14 Register 14 A014
15 Humidity alarm band-High (%) R/W 15 Register 15 A015
16 Return air humidity calibration (%) R/W 16 Register 16 A016
17 Return air temperature calibration (oC) R/W 17 Register 17 A017
18 Humidity set point (%) R/W 18 Register 18 A018
19 Temperature set point (oC) R/W 19 Register 19 A019
20 Temperature alarm band-High (oC) R/W 20 Register 20 A020
21 Water in temperature (oC) R 21 Register 21 A021
22 CW Valve 1 Opening (%) R 22 Register 22 A022
23 Humidity dead zone R/W 23 Register 23 A023
24 Humidity proportional band R/W 24 Register 24 A024
25 Steam production (kg/h) R 25 Register 25 A025
26 Current (A) R 26 Register 26 A026
27 Water out temperature (oC) R 27 Register 27 A027
28 Differential temperature (oC) R/W 28 Register 28 A028 Free Cooling unit only
29 FSC 1 Output (%) R 29 Register 29 A029
30 FSC 2 Output (%) R 30 Register 30 A030
31 FSC 3 Output (%) R 31 Register 31 A031
32 EEV 1 Opening R 32 Register 32 A032
33 EEV 1 Superheat (oC) R 33 Register 33 A033
34 EEV 1 Suction Temp (oC) R 34 Register 34 A034
35 EEV 1 Suction Pressure (psig) R 35 Register 35 A035
36 EEV 2 Opening R 36 Register 36 A036
37 EEV 2 Superheat (oC) R 37 Register 37 A037
38 EEV 2 Suction Temp (oC) R 38 Register 38 A038
39 EEV 2 Suction Pressure (psig) R 39 Register 39 A039
40 EEV 3 Opening R 40 Register 40 A040
41 EEV 3 Superheat (oC) R 41 Register 41 A041
42 EEV 3 Suction Temp (oC) R 42 Register 42 A042
43 EEV 3 Suction Pressure (psig) R 43 Register 43 A043
44 EC Fan output (%) R 44 Register 44 A044 EC Fan option only
45 Dew Point Temperature (oC) R 45 Register 45 A045
46 Dew Point Temp Dehum dead zone R/W 46 Register 46 A046
47 Dew Point Temp Humidify dead zone R/W 47 Register 47 A047
48 Temperature alarm band-Low (oC) R/W 48 Register 48 A048
49 Humidity alarm band-Low (%) R/W 49 Register 49 A049
50 Dew Point Temp alarm band-Low (oC) R/W 50 Register 50 A050
51 Dew Point Temp alarm band-High (oC) R/W 51 Register 51 A051
52 Alarm Sensitivity (%) R/W 52 Register 52 A052
53 CW Valve 2 Opening (%) R 53 Register 53 A053 Dual CW unit only
Remark:
The BMS variable list is applicable to software version PCO5-1.35 onwards.

52
BMS ± VARIABLE LIST

NOTE FOR INTEGER VARIABLE


Address Integer Description Address Integer Description
5 0 History deleted 5 52 Eeprom Error (EEV D2)
1 Comp. 1 high pressure trip 53 Eeprom Error (EEV D3)
2 Comp. 2 high pressure trip 54 MOP Time Out (EEV D1)
3 Comp. 1 low pressure trip 55 MOP Time Out (EEV D2)
4 Comp. 2 low pressure trip 56 MOP Time Out (EEV D3)
5 High temp. 57 LOP Time Out (EEV D1)
6 Low temp. 58 LOP Time Out (EEV D2)
7 High humidity 59 LOP Time Out (EEV D3)
8 Low humidity 60 Low Super Heat (EEV D1)
9 Filter blocked 61 Low Super Heat (EEV D2)
10 Heater overheat 62 Low Super Heat (EEV D3)
11 Airflow failed 63 High Super Heat (EEV D1)
12 Water on floor 64 High Super Heat (EEV D2)
13 Drip tray full 65 High Super Heat (EEV D3)
14 Auxiliary alarm 1 66 EEV Not Closed During Power Off (D1)
15 Auxiliary alarm 2 67 EEV Not Closed During Power Off (D2)
16 Auxiliary alarm 3 68 EEV Not Closed During Power Off (D3)
17 Alarm high conductivity 69 Probe S1 Error (EEV D1)
18 Warning high conductivity 70 Probe S1 Error (EEV D2)
19 Alarm Humidifier high current 71 Probe S1 Error (EEV D3)
20 Alarm CPY serial disconnected 72 Probe S3 Error (EEV D1)
21 Alarm Humidifier lack water 73 Probe S3 Error (EEV D2)
22 Alarm low production 74 Probe S3 Error (EEV D3)
23 Drain alarm 75 LAN Disconnected (EEV D1)
24 Alarm cylinder full 76 LAN Disconnected (EEV D2)
25 Warning Clean cylinder 77 LAN Disconnected (EEV D2)
26 Alarm CPY Offline 78 Comp.3 HP Tripped
27 Alarm Replace Humidifier Cylinder 79 Comp.3 LP Tripped
28 Cylinder maintenance mandatory 79 Pressure Probe 3 Failed
29 Cylinder maintenance recommended 81 Alarm High Discharge P3
30 pLAN Error 82 Warning High Discharge P3
31 Unit health check 83 Power Failure *
32 Unit run expired 84 Power Restore *
33 Water in high temp. 85 Unit Start *
34 Alarm high disch. P1 86 Unit Stop *
35 Alarm high disch. P2 87 Alarm Acknowledge *
36 Warning high disch. P1 88 Alarm CPY: E1 Config params. corrupted
37 Warning high disch. P2 89 Alarm CPY: E0 Internal Error
38 Alarm RAT sensor failed 90 Alarm Humidifier Foam Presence
39 Alarm RAH sensor failed 15 0 Unit On
40 Pressure probe 1 failed 1 Off by alarm
41 Pressure probe 2 failed 2 Off by supervisory
42 Unit off alarm 3 Off by schedule
43 Clock board error 4 Off by remote input
44 Anti freeze 1 tripped 5 Off by keyboard
45 Anti freeze 2 tripped 7 Standby
46 Water in sensor failed 44 0 Automatic rotation
47 Water out sensor failed 1 Timezones rotation
48 Coil temp.1 sensor failed 2 Manual rotation
49 Coil temp.2 sensor failed 75-82 0 Present/Rotation
50 Return air humidity sensor out of range 1 Present/No Rotation
51 Eeprom Error (EEV D1) 2 Absent
* : alarm log can be enabled/disabled at Alarm Setup

53
54
Version 1.0/2016/GEN5

You might also like