Professional Documents
Culture Documents
01-2017
Lab Report
Experiment’s Tittle
VARIATION IN REFRIGERENT COEFFICENT OF PERFORMANCE AT VARIOUS OPERATING
CONDITIONS
Scale 1 2 3 4 5
Criteria Poor Acceptable Excellent
1. Introduction • Unable to generate a • Adequately generate • Student capable to generate a
(10 marks) complete theoretical formula theoretical formula with small complete theoretical formula
i.e. only writing the final errors. from the beginning.
formula. • Make some but tolerable • All relevant engineering
• Make many errors in errors in applications of principles and concepts are
applications of engineering engineering principles and accurately and comprehensively
principles and concepts. concepts. demonstrated and applied.
2. Experimental • Unable to produce and • Adequately produce an • Student capable to produce a
Procedure appropriate procedure to run appropriate procedure to run detailed procedure to run the
(10 marks) the experiment. the experiment i.e. missing experiment.
• Having no objective(s). steps in procedure. • Objective clearly defined.
Would not allow experiment • Having objective(s). Would Would allow experiments to
to achieve any goals. allow experiment to achieve achieve goals.
most goals.
3. Data / result and • Unable to present • Adequately present • Students capable to articulate
Sample Calculation experimental result using experimental result using experimental result using
(20 marks) appropriate tables, charts, appropriate tables, charts, appropriate tables, charts,
graphs or other presentation graphs or other presentation graphs or other presentation
formats. formats. formats.
4. Discussion and • Unable to relate theoretical • Adequately relate theoretical • Students capable to relate
Conclusion analysis with experimental analysis with experimental theoretical analysis with
(20 marks) result and their practical result and their practical experimental result and their
implication. implication. practical implication.
• Unable to come out a clear • Conclusion is not clear, but • Student capable to express a
and understandable yet, understandable in such clear and concise conclusion.
conclusion. manner.
Assessment Rubric: Writing Performance Level. 20 marks
Scale 1 2 3 4 5
Criteria Poor Acceptable Excellent
1. Structure • Paragraphs are poorly • Paragraphs are usually well • All paragraphs are well
(5marks) organized; use of sections is organized; use of sections is organized; use of sections is
illogical and hinders logical and generally allows logical and allows easy
document navigation. easy document navigation. navigation through the
document.
2. Graphics, figures, • Figures, tables and equations • Some figures, tables and • All figures, tables and equations
tables and equations. are not clearly or logically equations are logically are clearly and logically
(5marks) identified and fail to support identified and adequately identified and strongly support
the text. support the text. the text.
3. Mechanics • Sentences are poorly written; • Sentences are generally well • Sentences are well written; there
(5marks) numerous incorrect word written; a few incorrect word are no incorrect word choices
choices and errors in choices and errors in grammar, and the text is free of errors in
grammar, punctuation and punctuation and spelling. grammar, punctuation and
spelling. spelling.
4. Formatting and • Report is formatted poorly • Formatting of the report is • Formatting of the report is
references and lacks a quality cover genarally consistent and professional and includes a
(5marks) page and index. adequate,includes a quality professional cover page and
• Fails to correctly report any cover page and index. index.
sources or to utilize • Most sources are correctly • All sources are correctly
appropriate citation forms. reported; appropriate citation reported; appropriate citation
forms are genarally utilized. forms are utilized thoughout.
FACULTY OF MECHANICAL ENGINEERING
UNIVERSITI TEKNOLOGI MARA
40450 SHAH ALAM
SELANGOR DARUL EHSAN
Tel: 03-55435190 Fax: 03-55435160
____________________________________________________________________________________
Experiment’s Title:
______________________________
VARIATION IN REFRIGERENT COEFFICENT OF PERFORMANCE AT VARIOUS OPERATING
CONDITIONS
_________________________________________________________
_______________________________________________________________________________________
Prepared by:
3.0 Data 3
4.0 Discussion 5
Name: MUHAMMAD NUR EZZUDDEAN BIN MISWAN HANIS 5
Student’s ID: 2022971071 5
Name: MUHAMMAD IKHMAL DANIEL BIN ZAWAWI 6
Student’s ID: 2022798531 6
NAME: MUHAMMAD IRFAN BIN MOHD FAISHALL 7
STUDENT ID: 2022970895 7
NAME: MUHAMMAD NABIL FAHMI BIN MOHD FAUZI 8
STUDENT ID: 2022798357 8
NAMA : MUHAMMAD NAJWAN BIN AZMAN HISHAM 9
STUDENT ID : 2022977733 9
5.0 Conclusion 10
Name: MUHAMMAD NUR EZZUDDEAN BIN MISWAN HANIS 10
Student’s ID: 2022971071 10
Name: MUHAMMAD IKHMAL DANIEL BIN ZAWAWI 10
NAME: MUHAMMAD IRFAN BIN MOHD FAISHALL 10
STUDENT ID: 2022970895 10
NAME: MUHAMMAD NABIL FAHMI BIN MOHD FAUZI 11
STUDENT ID: 2022798357 11
NAMA : MUHAMMAD NAJWAN BIN AZMAN HISHAM 11
STUDENT ID : 2022977733 11
6.0 References 12
1.0 Introduction
Without any artificial means, heat will move from warmer to cooler areas. According to
the second rule of thermodynamics, energy cannot be transformed from a low- to a high-
temperature state without some kind of active effort. This is accomplished with the help of a device
known as the refrigerator that is powered by the refrigeration process. The transfer of heat (energy)
from a low-heat domain to a high-heat domain occurs in a cyclical fashion throughout the
refrigeration process. Refrigerators are cyclical devices that remove heat from a certain area
utilising a vapour-compression cycle in order to keep its interior at a constant low temperature.
Compressor, condenser, expansion valve, and evaporator are the four parts of the refrigeration
cycle. The compressor boosts pressure, the condenser dumps heat, the expansion valve releases
pressure, and the evaporator soaks up the leftover warmth. The refrigerant is a working fluid that
must be present for this operation to take place. A fluid or gaseous material, a refrigerant is used
to isothermally transfer heat from a low-temperature source to a high-temperature sink.
1
2.0 Experimental Procedure
2
3.0 Data
3.3 Calculation
𝑃𝑐𝑜𝑛𝑑𝑒𝑛𝑠𝑒𝑟 − 𝑃1 ℎ3 − ℎ𝑓1
○ =
𝑃2 − 𝑃1 ℎ𝑓2 − ℎ𝑓1
● W1 − 2 =ℎ1 - ℎ2
● Since ℎ1 is enthalpy at evaporator so we can use the pressure to interpolate
below using value from table Table A -12.
𝑃𝑒𝑣𝑎𝑝𝑜𝑟𝑎𝑡𝑜𝑟 − 𝑃1 ℎ1 − ℎ𝑔1
○ =
𝑃2 − 𝑃1 ℎ𝑔2 − ℎ𝑔1
● The value of ℎ2 is at superheated so the entropy is equal with process at 1
(𝑠1 = 𝑠2 ) . By interpolating the values from table Table A -12.
𝑃𝑒𝑣𝑎𝑝𝑜𝑟𝑎𝑡𝑜𝑟 − 𝑃1 𝑠 − 𝑠𝑔1
○ =
𝑃2 − 𝑃1 𝑠𝑔2 − 𝑠𝑔1
● From the answer above we can get the ℎ2 from interpolation between
entropy and enthalpy from table superheated Table A-13.
𝑠1=2 − 𝑠1 ℎ − ℎ1
○ =
𝑠2 − 𝑠1 ℎ2 − ℎ2
● q2 − 3 = ℎ3 - ℎ2 + W
3
● The value of ℎ3 is a condenser so we can use the pressure to interpolate
below using value from table Table A -12.
𝑃𝑐𝑜𝑛𝑑𝑒𝑛𝑠𝑒𝑟 − 𝑃1 ℎ3 − ℎ𝑓1
○ =
𝑃2 − 𝑃1 ℎ𝑓2 − ℎ𝑓1
● The value of ℎ2 can be interpolated between entropy and enthalpy from
table superheated Table A-13.
𝑠1=2 − 𝑠1 ℎ − ℎ1
○ =
𝑠2 − 𝑠1 ℎ2 − ℎ2
4
4.0 Discussion
3 Qc 2
=
C
Wc =
P1
4 1
Qe
=
For Load =15
Value of 𝑄′𝑐 = mass flow rate x (ℎ3 − ℎ2 ) = 85.71 x (84.32 - 270.81) = 15.984 kW
Value of 𝑄′𝑒 = mass flow rate x (ℎ1 − ℎ4 ) = 85.71 x (235.52 - 84.32) = 12.959 kW
Value of 𝑊′𝑐 = 𝑃1 = - 35.29 W
The amount that a certain temperature can hold at once is called a load. The cooling load
and the heating load are the two different sorts of loads. The average rate at which heat is removed
from the cold space by refrigeration equipment is known as the cooling load. The rate of heat must
be provided to the air-conditioned room to maintain its temperature is known as the heating load.
Domestic refrigerators are the devices used for storing food. Wet and dry food items like meat,
fish, or fruits are examples of loads used in refrigeration techniques. In addition, electrical
appliances like a computer, radio, or television that emit some heat constitute the majority of the
room's load. Next, the real burden on manufacturing workers, each of whose bodies will radiate
heat into the environment. Therefore the amount of heat that each person will be considered as
load that applied in this experiment.
Based on the theory, coefficient of performance (COP) and load is directly proportional.
Thus, when the value of load increases the COP will decrease. Thermal efficiency for refrigeration
refers to how well work-added energy is converted to net heat output. Economically speaking, the
5
optimal refrigeration cycle is one that uses the least amount of mechanical work or electric energy
while removing the most heat from the inside of the refrigerator (cold reservoir). The relevant ratio
is therefore, and the better the refrigerator, the larger this ratio. The coefficient of performance, or
COP, is the name we give to this ratio. In general, operating circumstances, particularly the
absolute and relative temperatures between the heat sink and the system, have a significant impact
on COP. Condenser temperature and load is directly proportional. So, when the value of load
increases the temperature of the condenser will also increase. This is because, condenser is used
to change the properties of the refrigerant from the gas to liquid. So that it can flow in the
evaporator.
6
bottom line to maintain a high suction pressure, as long as doing so is consistent with the product's
needs.
The temperature difference between the ambient air inlet temperature and the refrigeration
temperature will grow as the load on the condenser increases. This is done to enhance the
amount of heat rejection while maintaining a constant surface area.
B. What is the effect of a cooling medium on the average refrigeration COP? Why?
Because water has a higher heat carrying capacity than air, using it as the cooling
medium instead of air may increase the coefficient of performance (COP). During this
experiment, an air-cooled condenser from a refrigerator was swapped out for a water-
cooled condenser.
C. What do you understand by the term load? Give examples of actual loads in refrigeration
practice in a domestic fridge, in a room, and in a factory.
The term "load" refers to the quantity of heat that must be delivered from the cold
chamber per unit of time, which is also known as refrigeration capacity. When the air
around a container is warmer than the container's inside temperature, sensible and latent
heat enters via its doors. Knowing the position, size, and number of door openings, as
well as the temperature to which they are exposed, will make calculating the heat load of
the leaking air much easier.
A refrigeration system, regardless of its size or sophistication, serves only one purpose.
This function entails transferring heat from an undesirable location or substance to a
location where it can be distributed into air or water. It is critical to be precise.
7
NAME: MUHAMMAD NABIL FAHMI BIN MOHD FAUZI
STUDENT ID: 2022798357
3 Qc 2
=
C
Wc =
P1
4 1
Qe
=
For Load =15
Value of 𝑄′𝑐 = mass flow rate x (ℎ3 − ℎ2 ) = 85.71 x (84.32 - 270.81) = 15.984 kW
Value of 𝑄′𝑒 = mass flow rate x (ℎ1 − ℎ4 ) = 85.71 x (235.52 - 84.32) = 12.959 kW
Value of 𝑊′𝑐 = 𝑃1 = 637.53 W
Heat will naturally move from a hotter zone to one that is cooler. However, heat must be
transmitted from the enclosed space to the outside, which is sometimes hotter than the enclosed
region, in order to cool an enclosed room. Refrigerators are needed for this procedure, which is
regarded as reverse. The refrigeration cycle consisted of four steps. Evaporator, compressor,
condenser, and expansion valve make up the parts.
The area with the highest temperature starts at the compressor, condenser, and expansion
valve inlet. The area with the lowest temperature starts at the expansion valve's outlet and moves
toward the evaporator before ending at the compressor's inlet. The condenser and evaporator both
transmit heat. Heat is delivered to the refrigerant at the evaporator when it travels through the
evaporator fins from the space to be refrigerated. In addition, heat transfer takes place at the
condenser. Heat from the chilled compartment is released to the surroundings at the condenser,
which serves as a reservoir.
However, it should be emphasised that there are differences between the theoretical and
experimental results. Remembering that not all of the components employed are 100% efficient is
the fundamental reason behind this. P-H diagrams and COP are affected by this. Other than that,
8
there were a few mistakes and poor experimentation techniques used during the trial. The first step
is to wait for the unit to stabilise. But because of time restrictions, we had to complete the
experiment quickly and did not allow enough time for the unit to stabilise. A few of the figures
were recorded while the reading varied. Second, there could occasionally be parallax inaccuracies,
for instance when obtaining measurements from gauges.
From the results of the experiment that has been carried out, I found that the more load that
is applied, the higher the temperature of the evaporator and condenser exit. This happens because
both components have to work hard to get an idle temperature. This causes the enthalpy in the
system to also change. However, we can solve this problem by making a comparison with table A
12. Therefore, the coefficient of performance also changes according to the added load in this
system. I can conclude that the more load is added, the less performance is produced in a system.
This is because I found that these two machines, the evaporator and the condenser, had to work
hard to reach the optimum temperature. Next, after doing all the calculations for this system, I have
obtained the appropriate value for Qc which is 15.984 kw, while for Qe it is 12.959 kW and for
Wc it is 637.53 Kw.
9
5.0 Conclusion
From this experiment, we can conclude that there is variation in COP of a vapour
compression refrigeration system at various evaporator loads. When the value of load changes, the
COP and the temperature of the condenser will also change. Lastly, the value of COP showed how
much energy can be saved while the performance of the refrigerator by manipulating the value of
load.
Results show that the aims of the experiment were successfully achieved. All parts of the
refrigeration cycle may have been affected by the load increase. At each of the four phases of the
refrigeration cycle, the pressure, enthalpy, and temperature were recorded and analysed. The COP
and efficiency of the refrigeration cycle may now be calculated. As was said before, certain errors
impacted the reliability of our findings.
According to the results of the experiment, our primary goal of detecting the variation in
the Coefficient of Performance (COPref) of a vapour compression refrigeration system was met.
This requires investigating how the COPref changes as the load increases. In this experiment, the
effect of COPref was that it increased as the value of load grew; even so, due to an experiment-
related variable, it declined and then increased again. Apart from this experiment, we can conclude
that the refrigeration cycle is superior as COPref increases. Furthermore, it is recommended that
we carefully conduct this experiment and implement all of the instructions in order to avoid errors.
It is also recommended that the refrigerant flow rate and cooling capacity be increased.
10
NAME: MUHAMMAD NABIL FAHMI BIN MOHD FAUZI
STUDENT ID: 2022798357
The experiment's goals were met, and they are listed as so in the outcomes section. It may
be said that the increase in load had an impact on every part of the refrigeration cycle. The four
states of the refrigeration cycle's parameters, including pressure, enthalpy, and temperature, were
identified and calculated. This enables us to figure out the refrigeration cycle's COP and efficiency.
There were mistakes, as was mentioned in the previous part, which put our findings in jeopardy.
In conclusion, I can say that the COP ref increase factor depends on several things, namely
the increase in load in terms of temperature produced by the evaporator and condenser. This shows
that the more the load increases, the higher the temperature and pressure, when the pressure and
temperature increase, the energy change also changes. Finally, we can apply this experiment to
everyday life so that we know all the processes that occur in a system, especially in systems that
have energy changes.
11
6.0 References
1. Hundy, G. F., Trott, A. R., & Welch, T. C. (2016). Condensers and Cooling Towers.
0-08-100647-4.00006-1
2. Setyawan, A., Sutandi, T., Faldian, & Margana, A. S. (2018). Simulation of the effect of
the condensing temperature on the performance of a split AC with R-410a under constant
cooling capacity. AIP Conference Proceedings. https://doi.org/10.1063/1.5049965
3. Power Gained by Fluid from Pump or Fan. (2023). Engineeringtoolbox.com.
https://www.engineeringtoolbox.com/pump-fan-power-d_632.html
4. Super Radiator Coils. (2021, February 19). The 4 Main Refrigeration Cycle Components
https://www.superradiatorcoils.com/blog/4-main-refrigeration-cycle-components
12