You are on page 1of 20

CLIENT: BP \ SONATRACH

LOCATION: IN-AMENAS, ALGERIA DOC NO.: 6877-LL-PS-00-00-21531


PROJECT: IN-AMENAS GAS PROJECT

JOB NO.: 6877 UNIT NO.: 60

LINE LIST
SYSTEM 60 - FIREWATER SYSTEM

REV DESCRIPTION DATE BY CHECK APPROVED

Z08 AS BUILT 10-Dec-06 NS EZ TJ


C07 RE-ISSUED FOR CONSTRUCTION 30-Sep-04 PAM DOJC/JW PAM
C06 ISSUED FOR CONSTRUCTION 2-Apr-04 JPP PAM PAM

21531: Utility 21531-60.xls System 60: Page 1 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

8 DO 06 60 001 U3P5 L 06-T-603 TUNDISH 8"-WW-0657001-U3P5 60-21488 ATM AMB 3.5 85 / -5 X 85 / -5 NOTE 9

21531: Utility 21531-60.xls System 60: Page 2 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

PT 08 60 001 A1A1 08-X-601 21505 VTA VTA VTA VTA X AMB A1-1 NOTE 9

21531: Utility 21531-60.xls System 60: Page 3 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

VT 06 60 001 A1A7 06-T-603 - TRIM 60-21488 ± 5mbarg 85 / -5 X 85 / -5 AMB A1-1 NOTE 9 C07

VT 08 60 001 A1A7 08-T-604 TRIM 60-21504 ±5mbarg 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

21531: Utility 21531-60.xls System 60: Page 4 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23
DELUGE GAS COMPRESSOR
6 WF 00 60 001 A1A7 L 00-X-601 60-21496 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
AFTERCOOLER 00-E-161C
DELUGE GAS COMPRESSOR
6 WF 00 60 002 A1A7 L 00-X-601 60-21496 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
AFTERCOOLER 00-E-161B
DELUGE GAS COMPRESSOR
6 WF 00 60 003 A1A7 L 00-X-601 60-21496 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
AFTERCOOLER 00-E-161A
DELUGE GAS COMPRESSOR
6 WF 00 60 004 A1A7 L 00-X-602 60-21496 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
00-CT-161C
DELUGE GAS COMPRESSOR
6 WF 00 60 005 A1A7 L 00-X-602 60-21496 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
00-CT-161B
DELUGE GAS COMPRESSOR
6 WF 00 60 006 A1A7 L 00-X-602 60-21496 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
00-CT-161A

WF 00 60 007 NOT USED

WF 00 60 008 NOT USED

WF 00 60 009 NOT USED


ALLOCATED TO VENDOR PACKAGE
6 WF 00 60 010 A1A7 L 6"-WF-0660020-U1A2 6"-WF-0060001-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 00 60 011 A1A7 L 6"-WF-0060001-A1A7 Test/Drain PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 00 60 012 A1A7 L 00-XV-6003 1"-WF-0060022-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 00 60 013 A1A7 L 00-XV-6003 1"-WF-0060022-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
6 WF 00 60 014 A1A7 L 6"-WF-0660020-U1A2 6"-WF-0060002-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 00 60 015 A1A7 L 6"-WF-0060002-A1A7 2"-WF-0060011-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 00 60 016 A1A7 L 00-XV-6002 1"-WF-0060022-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 00 60 017 A1A7 L 00-XV-6002 1"-WF-0060022-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
6 WF 00 60 018 A1A7 L 6"-WF-0660020-U1A2 6"-WF-0060003-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 00 60 019 A1A7 L 6"-WF-0060003-A1A7 2"-WF-0060011-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 00 60 020 A1A7 L 00-XV-6001 1"-WF-0060022-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 00 60 021 A1A7 L 00-XV-6001 1"-WF-0060022-A1A7 PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 00 60 022 A1A7 L 00-XV-6001/6002/6003 Drain PSE03-0971 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

WF 00 60 023 NOT USED

WF 00 60 024 NOT USED


ALLOCATED TO VENDOR PACKAGE
6 WF 00 60 025 A1A7 L 8"-WF-0660036-U1A2 6"-WF-0060004-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 00 60 026 A1A7 L 6"-WF-0060004-A1A7 Test/Drain PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 00 60 027 A1A7 L 00-XV-6006 1"-WF-0060037-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 00 60 028 A1A7 L 00-XV-6006 1"-WF-0060037-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
6 WF 00 60 029 A1A7 L 8"-WF-0660036-U1A2 6"-WF-0060005-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 00 60 030 A1A7 L 6"-WF-0060005-A1A7 2"-WF-0060026-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

21531: Utility 21531-60.xls System 60: Page 5 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23
ALLOCATED TO VENDOR PACKAGE
1/2 WF 00 60 031 A1A7 L 00-XV-6005 1"-WF-0060037-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 00 60 032 A1A7 L 00-XV-6005 1"-WF-0060037-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
6 WF 00 60 033 A1A7 L 8"-WF-0660036-U1A2 6"-WF-0060006-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 00 60 034 A1A7 L 6"-WF-0060006-A1A7 2"-WF-0060026-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 00 60 035 A1A7 L 00-XV-6004 1"-WF-0060037-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 00 60 036 A1A7 L 00-XV-6004 1"-WF-0060037-A1A7 PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 00 60 037 A1A7 L 00-XV-6004/6005/6006 Drain PSE03-0972 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

DELUGE
8 WF 01 60 001 A1A7 L 01-X-601 60-21497 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
01-E-142, 232, 234
DELUGE
3 WF 01 60 002 A1A7 L 01-X-601 60-21497 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
01-E-261, 262

WF 01 60 003 A1A7 L NOT USED

WF 01 60 004 A1A7 L NOT USED


ALLOCATED TO VENDOR PACKAGE
8 WF 01 60 005 A1A7 L 8"-WF-0660019-U1A2 8"-WF-0160001-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
3 WF 01 60 006 A1A7 L 8"-WF-0160001-A1A7 2"-WF-0160006-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 01 60 006 A1A7 L 3"-WF-0160006-A1A7 Test/Drain PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 01 60 007 A1A7 L 01-XV-6001 1"-WF-0160013-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 01 60 008 A1A7 L 01-XV-6001 1"-WF-0160013-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
4 WF 01 60 009 A1A7 L 8"-WF-0660019-U1A2 3"-WF-0160002-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 01 60 010 A1A7 L 3"-WF-0160002-A1A7 2"-WF-0160006-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 01 60 011 A1A7 L 01-XV-6002 1"-WF-0160013-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 01 60 012 A1A7 L 01-XV-6002 1"-WF-0160013-A1A7 PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 01 60 013 A1A7 L 01-XV-6001/6002 Drain PSE03-0973 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

DELUGE
8 WF 02 60 001 A1A7 L 02-X-601 60-21498 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
02-E-142, 232, 234
DELUGE
3 WF 02 60 002 A1A7 L 02-X-601 60-21498 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
02-E-261, 262

WF 02 60 003 A1A7 NOT USED

WF 02 60 004 A1A7 NOT USED

21531: Utility 21531-60.xls System 60: Page 6 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23
ALLOCATED TO VENDOR PACKAGE
8 WF 02 60 005 A1A7 L 8"-WF-0660018-U1A2 8"-WF-0260001-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
3 WF 02 60 006 A1A7 L 8"-WF-0260001-A1A7 2"-WF-0260006-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 02 60 006 A1A7 L 3"-WF-0260006-A1A7 Test/Drain PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 02 60 007 A1A7 L 02-XV-6001 1"-WF-0260013-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 02 60 008 A1A7 L 02-XV-6001 1"-WF-0260013-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
4 WF 02 60 009 A1A7 L 8"-WF-0660018-U1A2 3"-WF-0260002-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 02 60 010 A1A7 L 3"-WF-0260002-A1A7 2"-WF-0260006-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 02 60 011 A1A7 L 02-XV-6002 1"-WF-0260013-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 02 60 012 A1A7 L 02-XV-6002 1"-WF-0260013-A1A7 PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 02 60 013 A1A7 L 02-XV-6001/6002 Drain PSE03-0974 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

DELUGE
8 WF 03 60 001 A1A7 L 03-X-601 60-21499 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
03-E-142, 232, 234
DELUGE
3 WF 03 60 002 A1A7 L 03-X-601 60-21499 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
03-E-261, 262

WF 03 60 003 A1A7 NOT USED

WF 03 60 004 A1A7 NOT USED


ALLOCATED TO VENDOR PACKAGE
8 WF 03 60 005 A1A7 L 8"-WF-0660034-U1A2 8"-WF-0360001-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
3 WF 03 60 006 A1A7 L 8"-WF-0360001-A1A7 2"-WF-0360006-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 03 60 006 A1A7 L 3"-WF-0360006-A1A7 Test/Drain PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 03 60 007 A1A7 L 03-XV-6001 1"-WF-0360013-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 03 60 008 A1A7 L 03-XV-6001 1"-WF-0360013-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
4 WF 03 60 009 A1A7 L 8"-WF-0660018-U1A2 3"-WF-0360002-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 03 60 010 A1A7 L 3"-WF-0360002-A1A7 2"-WF-0360006-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 03 60 011 A1A7 L 03-XV-6002 1"-WF-0360013-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 03 60 012 A1A7 L 03-XV-6002 1"-WF-0360013-A1A7 PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 03 60 013 A1A7 L 03-XV-6001/6002 Drain PSE03-0975 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

8 WF 05 60 001 A1D1 L 05-X-602 8"-WF-0560060-A1D1 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 05 60 002 A1D1 L 8"-WF-0560001-A1D1 05-T-432 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 05 60 003 A1D1 L 8"-WF-0560001-A1D1 05-T-431A 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 05 60 004 A1D1 L 8"-WF-0560001-A1D1 05-T-431B 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 7 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

4 WF 05 60 005 A1A7 L 05-X-603 05-T-432 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 05 60 006 A1A7 L 05-X-603 05-T-431A 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 05 60 007 A1A7 L 05-X-603 05-T-431B 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

WF 05 60 008 NOT USED

05-P-431A/B
6 WF 05 60 009 A1A7 L 05-X-604 60-21493 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
05-P-434A/B

4 WF 05 60 010 A1A7 L 05-X-604 05-P-433A/B 60-21493 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

05-P-411A/B
6 WF 05 60 011 A1A7 L 05-X-608 60-21495 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
05-P-413A/B

4 WF 05 60 012 A1A7 L 05-X-608 05-P-412A/B 60-21495 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

WF 05 60 013 A1A7 L NOT USED

WF 05 60 014 A1A7 L NOT USED

ALLOCATED TO VENDOR PACKAGE


4 WF 05 60 015 A1A7 L 8"-WF-0660028-U1A2 4"-WF-0560005-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 05 60 016 A1A7 L 4"-WF-0560005-A1A7 Test/Drain PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 05 60 017 A1A7 L 05-XV-6001 1"-WF-0560027-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 05 60 018 A1A7 L 05-XV-6001 1"-WF-0560027-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
4 WF 05 60 019 A1A7 L 8"-WF-0660028-U1A2 4"-WF-0560006-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 05 60 020 A1A7 L 4"-WF-0560006-A1A7 2"-WF-0560016-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 05 60 021 A1A7 L 05-XV-6002 1"-WF-0560027-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 05 60 022 A1A7 L 05-XV-6002 1"-WF-0560027-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
4 WF 05 60 023 A1A7 L 8"-WF-0660028-U1A2 4"-WF-0560007-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 05 60 024 A1A7 L 4"-WF-0560007-A1A7 2"-WF-0560016-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 05 60 025 A1A7 L 05-XV-6003 1"-WF-0560027-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 05 60 026 A1A7 L 05-XV-6003 1"-WF-0560027-A1A7 PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 05 60 027 A1A7 L 05-XV-6001/6002 Drain PSE03-0976 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

WF 05 60 028 A1A7 L NOT USED

WF 05 60 029 A1A7 L NOT USED


ALLOCATED TO VENDOR PACKAGE
6 WF 05 60 030 A1A7 L 8"-WF-0660026-U1A2 6"-WF-0560009-A1A7 PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 05 60 031 A1A7 L 6"-WF-0560009-A1A7 Test/Drain PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 05 60 032 A1A7 L 05-XV-6004 1"-WF-0560038-A1A7 PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 05 60 033 A1A7 L 05-XV-6004 1"-WF-0560038-A1A7 PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
4 WF 05 60 034 A1A7 L 8"-WF-0660026-U1A2 6"-WF-0560010-A1A7 PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

21531: Utility 21531-60.xls System 60: Page 8 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23
ALLOCATED TO VENDOR PACKAGE
2 WF 05 60 035 A1A7 L 6"-WF-0560010-A1A7 2"-WF-0560031-A1A7 PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 05 60 036 A1A7 L 05-XV-6005 1"-WF-0560038-A1A7 PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 05 60 037 A1A7 L 05-XV-6005 1"-WF-0560038-A1A7 PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 05 60 038 A1A7 L 05-XV-6004/6005 Drain PSE03-0977 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

WF 05 60 039 A1A7 L NOT USED


ALLOCATED TO VENDOR PACKAGE
6 WF 05 60 040 A1A7 L 8"-WF-0660025-U1A2 6"-WF-0660045-A1A7 PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 05 60 041 A1A7 L 6"-WF-0660045-A1A7 Test/Drain PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 05 60 042 A1A7 L 05-XV-6006 1"-WF-0560048-A1A7 PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 05 60 043 A1A7 L 05-XV-6006 1"-WF-0560048-A1A7 PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
4 WF 05 60 044 A1A7 L 8"-WF-0660025-U1A2 4"-WF-0660046-A1A7 PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
2 WF 05 60 045 A1A7 L 4"-WF-0660046-A1A7 2"-WF-0560041-A1A7 PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/2 WF 05 60 046 A1A7 L 05-XV-6007 1"-WF-0560048-A1A7 PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1/4 WF 05 60 047 A1A7 L 05-XV-6007 1"-WF-0560048-A1A7 PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)
ALLOCATED TO VENDOR PACKAGE
1 WF 05 60 048 A1A7 L 05-XV-6006/6007 Drain PSE03-0978 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 (DELUGE SKIDS)

24 WF 06 60 001 A1A7 L 06-T-603 HEADER 60-21488 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

16 WF 06 60 001 A1A7 L 24"-WF-0660001-A1A7 SUB-HEADER 60-21488 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

06-X-601 A (TP 1)
10 WF 06 60 001 A1A7 L 16"-WF-0660001-A1A7 60-21489 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1
(06-P-601A )
06-X-601 A (TP 2)
10 WF 06 60 001 A1A7 L 16"-WF-0660001-A1A7 60-21489 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1
(06-P-602A )

6 WF 06 60 001 A1A7 L 16"-WF-0660001-A1A7 REDUCER 60-21489 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

06-X-601 A (TP 3)
3 WF 06 60 001 A1A7 L REDUCER 60-21489 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1
(06-P-603A )

16 WF 06 60 002 A1A7 L 24"-WF-0660001-A1A7 SUB-HEADER 60-21488 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

06-X-601 B (TP 1)
10 WF 06 60 002 A1A7 L 16"-WF-0660002-A1A7 60-21490 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1
(06-P-601B )
06-X-601 B (TP 2)
10 WF 06 60 002 A1A7 L 16"-WF-0660002-A1A7 60-21490 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1
(06-P-602B )

6 WF 06 60 002 A1A7 L 16"-WF-0660002-A1A7 REDUCER 60-21490 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

06-X-601 B (TP 3)
3 WF 06 60 002 A1A7 L REDUCER 60-21490 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1
(06-P-603B )
COLLECT'N SUB-HDR
10 WF 06 60 003 A1A7 L VALVE 11 60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
( WF-0660005)

10 WF 06 60 003 A1A7 L VALVE 11 06-T-603 60-21488 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

10 WF 06 60 004 A1A7 L 10"-WF-0660006-A1A7 10"-WF-0660003-A1A7 60-21490 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

06-X-601 A (TP 4) DISTRIBUTION


10 WF 06 60 005 A1A7 L (WF-0660007)
60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
(06-P-601A )

21531: Utility 21531-60.xls System 60: Page 9 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

2½ WF 06 60 005 DELETED BECOMES WF-0660088

3 WF 06 60 005 DELETED BECOMES WF-0660088

06-X-601 B (TP 4) DISTRIBUTION


10 WF 06 60 006 A1A7 L (WF-0660007)
60-21490 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
(06-P-601B )

2½ WF 06 60 006 DELETED BECOMES WF-0660089

3 WF 06 60 006 DELETED BECOMES WF-0660089

12 WF 06 60 007 A1A7 L 12"-WF-0660010-A1A7 12"-WF-0660010-A1A7 60-21491 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

12 WF 06 60 007 U1A2 L 12"-WF-0660010-A1A7 12"-WF-0660010-A1A7 60-21491 9.8 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

4 WF 06 60 007 A1A7 L 12"-WF-0660007-A1A7 06-LFH-1-43 60-21491 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

12 WF 06 60 008 U1A2 L 12"-WF-0660022-A1A7 12"-WF-0660017-A1A7 60-21507 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 008 A1A7 L 12"-WF-0660022-A1A7 12"-WF-0660017-A1A7 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 WILL BE BELOW GROUND.

4 WF 06 60 008 A1A7 L 12"-WF-0660008-A1A7 06-LFH-1-44 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 008 A1A7 L 12"-WF-0660008-A1A7 06-LFH-1-45 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 008 A1A7 L 12"-WF-0660008-A1A7 06-LFH-1-46 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 008 A1A7 L 12"-WF-0660008-A1A7 06-LFH-1-47 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 008 A1A7 L 12"-WF-0660008-U1A2 06-LFH-1-48 60-21507 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

12 WF 06 60 009 A1A7 L 12"-WF-0660010-A1A7 12"-WF-0660012-A1A7 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 009 U1A2 L 12"-WF-0660010-A1A7 12"-WF-0660012-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-01 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-02 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-03 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-04 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-05 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-06 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-07 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-08 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-09 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-79 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-94 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-61 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 009 A1A7 L 12"-WF-0660009-A1A7 06-LFH-1-10 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 10 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

6 WF 06 60 009 U1A2 L 12"-WF-0660009-U1A2 6"-WF-0660009-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

06-LFM-1-01
6 WF 06 60 009 A1A7 L 6"-WF-0660009-U1A2 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
06-LFM-1-02

6 WF 06 60 009 U1A2 L 12"-WF-0660009-U1A2 6"-WF-0660009-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

06-LFM-1-03
6 WF 06 60 009 A1A7 L 6"-WF-0660009-U1A2 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
06-LFM-1-04

4 WF 06 60 009 U1A2 L 12"-WF-0660009-U1A2 4"-WF-0660009-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

4 WF 06 60 009 A1A7 L 4"-WF-0660009-U1A2 06-LFH-1-97 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

12 WF 06 60 010 A1A7 L 12"-WF-0660009-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 010 U1A2 L 12"-WF-0660009-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFH-1-39 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFH-1-40 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFH-1-41 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFH-1-42 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFH-1-78 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFM-1-22 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFM-1-23 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFM-1-24 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 010 A1A7 L 12"-WF-0660010-A1A7 06-LFM-1-37 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART A1A7/PART U1A2

12 WF 06 60 011 A1A7 L 12"-WF-0660010-A1A7 12"-WF-0660012-A1A7 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 011 U1A2 L 12"-WF-0660010-A1A7 12"-WF-0660012-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-13 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-14 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-15 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-16 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-17 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-18 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-19 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-20 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFM-1-05 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-06 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFM-1-07 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 11 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

4 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 06-LFH-1-08 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 011 A1A7 L 12"-WF-0660011-A1A7 6"-WF-0660011-U1A2 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 011 U1A2 L 6"-WF-0660011-A1A7 6"-WF-0660011-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

6 WF 06 60 011 A1A7 L 6"-WF-0660011-U1A2 06-LFM-1-36 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

12 WF 06 60 012 A1A7 L 12"-WF-0660009-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 012 U1A2 L 12"-WF-0660009-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 012 A1A7 L 12"-WF-0660012-A1A7 06-LFH-1-21 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-A1A7 06-LFH-1-22 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-A1A7 06-LFH-1-23 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-A1A7 06-LFH-1-24 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-U1A2 06-LFH-1-25 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-A1A7 06-LFH-1-85 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-U1A2 06-LFM-1-09 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-U1A2 06-LFM-1-10 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-U1A2 06-LFM-1-11 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 A1A7 L 12"-WF-0660012-A1A7 06-LFM-1-12 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 012 U1A2 L 12"-WF-0660012-A1A7 06-LFM-1-25 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

6 WF 06 60 012 U1A2 L 12"-WF-0660012-U1A2 6"-WF-0660012-A1A7 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 012 A1A7 L 6"-WF-0660012-U1A2 06-LFM-1-38 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

12 WF 06 60 013 A1A7 L 12"-WF-0660011-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 013 U1A2 L 12"-WF-0660011-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 013 A1A7 L 12"-WF-0660013-A1A7 06-LFH-1-35 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 013 A1A7 L 12"-WF-0660013-A1A7 06-LFH-1-36 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 013 A1A7 L 12"-WF-0660013-A1A7 06-LFH-1-37 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 013 A1A7 L 12"-WF-0660013-A1A7 06-LFH-1-38 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 013 A1A7 L 12"-WF-0660013-A1A7 06-LFH-1-64 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 013 A1A7 L 12"-WF-0660013-A1A7 06-LFM-1-19 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 013 A1A7 L 12"-WF-0660013-A1A7 06-LFM-1-20 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 013 U1A2 L 12"-WF-0660013-A1A7 06-LFM-1-21 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART U1A2/PART A1A7

21531: Utility 21531-60.xls System 60: Page 12 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

12 WF 06 60 014 A1A7 L 12"-WF-0660011-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 014 U1A2 L 12"-WF-0660011-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFH-1-31 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFH-1-32 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFH-1-33 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFH-1-34 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFH-1-63 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFM-1-16 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFM-1-17 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 014 A1A7 L 12"-WF-0660014-A1A7 06-LFM-1-18 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART U1A2/PART A1A7

12 WF 06 60 015 A1A7 L 12"-WF-0660011-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 015 U1A2 L 12"-WF-0660011-A1A7 12"-WF-0660016-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFH-1-26 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFH-1-27 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART A1A7/PART U1A2

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFH-1-28 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFH-1-29 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFH-1-30 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFH-1-80 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFM-1-26 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFM-1-13 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFM-1-14 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 06-LFM-1-15 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 015 A1A7 L 12"-WF-0660015-A1A7 12"-WF-0660015-U1A2 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 015 U1A2 L 12"-WF-0660015-A1A7 12"-WF-0660015-A1A7 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

6 WF 06 60 015 A1A7 L 12"-WF-0660015-U1A2 06-LFM-1-27 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

12 WF 06 60 016 A1A7 L 12"-WF-0660008-U1A2 12"-WF-0660022-A1A7 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 016 U1A2 L 12"-WF-0660008-U1A2 12"-WF-0660022-A1A7 60-21506 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 016 A1A7 L 12"-WF-0660016-A1A7 06-LFH-1-69 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 016 A1A7 L 12"-WF-0660016-A1A7 06-LFH-1-70 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 13 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

12 WF 06 60 017 A1A7 L 12"-WF-0660010-A1A7 12"-WF-0660021-A1A7 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 017 U1A2 L 12"-WF-0660010-A1A7 12"-WF-0660021-A1A7 60-21507 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 017 A1A7 L 12"-WF-0660017-A1A7 06-LFH-1-52 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 017 A1A7 L 12"-WF-0660017-A1A7 06-LFH-1-53 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

DELETED

4 WF 06 60 017 A1A7 L 12"-WF-0660017-A1A7 06-LFH-1-66 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 017 A1A7 L 12"-WF-0660017-A1A7 06-LFH-1-67 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 017 A1A7 L 12"-WF-0660017-A1A7 06-LFH-1-68 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

PIPE ONLY NO VALVES, DESIGN


8 WF 06 60 018 A1A7 L 12"-WF-0660013-A1A7 02-X-601 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.
PIPE ONLY NO VALVES, DESIGN
8 WF 06 60 019 A1A7 L 12"-WF-0660014-A1A7 01-X-601 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.
PIPE ONLY NO VALVES, DESIGN
6 WF 06 60 020 A1A7 L 12"-WF-0660015-A1A7 00-X-601 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.

12 WF 06 60 021 A1A7 L 12"-WF-0660017-A1A7 12"-WF-0660022-A1A7 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 021 U1A2 L 12"-WF-0660017-A1A7 12"-WF-0660022-A1A7 60-21507 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 021 A1A7 L 12"-WF-0660021-A1A7 06-LFH-1-62 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 021 A1A7 L 12"-WF-0660021-A1A7 06-LFH-1-49 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 021 A1A7 L 12"-WF-0660021-A1A7 06-LFH-1-50 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 021 A1A7 L 12"-WF-0660021-A1A7 06-LFH-1-51 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

12 WF 06 60 022 A1A7 L 12"-WF-0660024-U1A2 12"-WF-0660021-U1A2 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 022 U1A2 L 12"-WF-0660024-U1A2 12"-WF-0660021-U1A2 60-21491 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW WILL BE BELOW GROUND.

4 WF 06 60 022 A1A7 L 12"-WF-0660022-A1A7 06-LFH-1-74 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 022 A1A7 L 12"-WF-0660022-A1A7 06-LFH-1-11 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART A1A7/PART U1A2

4 WF 06 60 022 A1A7 L 12"-WF-0660022-A1A7 06-LFH-1-95 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 022 A1A7 L 12"-WF-0660022-A1A7 06-LFH-1-96 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 022 A1A7 L 12"-WF-0660022-A1A7 06-LFH-1-65 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

WF 60 023 DELETED

12 WF 06 60 024 U1A2 L 12"-WF-0660012-U1A2 12"-WF-0660022-A1A7 60-21506 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW SOME SECTION OF THIS LINE WILL BE
ABOVE GROUND AND SOME SECTIONS
12 WF 06 60 024 A1A7 L 12"-WF-0660012-U1A2 12"-WF-0660022-A1A7 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 WILL BE BELOW GROUND.

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-71 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-72 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-73 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 14 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-75 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-76 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-77 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-60 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-83 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART A1A7/PART U1A2

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-81 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART A1A7/PART U1A2

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-84 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART A1A7/PART U1A2

4 WF 06 60 024 A1A7 L 12"-WF-0660024-A1A7 06-LFH-1-82 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 PART A1A7/PART U1A2

PIPE ONLY NO VALVES, DESIGN


6 WF 06 60 025 A1A7 L 12"-WF-0660022-A1A7 05-X-608 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.
PIPE ONLY NO VALVES, DESIGN
6 WF 06 60 026 A1A7 L 12"-WF-0660016-A1A7 05-X-604 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.
PIPE ONLY NO VALVES, DESIGN
8 WF 06 60 027 A1A7 L 12"-WF-0660016-A1A7 05-X-602 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.
PIPE ONLY NO VALVES, DESIGN
6 WF 06 60 028 A1A7 L 12"-WF-0660016-A1A7 05-X-603 60-21506 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.
PIPE ONLY NO VALVES, DESIGN
12 WF 06 60 029 A1A7 L 12"-WF-0660022-A1A7 REDUCER 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.

10 WF 06 60 029 A1A7 L REDUCER END FLANGE 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

WF 60 030 DELETED

WF 06 60 031 DELETED

8 WF 06 60 032 A1A7 L 06-T-603 TUNDISH 60-21488 AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

WF 60 033 DELETED

PIPE ONLY NO VALVES, DESIGN


8 WF 06 60 034 A1A7 L 12"-WF-0660010-A1A7 03-X-601 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.

WF 60 035 DELETED

PIPE ONLY NO VALVES, DESIGN


8 WF 06 60 036 A1A7 L 12"-WF-0660015-A1A7 00-X-602 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.

12 WF 06 60 037 A1A7 L 12"-WF-0660017-A1A7 12"-WF-0660021-A1A7 60-21507 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB A1-1

12 WF 06 60 037 U1A2 L 12"-WF-0660017-A1A7 12"-WF-0660021-A1A7 60-21507 AMB 13.6 50 / -5 H 20.5 50 / -5 AMB CW

4 WF 06 60 037 A1A7 L 12"-WF-0660037-A1A7 06-LFH-1-54 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 037 A1A7 L 12"-WF-0660037-A1A7 06-LFH-1-55 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 037 A1A7 L 12"-WF-0660037-A1A7 06-LFH-1-56 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 037 A1A7 L 12"-WF-0660037-A1A7 06-LFH-1-57 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 037 A1A7 L 12"-WF-0660037-A1A7 06-LFH-1-58 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 037 A1A7 L 12"-WF-0660037-A1A7 06-LFH-1-59 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

038 DELETED

21531: Utility 21531-60.xls System 60: Page 15 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

2 WF 06 60 039 A1A7 L 12"-WF-0660008-A1A7 REDUCER 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

1 1/2 WF 06 60 039 A1A7 L REDUCER WAREHOUSE 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

PIPE ONLY NO VALVES, DESIGN


2 WF 06 60 040 A1A7 L 12"-WF-0660008-A1A7 REDUCERS 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.

1.1/2 WF 06 60 040 A1A7 L REDUCER FIREHOSE WAREHOUSE 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

1.1/2 WF 06 60 040 A1A7 L REDUCER FIREHOSE MAINT. BLDG 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

PIPE ONLY NO VALVES, DESIGN


2 WF 06 60 041 A1A7 L 12"-WF-0660037-A1A7 REDUCER 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1 CONDITIONS WITHIN PIPE SPEC LIMITS.
VEHICLE MAINTENANCE
1.1/2 WF 06 60 041 A1A7 L REDUCER 60-21507 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
HOSE REEL

6 WF 06 60 042 A1A7 L 12"-WF-0660010-A1A7 FLANGED END 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 042 A1A7 L 6"-WF-0660042-U1A2 06-LFH-1-11 60-21491 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

WF 06 60 043 DELETED

WF 06 60 044 DELETED

WF 06 60 045 DELETED

WF 06 60 046 DELETED

WF 06 60 047 DELETED

WF 06 60 048 DELETED

WF 06 60 049 DELETED

WF 06 60 050 DELETED

WF 06 60 051 DELETED

WF 06 60 052 DELETED

WF 06 60 053 DELETED

WF 06 60 054 DELETED

WF 06 60 055 DELETED

WF 06 60 056 DELETED

WF 06 60 057 DELETED

WF 06 60 058 DELETED

WF 06 60 059 DELETED

8 WF 06 60 060 A1D1 L 8"-WF-0660059-A1D1 RINGMAIN 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-86 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-87 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-88 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 16 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-89 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-90 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-91 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-92 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFH-1-93 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-28 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-29 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-30 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-31 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-32 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-33 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-34 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

4 WF 06 60 060 A1D1 L 8"-WF-0660060-A1D1 06-LFM-1-35 60-21492 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

WF 06 60 061 DELETED

WF 06 60 062 DELETED

WF 06 60 063 DELETED

WF 06 60 064 DELETED

WF 06 60 065 DELETED

WF 06 60 066 DELETED

WF 60 067 DELETED

6 WF 06 60 068 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 069 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 070 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 071 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 072 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 073 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 074 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 075 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 076 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

6 WF 06 60 077 A1A7 L 10"-WF-0660029-A1A7 DELUGE - LPG STORAGE 60-21494 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 17 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

1 WF 06 60 078 A1A7 L 06-X-601A (TP 14) REDUCER 60-21489 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A4-1 H 40

2 WF 06 60 078 A1A7 L REDUCER 10"-WF-0660078-A1A7 60-21489 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A4-1 H 50

COLLECT'N SUB-HDR
10 WF 06 60 078 A1A7 L 10"-WF-0660003-A1A7 60-21489 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1
(06-X-601A TP 7)

1 WF 06 60 079 A1A7 L 06-X-601B (TP 14) REDUCER 60-21490 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A4-1 H 40

2 WF 06 60 079 A1A7 L REDUCER 10"-WF-0660079-A1A7 60-21490 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A4-1 H 50

10 WF 06 60 079 A1A7 L 06-X-601B (TP 7) 10"-WF-0660078-A1A7 60-21490 1.4 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

WF 06 60 080 DELETED

1 WF 06 60 081 A1A7 L 06-X-601B (TP17) DRAIN 60-21490 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

1 1/2 WF 06 60 082 A1A7 L 06-X-601B (TP8) REDUCER 60-21490 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

3 WF 06 60 082 A1A7 L REDUCER TUNDISH 60-21490 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

WF 06 60 083 DELETED

1 1/2 WF 06 60 084 A1A7 L 06-X-601A (TP8) REDUCER 60-21489 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

3 WF 06 60 084 A1A7 L REDUCER TUNDISH 60-21489 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

1 WF 06 60 085 A1A7 L 06-X-601A (TP17) DRAIN 60-21489 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

06-X-601 A (TP 5) DISTRIBUTION


10 WF 06 60 086 A1A7 L (12"-WF-0660007-A1A7)
60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
(06-P-602A )
06-X-601 B (TP 5) DISTRIBUTION
10 WF 06 60 087 A1A7 L (12"-WF-0660007-A1A7)
60-21490 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
(06-P-602B )
06-X-601 A (TP 6) REDUCER
2½ WF 06 60 088 A1A7 L 60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
(06-P-603A )
DISTRIBUTION
3 WF 06 60 088 A1A7 L REDUCER (WF-0660007)
60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

06-X-601 B (TP 6) REDUCER


2½ WF 06 60 089 A1A7 L 60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1
(06-P-603B )
DISTRIBUTION
3 WF 06 60 089 A1A7 L REDUCER (WF-0660007)
60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

10 WF 06 60 090 A1A7 L 10"-WF-0660086-A1A7 10"-WF-0660003-A1A7 60-21489 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

10 WF 06 60 091 A1A7 L 10"-WF-0660087-A1A7 10"-WF-0660003-A1A7 60-21490 9.8 AMB 13.6 85 / -5 H 20.5 85 / -5 AMB A1-1

NOTE 9
2 WF 06 60 092 A1A7 L 06-X-601 A (TP 9A) TUNDISH 60-21489 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1

NOTE 9
2 WF 06 60 093 A1A7 L 06-X-601 A (TP 9B) TUNDISH 60-21489 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1

NOTE 9
2 WF 06 60 094 A1A7 L 06-X-601 A (TP 9C) TUNDISH 60-21489 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1

NOTE 9
2 WF 06 60 095 A1A7 L 06-X-601 B (TP 9A) TUNDISH 60-21490 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1

NOTE 9
2 WF 06 60 096 A1A7 L 06-X-601 B (TP 9B) TUNDISH 60-21490 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1

NOTE 9
2 WF 06 60 097 A1A7 L 06-X-601 B (TP 9C) TUNDISH 60-21490 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1

8 WF 08 60 001 A1A7 L 08-T-604 REDUCER 60-21504 0.9 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

21531: Utility 21531-60.xls System 60: Page 18 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

6 WF 08 60 001 A1A7 L REDUCER 08-X-601 (08-P-601/602) 60-21505 0.9 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

3 WF 08 60 001 A1A7 L 8"-WF-0860001-A1A7 08-X-601 (08-P-603) 60-21505 0.9 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

8 WF 08 60 002 A1A7 L 08-T-604 DRAIN TO GRADE 60-21504 AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

4 WF 08 60 003 A1A7 L 6"-WF-0860005-A1A7 REDUCER 60-21505 11.3 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1

6 WF 08 60 003 A1A7 L REDUCER REDUCER 60-21504 11.3 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1 08 FE 6001 SECTION

4 WF 08 60 003 A1A7 L REDUCER VALVE 11 & SPEC. BREAK 60-21504 11.3 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1

VALVE 11 & SPEC.


4 WF 08 60 003 U1D1 L 4"-WP-0853005-U1D1 60-21504 0.9 AMB 3.5 50 / -5 H 5.5 50 / -5 AMB A1-1
BREAK

4 WF 08 60 003 A1A7 L 4"-WF-0860003 VALVE 12 60-21504 11.3 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1 ALTERNATIVE BRANCH

SPEC. BREAK & WP-


4 WF 08 60 003 A1A7 L VALVE 12 60-21504 11.3 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1
0853005 BRANCH

8 WF 08 60 004 A1A7 L 8"-WP-0853006-U1D1 8"-WF-0860001-A1A7 53-21501 0.9 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

08-X-601 (TP 4 & 5)


6 WF 08 60 005 A1A7 L DISTRIBUTION HEADER 60-21505 7.5 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1
(08-P-601/602)
08-X-601 (TP 6)
2 1/2 WF 08 60 005 A1A7 L REDUCER 60-21505 7.5 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1
(08-P-601)

3 WF 08 60 005 A1A7 L REDUCER 6"-WF-0860005-A1A7 60-21505 7.5 AMB 11.3 85 / -5 H 17 85 / -5 AMB A1-1

1 WF 08 60 006 A1A7 L 08-X-601 (TP14) REDUCER 60-21505 0.9 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1 H 40

2 WF 08 60 006 A1A7 L REDUCER 6"-WF-0860006-A1A7 60-21505 0.9 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1 H 50

6 WF 08 60 006 A1A7 L 08-X-601 (TP7) 6"-WP-0853008-U1D1 60-21505 0.9 AMB 3.5 85 / -5 H 5.5 85 / -5 AMB A1-1

WF 08 60 007 DELETED

1 WF 08 60 008 A1A7 L 08-X-601 (TP8) DRAIN 60-21505 AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

1 WF 08 60 009 A1A7 L 08-X-601 (TP17) DRAIN 60-21505 AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

WF 08 60 010 DELETED

2 WF 08 60 011 A1A7 L 08-X-601 (TP 9A) TUNDISH 60-21505 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

2 WF 08 60 012 A1A7 L 08-X-601 (TP 9B) TUNDISH 60-21505 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

2 WF 08 60 013 A1A7 L 08-X-601 (TP 9B) TUNDISH 60-21505 ATM AMB 3.5 85 / -5 X 85 / -5 AMB A1-1 NOTE 9

6 WF 08 60 014 U1A2 L VALVE 21 VALVE ?? 60-21516

6 WF 08 60 015 A1A7 L VALVE 21 VALVE ?? 60-21516

21531: Utility 21531-60.xls System 60: Page 19 of 20


CLIENT: BP \ SONATRACH
LOCATION: ALGERIA DOCUMENT NUMBER
PROJECT: IN AMENAS LINE LIST
GAS PROJECT 6877-LL-PS-00-00-21531
2-Apr-04
REV REVISION DESCRIPTION DATE BY CHK APPR JOB NO.: 6877
PIPELINE DESCRIPTION OPERATING DESIGN FIELD TEST FLEX INSULATION AND PAINT ISSUE/
NOM. SERVICE DESIGNATION PIPE FLUID FROM TO P&ID PRES. TEMP. PRES. TEMP. MEDIUM PRES. TEMP. TEMP. PAINT INSUL INSUL. DPP REV
LINE ZONE SYSTEM NUMBER SPEC. PHASE NO. HI / LO CLASS CLASS THK INSP SPECIAL
SIZE REQUIREMENTS
(in) (barg) (°C) (barg) (°C) (barg) (°C) (°C) (mm)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23

WW 06 60 001 NOT USED


60-21489
3 WW 06 60 002 U3P5 L 06-P-601A/B DRAINS REDUCER /21490 ATM AMB 3.5 85 / -5 X 85 / -5 NOTE 9

4 WW 06 60 002 U3P5 L REDUCER REDUCER 57-21482 ATM AMB 3.5 85 / -5 X 85 / -5 NOTE 9

8 WW 06 60 002 U3P5 L REDUCER 8"-WW-0652001-U3P5 57-21482 ATM AMB 3.5 85 / -5 X 85 / -5 NOTE 9

21531: Utility 21531-60.xls System 60: Page 20 of 20