Professional Documents
Culture Documents
bin
Chapter 3 Calibration
Chapter 4 Maintenance
Chapter 5 Function
BB / JTU 25.06.2000
Service documentation series KB/KBF
Introduction
The KBF series exists since 1993 in following states:
(Controler / Humidity control)
EM2-Board
L3-Board
The EM2-Board was used since beginning of Production of the KBF climatic
chamber.
D2 Controller
9/1997 Æ
L3-Board
The SPS-Control and the Binder Humidity Board are in use since:
KBF115 Æ 990086
KBF240 Æ 990176
KBF720 Æ 990444
BB / JTU 25.06.2000
Service documentation series KB/KBF
Chapter 1
Trouble Shooting
KB/KBF
Fault description Fault cause
No or to low cold output x Ambient temperature 22°C? For each Kelvin that the ambient
temperature is above 22°C, the cold output will be approx. 1.5K
lower.
x Compressor switched on? Warm air must be present on the left of
the unit (condenser). Copper pipe between compressor and
condenser must be hot.
x KB: Measure the cold output on the RD2.1 controller
x KBF: Check the operation of the Solid valve
x Condenser is soiled
x Air-Supply troubled
x In normal operation, the pipe of the pressure side had to heat up
to 50°CÆ70°C. If not, there is a fault at the compressor.
x If everything is in order electrically, it is likely that the cold gas has
leaked. Critical points are all bends, the condenser (soldering
joint) or an old chamber (rock wool).
BB / JTU 25.06.2000
Service documentation series KB/KBF
Check List - Humidity too less (D2-Controller and SM-Controller)
Most common faults with KBF is too less humidity take this list for trouble shooting
Pos. Remark
1 Water conductivity
2 Waterinlet pressure 1-10bar
3 Wateroutlet without any counterpressure
4 Test function of the Solid valve with 230V
5 Test the swimming switch, down position OK (located behind the steam cylinder)
6 Set controller to 80% r.H.
7 Measure voltage at controller pin 343 and 342 (new D2 controller with the green text
display) , or between pin 42-43 (old SM controller) The correct voltage for max. steam
production is 4,5 V
8 Measure voltage 4 and 5 from the humidity board (target of above point)
9 Water level in the steamgenerator (plastic bottle)?
10 Measure current which is flowing between the electrodes
11 L3 board: LED at the humidity board (LED shows to the bottom)
green voltage OK
yellow steam production
red blinking error message, permanent steam generator full
Or in case of old EM2-board:
Blinking red LED means faulty humidity board
Highlighted red LED means max. filling level of the steam cylinder is reached (means too
less water conductivity)
BB / JTU 25.06.2000
Service documentation series KB/KBF
Retrofitting of a RS232 interface card on SM humidity controller with KBF
series up to 9/1997
To enable communication between APT-COM or a other data acquisition system with a SM humidity
controller of elder KBF climatic chambers it is necessary to retrofit a interface card inside the
controller.
A) Unscrew the controller with the screw at its B) place a rectangle hole (size
front panel to pull it out of its frame. Insert the 42 X 11 mm) for the interface
interface card BINDER Part. No. 5014-0036 to socket trough the rear wall
this position: directly beside the interface
socket which already exists for
the RD2 temperature controller
RxD No . 91 ------- 2
SM humidity controller for KBF until September TxD No- 93 ------- 3
1997 GND No. 90 ------7
BB / JTU 25.06.2000
Service documentation series KB/KBF
To enter the parameter level go on as following:
x Press the and keys twice together. The following display will appear:
---
Sd.01
You can toggle through the levels with button “W“ from one parameter to the next
e.g. Sd.01 –Sd.02 - Sd.03...
On level Sd. 01 and Sd 04 you have to go in by pressing Enter to change parameter C112 resp.
C411,C412 and C413 as descried on following parameter list.
Sd01
C111
C112 0001
C113
C114
C115
C121 All other parameters remain unchanged.
Sd02
C211 Confirm any change with enter and go after all is
C221 done out with exit.
C222
C223 After this adjusting set the DIP-switch No.2 back to
C231 ON to avoid further changes.
Sd03
C311
C312
C313
Sd04
C411 0001
C412 0810
C413 0000
C414
Sd05
and so on
BB / JTU 25.06.2000
Service documentation series KB/KBF
Chapter 2
Cooling System
Refrigerants used
The following refrigerants have been and/or are used for units with cooling systems. The quantity
given here is the maximum filling quantity. R12 and R502 refrigerants are halogenised
refrigerants, which may no longer be used. However, a replacement coolant is available on request.
APT-Line
KB; KBF; KBWF; KBW 53, 115, 240 R134a; 300g
KB; KBF; KBWF; KBW 720 R134a; 500g
Since September 98
KB 53, 115 R134a; 150g
KB, KBW 240 R134a; 300g
KB, KBW 720 R134a; 500g
PT-Line
KBW all sizes R12; 500g
KB all sizes R12; 300g
Compressors used
KB/KBF/KBW/KBWF 53, 115 and 240 GL60TB
KB/KBF/KBW/KBWF 720 GP12TB
Chamber Description
KB/KBF/KBW/KBWF 53,115 and GL60TB
240
KB/KBF/KBW/KBWF 720 GP12TB
BB / JTU 25.06.2000
Service documentation series KB/KBF
¾ Compressor
¾ Evaporator (inside the chamber)
¾ Dehumidifier
¾ Liquefier
¾ Capilary Tube
¾ Semiconductor Relay (K2)
BB / JTU 25.06.2000
Service documentation series KB/KBF
Assumption: No Cooling
Assumption: No Cooling
BB / JTU 25.06.2000
Service documentation series KB/KBF
Functions:
A) Measuring voltage 230V AC on the filling level detector electrode of the steam cylinder.
B) Measuring of current between the electrodes for steam production
C) Measuring of the low-level DC voltage which is the humidity demand coming from the process
controller DICON 1000/1001
As well forward transfer o this states as binary messages to the PLC humidity control as signals
0 or +24V DC.
Description A)
A pair of electrodes in a plastic container is set under voltage 230V AC to generate steam for
controlled humidification.
This container is filled with tap water via a solenoid valve until the current between the two electrodes
reaches about 2A.. In case this maximum current is not reached until maximum filling of the container
the filling limitation electrode gets 230V AC (plug connectors L1/B1 against N)
+24V are given out via plug connector “SPS I 0.1” to the PLC as message that maximum filling level is
reached.
Caution !
High Voltage about plug connectors L1/B1 and N
Do not touch!
Description B)
The alternating current trough the steam electrodes is brought via a short induction path to the
BINDER humidity board. Loop between plug connectors L1 and L2.
The exact setting of the maximum permissible current between the steam electrodes becomes
adjusted via potentiometer R4 or R5 to set the switching point to 2A as limit for the current through the
steam electrodes.
With smaller current than 2A the red LED illuminates and plug connector SPS I 0.5 gives +24V DC to
the PLC as message that the 2A not reached yet..
With higher current through the electrodes the red LED extinguishes and the voltages at plug
connectors SPS I 0.5 gets reduced to 0V as message that the 2A is reached.
Caution !
High Voltage about plug connectors L1 and L2
Do not touch!
BB / JTU 25.06.2000
Service documentation series KB/KBF
Description C)
Humidity demand is given out from the process controller types DICON 1000/1001 (= D2 and PD2) as
a binary signal 0V or 24V to the control side of the two solid state relays for the electrode current path
(see wiring diagram KBF).
0V = no humidity demand
24V = steam production necessary
The binary signal is taken there and gets via plug connector HLR + and – to the BINDER humidity
board.
The Binder Humidity Board switches +24V on plug connector SPS I 0.0 as message for the SPS that
there is a humidity demand.
L2
induction
path
230V AC
L1
BB / JTU 25.06.2000
Service documentation series KB/KBF
* On this point the ( IC pin 3) the voltage divider between the two adjustment potentiometers
for the max. electrode current can be measured. Default setting is somewhat higher than 12 V.
This voltage divider determines the switching point for the water inlet valve.
The voltage on IC pin 3 and therewith the maximum tolerated electrode current can be
adjusted by turning on one of them.
Following table shows the coherence between measured voltages on IC pin 3 and the current through
the electrodes inside the steam cylinder.
Due to the tolerances of the components this values can not be taken as exact ones or all chambers.
But the ratio between difference in current and difference in voltage are constant for all KBF with PLC
and BINDER humidity board. It is round about 0,33V/A.
BB / JTU 25.06.2000
Service documentation series KB/KBF
Chapter 3
Calibration
Binder controllers can be adjusted by the customer to suit his particular operating conditions, i.e. the
controller has a calibration mode which, for example, can be used to match the temperature in the
chamber to the one shown on the controller‘s display.
Binder calibrates each chamber before it is dispatched to the customer. High-quality measuring
systems are used for this, whose accuracy is tested annually. However, if the measured temperature
does not match the displayed temperature, please follow the instructions below.
Important:
The values on the above chart can only be used if the value of measurement uncertainty on the
calibration certificate of the measuring instrument is smaller than the values of the chart.
When this is not the case, then you must take as limit value for an adjustment the
measurement uncertainty value of the calibration certificate.
Adjustment of the working set point. One and Two points adjustment.
Ideally the adjustment should be made to the customer’s most used set points.
Example: the customer works at 37°C, adjustment of the controller at 37°C.
If the customer uses different set points, the following instructions have to be taken in consideration:
When the difference of temperature between the most used set points is small:
Choose an adjustment value lying between this temperatures.
Example : The customer ‘s set points are 40 and 60°C, adjustment of the controller at 50°C.
BB / JTU 25.06.2000
Service documentation series KB/KBF
After an adjustment, the following chart gives you the tolerance permitted on one control-
measurement over the complete operating range.
Type of chamber type of controller range tolerances over the
compl. operating range
KB, KBW RD2 0°C up to 99,9°C +/-3K
The deviation over the complete operating range should be written down on a chart and fixed to the
chamber for reference.
The following chart shows you the optimal values for a two points adjustment according to the
correspondent controller.
After an adjustment, the following chart gives you the tolerance permitted on one control-
measurement over the complete operating range.
The deviation over the complete operating range should be written down on a chart and fixed to the
chamber for reference.
BB / JTU 25.06.2000
Service documentation series KB/KBF
x Operate the unit until it reaches the required nominal temperature and allow to settle. When the
unit has reached the required temperature, please allow it to continue running for approx. 1 hour -
only then is the unit reliably set for calibration.
x Read off the temperature displayed on your measuring instrument and compare this with the
controller display.
x Any variation can be changed on the controller. To do this, press the start/stop button and stop
the controller. Now press the actual/set value button, the mode button, the arrow up and arrow
down buttons simultaneously. A point will flash in the display. Now you can input the temperature
displayed on your measuring instrument by repeatedly pressing the button “arrow up” or “down”.
Confirm the entry by pressing the actual/set value button. Now press the start/stop button to start
the controller.
Re-check the input temperature with your measuring instrument once the unit has been re-
heated. This adjustment on the controller must be performed rapidly, in order to ensure that any
variation is as small as possible.
SM Calibrating instructions
x Switch the unit off at the main switch. Turn the fastening screw of the controller tray (lower centre
of the control panel of the controller) anti-clockwise until you can remove the controller tray.
x The S 301 multiple circuit breaker (large DIP Switch Block) is located on the CPU board. In order
to access the appropriate sub-menu for calibration, DIP switch 2 must be set.
x Push the controller tray back into the housing and turn the fastening screw in the clockwise
direction again.
x Insert the humidity measuring instrument probe at the measuring point, located in the centre of
the usable volume.
x In order to perform a precise calibration, it is essential that the nominal temperature of the device
is reached and remains steady (factory setting 37°C).
x Operate the unit until the required humidity is reached and allow to settle (cf. Point 10). When the
unit has reached the required humidity, please allow it to continue running for approx. 0.5 hours -
only then is the unit reliably adjusted and ready for calibration.
x Read off the humidity displayed on your measuring instrument (%r.H.) and compare this with the
controller display.
x If the controller display deviates from the measured value, parameter C611 and/or C612 must be
re-entered into the ”SD06” sub-menu.
Two fixed points can be set with C611 and C612, where C611 corresponds to the pivot of the
characteristic curve and C612 corresponds to the top fixed point.
It is also possible to change only the top fixed point ”C612”, whereby a linear displacement of the
whole characteristic curve is obtained. This method is only recommended if you are working with
one humidity value.
If you are working with two or more humidity values, you must proceed as follows:
Enter the measured value (lower value) at C611 (you must do this even if the value of the
measuring device does not deviate from the controller value !).
Enter a set value again (higher than the first), and wait for a steady condition again. Compare the
controller display with the value displayed on the measuring device. If there is a variation you
must enter the value displayed on the measuring device at C612.
You can return to the original menu by using the ”Enter” key and then ”Pgm”.
x Switch the unit off at the main switch. Remove the controller tray from the controller housing as
described above. Set the S 301.2 separate switch and insert the controller tray into the controller
housing again.
BB / JTU 25.06.2000
Service documentation series KB/KBF
D2 KBF Calibrating instructions
G R U N D S T E LLU N G
5X P gm
C O N F IG U R A T IO N 2 E xit
E nter
C O D E -N R . 0000
3X n
C ode-N r. 0003
E nter
D IS P LA Y
3X P gm
R E C A LIB R A T IO N E xit
C O D E -N R . 0000
4X n
C ode-N r. 0004
E nter
C O R R E C T IO N C O R R E C T IO N
IN P U T 2 IN P U T 1
P gm (hum idity) P gm (tem perature)
E nter E nter
F U LL S C A LE 1 P gm S T A R T V A LU E 0
S et w ith m n S et w ith m n
E nter E nter
E xit
For reset the calibration please set the start value and the end value to the same value. After reset the
start value is set to 0 and the end value to 1.
As from the firmware version E045.01.100 you come directly into the menu re-calibration with the
buttons and , which have to be pressed together for about 10 sec.
The firmware inquiry is effected by pressing the buttons PGM and at the same time.
BB / JTU 25.06.2000
Service documentation series KB/KBF
Chapter 4
Maintenance
Cooled incubators and climatic chambers
Binder’s cooled incubators and climatic chambers allow you to achieve constant conditions with a
temperature capacity of 0.0°C to 99.9°C.
Cooled incubators are used in biotechnology, medicine, the food industry, pharmaceutical and
cosmetics industry, botany and zoology.
Climatic chambers are intended for stability and durability tests for pharmaceutical products. Their
constant climatic conditions also make them suitable for sample conditioning for material tests of
paper, textiles, plastics or building materials.
The growth chamber variant also enables the simulation of day/night conditions.
The precise control technology, the efficient refrigeration system and humidification system allow the
greatest possible maintenance intervals.
During maintenance, all mechanical and electrical as well as electronic components are subjected to a
visual and functional inspection.
In addition, the control systems and sensors are checked with special
measuring instruments and re-adjusted if necessary.
BB / JTU 25.06.2000
Service documentation series KB/KBF
BB / JTU 25.06.2000
Service documentation series KB/KBF
BB / JTU 25.06.2000
Service documentation series KB/KBF
Symbol Meaning
X Defects
without error
/ not existence
BB / JTU 25.06.2000
Service documentation series KB/KBF
Chapter 5
Function
80,00°C
Temperature
70,00°C
60,00°C
50,00°C
40,00°C
30,00°C
20,00°C
00,00°C
00:00
12:30
21:00
33:30
46:00
58:00
70:30
83:00
94:00
99:00
Figure 4.1
80,00°C
Temperatur
60,00°C
40,00°C
00,00°C
00:00
04:00
17:00
29:00
41:30
54:00
67:00
79:00
92:00
Figure 4.2
BB / JTU 25.06.2000
Service documentation series KB/KBF
Hot gas injection
In the case of the KBF unit, hot gas injection with the PD2 and D2 controllers is a standard function.
The humidity accuracy is influenced by the hot gas injection. When hot gas is injected into the
dehumidification tube humidity is released, and therefore the humidity sensor registers a greater
humidity at the time of injection.
The function is switched off by the controller when the nominal temperature exceeds 23°C.
The following injection times are set in the controllers when the hot gas injection is activated:
The following menu shows how the hot gas injection can be switched off at an actual temperature of
25°C +/- 1°C. This flow chart is for controller version E045.01.1001.
GRUNDSTELLUNG
X x Pgm
CONFIGURATION 1
Enter
Enter
1XPGM
LIMIT COMPARATOR
Ex.. 90s evtl. shorten 23°C change to 25°C Ex. 94s evtl. extend
Figure 4.3
BB / JTU 25.06.2000
Service documentation series KB/KBF
Humidification
Humidification occurs through a steam cylinder in the humidity module. The humidity is measured by a
capacitive humidity sensor (4-20mA) which is temperature-compensated. The controller drives the
humidity board via a 0-10V output. The humidity board charges two electrodes which are located in
the steam cylinder. The current which flows between the two electrodes can be regulated via the water
level.
Dehumidification
In order to maintain a constant humidity in the KBF, the inner chamber is permanently dehumidified.
Cold gas is conducted into the W pipe after the drier by means of a capillary tube. The
W pipe is a copper pipe which is located behind the rear panel between the interior and exterior
chambers.
Due to the cold gas, the W pipe is the coldest point in the inner chamber. The humidity condenses on
the W pipe and then runs down into the steam container.
Hot gas
Before the evaporator the warm cold gas is sprayed into the W pipe by means of an Electro valve,
thus preventing icing up. The pulse duration and pulse length are controlled by the controller.
dryer injection
valve evaporator
solenoid
valve
condenser
capillary tube
compressor
dehumidification
solenoid valve
Hot gas
Figure 4.4
BB / JTU 25.06.2000
Service documentation series KB/KBF
Humidity controller SM
On the controller’s main plate there are 2 plugs strips (E1/E2) which can be plugged onto the front-end
plates. The front-end plated determine the type of signal that can be processed. E1 is in direction
contacts and E2 is in direction front cover.
As the SM controller, the front-end 1 is being used for the humidity sensor.
The power supply for the humidity sensor is put out on Pin 95+ and 96-.
The humidity sensor delivers a signal 0 to 20mA onto the front-end 1 (Pin 111+ and 112-).
Via the exit 1 (Pin 42 a. 43) the humidity control is being controlled by means of a signal 0-10V.
The humidity control switches as follows:
- +
BB / JTU 25.06.2000
Service documentation series KB/KBF
D2/PD2 Controller
When the humidity level in the oven is smaller as the set value, the controller sends, in relation with
the parameter and the temperature, the following voltages:
I = Iges x S1 x L1
I between the electrodes = max. I x V from controller at 15°C x Pot. setting 40%
standard
I = current flowing between the electrodes
Iges = Maximum current
S1 = Voltage signal from controller.
L1 = Setting of the steam output limitation.(Potentiometer P1 on circuit board L3)
BB / JTU 25.06.2000
Service documentation series KB/KBF
Humidification system.
The humidity is produced through steam generated in a container located in the humidity module. The
humidity is measured by a capacitive humidity Sensor (4-20mA) which is temperature compensated.
The controller activates the PLC through a 0-24V output. The humidity circuit board feeds the two
electrodes contained in the steam container. The current flowing through the electrodes is regulated
via the water level.
Dehumidification
In order to maintain a constant humidity in the KBF, the inner chamber is permanently dehumidified.
After the dryer , cold gas is injected through an Electro-valve in the dehumidification evaporators. The
dehumidification evaporators are of the same construction as the cooling evaporators. They are
located behind the rear panel of the inner chamber. (See picture 4:7)
Due to the cold gas, the dehumidification evaporators are the coldest point in the inner chamber. The
humidity condenses on the dehumidification evaporators and then flows down into the steam
container.
Icing prevention.
To prevent the icing of the dehumidification evaporators, the plates are activated alternatively every
3,5 days. To avoid an irregular humidity during this transfer process, the previously inactive evaporator
will be ON for 0,5 seconds and every 30 seconds a 0,5 second will be added. After one hour it will be
constantly ON, and the other dehumidification evaporator will start being deactivated, 0,5 second and
every 30 seconds a 0,5 second deactivation will be added until it is completely deactivated. See
following chart.
Time in second Output SPS Q0.0 Output SPS Q0.1
Electro valve Y3 Electro valve Y4
Electro-valve status Electro- valve status
After 3 days ON OFF ON OFF
0 to 30 s. Constant -- 0,5 s. 29,5 s.
30 to 60 s. Constant -- 1,0 s. 29,0 s.
60 to 90 s. Constant -- 1,5 s. 28,5 s.
90 to 120 s. Constant -- 2,0 s. 28,0 s.
120 to 150 s. Constant -- 2,5 s. 27,5 s.
Etc...
3600 to 3630 s. Constant -- Constant --
3630 to 3660 s. 29,5 s. 0,5 s. Constant --
3660 to 3690 s. 29,0 s. 1,0 s. Constant --
3690 to 3720 s. 28,5 s. 1,5 s. Constant --
Etc...
BB / JTU 25.06.2000
Service documentation series KB/KBF
C apillary tube
Dryer C ooling evaporators
S olenoid-
valve
C ondenser
S olenoid-
valve
C ompressor
Deshumidification evaporators
BB / JTU 25.06.2000
Service documentation series KB/KBF
Chapter 6
Following pictures show the different states of KBF construction mentioned in the
overview of chapter 1.
BB / JTU 25.06.2000
Construction of climatic chambers
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
INTELLIGENTE TEMPERATURTECHNIK
steam cylinder
humidity sensor
INTELLIGENTE TEMPERATURTECHNIK